Emerson 0037-7303A Installation And Operation Manual

Page 1
Commercial Communicating
MENU
Programmable Thermostat Installation and Operation Manual
026-1729 Rev 2 15-NOV-2016
White-Rogers Part No. 0037-7303A
Page 2
Page 3
Emerson Climate Technologies Retail Solutions
1065 Big Shanty Road NW, Suite 100
Kennesaw, GA 30144, USA
Phone 770-425-2724
Fax 770-425-9319
Page 4
Page 5
Table of Contents
1 INTRODUCTION.......................................................................................................................................................... 1
1.1. ABOUT THIS GUIDE ...................................................................................................................................................... 1
1.2. SYSTEM COMPATIBILITY .............................................................................................................................................. 1
2 GETTING STARTED ................................................................................................................................................... 1
2.1. PRE-INSTALLATION CHECKLIST ................................................................................................................................... 1
2.2. REQUIRED ITEMS .......................................................................................................................................................... 1
2.3. REQUIRED TOOLS ......................................................................................................................................................... 1
2.4. DIMENSIONS ................................................................................................................................................................. 2
3 INSTALLING THE THERMOSTAT ......................................................................................................................... 3
3.1. QUICK GUIDE ............................................................................................................................................................... 3
3.2. STEP 1: REMOVE THE OLD THERMOSTAT................................................................................................................... 3
3.2.1. Thermostat Components ....................................................................................................................................... 3
3.2.2. Removing the Old Thermostat............................................................................................................................... 3
3.3. STEP 2: MOUNTING THE NEW THERMOSTAT .............................................................................................................. 4
3.3.1. Mount the New Thermostat................................................................................................................................... 4
3.4. STEP 3: CONFIGURING THE THERMOSTAT .................................................................................................................. 5
3.4.1. Configure the Thermostat ..................................................................................................................................... 5
3.4.2. Installation Menu Options .................................................................................................................................... 6
3.5. STEP 4: CHECK THE THERMOSTAT OPERATION.......................................................................................................... 7
3.5.1. Check the Fan Operation...................................................................................................................................... 7
3.5.2. Check the Cooling System..................................................................................................................................... 7
3.5.3. Check the Heating System..................................................................................................................................... 7
3.5.4. Check the Back Up Heating System (Heat Pump Systems Only).......................................................................... 8
3.6. STEP 5: GETTING TO KNOW YOUR THERMOSTAT ...................................................................................................... 8
3.6.1. Thermostat Buttons ............................................................................................................................................... 8
3.6.2. Thermostat Indicators and Display....................................................................................................................... 9
3.6.3. Using the Navigation Keypad ............................................................................................................................. 10
3.6.4. Initiating a Temporary Hold ............................................................................................................................... 10
3.6.5. Setting One-Touch Away Preset ......................................................................................................................... 10
4 CUSTOMIZING THERMOSTAT SETTINGS........................................................................................................ 11
4.1. PROGRAMMING A HEATING/COOLING SCHEDULE...................................................................................................... 11
4.1.1. To Run the Thermostat as a Non-Programmable Model.................................................................................... 11
4.1.2. To Customize the Heating/Cooling Schedule...................................................................................................... 12
4.1.3. To Set a Heating/Cooling Schedule .................................................................................................................... 12
4.2. SETTING THE THERMOSTAT CLOCK ........................................................................................................................... 13
4.2.1. To Set the Time and Date.................................................................................................................................... 13
4.2.2. To Set Your Time Zone........................................................................................................................................ 14
4.2.3. To Enable/Disable Daylight Saving Time........................................................................................................... 14
4.3. SETTING ALERTS ........................................................................................................................................................ 15
4.3.1. To Set an Alert..................................................................................................................................................... 15
4.3.2. To Configure Alert Notification .......................................................................................................................... 16
4.4. SETTING THE THERMOSTAT LOCK ............................................................................................................................. 16
4.4.1. To Lock the Thermostat Display ......................................................................................................................... 16
4.4.2. To Unlock the Thermostat Display ..................................................................................................................... 17
4.5. SETTING VACATION HOLD ......................................................................................................................................... 18
4.5.1. To Set Vacation Hold .......................................................................................................................................... 18
Table of Contents • v
Page 6
5 WIRING CHART ........................................................................................................................................................ 19
5.1.
COMMUNICATION AND SENSOR CONNECTIONS/TERMINALS ...................................................................................... 19
6 WIRING CONNECTION TO SITE SUPERVISOR................................................................................................ 20
7 E2 SETUP ..................................................................................................................................................................... 21
8 NETWORK SETUP AND COMMISSIONING ....................................................................................................... 22
8.1. COM PORT ASSOCIATIONS - E2 VERSIONS 3.XX AND BELOW .................................................................................. 22
8.2. COM PORT ASSOCIATIONS - E2 VERSIONS 4.0 AND ABOVE ..................................................................................... 22
8.3. SET UP NETWORK PORTS ........................................................................................................................................... 23
8.4. ADDING A THERMOSTAT ............................................................................................................................................ 23
9 DESCRIPTION OF INSTALLATION MENU OPTIONS...................................................................................... 25
9.1. HVAC EQUIPMENT SETUP ......................................................................................................................................... 25
9.2. ADVANCED SETUP ...................................................................................................................................................... 25
9.3. INSTALLATION MENU ................................................................................................................................................. 27
9.3.1. About the Device ................................................................................................................................................. 27
9.3.2. Economizer Settings ............................................................................................................................................ 27
9.3.3. Sensor Settings .................................................................................................................................................... 27
9.3.4. Network Button.................................................................................................................................................... 28
10 TROUBLESHOOTING GUIDE .............................................................................................................................. 29
10.1. RESET OPERATION .................................................................................................................................................... 31
vi • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
White-Rodgers Part No. 0037-7303A
Page 7
Page 8
1 Introduction
2 Getting Started
1.1. About this Guide
This manual describes how to install and configure the Commercial Communicating Programmable Thermostat (P/N 810-1500).
1.2. System Compatibility
This Commercial Communicating Programmable Thermostat replaces thermostats for the following types of system:
• Standard Heat & Cool Systems
• Two Stage Heat & Two Stage Cool Systems
• Air Source Heat Pump (with Aux. or Emergency Heat)
• Ground Source Heat Pump (with Aux. or Emergen­cy Heat)
• Air or Ground Source Heat Pump (No Aux. or Emergency Heat)
• Standard Heat Only Systems
• Standard Central Air Conditioning
• Gas or Oil Heat
• Electric Furnace
• All Systems Listed Above with Economizer Control
CAUTION! Failure to read and follow all in­structions carefully before installing or operat­ing this control could cause personal injury and/or property damage.
2.1. Pre-Installation Checklist
Before you begin to install your Commercial
Communicating Programmable Thermostat:
• Read these instructions thoroughly.
• Check the package from your thermostat to make sure you have all of the required parts (see Section
2.2., Required Items).
• Assemble the required tools (see Section 2.3., Re- quired Tools).
