2 3-5 Change the last paragraph on the page to read as follows:
”Damping electronics are available as an option. Transmitters with standard
electronics can be retrofitted with the adjustable damping feature by changing out
both the amplifier board and the calibration board. Please reference Table 6-2
(Rosemount 1154DP, 1154HP, and 1154GP Spare Parts) for the applicable part
numbers.”
3 6-9 Table 6-2,”Rosemount 1154DP, 1154HP, and 1154GP Spare Parts”, in all locations
the following part numbers are updated:
Amplifier Circuit Board, Output Code R:
”01154-0001-0005” is replaced by ”01154-0153-0001”
Amplifier Circuit Board with Damping, Output Code R:
”01154-0021-0004” is replaced by ”01154-0156-0001”
Amplifier Circuit Board, Output Code R, N0026:
”01154-0001-0006” is replace by ”01154-0153-0002”
(5)
Sensor Module, 316 SST
0-25/150 inH
O: ”01154-0300-0242” is replaced by ”01154-5300-0242”
2
:
”01154-0300-0342” is replaced by ”01154-5300-0342”
”01154-0300-0142” is replaced by ”01154-5300-0142”
0-125/750 inH
O: ”01154-0300-0252” is replaced by ”01154-5300-0252”
2
”01154-0300-0352” is replaced by ”01154-5300-0352”
”01154-0300-0152” is replaced by ”01154-5300-0152”
0-17/100 psi: ”01154-0300-0262” is replaced by ”01154-5300-0262”
”01154-0300-0362” is replaced by ”01154-5300-0362”
”01154-0300-0162” is replaced by ”01154-5300-0162”
0-50/300 psi: ”01154-0300-0272” is replaced by ”01154-5300-0272”
”01154-0300-0372” is replaced by ”01154-5300-0372”
”01154-0300-0172” is replaced by ”01154-5300-0172”
0-170/1,000 psi: ”01154-0300-0282” is replaced by ”01154-5300-0282”
”01154-0300-0182” is replaced by ”01154-5300-0182”
0-500/3,000 psi: ”01154-0300-0192” is replaced by ”01154-5300-0192”
0-1,000/4,000 psi: ”01154-0300-0102” is replaced by ”01154-5300-0102”
4 6-10 Table 6-2,” Rosemount 1154DP, 1154HP, and 1154GP Spare Parts”, the table
footnotes are updated to add note (5) which will read as follows:
Effect.
Date
10/21/09
4/13/12
4/13/12
4/13/12
(5) IMPORTANT NOTICE: To maintain a transmitter’s qualified configuration,
when purchasing or installing a new Sensor Module, Rosemount Qualification
report D2011019 must be carefully reviewed to verify that the Sensor Module
to be installed and the associated Amplifier Circuit Board in a given
transmitter is a qualified configuration. As detailed in the referenced report, not
all Sensor Module part numbers are considered qualified in conjunction with certain
Amplifier Circuit Boards.
Page 3
Reference Manual
NOTICE
Alphaline, Rosemount and the Rosemount logotype are registered trademarks of Rosemount
Inc.
␦-Cell is a trademark of Rosemount Inc.
Loctite is a registered trademark of Henkel HGaA Corporation.
Swagelok is a registered trademark of Swagelok Company.
D.C. 55 is a registered trademark of Dow Corning Corporation.
Lubri-Bond is a registered trademark of E/M Corporation
Grafoil is a trademark of Union Carbide Corp.
Cover Photo: 1153-001AB
Rosemount Nuclear Instruments, Inc. satisfies all obligations coming from
legislation to harmonize product requirements in the European Union.
Read this manual before working with the product. For personal and system safety and
optimum product performance make sure you thoroughly understand the contents before
installing, using, or maintaining this product.
For equipment service needs outside the United States, contact the nearest Rosemount
representative.
Within the United States, the North American Response Center is at your service 24 hours a
day, and is a single-point contact for all Rosemount equipment service needs. If at any time
you are not sure what to do, have a question about using the product, or have a service or
support request, call the center toll-free at 1-800-654-RSMT (7768). This contact is your
fastest link to quick and complete answers about any Rosemount Group product or service.
www.rosemountnuclear.com
Page 4
Rosemount 1154
Rosemount Nuclear Instruments, Inc.
Warranty and Limitations of Remedy
Authorization for return is required from Rosemount Nuclear Instruments, Inc. prior to
shipment. Contact the Nuclear Instruments Group (952-949-5210) for details on obtaining
“Returned Material Authorization (RMA)”. Rosemount Nuclear Instruments will not accept any returned material without a Returned Material Authorization. Materials returned
without authorization are subject to return to customer.
Material returned for repair, whether in or out of warranty, should be shipped prepaid to:
Rosemount Nuclear Instruments, Inc.
8200 Market Blvd
Chanhassen, MN 55317
USA
RETURN OF MATERIAL
The warranty and limitations of remedy applicable to this Rosemount
equipment are as stated on the reverse of the current Rosemount quotation
and customer acknowledgment forms.
IMPORTANT
The Rosemount 1154 Alphaline Pressure Transmitter is designed for nuclear use, has been
tested per IEEE Std 323-1974 and IEEE Std 344-1975 as defined in Rosemount Report
D8400102, and is manufactured to the requirements of NQA-1; 10CFR50, Appendix B
quality assurance programs; and 10CFR Part 21. During qualification testing, interfaces
were defined between the transmitter and its environment that are essential to meeting
IEEE Std 323-1974 requirements. To ensure compliance with 10CFR Part 21, the
transmitter must comply with the requirements herein throughout its installation, operation
and maintenance. It is incumbent upon the user to ensure that the Rosemount Nuclear
Instruments, Inc.’s component traceability program is continued throughout the qualified life
of the transmitter.
In order to maintain the qualified status of the transmitter, the essential environmental
interfaces must not be compromised. Performance of any operations on the transmitter
other than those specifically authorized in this manual may compromise an essential
environmental interface.
Where the manual uses the terms requirements, mandatory, must, or required, the
instructions so referenced must be carefully followed. Rosemount Nuclear Instruments, Inc.
expressly disclaims all responsibility and liability for transmitters for which the foregoing has
not been complied with by the user.
Reference Manual
00809-0100-4514, Rev BA
January 2008
ii
Page 5
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
Revision Status
Changes From June 1999 to January 2008
Page (New)Page (Old)Changes
CoverCover
Inside Cover, i,
ii, 5-8 & Back
Cover
3-5, 6-8 & 6-93-5, 6-9 & 6-10Include errata sheet information on circuit board number changes:
ThroughoutThroughoutReferences to Fisher-Rosemount were changed to Emerson Process Management.
i, back coverCover, i, ii &
-Cover, i, back
2-1,3-1,4-1,5-1,
6-1
2-22-2
2-22-3Updated reference to Swagelok catalog and added web address, removed street address.
2-42-4
2-42-5
2-6 & 2-72-6 & 2-7Added word “nominal” to Notes in drawings. Changed significant digits to conform to standard.
5-7 & 6-95-8 & 6-10
6-16-2
6-96-10Replaced pipe mount bracket kit (adapters) P/N 01154-0038-0001 with P/N 01154-0044-0001
-Back CoverAdded trademark & registration information
ii, 5-9, 5-10 &
Back Cover
back cover
page
2-1,3-1,4-1,5-1,
6-1
Document revision dates changed from June 1999 to January 2008, rev from AA to BA.
Include errata sheet information on address and phone number.
• Replaced amplifier circuit card, output code R P/N 01154-0001-0001 with 01154-0001-0005.
• Replaced amplifier circuit card with damping, output code R P/N 01154-0021-0002 with
01154-0021-0004.
OVERVIEWThis manual is designed to assist in installing, operating, and maintaining the
Rosemount 1154 Pressure Transmitter. The manual is organized into the
following sections:
Section 2: Installation
Provides general, mechanical, and electrical installation considerations to
guide you through a safe and effective transmitter installation.
Section 3: Calibration
Provides transmitter calibration procedures.
Section 4: Operation
Provides descriptions of how the transmitter operates.
Section 5: Maintenance and Troubleshooting
Provides basic hardware troubleshooting considerations including sensing
module checkout, disassembly and reassembly procedures, and
post-assembly tests.
ABOUT THE
TRANSMITTER
Section 6: Specifications and Reference Data
Provides nuclear, performance, functional, and physical transmitter
specifications; also includes ordering information, and a list of spare parts.
Rosemount 1154 Pressure Transmitters are designed for precision pressure
measurements in nuclear applications requiring reliable performance and
safety over a specified qualified life. These transmitters were generically
tested to the IEEE Std 323-1974 and IEEE Std 344-1975 per the Qualification
Test Report D8400102. The Rosemount 1154 has been qualification tested to
environments typical of Pressurized Water Reactors (PWR) under accident
conditions. Stringent quality control during the manufacturing process
includes traceability of pressure retaining parts, special nuclear cleaning, and
hydrostatic testing.
Rosemount 1154 Transmitters are uniquely built to Class 1E nuclear service
while retaining the working concept and design parameters of the Rosemount
1151 Series that have become a standard of reliable service. Units are
available in gage (G), differential (D), and high-line differential (H)
configurations, with a variety of pressure range options, as shown in Table 6-1
on page 6-8. Figure 2-5 on page 2-7 shows dimensional drawings for the
transmitters.
OVERVIEWThis section contains information and instructions regarding the following
installation-related information:
•General Considerations
•Mechanical Considerations
Process Connections
Conduit
•Electrical Considerations
•Installation Procedures
Mechanical
Electrical
GENERAL
CONSIDERATIONS
The quality and accuracy of flow, level, or pressure measurement depends
largely on the proper installation of the transmitter and its associated impulse
piping and valves. For flow measurement, proper installation of the primary
measuring element is also critical to the accuracy of the measurement.
