Emerson 00809-0200-4708 User Manual

Reference Manual
00809-0200-4708, Rev AA January 2014
SteamLogic OPC Server

Table of contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
OPC mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
Network architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Supported OPC versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
OPC server configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4

1.1 Introduction

The Smart Wireless Gateway enables IEC62591 WirelessHART technology; wireless transmitters communicating with each other and the Gateway in a self-organizing wireless mesh network. The Gateway manages the network, its communication, security and connectivity. The gateway is the entry point for wireless device data that is then converted to a format that is compatible with other systems. In the case of steam trap monitoring this other system is SteamLogic, monitoring software. This document focuses on OPC system integration for the SteamLogic software and the Rosemount 708 Wireless Discrete Transmitter.
The objective of the SteamLogic OPC Server is to give access to the trap state that is calculated within the SteamLogic software.

1.2 OPC mapping

The following table translates the OPC value, seen by the client, to a steam trap state and user interface icon.
OPC
value
0 Good Steam trap is functioning normally under the current settings
1 Cold
State
User interface
icon
Meaning
Steam trap is in a failed cold position. This steam trap may have a mechanical failure or could be plugged with solids. It could also be flooding or undersized for the application making it unable to remove enough condensate. Otherwise the steam supply could be turned off.
Smart Wireless Gateway for SteamLogic OPC Server
January 2014
Reference Manual
00809-0200-4708, Rev AA
OPC
value
2 Noisy Transition state before going to fully blowthru
3 Blow Thru
State
User interface
icon
Meaning
Steam trap has failed in the open position. It may have a mechanical failure causing it to stick open or could be installed improperly.
There are three reasons for this status;
1. The device has recently been configured and the state has not been determined yet
4
No Data Available
2. The gateway has lost communication with the device so the state cannot be confirmed
3. The device has a fault/error causing the state to be undeterminable
5
Device Not Configured
The device has been discovered, but has not been configured with the required settings. Edit the trap details to configure the device.
Use the out of service feature in the device edit tab when a steam trap has a
6 Out of Service
scheduled period of down time to eliminate presenting the trap as cold. Out of Service overrides all other trap states.
Note:
OPC Item's Quality is read from the SteamLogic's Monitor Status:
User
OPC
value
Good Good The device is operating normally and reporting live information
Bad Bad Device malfunction. Use AMS, 475 handheld, or other HART tool to troubleshoot
State
interface
icon
Meaning
2
Smart Wireless Gateway for SteamLogic OPC Server
Reference Manual
00809-0200-4708, Rev AA
Note:
OPC Item's Timestamp is read from SteamLogic's State Change Timestamp.
The above Trap Status, Monitor Status, and State Change Timestamp icons and values are based on the SteamLogic version 1.1.0 and SteamLogic Database version 5.
The OPC TrapState item's data type is byte “VT_I1” in an OPC client.

1.3 Network architecture

This section describes the network architecture used to establish OPC communications between the SteamLogic software and the host system. This communication path will allow the calculated trap state, a timestamp, and quality to be monitored by an OPC client. All other parameters, including PV, SV, TV, and QV, are available through the Gateway protocol interfaces (Modbus, OPC, Ethernet/IP, HART-IP).
The following network architecture diagrams will help when integrating data from SteamLogic into the host system.
Smart Wireless Gateway for SteamLogic OPC Server
January 2014
An OPC server (proxy) is provided by Rosemount as part of the SteamLogic software installation package. The Host System will need OPC client capabilities that are used to establish communications with the SteamLogic OPC Server.
As shown in the architecture drawing the Gateway transmits the device data via the HART-IP protocol to the SteamLogic polling service. The steam trap status is then calculated within the SteamLogic polling service and stored in the SteamLogic database. Using the SteamLogic OPC server the trap state can be accessed via the OPC client within the host system.
Smart Wireless Gateway for SteamLogic OPC Server
3
Loading...
+ 5 hidden pages