2.2. Required Items
• Thermostat (1)
• Wall anchors (2)
• Mounting screws (2)
2.3. Required Tools
• Flat blade screwdrivers – 1 large and 1 small
• Hand or power drill with 3/16 inch drill bit
• Wire strippers
• Level (optional)
To prevent electrical shock and/or equipment dam­age, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
This product does not contain mercury. However, this product may replace a unit which contains mercu­ry. Do not open mercury cells. If a cell becomes dam­aged, do not touch any spilled mercury. Wearing non­absorbent gloves, clean up the spilled mercury and place into a container that can be sealed.
For proper disposal refer to www.white-rodgers.com for a location to send the product containing mercury.
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.
About this Guide Introduction • 1
Page 9
2.4. Dimensions
*Note: Dimensions shown in inches
Figure 2-1 - Mounting Dimensions
Figure 2-2 - Thermostat Dimensions
2 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 10
3 Installing the
Thermostat
3.1. Quick Guide
3.2. STEP 1: Remove the Old Thermostat
WARNING! To prevent electrical shock and/or equipment damage, disconnect electric power to the system at the main fuse or circuit breaker box until installation is complete.
1. Removing the old thermostat.
Turn OFF power at the breaker
CAUTION! To prevent electrical shock and/or equipment damage, disconnect electric power to the system at the main fuse or circuit breaker box until installation is complete.
• Remove the cover from the old thermostat to expose the wires.
• Identify each wire to corresponding terminal and disconnect.
• Remove the old thermostat from the wall, making sure that the thermostat wires do not fall back into wall opening.
2. Mount the new thermostat.
• Feed the thermostat wires through the thermostat hole.
• Wire the new thermostat.
• Turn ON the power at the breaker.
3. Configure the thermostat.
4. Check thermostat operation.
5. Getting to Know the Commercial Communicat­ing Programmable Thermostat
.
The sections that follow provide detailed instruc-
tions for completing these steps.
3.2.1. Thermostat Components
The standard heat/cool thermostat normally con-
sists of three basic parts:
1. Cover
2. Base, which you can remove by loosening all screws
3. Switching sub-base screwing the mounting screws that hold it on the wall or adaptor plate
, which you can remove by un-
3.2.2. Removing the Old Thermostat
1. Remove the front cover of the old thermostat.
2. With wires still attached, remove the wall plate from the wall by unscrewing it. If the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.
3. Identify each wire attached to the old thermostat as shown in Figure 3-1. Before removing wires from the old thermostat’s switching sub-base, label each wire with the letter on the old thermostat. Ignore wire colors and use the letter designation only.
4. Disconnect the wires from the old thermostat one at a time.
WARNING! Do not let wires fall back into the wall.
Quick Guide Installing the Thermostat • 3
TIP: You may want to wrap the wires around a pencil to keep them from falling back into the wall.
Page 11
Figure 3-1 - Thermostat Wires with Labels
G
W
C
R
Y
3.3. STEP 2: Mounting the New Thermostat
WARNING! Take care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat. Personal inju­ry and/or property damage may occur.
To prevent personal injury and/or property damage, contact Customer Service at your utility company before attempting any step in the installation process that you are unsure about how to perform.
3.3.1. Mount the New Thermostat
1. Unpack the thermostat and separate the Mount­ing Plate from the thermostat. Remove the pack-
ing material from the thermostat. Gently pull the thermostat straight off of the base: hold the thermo­stat from the back by the lower corners with one hand, and pull the Mounting Plate off with the other hand.
wires are fed through. Each terminal is labeled with a letter or a letter with a number (O, B, R, etc.).
Connect the wires as follows:
• Strip insulation about 3/8 inch from end of wire.
• Feed the thermostat wires through the rectangular hole in the thermostat Mounting Plate.
• Locate the terminal that the wire needs to connect to (refer to Section 5, Wiring Chart).
• Bend the wire slightly, insert the wire under the con­tact plate, and tighten the screw down onto the wire.
For full details on where to connect each wire, see
Section 5, Wiring Chart.
Figure 3-2 - Location of Wire Terminals
4. Mark mounting hole locations. Place the thermo­stat Mounting Plate over the hole in the wall and mark the mounting hole locations (Figure 3-3) us­ing the Mounting Plate as a template.
NOTE: Forcing or prying on the thermostat will cause damage to the unit.
2. Feed the thermostat wires through the rectangu­lar hole between the terminal blocks in the ther­mostat Mounting Plate.
3. Connect the wires to the thermostat Mounting Plate. Connect the wires beneath the terminal
screws on the base. Figure 3-2 shows the location of the wire terminals in the Commercial Communi­cating Programmable Thermostat. There are two sets of terminals on either side of the hole where the
4 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Figure 3-3 - Thermostat Mounting Hole Locations
5. Drill holes. Move the Mounting Plate out of the way. Drill mounting holes using a 3/16 inch drill bit.
6. Install the Mounting Plate. Fasten the Mounting
Page 12
Plate loosely onto the wall using the two mounting screws in the mounting holes. If desired, place a lev­el against the bottom of the Mounting Plate and ad­just until level before tightening screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not al­low you to tighten base snugly, use plastic wall an­chors to secure the sub-base. Push excess wire into the wall and plug the hole with a fire resistant mate­rial (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
7. Fas te n th e t he rmo st at to the Mo un ti ng Pla te . The thermostat is designed with a quick connect feature between the thermostat unit and Mounting Plate. When installing the thermostat onto the Mounting Plate, make sure the retention tabs on the Mounting Plate are in line with the retention slots in the ther­mostat. Gently press the thermostat onto the Mount­ing Plate until you hear the retention tabs make a clicking sound and the thermostat is securely fas­tened to the Mounting Plate. If the thermostat does
not easily click onto the Mounting Plate, be certain not to press with excessive force or else damage could occur to the thermostat and/or Mounting Plate.
8. Turn the power back ON at the breaker.
For wiring specifications, refer to Section 5, Wir-
ing Chart.
NOTE: It is important to select the proper set­ting for the first item on the configuration menu that specifies the type of HVAC system.
3.4. STEP 3: Configuring the Thermostat
3.4.1. Configure the Thermostat
1. Press the SYSTEM button one or more times to set the system to OFF.
2. Simultaneously press and hold the LEFT and RIGHT arrow buttons for 3 seconds to enter the In­stallation Menu. The display will show the first lev­el of the Installation Menu.
3. While in the Installation Menu, UP and DOWN scroll the cursor up and down respectively, LEFT goes back one menu level and the ACTION button selects the highlighted menu item.
4. To exit all menus and return to the program opera­tion, press the LEFT arrow button again to return to the home screen.
If no key is pressed within two minutes, the ther-
mostat will revert to normal operation.
STEP 3: Configuring the Thermostat Installing the Thermostat • 5
Page 13
3.4.2. Installation Menu Options
The installation menu table summarizes the configuration options. For more details on each Installation
Menu option, see Section 9, Description of Installation Menu Options.