Transmitter installation should minimize the effects of temperature gradients
and temperature fluctuations, and avoid vibration and shock during normal
operation. Take care when designing the measurement to minimize the error
caused by incorrect installation. The ambient temperature of the transmitter
environment affects the qualified life of the transmitter (see Figure 2-1).
www.rosemountnuclear.com
Page 14
Rosemount 1154
Electronics
Qualified Life
Temperature (°F)
Time (Years)
Module
Qualified
Life
Figure 2-1. Qualified
Life vs. Ambient Temperature.
Reference Manual
00809-0100-4514, Rev BA
January 2008
MECHANICAL
CONSIDERATIONS
This section contains information you should consider when preparing to
mount the transmitter. Read this section carefully before proceeding to the
mechanical installation procedure.
Mount the Rosemount 1154 transmitter to a rigid support (a support with a
fundamental mechanical resonant frequency of 40 Hz or greater). A mounting
bracket included with the transmitter facilitates panel mounting. Figure 2-4 on
page 2-6 shows the qualified mounting configurations. The transmitter was
seismic qualified with the bracket mounted with four
3
/8-in. diameter bolts.
Orientation with respect to gravity is not critical to qualification. However, if the
transmitter is mounted with the flanges in a horizontal position, zero the
transmitter to cancel the liquid head effect caused by the difference in height
of the process connections.
If the transmitter is mounted to a non-rigid panel, the user must ensure that
seismic input to the mounting bracket does not exceed qualification levels
given in Rosemount Report D8400102.
Process ConnectionsProcess tubing installation must prevent any added mechanical stress on the
transmitter under seismic disturbances. This may be done by using
stress-relief loops in the process tubing or by separately supporting the
process tubing close to the transmitter.
3
/8-in.
The process connections to the transmitter flanges were qualified with
tubing using Swagelok
®
compression fittings. For options using 1/4–18 NPT
connections, the user assumes responsibility for qualifying the interface.
The Swagelok tube fittings are shipped completely assembled for immediate
use. Do not disassemble them before use; doing so may contaminate the
fittings and result in leaks. Insert the tubing into the Swagelok tube fitting,
making sure that the tubing rests firmly on the shoulder of the fitting and that
the nut is finger tight. Tighten the nut one-and-one-quarter turns past finger
tight to prepare the transmitter for use. Do not overtighten.
2-2
Page 15
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
Transmitters with Flange Options A, D, H, J, L, or M are shipped with
Swagelok fittings for process connections. Included are front ferrule, rear
ferrule, and nut. Ensure that the fittings are placed on the tubing with the
orientation and relative position shown in Detail A, Figure 2-5 on page 2-7.
Process tubing used is
the pressure involved.
The connections can be loosened and re-tightened 20-30 times without
compromising the leak proof seal. To reconnect, insert the tubing with
pre-swaged ferrules into the fitting until the front ferrule sits in the fitting.
Tighten the nut by hand, then rotate one-quarter turn more or to the original
one-and-one-quarter tight position. Then snug the nut slightly with a wrench.
For more information regarding the use of Swagelok tube fittings, refer to:
Fittings Catalog MS-01-140
“Gaugable Tube Fittings and Adapter Fittings”
www.swagelok.com
If the drain/vent valves must be opened to bleed process lines, torque them to
7.5 ft-lb (10 N-m) when closing.
Proper location of the transmitter with respect to the process tubing depends
on various process parameters. When determining the best location, consider
the following:
•Keep hot or corrosive fluids from contacting the transmitter.
•Prevent sediment from depositing in the impulse tubing.
•Ambient temperature gradients and fluctuations can result in erroneous
transmitter readings.
•Keep impulse tubing as short as possible.
•For differential transmitters, balance the liquid head on both legs of the
impulse tubing.
•For liquid flow or pressure measurements, make taps on the side of the
line to avoid sediment deposits, and mount the transmitter beside or
below the taps so gases vent into the process line (see Figure 2-6 on
page 2-8).
•For gas flow or pressure measurements, make taps on the top or side
of the line and mount the transmitter beside or above the taps so liquid
drains into the process line (see Figure 2-6 on page 2-8).
•For steam flow or pressure measurements, make taps on the side of
the line, and mount the transmitter below the taps so the impulse tubing
stays filled with condensate (See Figure 2-6 on page 2-8).
•For steam service, fill the lines with water to prevent steam from
contacting the transmitter. Condensate chambers are not necessary
since the volumetric displacement of the transmitter
is negligible.
3
/8-inch outside diameter, and of suitable thickness for
2-3
Page 16
Rosemount 1154
Reference Manual
00809-0100-4514, Rev BA
January 2008
The piping between the process and the transmitter must transfer the
pressure measured at the process taps to the transmitter. Possible sources of
error in this pressure transfer are:
•Leaks
•Friction loss (particularly if purging is used)
•Trapped gas in a liquid line or trapped liquid in a gas line (head error)
•Temperature-induced density variation between legs (head error), for
differential transmitters
To minimize the possibility of errors, take the following precautions:
•Make impulse tubing as short as possible.
•Slope tubing at least one inch per foot up toward the process
connections for liquid and steam.
•Slope tubing at least one inch per foot down toward the process
connections for gas.
•Avoid high points in liquid lines and low points in gas lines.
•Use impulse tubing of sufficient diameter to avoid friction effects.
•Ensure that all gas is vented from liquid tubing legs.
•Ensure that impulse tubing is of adequate strength to be compatible
with anticipated pressures.
For differential transmitters, also consider the following:
•Keep both impulse legs at the same temperature.
•When using sealing fluid, fill both piping legs to the same level.
•When purging, make the purge connection close to the process taps
and purge through equal lengths of the same size tubing. Avoid purging
through the transmitter.
ConduitThe conduit connection to the transmitter is
conduit seal at the conduit entry to prevent moisture from accumulating in the
terminal side of the housing during accident conditions. To prevent the conduit
from adding mechanical stress to the transmitter during seismic disturbances,
use flexible conduit or support the conduit near the transmitter. Install the
conduit seal in accordance with the manufacturer’s instructions or use the
procedure on page 2-8.
ELECTRICAL
CONSIDERATIONS
This section contains information that you should consider when preparing to
make electrical connections to the transmitter. Read this section carefully
before proceeding to the electrical installation procedures.
The Rosemount 1154 pressure transmitter provides a 4–20 mA signal when
connected to a suitable dc power source. Figure 2-2 on page 2-5 shows a
typical signal loop consisting of transmitter, power supply, and various
receivers (controller, indicator, computer, etc.). The power supply must supply
at least 12 volts to the transmitter terminals at 30 mA (overscale) signal, or the
maximum output current required for proper system operation. Any power
supply ripple appears in the output load. The supply voltage versus load
limitation relationship is shown in Figure 2-3 on page 2-5. See qualification
report D8400102 for details. The load is the sum of the resistance of the
signal leads and the load resistance of the receivers.
1
/2–14 NPT. Use a qualified
2-4
Page 17
Reference Manual
Power
Supply
Terminal Side
Cover Removed
4—20 mA DC
Design
Region
Qualified
Region
1825
1575
1500
1000
500
0
0
12
13.5
35
40
45
50
Power Supply (V DC)
Load Resistance (Ω)
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
Signal wiring need not be shielded, but twisted pairs yield the best results. In
electrically noisy environments, shielded cable should be used for best
results. Do not run signal wiring in conduit or open trays with power wiring, or
near heavy electrical equipment. Signal wiring may be ungrounded (floating)
or grounded at any place in the signal loop. The transmitter case may be
grounded or ungrounded.
The capacitance-sensing element uses alternating current to generate a
capacitance signal. This alternating current is developed in an oscillator circuit
with a frequency of 32,000 ±10,000 Hz. This 32,000 Hz signal is capacitor
coupled to transmitter case ground through the sensing element. Because of
this coupling, a voltage may be imposed across the load, depending on
choice of grounding.
The impressed voltage, which is seen as high frequency noise, has no effect
on most instruments. Computers with short sampling times in a circuit where
the negative transmitter terminal is grounded will detect a significant noise
signal. Filter this noise with a large capacitor (1 µf) or by using a 32,000 Hz LC
filter across the load. Signal loops grounded at any other point are negligibly
affected by this noise and do not need filtering.
Figure 2-2. Transmitter Wiring
Connections.
Figure 2-3. Supply Voltage vs.
Load.
2-5
Page 18
Rosemount 1154
1.8
(45.7)
2.3
(58)
Center of Gravity
(Includes Bracket)
ACCEPTABLE ALTERNATE
MOUNTING
PANEL MOUNTING HOLE
PATTERN
(BACK SIDE)
MOUNTING BRACKET FOR PANEL
MOUNT SHOWN IN TYPICAL
MOUNTING CONFIGURATION
10 (254)
Minimum
Clearance
2.75
(69.9)
3
/8-in.
Bolts (4)
(Customer
Supplied)
4.93
(125)
1.2
(30)
2.3
(58)
Center of Gravity
(Includes Bracket)
5
(127)
2.81
(71.4)
NOTE
Dimensions are nominal in inches (millimeters).
NOTES
1. Orientation with respect to gravity is not critical.
2. Units can alternately be mounted with process
connection adjacent to bracket.
2.81 (71.4)
Reference Manual
00809-0100-4514, Rev BA
January 2008
INSTALLATION
PROCEDURES
Installation consists of mounting the transmitter and conduit and making
electrical connections. Procedures follow for each operation.