Press UP or DOWN arrow to
Menu Name Submenu
HVAC EQUIPMENT SETUP
Air Conditioner: 1 Stage
Air Conditioner: 2 Stage
Outdoor
Air Source Heat Pump: 1 Stage Air Source Heat Pump: 2 Stage
Air Handler: No Heat
Air Handler: Electric Heat – 1 Stage
Indoor
Air Handler: Electric Heat – 2 Stage
Furnace Gas / Oil – 1 Stage
Furnace Gas / Oil – 2 Stage
Network
Installation Info
Network Status
About This Device Dedicated Screen
ADVANCED HVAC OPTIONS
Heat
Cycle Rates
Cool
Back-up Heat
Compressor Lockout On, Off
Comfort Alert Active
Protection
Frost Protection On, Off
O/B Configuration O: Cool, B: Heat
Fast Second Stage
Heat On, Off
Cool On, Off
Dual Fuel Off, Smart Fuel, Sensor
Smart Fuel 1-9 If set to Smart Fuel
Sensor
Aux Lockout 34 to 90
HP comfort/economy Comfort, Economy
Select Other Options
(Default in Bold)
None
Comfort
Standa rd
Economy
Comfort
Standa rd
Economy
Comfort
Standa rd
Economy
On, Off
Balance Point
-20 to 30
° F (Default -20)
° F (Default 90) If set to Sensor
Comments
Available with heat pump multistage configuration
Available when Heat Pump and a Gas Furnace are specified in Equipment Setup
If set to Sensor
Table 3-1 - Installation Menu
6 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 14
Press UP or DOWN arrow to
Menu Name Submenu
Heat Lockout Outdoor
Cool Lockout Outdoor
Compressor
Optimization
Dehumidification Off, OC, OD
Dehum Setpoint Range: 40% to 80%
Dead Band Range: 2, 3, 4F
Power-Up delay
Table 3-1 - Installation Menu
Select Other Options
(Default in Bold)
-15 to 120
-20 to 95
10sec to 120sec
Comments
Off
° F
Off
° F
On, Off
Off
3.5. STEP 4: Check the Thermostat Operation
CAUTION! To prevent compressor and/or property damage, if the outdoor temperature is below 55°F, DO NOT operate the cooling sys­tem.
Once you have installed your new thermostat, you need to check that the fan, cooling system, and heat­ing system are all operating properly.
If your system does not have a G terminal connec­tion, skip to Heating System.
3.5.1. Check the Fan Operation
1. Press the MENU button and select FAN ON in the thermostat display. The blower should begin to op­erate. Place your hand by a vent to confirm blower is running.
2. Select FAN AUTO to return to standard setting. The blower will now cycle by calling for cool or heat.
3.5.2. Check the Cooling System
1. Press the SYSTEM button one or more times to se­lect COOL.
2. Press the DOWN arrow button to adjust the thermo­stat setting 1° below room temperature. The blower should come on immediately on high speed, fol­lowed by cold air circulation.
NOTE: If compressor lockout is set to ON, the thermostat will not call for cool until after the 5-minute safety time period and will display the message A/C return < 5 min
utes expire the thermostat will call for cool.
3. If the system is a multi-stage cooling system, adjust the temperature setting to at least 3° below room temperature. The second stage cooling should begin to operate.
4. Press the UP arrow button to adjust the temperature setting above room temperature. The cooling sys­tem should stop operating.
. After the 5 min-
3.5.3. Check the Heating System
1. Press the SYSTEM button one or more times to se­lect HEAT mode. If the auxiliary heating system has a standing pilot, be sure to light it.
2. Press the UP arrow button to adjust the thermostat setting to 1° above room temperature. The heating system should begin to operate.
NOTE: If the system is configured as a heat pump and compressor lockout is set to ON thermostat will not call for heat until after the
5-minute safety time period and will display the message A/C return < 5 min the thermostat will call for heat.
3. If the system is a multi-stage heating system, adjust the temperature setting to at least 3° above room temperature. If the system is configured for a multi­stage furnace (non-heat pump), the second stage of the heating should begin to operate. Within a very short period, the Back Up heat should begin to run
. After the 5 minutes expire
, the
STEP 4: Check the Thermostat Operation Installing the Thermostat • 7
Page 15
and Back Up Heat will be displayed.
1
2
341567
8
9
10
4. Press the DOWN arrow button to adjust the thermo­stat below room temperature. The heating system should stop operating.
WARNING! It is recommended to turn OFF the HVAC power before removing the thermo­stat from the Mounting Plate when installed.
3.5.4. Check the Back Up Heating System (Heat Pump Systems Only)
The Back Up Heat bypasses the Heat Pump to use the heat source wired to E & W2 terminals of the ther­mostat. Back Up is typically used when compressor operation is not desired, the user prefers to utilize the back-up heat only or the compressor is not able to sat­isfy the demand for heat to the user’s desire.
1. Press the SYSTEM button one or more times to se­lect Back Up Heat mode. If the auxiliary heating system has a standing pilot, be sure to light it.
2. Press the UP arrow button to adjust the thermostat setting to 1° above room temperature. The AUX heating system should begin to operate. Back Up should display.
NOTE: If compressor lockout is set to ON, the thermostat will not call for heat until after the 5-minute safety time period and will display the message A/C return < 5 min
utes expire the thermostat will call for Back Up heat.
3. If the system is a multi-stage Back Up heating sys­tem, adjust the temperature setting to at least 3° above room temperature to turn on all stages.
4. Press the DOWN arrow button to adjust the thermo­stat below room temperature. The heating system should stop operating.
. After the 5 min-
3.6. STEP 5: Getting to Know Your Thermostat
Before setting up your thermostat, you should fa­miliarize yourself with its features and user interface. Your thermostat consists of two parts: the thermostat chassis and the Mounting Plate. To detach the two items, gently pull on the thermostat chassis until the retention tabs release. To attach the thermostat back onto the Mounting Plate, align the retention tabs on the Mounting Plate with the retention slots in the ther­mostat and gently press the two together until the re­tention tabs click. If the thermostat does not easily click onto the Mounting Plate, make sure not to press with excessive force or else damage could occur to the thermostat and/or Mounting Plate.
3.6.1. Thermostat Buttons
Figure 3-4 - Thermostat Buttons and Indicators
Button Function
1 LEFT Arrow Navigates menu items
2UP Arrow
3 Action Button
4 Mail LED Indicates message in Inbox
5 LED
6 RIGHT Arrow Navigates menu items
7 DOWN Arrow Navigates menu items
8 Energy Button
9 Menu Button
10 Soft Keys
Table 3-2 - Functions of Buttons and Indicators
Raises temperature setpoint/ changes selected item
Selects action of selected menu item
Indicates curtailment event is occurring
Takes user to the Energy Monitor Screen
Takes user to the Main Settings Menu
Perform action listed on LCD above the button
8 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 16
3.6.2. Thermostat Indicators and
1:54 PM – Mar. 12
COOL AWAY
79°
F
85°
Set At
UnOcc
INBOX
1
3
4
5
2
Display
Figure 3-5 - Thermostat Display
Screen Section Function
1 Messaging Area
2 Temperature
Setpoint
3
Temperature
4 Rate Status
Soft Key
5
Actions
Rotates day/time, thermostat and utility related messages
Displays current measured room temperature
Displays currently programmed setpoint
- Blank when OFF
- SET AT changes to HOLD AT when in temporary or permanent hold
Displays current rate in effect (may be blank at base rate)
Actions to be performed when corresponding button is pressed
Table 3-3 - Thermostat Display Screen Sections
STEP 5: Getting to Know Your Thermostat Installing the Thermostat • 9
Page 17
3.6.3. Using the Navigation Keypad
Home
Vacation Hold
Thermostat Lock
Alerts
Schedules
Clock
Main Menu
Off
On
Home
Cooling Schedule
Heating Schedule
Periods Per Day
Schedules
Schedules
On
4
Set Time & Date
CANCEL SAVE
12 : 00 pm
1/1/10 Friday
1:54 PM – Mar. 12
COOL END HOLD
75°
F
77°
Hold At
FAN ON
UnOcc
Hold Until
5:30PM – Mon
Away Preset
Next
85°F 62°F
Cooling Heating
When on a menu screen, the five-way navigation pad functions as follows:
Use the listings.