MechanicalTransmitter
Be careful not to break the neck seal between the sensor module and the
electronics housing.
The threaded interface between the sensor module and the electronics
housing is hermetically sealed before shipment. The integrity of this seal is
necessary for the safe operation of the transmitter during accident conditions.
If the seal is broken, reseal it according to “Connecting the Electrical Housing
to the Sensor Module” on page 5-7.
1.Mount the bracket to a panel or other flat surface as shown in
Figure 2-4. Use four
grade 2 bolts were used during qualification testing. Torque each bolt
to 19 ft-lb (26 N-m).
2.Attach the transmitter to the mounting bracket, as shown in
Figure 2-4. Use four
unit). Torque each bolt to 21 ft-lb (29 N-m).
/8-in. diameter bolts (not supplied with unit). SAE
7
/16-20 ⫻ 3/4 bolts with washers (supplied with
2-6
Page 19
Reference Manual
0.8
(20)
DETAIL A
3
/8-in. Mating
Tubing
Pressure
Range Code
Dimension
A
4, 52.13 (54)
6, 72.19 (55.6)
82.25 (57.2)
92.28 (57.9)
02.33 (59.1)
4.7 Max. (119.4)
4.7 Max. (119.4)
1.63
(41.3)
1.63
(41.3)
Low Side
Vent
Low Side
Vent
7
/16–20
UNF
(typical)
Dim.
A
Dim.
A
NOTE
Dimensions are nominal in inches
(millimeters).
4.72 Max. (119.9)
4.72 Max. (119.9)
9 Max.
(228.6)
9 Max.
(228.6)
3.4 (86.4)
3.4 (86.4)
0.8 (20) To End of Mating Tube
0.8 (20) To End of Mating Tube
Compression Fittings (2) Swagelok
for
3
/8-in. Tubing (optional 1/4–18
NPT available)
Compression Fittings (1) Swagelok for
3
/8-in.
Tubing (optional
1
/4–18 NPT available)
Welded
Drain/Vent Valve
(2) (optional
1
/4–
18 NPT
available)
Welded
Drain/Vent
Valve (1)
(optional
1
/4–18
NPT available)
0.75 (19)
Clearance for
Cover Removal
(typical)
Nameplate
(remove for zero
and span adjust)
Transmitter
Circuitry
(this side)
Ter min a l
Connections
(this side)
7
/16–14 UNC
(4 places)
0.75 (19) Clearance
for Cover Removal
(typical)
Nameplate
(remove for zero
and span adjust)
Transmitter
Circuitry
(this side)
Terminal
Connections
(this side)
7
/16–14 UNC
(4 places)
ROSEMOUNT 1154DP AND 1154HP
ROSEMOUNT 1154GP
3.7
(94)
7
/16–20
UNF
(typical)
3.7
(94)
1
/2–14 NPT
Conduit
Connection
(1 Place)
1
/2–14 NPT
Conduit
Connection
(1 Place)
00809-0100-4514, Rev BA
January 2008
Figure 2-5. Transmitter Dimensional Drawings.
Rosemount 1154
2-7
Page 20
Rosemount 1154
Blocking Valves
Flow
3-Valve Manifold
Plugged Tees for
Steam Service or
Sealing Fluid
Drain/Vent
Valves
Sufficient
Length
for Cooling
ROSEMOUNT 1154DP, HP
Plugged Tee for
Steam Service or
Sealing Fluid
Blocking
Valve
Drain/Vent
Valve
ROSEMOUNT 1154GP
Drain/Vent
Valve s
Drain/Vent
Valve
3-Valve
Manifold
Flow
ROSEMOUNT 1154DP, HP
ROSEMOUNT 1154 GP
LIQUID SERVICE
GAS SERVICE
L
H
Sufficient
Length
for Cooling
H
L
Sufficient
Length
for Cooling
Reference Manual
00809-0100-4514, Rev BA
January 2008
Conduit
1.Seal the conduit threads with thread sealant. (The transmitter conduit
seal interface was qualified using Grafoil
mate with a standard
2.Starting at zero thread engagement, install the conduit into the
transmitter between 4 and 7 turns, or a minimum of 12.5 ft-lb (16.9
N-m). Hold the electronics housing securely to avoid damaging the
threaded neck seal between the sensor module and the electronics
housing during conduit installation.
3.Provide separate support for the conduit if necessary.
Electrical1.Remove the cover from the terminal side of the transmitter
2-8
(see Figure 2-5 on page 2-7).
2.Connect the power leads to the “SIGNAL” terminals on the transmitter
terminal block (see Figure 2-7 on page 2-9). Torque the terminal
screws to 5 in-lb (0.6 N-m), or hand-tight.
NOTE
Do not connect signal leads to the “TEST” terminals.
3.Recheck connections for proper polarity.
4.Check the cover O-ring grooves for cleanliness. If chips or dirt are
present, clean the seat and mating portion of the cover with alcohol.
Lubricate replacement O-ring with O-ring grease (RMT P/N
01153-0248-0001 or P/N 01153-0053-0001). The transmitter was
qualified using Dow Corning
5.Spray the inside threads of the electronics covers with cover lubricant
(Rosemount P/N 01153-0333-0001 or equivalent) if necessary; if
covers are already sufficiently lubricated, do
not spray.
6.Carefully replace cover and tighten to 16.5 ft-lb (22.4 N-m).
OVERVIEWEach transmitter is factory calibrated to the range specified by the customer.
This section contains the following transmitter calibration information:
•Calibration
Span Adjustment
Zero Adjustment
•Calibration Procedures
Zero and Span Adjustment
Linearity Adjustment
Damping Adjustment
Correction for High Line Pressure
CALIBRATIONThe Rosemount 1154DP, HP, and GP transmitters are factory calibrated to the
range shown on the nameplate. This range may be changed within the limits
of the transmitter. Zero may also be adjusted to elevate or to suppress. The
span and zero adjustments are external and located under
the nameplate.
Span AdjustmentThe span on any Rosemount 1154 transmitter is continuously adjustable to
allow calibration anywhere between maximum span and
1
(
/4 of maximum span for Range Code 0). For example, the span on a Range
Code 4 transmitter can be continuously adjusted between 0–150 and 0–25
inH
O.
2
1
/6 of maximum span
Zero AdjustmentThe zero can be adjusted for up to 500 percent of span suppression (300
percent for Range Code 0) or 600 percent of span elevation (400 percent for
Range Code 0) (see Figure 3-1 on page 3-2).
The zero may be elevated or suppressed to these extremes with the limitation
that no applied pressure within the calibrated range exceeds the full-range
pressure limit. For example, a Range Code 4 transmitter cannot be calibrated
for 150 to 200 inH
inH
O exceeds the 150 inH2O upper range pressure limit of a Range Code 4.
2
The transmitter may be calibrated to cross zero, (e.g., –75 to 75 inH
this may result in a slight loss of linearity.
O (only 300 percent zero suppression) because the 200
2
O) but
2
www.rosemountnuclear.com
Page 24
Rosemount 1154
600% Zero Elevation
Output
(mA)
20
4
Pressure (inH2O)
600% Zero Elevation
➀
20
Output
(mA)
4
0
25
Pressure (inH2O)
No Zero Elevation or Suppression
➀
20
4
Output
(mA)
Pressure (inH2O)
500% Zero Suppression
➀
➀ Graphs based on a Range Code 4 (0–25 to 0–150 inH2O)
Rosemount 1154 with a calibrated span of 25 inH
2
O.
–150 –125 –100
–75 –50
–250
25
0
2550
75 100 125 150
Figure 3-1. Zero Adjustment
Range.
Reference Manual
00809-0100-4514, Rev BA
January 2008
CALIBRATION
PROCEDURES
Zero and Span
Adjustment
NOTE
The Rosemount 1154 Pressure Transmitter contains electronic circuit boards
which may be static sensitive.
NOTE
Covers need not be removed for zero and span adjustment.
The zero and span adjustment screws are accessible externally. They are
located behind the nameplate on the side of the electronics housing (see
Figure 3-2 on page 3-3). The transmitter output increases with clockwise
rotation of the adjustment screws.
The zero adjustment screw has very little effect on the span. The span
adjustment, however, does affect the zero. The effect of interaction is more
apparent with suppression or elevation. The span adjustment changes the
zero output and the full-scale output by approximately the same percentage.
Therefore, it is best to calibrate the transmitter from zero to the desired span
and finish the calibration by adjusting the zero screw to achieve the desired
elevation or suppression.
3-2
Page 25
Reference Manual
Zero
Span
4mA
Existing Span
Desired Span
------------------------------------×4mA
100 inH
2
O
50 inH
2
O
----------------------------- -×8mA==
00809-0100-4514, Rev BA
January 2008
Figure 3-2. Zero and Span
Adjustment Screws.
Rosemount 1154
Example (for Range Code 4)
Initial transmitter calibration: 25 to 125 inH
(100 inH
O span with zero suppressed 25 inH2O)
2
Desired transmitter calibration: –75 to –25 inH
(50 inH
O span with zero elevated 75 inH2O)
2
1.Adjust the zero to eliminate any existing zero elevation or
suppression. With 0 inH
O pressure applied to the transmitter, turn
2
the zero adjustment until the output reads 4 mA. The unit is now
calibrated for 0 to 100 inH
O.