and arrows to move through the displayed menu
Use the
and arrows to advance to the next screen or return to
a previous screen.
Use the
key to confirm a selection or advance to the next screen.
The key is also used to toggle back and forth between options, such as ON/OFF, as shown in the Schedul
es menu.
When setting preferences for a specific menu option:
Use the
and arrows to change the setting of the highlighted
item.
Use the Use the three “soft keys” at the bot
and arrows to tab between values.
tom of the screen to complete a
step.
Table 3-4 - Use of the Navigation Keypad
3.6.4. Initiating a Temporary Hold
TEMPORARY HOLD lets you override a programmed heating/cooling schedule for a brief period of time.
Step 1: To initiate a TEMPORARY HOLD, adjust the temperature
by pressing the and arrows. To change the duration
of the temporary hold, press the and arrows.
Table 3-5 - Initiate a Temporary Hold
3.6.5. Setting One-Touch Away Preset
AWAY PRESET lets you override a programmed temperature indefinitely. This feature will help you save money if you’re going to be away from home for an extended period of time. The unit has been shipped with “Away” settings of 85° in the summer and 62° in the winter, but those temperatures can easily be changed with the touch of one key.
Step 1: To change the default setting, press the Away Key for
Table 3-6 - One-Touch Away Preset
10 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
three seconds. The screen shown will appear. Select your heat and cool away presets and press Next to proceed to save screen.
Page 18
4 Customizing Thermostat Settings
Home
Vacation Hold
Thermostat Lock
Alerts
Schedules
Clock
Main Menu
Off
On
4.1. Programming a Heating/Cooling Schedule
By programming a thermostat schedule, you can save energy while maintaining comfort. The Commercial Communicating Programmable Thermostat was installed with following pre-programmed, energy-efficient schedule. If this schedule meets your needs, no further action is required.
HEATING
MORN DAY EVEN NITE
Period
Mon-Fri 70
Sat-Sun 70
Table 4-1 - Heating/Cooling Schedule
6:00am ­8:00am
° F 60° F 70° F 62° F
° F 60° F 70° F 62° F
MORN DAY EVEN NITE
Period
Mon-Fri 78
Sat-Sun 82
6:00am -
8.00am
° F 85° F 78° F 82° F
° F 78° F 78° F 82° F
8:00am ­6:00pm
COOLING
8:00am ­6:00pm
6:00pm ­10:00 pm
6:00pm ­10:00 pm
10:00pm ­6:00am
10:00pm ­6:00am
Table 4-2 - Heating/Cooling Schedule
4.1.1. To Run the Thermostat as a Non-Programmable Model
Menu > Settings > Schedules
Step 1: Press the MENU key.
Step 2:
Step 3:
Table 4-3 - Running the Thermostat as a Non-Programmable Model
From the Settings menu, use the and arrows to select
SCHEDULES. Press .
If the SCHEDULES feature is ON, press the key to turn it OFF.
Programming a Heating/Cooling Schedule Customizing Thermostat Settings • 11
Page 19
4.1.2. To Customize the Heating/Cooling Schedule
Home
Vacation Hold
Thermostat Lock
Alerts
Schedules
Clock
Main Menu
On
Thermostat Settings
Home
Cooling Schedule
Heating Schedule
Periods Per Day
Schedules
Schedules
On
4
Home
Cooling Schedule
Heating Schedule
Periods Per Day
Schedules
Schedules
On
4
Home
Individual Days
Weekdays/Weekends
Heating Schedule
Mon - Fri
CANCEL SAVE
Night
Evening
Day
Morning
Period
10:00 PM
6:00 PM
8:00 AM
6:00 AM
Starts At
62°
70°
60°
70°
Heat To
Menu > Settings > Schedules
You can easily change the day, time period or temperature settings of the pre-programmed schedule.
Step 1: Press the MENU key.
Step 2:
From the Settings menu, use the and arrows to select
SCHEDULES. Press .
Step 3: If the SCHEDULES feature is OFF, press ENTER. You
should now see options to set a schedule for heating, cooling and periods per day. Start by deciding how many times during the day you want the temperature to change. If you want to set one temperature for daytime and one temperature for night time, select 2. If you want to set four temperature settings throughout the day (morning, day, evening, night) select 4.
To make your selection, use the and arrows to select PERIODS PER DAY. Press ENTER to select either 2 or 4.
Table 4-4 - Customizing the Heating/Cooling Schedule
4.1.3. To Set a Heating/Cooling Schedule
Menu > Settings > Schedules > Set Heat (or Cool) Schedule
Step 1:
Step 2: From the HEAT SCHEDULE screen, you can either:
From the SCHEDULES menu, use the and arrows to
select SET HEAT SCHEDULE. Press .
Set a separate schedule for weekdays and weekend days, OR Set a single schedule that will run seven days a week.
Use the and arrows to make your selection. Press .
Step 3:
The first day part should be highlighted. Using the and
arrows, adjust the start time for the first temperature
setting. Times adjust in increments of 15 minutes. Once the
start time is selected, press to move to the HEAT TO column.
Step 4: Repeat steps 2 and 3 until all day periods are complete.
When finished, press NEXT.
Table 4-5 - Setting a Heating/Cooling Schedule
12 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 20
Step 5: When asked to confirm your selection, press YES.
Home
Cooling Schedule
Heating Schedule
Periods Per Day
Schedules
Schedules
On
4
Home
Vacation Hold
Thermostat Lock
Alerts
Schedules
Clock
Main Menu
On
Thermostat Settings
Home
Display On Home
Daylight Savings
Time Zone
Set Time & Date
1:54 PM — 3/12/10
On
On
Set Time & Date
Next
12 : 00 pm
01/01/10
Friday
Step 6:
Return to the SCHEDULES menu, use the and
arrows to select SET COOL SCHEDULE. Press .
Step 7: Repeat SET SCHEDULE steps 2-5 to set the cool schedule.
When finished, press NEXT. When asked to confirm your selection, press YES.
Table 4-5 - Setting a Heating/Cooling Schedule
4.2. Setting the Thermostat Clock
Menu > Settings > Clock
If the thermostat is connected to a smart meter, the time will be automatically set and maintained. To set or change the time/time zone, perform the following steps:
4.2.1. To Set the Time and Date
Menu > Settings > Clock > Set Time & Date
Step 1: Press the MENU key.