2
2.Adjust the span to the desired new span. To reduce the span, turn the
span screw until the output, with 0 inH
O
2
O
2
O pressure input, equals:
2
3.Adjust the zero screw to bring the output, with 0 inH
4 mA. The transmitter calibration should now be very close to 0 to 50
inH
4.Check full-scale output and fine tune the span and zero adjustment if
required. Remember zero adjustments do not affect span, but span
adjustments do affect zero predictably. Adjusting the span screw
affects the zero
this effect, simply overadjust by 25 percent.
For example, if, after completing step 3, the transmitter output reads
19.900 mA at 50 inH
(at 50 inH
19.900 + (20.000 – 19.900) ⫻ 1.25 =
19.900 + 0.125 = 20.025
Since the span adjustment affects zero 1/5 as much as the span, the
0.125 mA increase in span causes a 0.025 mA increase in zero.
Therefore, turn the zero adjustment (at 50 inH
reads 20.000 mA. The unit should now be calibrated for 0 to 50
inH
5.Zero Elevation/Suppression. Elevate zero. Turn the screw until the
output reads 4 mA with –75 inH
transmitter (applying 75 inH
give the same result). The output may stop changing before the
desired 4 mA reading is obtained. If this occurs, turn off power to the
unit and unplug the amplifier board (refer to “Electrical Housing
Disassembly” on page 5-6 and Table 5-1 on page 5-5). To elevate or
suppress zero a large amount, use the following procedure:
O input, back to
2
O.
2
1
/5 as much as it affects the span. To compensate for
•Solder: 60% tin, 40% lead (60/40) – Fed Spec QQ-S-571
•Flux: MIL F 14256, Type A, Fed Spec QQ-S-571 Type RA
Method
a. Locate the three turret terminals on the component side of the
amplifier board. Remove any jumper wires between them (see
Figure 3-3).
b. To elevate zero, connect a jumper wire between the middle
terminal and the terminal marked “EZ” (see Figure 3-3, Detail B).
c. Wrap the jumper wire once around each terminal and cut off
any excess.
d. Solder the jumper wire to the terminals using proper electronics
soldering techniques. Clean solder joints thoroughly with isopropyl
alcohol.
e. Plug the amplifier board back in and complete the
zero adjustment.
Figure 3-3. Jumper Wire
Placement.
To suppress zero, follow the same procedure, except connect the jumper wire
between the middle terminal and the terminal marked “SZ” (see Figure 3-3,
Detail C).
6.Recheck full scale and zero and fine tune if necessary.
NOTE
There is some mechanical backlash in the zero and span adjustments, so
there is a dead band when you change the direction of adjustment. Because
of the backlash, the simplest procedure, if the desired setting is overshot, is to
intentionally overshoot a larger amount before reversing the direction of the
adjustment.
Linearity AdjustmentIn addition to the span and zero adjustments, there is a linearity adjustment
located inside the transmitter on the amplifier board (see Figure 3-4 on
page 3-5). Linearity is factory calibrated for optimum performance over the
calibrated range of the instrument and is not normally adjusted in the field. If
you want to maximize linearity over some particular range, use the following
procedure:
1.Apply mid-range pressure and note the error between theoretical and
actual output signal.
2.Apply full-scale pressure. Multiply the error noted in step 1 by six and
by the rangedown factor:
3.Add the result to the full-scale output for negative errors, or subtract
the result from the full-scale output for positive errors by adjusting the
linearity trimmer (see Figure 3-4). Example: At
4-to-1 rangedown the midscale point is low by 0.05 mA. Therefore,
adjust the “Linearity” trimmer until full-scale output increases by (0.05
mA ⫻ 6 ⫻ 4) = 1.2 mA.
4.Readjust zero and span.
NOTE
If you remove either cover during the above procedures, replace the O-ring
and torque the cover per the instructions given in Section 5 Maintenance and Troubleshooting. Spare cover O-rings are supplied with each
transmitter.
Figure 3-4. Linearity and
Damping Adjustment.
Damping AdjustmentDamping electronics are available as an option. Transmitters with standard
electronics can be retrofitted with the adjustable damping feature by changing
out both the amplifier board (RMT P/N 01154-0021-0004) and the calibration
board (RMT P/N 01154-0023-0002).
3-5
Page 28
Rosemount 1154
Reference Manual
00809-0100-4514, Rev BA
January 2008
The damping adjustment permits damping of rapid pressure variations by
adjusting the single-turn trim potentiometer located on the upper right-hand
side of the amplifier board (see Figure 3-4). The available settings, when
adjusted to the maximum position, provide time-constant values of at least 1.2
seconds for Range Code 4 and 0.8 seconds for Range Codes 5–9 and 0.
Transmitters with the electronic damping option are calibrated and shipped
with the adjustment set at the counterclockwise stop, giving the minimum
time-constant.
To adjust the damping, turn the damping adjustment potentiometer until the
desired time-constant is obtained. It is best to set the damping to the shortest
possible time-constant. Since transmitter calibration is not affected by the
damping setting, you may adjust the damping with the transmitter installed on
the process.
The damping adjustment potentiometer has positive stops at both ends. Forcing
the potentiometer beyond the stops may cause permanent damage.
Correction For High Line
Pressure (Rosemount
1154DP and 1154HP
Only)
NOTE
If you remove either cover during the above procedures, replace the O-ring
and torque the cover per the instructions given in Section 5 Maintenance and Troubleshooting of this manual. Spare cover O-rings are supplied with
each transmitter.
Span
If a differential transmitter is calibrated with the low side at ambient pressure
but will be used at high line pressure, correct the span adjustment to
compensate for the effect of static pressure on the unit. If zero is elevated or
suppressed, also correct the zero adjustment. Correction factors, expressed
in percent of differential pressure input at end points per 1,000 psi static
pressure, are:
Range Codes 4, 5, and 8:
+0.75% of input/1,000 psi
Range Codes 6 and 7:
+1.25% of input/1,000 psi
The correction procedure below uses the following example:
Range Code 5, calibrated at –100 to 300 inH
line pressure. Note that steps 3–6 are omitted for ranges based at zero
differential pressure.
1.Calibrate the unit per preceding section to output = 4 mA at –100
inH
O and 20 mA at 300 inH2O.
2
2.Calculate correction factor:
3.Calculate zero adjustment correction in terms of pressure:
4.Convert pressure correction to percent of input span:
5.Calculate correction in terms of output span (mA):
6.Add the milliamp correction to the ideal zero output (4 mA). This is the
corrected ideal zero output:
7.Calculate full-scale adjustment correction in terms of pressure:
8.Repeat step 4 with the results of step 7:
9.Repeat step 5 with the result of step 8:
10. Add the mA correction to the ideal full-scale output (20 mA). This is
the corrected ideal full-scale output:
11. Readjust zero and span adjustments for corrected outputs:
3.964 mA at –100 inH
20.108 mA at 300 inH
O
2
O
2
There is an uncertainty of ±0.5 percent of input reading per 1,000
psi associated with the span correction.
Zero
Zero shift with static pressure is not systematic. However, if the calibrated
range includes zero differential pressure, the effect can be trimmed out after
installation and with the unit at operating pressure.
3-7
Page 30
Rosemount 1154
Reference Manual
00809-0100-4514, Rev BA
January 2008
Equalize pressure to both process connections, and turn the zero adjustment
until the ideal output at zero differential input is observed. Do not readjust the
span potentiometer.
If the transmitter does not include zero differential pressure within its
calibrated span, the zero effect or zero correction can be determined before
the unit is suppressed or elevated to eliminate the zero effect after correcting
for the span effect.
The following procedure illustrates how to eliminate the zero effect for a
non-zero differential pressure calibration. The example uses a Range Code 5,
calibrated from 100 to 500 inH
1.Using standard calibration procedures, calibrate the unit to the
required span, with the 4 mA or zero point corresponding to zero
differential pressure:
O, with 1,200 psi static line pressure.
2
4 mA at 0 inH
O and 20 mA at 400 inH2O
2
2.Apply static pressure to both high and low process connections with
zero differential pressure across the transmitter, and note the zero
correction (zero shift). For example, if the output reads 4.006 mA, the
zero correction is calculated as:
4.00 mA – 4.006 mA = –0.006 mA
Note the sign associated with this correction, as this result is added
when determining the final, ideal transmitter output.
3.Remove static pressure and correct for the span effect as outlined in
the span correction procedure. Calibrate the unit to the calculated
output values. If, for example, the span correction procedure yielded
4.029 mA and 20.144 mA, calibrate the unit for:
4.029 mA at 100 inH
20.144 mA at 500 inH
O
2
O
2
4.Add the zero correction (–0.006 mA), found in step 2, to the ideal zero
point value calculated in step 3.
4.029 mA + (–0.006 mA) = 4.023 mA
5.To eliminate the zero effect, readjust the zero potentiometer so the
output reads the ideal zero point calculated in step 4 (do not readjust
the span potentiometer). Note that all the calibration points will shift
the same amount toward the correct reading. The example output is
now 4.023 mA at 100 inH
O.
2
The transmitter output is now 4–20 mA over its calibrated span when the unit
is operated at 1,200 psi static line pressure.
OVERVIEWThis section provides brief descriptions of basic transmitter operations in the
following order:
•Transmitter Operation
™
•The ␦-Cell
•Demodulator
•Linearity Adjustment
•Oscillator
•Voltage Regulator
•Zero and Span Adjustments
•Current Control
•Current Limit
•Reverse Polarity Protection
Sensor
TRANSMITTER
OPERATION
www.rosemountnuclear.com
The block diagram in Figure 4-2 on page 4-3 illustrates the operation of the
transmitter.
The Rosemount 1154 Alphaline Pressure Transmitters have a variable
capacitance sensing element, the δ-Cell (Figure 4-1 on page 4-2). Differential
capacitance between the sensing diaphragm and the capacitor plates is
converted electronically to a 2-wire 4–20 mA dc signal.
Where:
Pis the process pressure.
Page 32
Rosemount 1154
fV
pp–
I
ref
C1C2+
--------------------=
I
diff
fV
pp–C2C1
–()=
PConstant I
diff
×I
ref
C2C1–
C
2C1
+
--------------------
⎝⎠
⎜⎟
⎛⎞
==
Leadwires
Isolating
Diaphragm
Welded Seals
Capacitor
Plates
Sensing
Diaphragm
Rigid
Insulation
Silicone Oil
Reference Manual
00809-0100-4514, Rev BA
K1is a constant.
is the capacitance between the high pressure side and the sensing
C
1
diaphragm.
is the capacitance between the low pressure side and the sensing
C
2
diaphragm.
Where:
is the current source.
I
ref
is the peak-to-peak oscillation voltage.
V
p-p
fis the oscillation frequency.
Where:
is the difference in current between C1 and C2.
I
diff
January 2008
Figure 4-1. The
Therefore:
δ-Cell.
4-2
Page 33
Reference Manual
DEMODULATOR
CURRENT
DETECTOR
OSC.
CONTROL
AMP.
OSCILLATOR
SENSOR
VOLTAGE
REGULATOR
CURR.
CONTROL
AMP.
CURRENT
LIMITER
REVERSE
POLARITY
PROTECTION
CURRENT
CONTROL
-
+
TEST
SIGNAL
+
-
I
diff
fV
pp–C2C1
–()=
00809-0100-4514, Rev BA
January 2008
Figure 4-2. Electrical Block
Diagram.
Rosemount 1154
THE δ-CELL™ SENSORProcess pressure is transmitted through an isolating diaphragm and silicone
oil fill fluid to a sensing diaphragm in the center of the
pressure is transmitted in like manner to the other side of the sensing
diaphragm.
The position of the sensing diaphragm is detected by the capacitance plates
on both sides of the sensing diaphragm. The capacitance between the
sensing diaphragm and either capacitor plate is approximately 150 pf. The
sensor is driven through transformer windings by an oscillator at roughly 32
kHz and 30 V
p-p
.
δ-Cell. The reference
DEMODULATORThe demodulator consists of a diode bridge that rectifies the ac signal from
the sensor cell to a dc signal.
(the sum of the dc currents through two
ref
LINEARITY
ADJUSTMENT
The oscillator driving current, I
transformer windings) is controlled to be a constant by an integrated circuit
amplifier.
The dc current through a third transformer winding is a current directly
proportional to pressure, i.e.,
The diode bridge and span temperature compensating thermistor are located
inside the sensor module. The effect of the thermistor is controlled by
resistors located in the electronics housing.
Linearity is adjusted by a variable-resistance network, capacitor, and diodes.
The currents generated through this part of the circuit are summed into the
inputs of the oscillator control circuit. This provides a programmed correction
that raises the oscillator peak-to-peak voltage to compensate for first-order
nonlinearity of capacitance as a function of pressure.
4-3
Page 34
Reference Manual
fV
pp–
I
ref
C1C2+
--------------------=
00809-0100-4514, Rev BA
Rosemount 1154
January 2008
OSCILLATORThe oscillator has a frequency determined by the capacitance of the sensing
element and the inductance of the transformer windings.
The sensing element capacitance is variable. Therefore, the frequency is
variable about a nominal value of 32 kHz.
An integrated circuit amplifier is used as a feedback control circuit and
controls the oscillator drive voltage such that:
VOLTAGE REGULATORThe transmitter uses a zener diode, transistor, and resistors to provide a
constant voltage of 6.4 V dc for the reference and 7 V dc for the oscillator.
ZERO AND SPAN
ADJUSTMENTS
Zero adjustment components consist of a potentiometer and resistor that
develop a separate adjustable current that sums with the sensor current. The
coarse zero switch switches resistors into the circuit as needed.
Span adjustment is performed with a potentiometer which determines the
amount of loop current which is sensed and fed back to the current control
amplifier.
CURRENT CONTROLThe current control amplifier consists of an integrated circuit, two transistors,
and associated components. The IC reference voltage is established at the
junction of a resistor network. The current control amplifier drives the current
control to a level such that the current detector feeds back a signal equal to
the sum of the zero current and the variable sensor current.
CURRENT LIMITA current limiter prevents the output current from exceeding 30 mA in an
overpressure condition.
REVERSE POLARITY
A zener diode provides reverse polarity protection.
Use only the procedures and new parts specifically referenced in this manual to
ensure specification performance and certification compliance. Unauthorized
procedures or parts can render the instrument dangerous to life, limb, or property.
Rosemount 1154
OVERVIEWThis section outlines a technique for checking out the components, a method
for disassembly and reassembly, and a troubleshooting guide.
NOTE
Maintenance of traceability of any replacement parts is the responsibility of
the user (see “Important Notice” on page 6-11 and Important Notice at the
beginning of this manual preceding the Table of Contents).
The Rosemount 1154 has no moving parts and requires a minimum of
scheduled maintenance. Calibration procedures for range adjustment are
outlined in Section 3: Calibration. A calibration check should be conducted
after inadvertent exposure to overpressure, unless your plant considers this
factor separately in the plant error analysis.
Test terminals are available for in-process checks. For further checks, the
transmitter can be divided into three active physical components: the sensing
module, the amplifier board, and the calibration board.
An exploded view of the transmitter is provided in Figure 5-2 on page 5-5. In
the following procedures, numbers in parentheses refer to item numbers in the
exploded view.
www.rosemountnuclear.com
Page 36
Reference Manual
COMPONENT SIDE UP
00809-0100-4514, Rev BA
Rosemount 1154
January 2008
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the people performing the operations. Information that
raises potential safety issues is indicated by a warning message. The following
warning messages appear in this section.
Use only the procedures and new parts specifically referenced in this manual to
ensure specification performance and certification compliance. Unauthorized
procedures or parts can render the instrument dangerous to life, limb, or property.
Process O-rings may retain some process fluid after disassembly of process
flanges. If this fluid is determined to be contaminated, take appropriate safety
measures.
TEST TERMI NALSThe test terminals are connected across a diode through which the loop signal
current passes. The indicating meter or test equipment shunts the diode when
connected to the test terminals. As long as the voltage across the terminals is
kept below the diode threshold voltage, no current passes through the diode.
To ensure that there is no current leaking through the diode while making a test
reading or when connecting an indicating meter, the resistance of the test connection or meter should not exceed 10 Ω .
BOARD CHECKOUTNOTE
Numbers in parentheses refer to item numbers in Figure 5-2 on page 5-5.
NOTE
The Rosemount 1154 Pressure Transmitter contains electronic circuit boards
which may be static sensitive.
You can easily check the printed circuit boards (5 and 6) for a malfunction by
substituting spare boards into the circuit. If this procedure turns up a malfunctioning board, return the defective board to Rosemount Nuclear Instruments,
Inc. for replacement. Because of parts traceability, qualification becomes the
responsibility of the customer in the event of unauthorized board repairs.
Figure 5-1. Header Board
Connections.
5-2
Page 37
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
SENSING MODULE
CHECKOUT
NOTE
Numbers in parentheses refer to item numbers in Figure 5-2 on page 5-5.
The sensing module (12) is not field-repairable and must be replaced if
defective. If no defect such as a punctured isolating diaphragm or loss of fill
fluid is observed, check the sensing module in the following manner:
1.Disengage the header assembly board (4) as described in step four
of the electrical housing disassembly procedure on page 5-6. You
need not remove the sensing module from the electrical housing for
checkout.
2.Jump connections 1 and 2 on the header assembly board (see Figure
5-1 on page 5-2).
3.Using a low-voltage ohmmeter, check the resistance between the
jumper wire and the sensing module housing. This resistance should
be greater than 10 MΩ . Remove the jumper wire.
4.Jump connections 3 and 4 on the header assembly board and repeat
step 3 (see Figure 5-1 on page 5-2).
NOTE
The above procedure does not completely test the sensing module. If circuit
board replacement does not correct the abnormal condition and no other
problems are obvious, replace the sensing module.
5-3
Page 38
Rosemount 1154
DISASSEMBLY
PROCEDURE
Reference Manual
00809-0100-4514, Rev BA
January 2008
Process Flange Removal
NOTE
Numbers in parentheses refer to item numbers in Figure 5-2 on page 5-5.
NOTE
The Rosemount 1154 Pressure Transmitter contains electronic circuit boards
which may be static sensitive.
Process O-rings may retain some process fluid after disassembly of process
flanges. If this fluid is determined to be contaminated, take appropriate safety
measures.
NOTE
Read the Process Flange Reassembly Procedure on page 5-8 before
attempting disassembly. Special testing and traceability are required.
1.Remove the transmitter from service before disassembling flanges.
2.Detach process flanges (13, 15) by removing the four large bolts (14).
Take care not to scratch or puncture the isolating diaphragms.
Identify high and low (“H” and “L”) flanges for reassembly.
NOTE
Carefully remove the O-rings (11) from the cell if they do not come off when
the flange is removed. Do not pry the O-ring from its seat, as you may
damage the isolating diaphragm.
3.Clean isolating diaphragms with a soft rag and a mild cleaning
solution. Do not use any chlorine or acid solutions to clean the
diaphragms. Rinse diaphragms with distilled water.
5-4
Page 39
Reference Manual
1
2
3
5
4
6
7
1
2
10
9
10
8
13
11
12
11
15
14
A
B
C
D
A
B
C
D
12
15
11
Module
Flange
O-ring
Detail A
16
17
20
18
19
00809-0100-4514, Rev BA
January 2008
Figure 5-2. Rosemount 1154, Exploded View.