Step 2:
From the Settings menu, use the and arrows to select
CLOCK. Press .
Step 3:
Use the a nd a rro ws to sele ct SE T TI ME AN D DATE.
Press .
Step 4:
Use the and arrows to change the value in each field,
and to toggle between fields. Once the time and date
are set, press NEXT.
Step 5: When asked to confirm your selection, press YES.
Table 4-6 - Setting the Time and Date
Setting the Thermostat Clock Customizing Thermostat Settings • 13
Page 21
4.2.2. To Set Your Time Zone
Home
Display On Home
Daylight Savings
Time Zone
Set Time & Date
1:54 PM — 3/12/10
On
On
Alaska Standard Time
Pacific Standard Time
Mountain Standard Time
Central Standard Time
Eastern Standard Time
Select Time Zone
Hawaii Standard Time
Home
Display On Home
Daylight Savings
Time Zone
Set Time & Date
1:54 PM — 3/12/10
On
On
Menu > Settings > Clock > Set Time Zone
Step 1:
From the CLOCK screen, use the and arrows to scroll through the menu listings until TIME ZONE is highlighted.
Press .
Step 2:
Use the and arrows to select a time zone, then press ENTER.
Table 4-7 - Setting the Time Zone
4.2.3. To Enable/Disable Daylight Saving Time
Menu > Settings > Clock > Daylight Saving
Step 1:
Table 4-8 - Enabling/Disabling Daylight Savings Time
From the CLOCK screen, use the and arrows to
select DAYLIGHT SAVING. Press . Press ENTER to select either ON or OFF.
14 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 22
4.3. Setting Alerts
Home
Beep On Alert / Message
HVAC Maintenance
Alerts
Active Alerts
UV Lights
Humidifier Pad
Air Filter
Maintenance Reminders
Off
Off
Off
Remind Me In
Status
Air Filter Reminder
3 mo
On
Air Filter
3
Remind me to replace this in:
Months
Menu > Settings > Alerts
The Commercial Communicating Programmable Thermostat is designed to alert you to important informa­tion about your energy use. You can set the unit to notify you - with an auditory beep or with a pop-up message
- when a new load control or pricing event takes place, or when it’s time to perform routine maintenance such as changing the filter on your HVAC unit. To enable alerts, perform the following steps:
4.3.1. To Set an Alert
Step 1:
Step 2:
Step 3:
Step 4:
From the ALERTS screen, you can choose to be alerted when it’s time to perform routine HVAC maintenance. You can also choose the manner in which you’d like to be alerted:
• By having the unit “beep”
Via pop-up message on the thermostat display
Use the
MAINTENANCE. Press
and arrows to select HVAC
.
From this screen, you can choose to be reminded to change the air filter, humidifier pad and UV lights on your HVAC
unit. Using the
press
to turn the reminder ON.
To activate the selected reminde
and arrows, select a reminder and
r, press ENTER.
Use the and arrows to select REMIND ME IN, then
press
.
Use the and arrows to select the number of months from today that you’d like to b
routine maintenance. Press
e reminded to perform the
to return to the HVAC
MAINTENANCE menu.
Step 5:
Repeat steps 2-4 for any other equipment maintenance
reminders of interest. Press menu.
Table 4-9 - Setting an Alert
Setting Alerts Customizing Thermostat Settings • 15
to return to the ALERTS
Page 23
4.3.2. To Configure Alert Notification
Thermostat Lock
CANCEL UNLOCK
0 0 0
Home
Beep On Alert / Message
HVAC Maintenance
Alerts
Active Alerts
Off
Once Upon Receipt
Beeper On Alert/ Message
Pop-Up Notifications
Beeper Notifications
HVAC Reminders
Alerts
On
Menu > Settings > Alerts > Beeper Notifications
Step 1: From the BEEPER NOTIFICATIONS screen, you can
choose the manner in which you want to be alerted when you receive priority messages or notification of a utility event or peak rate.
Use the and arrows to make a selection and press .
Step 2:
To change the default setting, use the and arr ow keys to select whether you would like to turn the alert OFF, be alerted once when the message is received, or every 15 minutes until you acknowledge the alert. Make your selection then press ENTER.
Repeat steps 1-2 until all BEEPER NOTIFICATIONS are
set. Press to return to the main ALERTS menu.
Step 3: To be alerted by text which pops up on your thermostat
display, use the and arrow to select POPUP NOTIFICATIONS, then press ENTER to select either ON or OFF.
Table 4-10 - Configuring Alert Notification
4.4. Setting the Thermostat Lock
Menu > Settings > Thermostat Lock
Thermostat lock lets you prevent unwanted users from changing thermostat settings.
4.4.1. To Lock the Thermostat Display
Step 1:
Table 4-11 - Locking the Thermostat Display
From the THERMOSTAT LOCK screen, enter a three-digit combination that will be required to unlock the thermostat. Write down the code for safekeeping, then press LOCK in the bottom RIGHT corner of the display.
16 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 24
4.4.2. To Unlock the Thermostat Display
1:54 PM – Mar. 12
COOL UNLOCK
79°
F
76°
Set At
$0.08
kWh
Base Rate
INBOX
Thermostat Lock
CANCEL UNLOCK
0 0 0
Step 1:
Press UNLOCK in the lower RIGHT hand corner of the display.
Step 2:
Enter the three-digit combination you set, then press UNLOCK.
Table 4-12 - Unlocking the Thermostat Display
NOTE: If you have forgotten your combina­tion, simultaneously press the LEFT, MID­DLE and RIGHT keys at the bottom of the display for 20 seconds to unlock and reset the
code to 000.
Setting the Thermostat Lock Customizing Thermostat Settings • 17
Page 25
4.5. Setting Vacation Hold
Vacation Hold
55°
Heating Setpoint
SET
Hold Until...
CANCEL SAVE
12 : 00 PM
FRI 6/12/09
Menu > Settings > Vacation Hold
Vacation Hold lets you override your thermostat’s programmed schedule while you are away and ensures
that you return to a comfortable home.
4.5.1. To Set Vacation Hold
Menu > Settings > Vacation Hold
Step 1: From the VACATION HOLD screen, select the desired
vacation hold temperature and press SET.
Step 2: Vacation hold can remain in effect for up to one year. Select
the date and time on which you’d like the thermostat to return to its programmed schedule, then press NEXT.
Step 3: When asked to confirm your selection, press YES.
Table 4-13 - Setting Vacation Hold
18 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 26
5 Wiring Chart
Fo r all systems, the follow ing terminals are wired ac cording to whether you have a single or dual transformer system as shown:
RH RC C L G
ngle Transformer
Si System
Dual Transformer System
Table 5-1 - Terminal Wiring Depending on Type of Transformer Used
1. *FAILURE TO IDENTIFY GROUNDED COMMON COULD CAUSE SEVERE DAMAGE TO HVAC SYSTEMS.