Rosemount 1154
Table 5-1. Rosemount 1154 Parts List.
PartDescriptionPartDescription
1Electronics Cover 11Metal O-Ring for Process Flange
2O-Ring for Electronics Cover12Sensor Module
3Electronics Housing13Process Flange
4Header Assembly Board14Process Flange Bolts
5Calibration Board15Process Flange
6Amplifier Board16Zero and Span Adjustment Screws
7Holding Screws17Nameplate
8Process Flange Nuts18Snap Rings
9Sensor Module Lock Nut19O-Ring for Adjustment Screw
10Valve Stem20Nameplate Screws
5-5
Page 40
Rosemount 1154
Reference Manual
00809-0100-4514, Rev BA
January 2008
Electrical Housing
Disassembly
1.The signal terminals and test terminals are accessible by unscrewing
the cover (1) on the terminal side. This compartment is identified as
“terminal side” on the nameplate. The terminals are permanently
attached to the housing and must not be removed.
2.Circuit boards are located in a separate compartment identified as
“Circuit Side” on the nameplate. Remove power from the transmitter
before removing the circuit side cover. Unscrew the cover (1) on the
circuit side to access the circuit boards. A special cover wrench (RMT
P/N 01153-0382-0001) is available from Rosemount to remove and
replace the housing covers.
3.Unplug the amplifier board (6) after removing 3 holding screws (7).
4.The header assembly board (4) is permanently attached to the sensor
module (12) and contains the temperature-compensating resistors.
Carefully pull this board off the bayonet pins and rotate the board 180
degrees about the axis formed by the connecting leads. This allows
access to the calibration board (5).
5.Disconnect the calibration board (5) by aligning the zero and span
adjust screws so that their slots are perpendicular to the board.
Remove the board by inserting a 6–32 screw in the rivnut on the
board and carefully pulling the board off the bayonet pins.
6.If replacement of the zero and span adjustment screws (16) is
necessary, remove the nameplate (17) and detach the snap rings (18)
inside the housing.
Removing Sensor
Module from Electrical
Housing
REASSEMBLY
PROCEDURE
1.Remove flanges per Process Flange Removal Section on page 5-4.
2.Remove amplifier board and calibration board as described in the
Electrical Housing Disassembly Section above.
3.Loosen the lock nut (9).
4.Unscrew the sensor module (12) from the electronics housing,
simultaneously turning the header board and leads to prevent them
from being twisted or damaged. The threaded connection has a
sealing compound on it and must be broken loose. Be careful not to
damage the isolating diaphragms when unscrewing the sensor
module. Then carefully pull the header assembly board (4) through
the hole.
5.The sensor module (12) is a welded assembly and cannot be further
disassembled.
NOTE
Numbers in parentheses refer to item numbers in Figure 5-2 on page 5-5.
NOTE
The Rosemount 1154 Pressure Transmitter contains electronic circuit boards
which may be static sensitive.
5-6
Page 41
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
Preliminary1.Replace the cover O-rings (2) whenever you remove a cover. Clean
the sealing areas with alcohol, if necessary, and lightly grease the
O-ring with Dow Corning 55 Silicone O-ring Grease (Rosemount P/N
01153-0248-0001 or P/N 01153-0053-0001). Spray the inside threads
of the electronics covers with cover lubricant (Rosemount P/N
01153-0333-0001 or equivalent) if necessary; if covers are already
sufficiently lubricated, do not spray.
2.Verify that the circuit boards are clean.
3.Verify that the bayonet pins on the connection board are clean.
4.If you remove the sensor module, clean the thread sealant from the
sensor module threads, lock nut, and electronics housing threads
with a wire brush.
Connecting the Electrical
Housing to the Sensor
Module
Electrical Housing
Reassembly
1.Run the lock nut down to the base of the sensor module threads.
3
2.Apply a heavy, continuous bead (about
580-PST sealant (RMT P/N 01153-0329-0001) around the top sensor
module threads.
3.Insert the header assembly board (4) through the hole in the bottom
of the electronics housing.
4.Screw the sensor module (12) into the electrical housing (3) making
sure that five full threads are engaged. Be careful not to damage or
twist the sensor leads. Turn the header board to avoid
twisting wires.
5.Align the sensor module with the high and low pressure sides
oriented per Figure 2-5 on page 2-7. Alternately, tighten the module
one-half turn further to reverse the orientation of the module about the
electronics housing.
6.Tighten the lock nut (9) to 35 ft-lb (48 N-m) torque.
7.Wipe off excess sealant.
8.Place the assembled unit in an oven at 200 ±5 °F (93 ± 3 °C) for 12
hours to cure the sealant.
1.Replace the zero and span adjustment screw O-rings (19) whenever
you remove the zero and span adjustment screws (16). Lightly grease
the O-rings with Dow Corning 55 Silicone O-ring Grease (Rosemount
P/N 01153-0248-0001 or P/N 01153-0053-0001). Reinstall the
adjustment screws and secure with snap rings (18).
2.Align the zero and span adjustment screws with the potentiometer
stems on the calibration board (5) and push the calibration board onto
the bayonet pins.
3.Slide the header assembly board (4) onto the bayonet pins with the
component side toward the pins. Slide any excess wire behind the
calibration board, taking care to avoid kinks.
4.Push the amplifier board (6) onto the bayonet pins and secure with
holding screws (7). Use nominal torque of 10 in-lb (1.1 N-m).
5.Carefully replace the cover and tighten to 16.5 ft-lb (22.4 N-m)
(“Preliminary” on page 5-7).
6.Replace the nameplate (17), and secure with two nameplate
screws (20).
/8-in. wide) of Loctite®
5-7
Page 42
Rosemount 1154
Reference Manual
00809-0100-4514, Rev BA
January 2008
Process Flange
Reassembly
1.Replace the metal O-rings (11) with new O-rings if the flanges
were removed.
2.Carefully place an O-ring (11) in the isolator well of the high side (“H”)
of the sensing module. Place the O-ring so the edge of the rolled ring
faces the module (see Detail A of Figure 5-2 on page 5-5).
3.Carefully place the flange (13 or 15) as shown in Figure 5-2 on
page 5-5. Take care not to disturb the O-rings or damage the
diaphragms.
4.On differential units, repeat steps 2 and 3 for the low side (“L”) of the
module. If a gage unit has two O-rings (one on each side), repeat
steps 2 and 3 for the low side. If the gage unit has only one O-ring,
reassemble with one O-ring on the high side.
5.Keeping the flanges parallel to each other and to the module faces,
insert the four bolts (14) (and four washers on Range Code 9) and
finger-tighten the nuts (8).
Each spare parts kit contains the correct number of nuts, bolts, and
washers for the specific transmitter range code it is designated for.
Due to consolidation of parts kits, the bolt length and quantity of
washers required may differ from existing transmitter assemblies
and/or parts kits. Verify by part number that the appropriate spare
parts kit is used for the transmitter range code being re-assembled.
Contact Rosemount Nuclear Instruments, Inc. if there are questions.
6.Evenly seat the flanges on the sensor module housing, using a hand
torque wrench as specified in steps 7 through 11. See Figure 5-2 on
page 5-5 to identify the bolts.
7.Alternately tighten bolts A and B to 10 ft-lb (13.6 N-m) torque.
8.Alternately tighten bolts C and D to 10 ft-lb (13.6 N-m) torque.
9.Check the torque on bolts A and B.
10. Check the torque on bolts C and D.
11. Repeat steps (7)-(10) at 15 ft-lb (20 N-m) torque, at 20 ft-lb
(27 N-m) torque, at 25 ft-lb (34 N-m) torque, at
30 ft-lb (41 N-m) torque, and at 35 ft-lb (48 N-m) torque until all bolts
are torqued to 35 ±1 ft-lb (48 ±1 N-m).
12. Expose all ranges of gage transmitters to two temperature cycles
over the expected temperature operating range before calibrating.
Expose differential and high-line differential Range Code 4’s to two
temperature cycles over the expected temperature operating range
before calibrating.
5-8
Page 43
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
POST ASSEMBLY TESTS1.Conduct hydrostatic testing to 150% of maximum working pressure or
2,000 psi, whichever is greater.
2.Calibrate the transmitter per the calibration section of this manual.
3.Conduct nuclear cleaning to 1 ppm chloride content of transmitter
“wetted parts.”
High OutputPrimary ElementCheck for restrictions at primary element, improper installation or poor condition. Note any
Impulse PipingCheck for leaks or blockage.
Transmitter
Electronics
Transmitter
Electronics Failure
Sensing ModuleSee Sensing Module Checkout section. The sensing element is not field repairable and must
Power SupplyCheck the power supply output voltage at the transmitter.
changes in process fluid properties that may affect output.
Ensure blocking locking valves are fully open.
Check for entrapped gas in liquid lines, or liquid in dry lines.
Ensure that density of fluid in impulse line is unchanged.
Check for sediment in transmitter process flanges.
Make sure that post connectors and the sensor connections are clean. If the electronics are
still suspect, substitute new electronics.
be replaced if found to be defective. See “Disassembly Procedure” for instructions on
disassembly. Check for obvious defects, such as a punctured isolating diaphragm or fill fluid
loss, and contact Rosemount Nuclear Instruments, Inc. at (952) 949-5210.
Continued on Next Page
5-9
Page 44
Rosemount 1154
Do not use over 100 volts to check the loop, or damage to the transmitter
electronics may result.
Do not use over 100 volts to check the loop, or damage to the transmitter
electronics may result.