2.* FAILURE TO REMOVE PROVIDED JUMPER ON DUAL TRANSFORMER INSTALLATIONS COULD CAUSE SEVERE DAMAGE TO HVAC SYSTEMS.
1
24 VAC Hot
* Jumper should remain installed
24 VAC – Heat
2
*
REMOVE PROVIDED JUMPER
24 VAC – Cool
2
*
REMOVE PROVIDED JUMPER
24 VAC Common
24 VAC Common
The following terminals on the thermostat Mounting Plate are wired according to the type of HVAC system
connected to and the thermostat is configured as.
Y1 Y2 W/E W2 O/B
Conventional HVAC
Heat Pump
Cool Mode Stage 1
Compressor Contactor
Cool Mode Stage 2
Compressor Stage 2
Heat Mode Stage 1
AUX Heat Stage 1
System/Comfort Alert Diagnostics
System/Comfort Alert Diagnostics
Heat Mode Stage 2
AUX Heat Stage 2
Blower/Fan
Blower/Fan
-
Reversing Va lv e
Table 5-2 - Terminal Wiring Depending on Type of HVAC System
5.1. Communication and Sensor Connections/Terminals
SCOM S1 S2 S3 B+ A- MCOM EC_OUT EC_COM
Sensor Common
Table 5-3 - Commu
OAT
Remote Ind
oor Temperature (RMT)
nication and Sensor Connections/Terminals
Supply Air T
emperature
485 MODBUS Connections
485 MODBUS Shield
Economizer
og Output
Anal (+)
Economizer Analog Output (-)
Communication and Sensor Connections/Terminals Wiring Chart • 19
Page 27
6 Wiring Connection to Site Supervisor
Figure 6-1 - Site Supervisor Wiring
20 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 28
7E2 Setup
Connect the network cable to the three-terminal connector on the COM port that has been configured for the thermostat. The thermostat polarity markings are the same as E2; connect the thermostat B+ wire to the E2 RS485 + terminal and connect the thermostat A- wire to the E2 RS485 - terminal. The shield cable should be connected to the C terminal.
Figure 7-1 - E2 MODBUS connection
Communication and Sensor Connections/Terminals E2 Setup • 21
Page 29
8 Network Setup and Commissioning
E2 PIB COM PORT ASSOCIATIONS
COM1
COM4
COM6
COM2
Serial Device RS485 COM Port (2 Connectors)
RS485 COM Card (2 Connectors)
Serial Device RS232 Port
POWER INTERFACE BOARD (PIB)
E2 Modem/Expansion COM Card Mounted Above PIB
Plug-In Modem Card
COM3
E2 Enclosure (Right Side)
RS485
RS232
E2 PIB COM PORT ASSOCIATIONS
COM1
Serial Device
RS232 Port
POWER INTERFACE BOARD
(PIB)
E2 Enclosure (Right Side)
COM2 COM6
COM4
Serial Device RS485 COM Ports
Plug-In Modem Card
COM3
Connect the MODBUS network cable to the three-
8.1. COM Port Associations
- E2 Versions 3.xx and
terminal connector on the COM port you wish to as­sign as MODBUS.
Below
Connecting the thermostat to an E2 requires the E2 to be version 3.0 or above. Contact Emerson Retail Solutions for upgrade information if the controller is a version before 3.0.
An E2 has up to three COM ports that can be as­signed for MODBUS communication: COM2, an RS485 port on the E2 power interface board, and COM4 and COM 6 , which are o ptional p o rts requir i ng expansion cards.
COM ports can only be used for one function; in other words, if COM2 is set up as the I/O network, you cannot connect MODBUS devices to COM2. En­sure your E2 is equipped with an RS485 COM Card (P/N 637-4890) and configured in E2 General Ser-
, Serial tab) to enable COM4 or
vices ( an E2 Expansion COM Card (P/N 637-4871) to en-
able COM6.
8.2. COM Port Associations
- E2 Versions 4.0 and Above
An E2 has three COM ports that can be assigned for MODBUS communication (COM2). COM ports can only be used for one function; in other words, if COM2 is set up as the I/O network, you cannot con­nect MODBUS devices to COM2. Ensure your E2 is
configured in E2 General Services ( Serial tab)
to enable COM4 or COM6.
Connect the MODBUS network cable to the three­terminal connector on the COM port you wish to as­sign as MODBUS. Reverse polarity of +/- on RS485 cable from E2 to the device.
,
Figure 8-1 - Location of E2 COM Ports (E2 versions 3.xx and below)
22 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Figure 8-2 - Location of E2 COM Ports - E2 PIB Board (E2 version 4.0 and above)
Page 30
8.3. Set Up Network Ports
8.4. Adding a Thermostat
Before communicating to the thermostat, the port on the E2 that has the cable connected to the thermo­stat must be configured to use the thermostat.
1. Log in to the E2 with Level 4 access.
2. Press
3. Press
Figure 8-3 - Serial Communications Manager Screen
4. This screen will have a “Connection” field for all
5. Four fields will become visible underneath the
Baud - Default setting is 19.2k. The baud rate set-
Data Size - Leave this field at the default value (8).
Parity - Leave this field at the default value (None).
Stop Bits - Leave this field at the default value (1).
followed by  - General Con-
troller Info.
+ to open the Serial tab of the General
Controller Info setup screens:
COM ports on the E2. Highlight the COM port con­nection field that will be used for MODBUS, and
press
- LOOK UP. From the list of network
types, select MODBUS (1-3).
COM port connection field, which pertain to the way the device communicates:
ting should be set to match the baud rate dip switch settings of all thermostat devices. (All devices con­nected to the same COM port should be set to the same baud rate.)
The parity settings should be set to match the parity dip switch settings of all thermostat devices.
To enable communications between the E2 and the thermostat units, the devices must be added and ad­dressed in E2.
1. Log in to the E2 with Level 4 access.
2. Press
Figure 8-4 - Connected I/O Screen
3. In the Connected I/O screen, under the ECT tab, En-
4. Press
5. Locate the thermostat units you added to the net-
 - Connected I/O Boards and
Controllers.
ter the number of devices in the WR T-Stat number field.
to return to the Network Setup menu,
then select
work list (press li st). T he defa ult na m e for t he Comm ercial Commu -
nicating Programmable Thermostat increments up starting with WR T-Stat001. The two and three-let-
- Network Summary.
and to scroll through the
6. Press
Set Up Network Ports Network Setup and Commissioning • 23
to save changes and exit.
Page 31
ter designator does not apply here.
Figure 8-5 - Network Summary Screen
6. By default, each thermostat’s board number in the network list is indicated by a - (dash). To set the ad-
dress and begin communication, press Commission. (If you have more than one MODBUS
network, specify which network you want the de­vice to belong to.) A screen will open that will allow you set the address:
to
work Setup menu, then press mary (Figure 8-5). Locate the thermostats you set
up, and look at each device’s status in the Status field. You will see one of the following messages:
Online - The thermostat is communicating normal­ly.
Offline - The thermostat is not communicating, has not been commissioned, is not functional, or is not powered up. Verify the thermostat is powered up, wired correctly, and has the proper network address, baud rate, and parity.