SymptomPotential SourceCorrective Action
Reference Manual
00809-0100-4514, Rev BA
January 2008
Low Output or
No Output
Erratic OutputLoop Wiring
Primary ElementCheck for restrictions at primary element, improper installation or poor condition.
Loop Wiring
Impulse PipingEnsure that the pressure connection is correct.
Transmitter
Electronics
Connections
Test Diode FailureReplace electronics housing.
Transmitter
Electronics Failure
Sensing ModuleNOTE: See Sensing Module Checkout section. The sensing element is not field repairable
Power SupplyCheck the power supply output voltage at the transmitter.
Note any changes in process fluid properties that may affect output.
Check for adequate voltage to the transmitter.
Check the milliamp rating of the power supply against the total current being drawn for all
transmitters being powered.
Check for shorts and multiple grounds.
Check for proper polarity at the signal terminal.
Check loop impedance.
Check wire insulation to detect possible shorts to ground.
Check for leaks or blockage.
Check for entrapped gas in liquid lines.
Check for sediment in the transmitter process flange.
Ensure that blocking valves are fully open and that bypass valves are tightly closed.
Ensure that density of the fluid in the impulse piping is unchanged.
Ensure that calibration adjustments are in allowable range.
Check for shorts in sensor leads.
Make sure post connectors are clean, and check the sensor connections.
If the electronics are still suspect, substitute new electronics.
and must be replaced if found to be defective. See “Disassembly Procedure” for instructions
on disassembly. Check for obvious defects, such as a punctured isolating diaphragm or fill
fluid loss, and contact Rosemount Nuclear Instruments, Inc. at (952) 949-5210.
Check for inadequate voltage to the transmitter.
Check for intermittent shorts, open circuits, or multiple grounds.
Impulse Piping and
Process
Connections
Transmitter
Electronics
Transmitter
Electronics Failure
Power SupplyCheck power supply output voltage.
5-10
Check for entrapped gas in liquid lines, or liquid in dry lines.
Check for intermittent shorts or open circuits.
Make sure that bayonet and sensor connectors are clean and properly connected.
Qualified per IEEE Std 323-1974 and IEEE Std 344-1975, as stated in
Rosemount Report D8400102.
Radiation
Accuracy within ±(1.5% of upper range limit + 1.0% of span) during and after
exposure to 55 megarads TID gamma radiation at the centerline at the
following dose rate: 2 megarads/hr for 2 hr,
1.5 megarad/hr for 4 hr, 1 megarad/hr up to
55 megarads TID and an additional 55 megarads TID at a rate of
1 megarad/hr during post-accident operation
Range Code 0: ±(2.25% of upper range limit + 1.0% of span)
Seismic
Accuracy within ±0.5% of upper range limit after a seismic disturbance
defined by a required response spectrum with a ZPA of 7 g
Range Code 0: ±0.75% of upper range limit
Steam Pressure/Temperature
Accuracy within ±(2.5% upper range limit + 0.5% of span) during and after
sequential exposure to steam at the following temperatures and pressures,
concurrent with chemical spray for the first 24 hr:
420 °F (215.6 °C), 50 psig for 3 minutes
350 °F (176.6 °C), 110 psig for 7 minutes
320 °F (160.0 °C), 75 psig for 8 hours
265 °F (129.4 °C), 24 psig for 56 hours
www.rosemountnuclear.com
Range Code 0: ±(3.75% of upper range limit + 0.5% of span)
Chemical Spray
Composition is 0.28 molar boric acid, 0.064 molar sodium thiosulfate, and
sodium hydroxide to make an initial pH of 11.0 and a subsequent pH ranging
from 8.5 to 11.0. Chemical spray is sprayed at a rate of
0.25 gal/min/ft
2
.
Page 46
Rosemount 1154
Electronics
Qualified Life
Temperature (°F)
Time (Years)
Module
Qualified Life
Reference Manual
00809-0100-4514, Rev BA
January 2008
Post DBE Operation
Accuracy at reference conditions shall be within ±2.5% of upper range limit
(±3.75% for Range Code 0) for one year following DBE.
Quality Assurance Program
In accordance with NQA-1, 10CFR50 Appendix B, and ISO 9001:2000
Nuclear Cleaning
To 1 ppm maximum chloride content
Hydrostatic Testing
To 150% of maximum working pressure or 2,000 psi (13.8 MPA), whichever is
greater
Traceability
In accordance with NQA-1, 10CFR50 Appendix B; chemical and physical
material certification of pressure-retaining parts
Qualified Life
Figure 6-1. Qualified Life vs.
Ambient Temperature.
The transmitter qualified life is dependent on continuous ambient temperature
at the installation site (see Figure 6-1). Replacement of amplifier and
calibration circuit boards at the end of their qualified life permits extension of
the transmitter qualified life to the module qualified life. See Rosemount
Report D8400102 for details.
PERFORMANCE
SPECIFICATIONS
6-2
Based on zero-based ranges under reference conditions.
Accuracy
±0.25% of calibrated span; includes combined effects of linearity, hysteresis,
and repeatability
Dead Band
None
Page 47
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
Drift
±0.2% of upper range limit for 30 months
Range Code 0: ±(0.3% of upper range limit)
Temperature Effect
Range Codes 4–9:
±(0.75% upper range limit +0.5% span) per 100 °F (55.6 °C) ambient
temperature change
Range Code 0:
±(1.13% upper range limit +0.5% span) per 100 °F (55.6 °C) ambient
temperature change
Overpressure Effect
Rosemount 1154DP:
Maximum zero shift after 2,000 psi (13.8 MPa) overpressure:
Range CodeOverpressure Effect
4±0.25% of upper range limit
5±1.0% of upper range limit
6, 7±3.0% of upper range limit
8±6.0% of upper range limit
Rosemount 1154HP:
Maximum zero shift after 3,000 psi (20.68 MPa) overpressure:
Range CodeOverpressure Effect
4±1.0% of upper range limit
5±2.0% of upper range limit
6, 7±5.0% of upper range limit
Rosemount 1154GP:
Maximum zero shift after 2,000 psi (13.8 MPa) overpressure:
Range CodeOverpressure Effect
4±0.25% of upper range limit
5–8±1.0% of upper range limit
After 4,500 psi (31.0 MPa) overpressure:
Range CodeOverpressure Effect
9±0.5% of upper range limit
After 6,000 psi (41.37 MPa) overpressure:
Range CodeOverpressure Effect
0±0.25% of upper range limit
6-3
Page 48
Rosemount 1154
Reference Manual
00809-0100-4514, Rev BA
January 2008
Static Pressure Zero Effect
Rosemount 1154DP:
Per 1,000 psi (6.89 MPa):
Range CodeStatic Pressure Zero Effect
4, 5±0.2% of upper range limit
6–8±0.5% of upper range limit
Rosemount 1154HP:
Per 1,000 psi (6.89 MPa):
Range CodeStatic Pressure Zero Effect
All Ranges±0.66% of upper range limit
Static Pressure Span Effect
Effect is systematic and can be calibrated out for a particular pressure before
installation. Correction uncertainty is ±0.5% of input
reading/1,000 psi (6.89 MPa).
FUNCTIONAL
SPECIFICATIONS
Power Supply Effect
Less than 0.005% of output span/volt
Load Effect
No load effect other than the change in voltage supplied to
the transmitter
Mounting Position Effect
No span effect; zero shift of up to 1.5 inH
O (372 Pa) which can be calibrated
2
out
Response Time
Fixed time constant (63%) at 100 °F (37.8 °C) as follows:
Range CodeResponse Time
40.5 seconds or less
all others0.2 seconds or less
Adjustable damping is available through a special
N option.
Service
Liquid, gas, or vapor
6-4
Output
4–20 mA dc
Power Supply
Design limits are as shown in Figure 2-3 on page 2-5. See qualification report
D8400102 for additional detail.
Page 49
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
Span and Zero
Continuously adjustable externally
Zero Elevation and Suppression
Maximum zero elevation: 600% of calibrated span
(400% of calibrated span for Range Code 0)
Maximum zero suppression: 500% of calibrated span (300% of calibrated
span for Range Code 0)
Zero elevation and suppression must be such that neither the calibrated span
nor the upper or lower range value exceeds 100% of the upper range limit.
Temperature Limits
Normal operating limits: 40 to 200 °F (4.4 to 93.3 °C)
Qualified storage limits: –40 to 120 °F (–40.0 to 48.9 °C)
Humidity Limits
0–100% relative humidity (NEMA 4X)
Volumetric Displacement
3
Less than 0.01 in
(0.16 cm3)
Turn-o n T i me
2 seconds maximum. No warm-up required
Pressure Ranges
Rosemount 1154DP and 1154HP:
Range CodePressure Ranges
40–25 to 0–150 inH2O (0–6.22 to 0–37.3 kPa)
50–125 to 0–750 inH
60–17 to 0–100 psi (0–0.12 to 0–0.69 MPa)
70–50 to 0–300 psi (0–0.34 to 0–2.07 MPa)
80–170 to 0–1,000 psi (0–1.17 to 0–6.89 MPa)
O (0–31.08 to 0–186.4 kPa)
2
(DP units only)
Rosemount 1154GP:
Range CodePressure Ranges
4–8as listed for Rosemount 1154DP
90–500 to 0–3,000 psi (0–3.45 to 0–20.68 MPa)
00–1,000 to 0–4,000 psi (0–6.89 to 0–27.56 MPa)
Maximum Working Pressure
Rosemount 1154DP and 1154HP:
Static pressure limit
Rosemount 1154GP:
Upper range limit
6-5
Page 50
Rosemount 1154
Reference Manual
00809-0100-4514, Rev BA
January 2008
Static Pressure and Overpressure Limits
Rosemount 1154DP:
0.5 psia to 2,000 psig (3.4 kPa abs to 13.8 MPa) maximum rated static
pressure for operation within specifications; overpressure limit is 2,000
psig (13.8 MPa) on either side without damage to
the transmitter.
Rosemount 1154HP:
0.5 psia to 3,000 psig (3.4 kPa abs to 20.7 MPa) maximum rated static
pressure for operation within specifications; overpressure limit is 3,000
psig (20.7 MPa) on either side without damage to
the transmitter.
Overpressure Limits
Rosemount 1154GP:
Operates within specifications from 0.5 psia
(3.4 kPa abs) to upper range limit. Overpressure limits without damage to
the transmitter:
PHYSICAL
SPECIFICATIONS
Range CodeOverpressure Limit
4–82,000 psig (13.8 MPa)
94,500 psig (31.0 MPa)
06,000 psig (41.34 MPa)
Materials of Construction
Isolating Diaphragms:
316L SST
Drain/Vent Valves:
316 SST
Process Flanges:
CF-8M (cast version of 316 SST)
Process O-rings:
316L SST
Electronics Housing O-rings:
Ethylene propylene
Fill Fluid:
Silicone oil
Flange Bolts and Nuts:
Plated alloy steel, as specified in ASTM A540
6-6
Electronics Housing:
316 SST
Mounting Bracket:
316L SST
Mounting Bolts (Bracket to transmitter):
SAE J429 carbon steel, Grade 2 or Grade 5
Page 51
Reference Manual
00809-0100-4514, Rev BA
January 2008
Electrical Connections
1
/2–14 NPT conduit with screw terminals
Process Connections
3
/8 in. Swagelok compression fitting, 316 SST
1
(
/4–18 NPT optional)
Weight
24 lb (10.9 kg) including mounting bracket
Rosemount 1154
6-7
Page 52
Rosemount 1154
ORDERING INFORMATION
Table 6-1. Transmitter Design Specifications.
ModelDescription
115 4Alphaline Pressure Transmitters for Nuclear Applications, IEEE Std 323-1974 and IEEE Std 344-1975
Welded 3/8 in. Swagelok Compression Fitting Process Connection and Welded Drain/Vent Valve
¼–18 NPT Process Connection and Welded Drain/Vent Valve
¼–18 NPT Process Connection and Drain Hole (Drain/Vent Valve not supplied)
One Flange Code Option A and One Remote Seal
One Flange Code Option B and One Remote Seal
One Flange Code Option C and One Remote Seal
Two Remote Seals
Welded
Welded
One Flange Code Option H and One Remote Seal
One Flange Code Option J and One Remote Seal
(Differential)
O
(0–6.22 to 0–37.3 kPa)
(0–31.08 to 0–186.4 kPa)
(0–0.12 to 0–0.69 MPa)
(0–0.34 to 0–2.07 MPa)
(0–1.17 to 0–6.89 MPa)
3
/8 in. Swagelok Compression Fittings on Both Process Connection and Drain/Vent Connection
3
/8 in. Swagelok Compression Fitting Process Connection and ¼–18 NPT Drain Hole
2
O
2
Rosemount 1154HP
(Differential)
0–25 to 0–150 inH2O
(0–6.22 to 0–37.3 kPa)
0–125 to 0–750 inH2O
(0–31.08 to 0–186.4 kPa)
0–17 to 0–100 psi
(0–0.12 to 0–0.69 MPa)
0–50 to 0–300 psi
(0–0.34 to 0–2.07 MPa)
—0–170 to 0–1,000 psi
Rosemount 1154GP
(Gage)
0–25 to 0–150 inH2O
(0–6.22 to 0–37.3 kPa)
0–125 to 0–750 inH2O
(0–31.08 to 0–186.4 kPa)
0–17 to 0–100 psi
(0–0.12 to 0–0.69 MPa)
0–50 to 0–300 psi
(0–0.34 to 0–2.07 MPa)
(0–1.17 to 0–6.89 MPa)
(0–3.45 to 0–20.68 MPa)
(0–6.89 to 0–27.56 MPa)
(1) The Rosemount 1154 with Output Code R Electronics is also available with adjustable damping. This option is specified
by appending “N0037” to the end of the complete model number, for example, 1154DP4RAN0037.
(2) Note: Customer assumes responsibility for qualifying connection interfaces on these options. Contact Rosemount
Nuclear Instruments, Inc. for details.
6-8
Page 53
Reference Manual
00809-0100-4514, Rev BA
January 2008
Table 6-2. Rosemount 1154DP, 1154HP, and 1154GP Spare Parts.
Rosemount 1154
Spare Parts Category
Traceable Part
Quantity Required
Item Number (see Figure 5-2 on page 5-5)
Part DescriptionOrder No.Order No.Order No.
Amplifier Cir. Board, Output Code R
Calib. Cir. Board, Output Code R
Amplifier Cir. Board with Damping,
Bolts and Nuts for Process Flange
Range Codes 4–8 (Pkg of 4)
Range Code 9 (Pkg of 4)
Range Code 10 (Pkg of 4)
Panel Mounting Bracket with Bolts
Universal Mounting Bracket with Bolts
Bolts and Washers for Bracket (Pkg of 4)
Pipe Mount Bracket Kit (Adapters)
Pipe Mount Bracket Kit
(Bracket and Adapters)
Conduit Elbow (M22)
Conduit Elbow (½–14 NPT)
Amplifier Circuit Board, Output Code R,
(4)
N0026
(3)
Rosemount
1154DP
1A01153-0040-000101153-0040-000101153-0040-0001
7
9
(3)
14/8
1
X
1
X
1
X
101153-0013-0001
601154-0001-000601154-0001-0006—
01153-0245-0001
—
—
01153-0013-0003
01153-0321-0001
01154-0044-0001
01154-0038-0002
01154-0035-0001
01154-0040-0001
Rosemount
1154HP
01153-0245-0001
—
—
01153-0013-0001
01153-0013-0003
01153-0321-0001
01154-0044-0001
01154-0038-0002
01154-0035-0001
01154-0040-0001
Rosemount
1154G P
01153-0245-0001
01153-0246-0001
01153-0246-0002
01153-0013-0001
01153-0013-0003
01153-0321-0001
01154-0044-0001
01154-0038-0002
01154-0035-0001
01154-0040-0001
(1) Rosemount recommends one spare part or kit for every 25 transmitters in Category “A,” one spare part or kit for every
50 transmitters in Category “B,” and one spare part or kit for every 5 transmitters in Category “C.”
(2) Two flanges are required per transmitter. Flange parts depend on desired connection and transmitter type.
(3) Each spare parts kit contains the correct number of nuts, bolts, and washers for the specific transmitter range code it is
designated for. Due to consolidation of parts kits, the bolt length and quantity of washers required may differ from
existing transmitter assemblies and/or parts kits. Verify by part number that the appropriate spare parts kit is used for
the transmitter range code being re-assembled. Contact Rosemount Nuclear Instruments, Inc. if there are questions.
(4) For use with existing N0026 transmitter only.
6-10
Page 55
Reference Manual
00809-0100-4514, Rev BA
January 2008
Rosemount 1154
SPARE PARTS SHELF
LIFE
Store all spare transmitters and spare component parts in accordance with
ANSI N45.2.2 level B.
Qualified transmitters, spare circuit boards, spare O-rings: the qualified life (as
defined in Qualification Test Report D8400102) plus the shelf life is equal to
the typical design life of the plant (40 years) when the ambient storage
temperature is below 90 °F.
Lubricants and sealant: The date of the end of shelf life (use by date) is
provided with the lubricants and/or sealant, at the time of shipment. The
product has a minimum of six months shelf life at the time
of shipment.
All other parts: Shelf life is not applicable.
IMPORTANT NOTICEThere are factors to consider concerning maintenance of qualification and
traceability during on-site instrument repair because of the nuclear use
intended for these parts. Rosemount Nuclear Instruments, Inc. rigidly
controlled the original assembly of the instrument to ensure that the
specifications were met. Since we are not installing the replacement parts in
the instruments, Rosemount Nuclear Instruments, Inc. is unable to ensure
that the specifications are being satisfied. Replacing parts has ramifications under 10CFR21, for which the user is responsible. These
same regulations additionally mandate a component traceability program,
which the user must undertake for the replacement parts. In view of this, and
in order to maintain the qualification of the product, the user must ensure that
all replacement parts are installed in accordance with the Rosemount Nuclear
Instruments, Inc. approved installation and calibration procedures herein.
NOTES:
1.Rosemount 1154 spare parts are not hydrostatic tested or nuclear
cleaned.
2.Part numbers shown may differ from those currently supplied. The
part numbers shown are current at the time of printing of this manual,
but may be revised in the future. Parts provided are compatible and
interchangeable with those listed on your order as to the form, fit, and
function of the part required. Please adjust your needs accordingly.
The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount, the Rosemount logotype, and Alphaline are registered trademarks of Rosemount, Inc.
Cell is a trademarks of Rosemount, Inc.
Swagelok is a registered trademark of Swagelok Co.
Emerson Process Management
Rosemount Nuclear Instruments, Inc.
8200 Market Boulevard
Chanhassen, MN 55317 USA
T (952) 949-5210
F (952) 949-5201
Rosemount Nuclear Instruments, Inc. satisfies all obligations
coming from legislation to harmonize product requirements in the
European Union.
¢00809-XXXX-XXXX ¤
www.rosemountnuclear.com