Unknown - The thermostat is not communicating or has not been commissioned. Verify the thermostat is powered up, wired correctly, and has the proper net­work address, baud rate, and parity.
No Port - No port is set up in the E2 Serial Config­uration Manager to be a MODBUS port.
Wrong FW Rev - This message is likely caused by the thermostat having a firmware version older than the minimum revision required by E2 for communi­cation. Replace the thermostat with a new controller that has the latest version of firmware on it.
- Network Sum-
Figure 8-6 - Set the Address of the Thermostat
7. In the list of MODBUS devices, choose the address number corresponding to the thermostat’s dip
switch/jumper setting, and press If a network ID has already been selected, its name
will be shown next to the network ID in this list. If the network ID you are trying to assign has already been used, you must set the network ID dip switch/ jumper on this device to a different number that is not being used.
8. Repeat Steps 5 and 6 until each thermostat device has been commissioned.
9. When finished, press
24 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
to return to the Net-
to select it.
Page 32
9 Description of Installation Menu Options
Following are detailed descriptions of the config-
uration menu options.
9.1. HVAC Equipment Setup
This menu item specifies the system configura­tion. It can be configured for Heat Pump or two stage heat/two stage cool multi-stage operation.
NOTE: It is important to select the proper set­ting for this option, even if you skip the rest of the Configuration menu.
If the system is a single or multi-stage convention­al system, your options are:
Outdoor Options
• Air Conditioner: 1 Stage
• Air Conditioner: 2 Stage (default)
• Air Source Heat Pump: 1 Stage
• Air Source Heat Pump: 2 Stage
• None
Indoor options
• Air Handler: No Heat
• Air Handler: Electric Heat – 1 Stage
• Air Handler: Electric Heat – 2 Stage
• Furnace Gas / Oil – 1 Stage
• Furnace Gas / Oil – 2 Stage (default)
2. Advanced Setup — Compressor Lockout
This menu item controls the compressor lockout feature. This feature is intended to help protect the compressor from short cycling. Some newer com­pressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs, A/C return < 5 min will be displayed on the messaging area of the thermostat.
Options for this menu item include:
OFF – (Default) No compressor wait time. Assumes lockout feature is already present.
ON – Waits 5 minutes before turning on the com­pressor after a power loss or during cooling/heating cycles. Protects the compressor from short cycling.
3. Advanced Setup — Comfort Alert Active Protection
The Commercial Communicating Programmable Thermostat is competitive with the Copeland Comfort alert protocol. When connected to the comfort alert module and active protection is selected, the thermo­stat will turn off the air condition/heat pump compres­sor if a condition exists that may potentially damage the system.
4. Advanced Setup — Frost Protection
Frost protection when enabled ON provides pro­tection by activating heat even if system switch is OFF when the Room Temperature falls to 42° F. Heat will stay on until room temperature rises above 42° F. If Thermostat is Heat Pump configured thermostat will use Auxiliary heat in Frost Protection mode.
9.2. Advanced Setup
1. Advanced Setup — Cycle Rate
This menu item controls and provides choices of Comfort, Standard (default), and Economy cycle rates for Heating, Cooling and Back-up Heat (on heat pump configuration). Normal setting is standard if more frequent cycles are desired choose the Comfort selection. If less cycles are desired, choose the Econ­omy selection.
HVAC Equipment Setup Description of Installation Menu Options • 25
5. Advanced Setup — O/B Configuration
This configures whether the O/B terminal for the heat pump reversing valve will be energized during cool (O) or heat (B) mode.
6. Advanced Setup — Fast Second Stage (Multistage Systems)
A selection of on will enable the thermostat to turn on all available stages whenever the setpoint it manu­ally changed 3 degrees or more from the current room temperature.
7. Advanced Setup — Dual Fuel (Available When
Page 33
Configured for Heat Pump with Gas Furnace)
The thermostat has the capability to control dual fuel systems without an outdoor sensor or Smart Fuel logic.
8. Advanced Setup — Dual Fuel by Smart Fuel Operation
In the Smart fuel logic configuration, the Com­mercial Communicating Programmable Thermostat can determine when the heat pump is no longer effi­cient and optimize system changeover to the fossil fuel back-up. In the Smart Fuel Logic menu, you have a choice of 1-9 settings. Default setting is 5 and can be adjusted up to 9 to bring on fossil fuel sooner at higher outdoor temperature or down to 1 to keep the heat pump on at a lower outdoor temperature.
9. Advanced Setup — Dual Fuel by Sensor Operation (Available When Outdoor Sensor is Connected and Enabled)
In sensor configuration the Commercial Commu­nicating Programmable Thermostat you can select the outdoor ambient temperature (HP Lockout) the sys­tem will switch from heat pump to fossil fuel (-20 to 30° F range). You can also select an outdoor ambient at which temperature and above the Auxilia­ry heat is disabled (Aux Lockout selection range 34 to 90° F).
10. Advanced Setup — Heat Pump Comfort / Economy Operation in Heat mode (Available when configured for Heat Pump)
Comfort mode: In Heating mode. If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat will be energized to satisfy the same heating set point.
Economy mode: In Heating mode. If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat will be energized to satisfy only when the tem­perature has dropped 2.0° F (1.1° C) below the heat­ing setpoint. Selecting economy mode will add a deadband between the heat pump & auxiliary heat in heating mode. The actual temperature maintained will be lower than the true heating setpoint to maximize the heat pump efficiency.
11. Advanced Setup — Heat Lockout Outdoor (Available When Outdoor Air Sensor is Enabled)
Disables heating operation based on outdoor air temperature. When the outdoor air temperature is above this value, all heating is disabled. (Setting range is from -15 to 120° F.)
12. Advanced Setup — Cool Lockout Outdoor
(Available When Outdoor Air sensor is Enabled)
Disables cooling operation based on outdoor air temperature. When the outdoor air temperature is be­low this value, all heating is disabled. (Setting range is from -20 to 95° F.)
13. Advanced Setup — Compressor Optimization
Allows for a more comfortable and efficient oper­ation of heating and cooling. When the Compressor Optimization is enabled “on” the circulator blower (fan) will energize five seconds after the compressor energizes when cooling (and heating for heat pump applications). In cooling to extract additional cooling form the system the circulator blower (fan) will re­main energized for twenty seconds after the compres­sor de-energizes when cooling.
14. Advanced Setup — Dehumidification
This feature functions in the cooling mode and al­lows for dehumidification by enabling cooling opera­tion to reduce humidity. You have two dehumidification mode choices: Optimum Comfort (OC) and Optimum Dehumidify (OD).
Optimum Comfort (OC): Operates by alerting the room temperature to a “feels like” temperature when the indoor humidity level is above the user setting. The altered temperature allows for longer cooling cycles to lower the indoor humidity.
Optimum Dehumidification: Operates by initiating a cooling cycle when humidity level is above the user setting and the room temperature is not less than three degrees below the setpoint. Cooling will re­main on until the humidity level drops to within 2% of the setting, or the room temperature falls to 3 de­grees below the setpoint.
15. Advanced Setup — Deadband
Deadband is a user selectable temperature range the thermostat will maintain between the heating and cooling setpoints while operating in auto-changeover mode. In auto-changeover the cooling setpoint must be higher than the heating setpoint to avoid a conflict. The user can program the heat and cooling setpoints at the same setting and the deadband will resolve set­point conflicts. Default setting is 2 with a range of 2 to 4° F.
16. Advanced Setup — Power-up Delay
The feature will momentarily delay system start­up after a power outage (each time 24VAC power supply to thermostat is interrupted and reapplied) the user can select a delay of operation of the system (fan, cooling or heating). This feature can be used to se-
26 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 34
quence start up multiple unit/thermostat in one loca­tion. The default value is OFF. The range of settings is from 10 sec to 120 sec.
9.3. Installation Menu
9.3.1. About the Device
This menu item provides access to a customer screen providing details about the thermostat and communication firmware version.
9.3.2. Economizer Settings
1. Mode
Installer can select between a fixed or variable damper operation.
2. Actuator Setting
Installer can select between 0-10VDC actuator or 2-10VDC actuator operation (Table 9-1).
3. Minimum Damper
Installer can select a minimum fresh air position for the damper. When the fan G terminal is ON and the thermostat is in occupied mode, the minimum fresh air position will be maintained.
4. Use for Cooling (Economizer) — Outdoor and Supply Air Temperature Sensors Required
Allows the operation of the mechanical cooling if the free cooling (economizer) cannot maintain the cooling setpoint.
OFF -Typically applies when the SAT (supply air temperature sensor) is installed after the mechanical cooling refrigeration coils. In this case, mechanical cooling will never operate at the same time as free cooling.
ON -Typically applies when the SAT (supply air temperature sensor) is installed before the mechani­cal cooling refrigeration coils in the mixing plenum. In this case, mechanical cooling is allowed when the free cooling (economizer operation) cannot main­tain the cooling setpoint.
Default value: OFF.
5. Changeover OT Setpoint — Outdoor Air Temperature Sensor Required
In Cooling mode. If the outdoor temperature is be­low this value, the cooling will be switched over from mechanical (compressor) to free cooling (economiz­er). 14 to 70º F (-10.0 to 21.0º C). Default value: 55º F(13.0º C).
6. Supply Air Setpoint — Supply Air Temperature Sensor Required
Installer can select the supply air setpoint that al­lows for economizer (free cooling) operation. Supply air setpoint. Free cooling supply air setpoint when economizer mode is enabled. Range 50 to 90º F (10.0 to 32.0º C). Default value: 55º F (13.0º C).
7. Economizer Delta — Outdoor Air Temperature Sensor Required
The Economizer Delta number is used to decide if the room temperature is above the outdoor tempera­ture. If the indoor temperature is above the selected delta setting the economizer will be enabled. Range 1 to 10º F.
8. Occupancy Pre-purge
The feature is used prior to the occupied program periods. The thermostat will automatically turn on the circulator blower and open damper for a pre-purge up to three hours before the Day schedule period time. When enabled, the circulator blower is on during the occupied time until the unoccupied Night scheduled program time. Ran ge OFF; 10 min; 3 0 min; 1 hr; 2 hr; 3 hr. Default: OFF.
9.3.3. Sensor Settings
1. OAT Enable
Turns on the outdoor air temperature sensor
2. OAT Display
Outdoor Temperature displayed on home screen
3. OAT Offset
Installer offset of outdoor air temperature sensor to compensate for conditions (direct sunlight) affecting the sensor
4. IRT Enable
Turns on the indoor remote air temperature sensor
5. IRT Display
Displays indoor remote reading on home screen
Outside
Air%
Setting for 0~10VDC Actuator
Setting for 2~10VDC Actuator
Table 9-1 - Actuator Setting Options
0
%5%10%15%20%25%30%
0% 5%
0 to 20 %
10%15%20%25%30
%
24%28%32%36%40%44
%
Installation Menu Description of Installation Menu Options • 27
Page 35
6. IRT Offset
Installer offset of indoor remote air temperature sensor to compensate for conditions (lighting, office equipment) affecting the sensor.
7. IRT Weight
Define the weight of indoor temperature room temperature display calculation. Default value of 50% gives equal weighting between the remote sensor and thermostat internal sensor. Setting Range 0%, 25%, 50%, 75%, 100%
8. SAT Enable
Turns on the supply air temperature sensor
9. SAT Display
Supply Temperature displayed on home screen
10. SAT Offset
Installer offset of supply air temperature sensor to compensate for conditions affecting the sensor
11. RH Display
Relative Humidity displayed on home screen
12. RH Offset
Installer offset of indoor humidity to compensate for conditions affecting the sensor
13. Fan Proof
When enabled, the thermostat will check the status of the fan proof input S4 terminal input. If the fan is not operating, all associated system functions are turned off and an alarm is initiated.
14. Sensor Status
This feature shows the user the status of each sen­sor. E2 can override the value from each sensor.
Set the method for the Protocol Parity
Parity
check. When the Protocol Parity is highlighted in In­stallation Menu, the user can press the RIGHT button to access the Protocol Parity screen. It will display as follows: The default value is None. The option values include Odd and Even. UP, DOWN, LEFT and RIGHT arrow buttons, refer to Section 3.6.3., Using the Navigation Keypad. LEFT, MIDDLE, RIGHT soft buttons and RIGHT arrow button are disabled.
Address
Set the address of thermostat. When the Address is highlighted in Installation Menu, the user can press the RIGHT arrow button to access the Ad­dress screen. It will display as follows: The default value is 136. The option Value is from 1 to 240. UP, DOWN, LEFT and RIGHT arrow buttons, refer to Section 3.6.3., Using the Navigation Keypad. LEFT, MIDDLE, RIGHT soft buttons and RIGHT arrow button are disabled.
Network Status
Get the network status between thermostat and a MODBUS RTU Master Building controller. When the Status is highlighted in Installa­tion Menu, the user can press the RIGHT arrow but­ton to access the status screen.
Network Message
Every message will appear in the Inbox (maximum inbox capacity = 5 messages). If the inbox reaches the maximum capacity and a new message comes in, the user cannot select which mes­sage to delete from the inbox (either the oldest, opened message will be erased or if all messages have not been opened or read, the oldest, unread message will be erased). The message header will display the time when mail was received. When there is an un­read message, the Mail LED will display on the home screen. Unread messages will be bulleted and appear in bold. When the Inbox is highlighted in the Installa­tion Menu, the user can press the RIGHT arrow but­ton to access the Inbox screen.
9.3.4. Network Button
Network Configuration is accessed by pressing the
NETWORK button.
Network: Installation Info/ Network Status
This menu item provides access to a customer screen providing details on the installation and the Network Status.
Baud Rate
tion.When t h e Baud Rate i s highlighted in Installation Menu, the user can press the RIGHT button to access the Baud Rate screen. The default value is 9600. The option values include 19200 and 38400. UP, DOWN, LEFT, and RIGHT arrow buttons, refer to Section
3.6.3., Using the Navigation Keypad. LEFT, MID- DLE, RIGHT soft button and RIGHT arrow button are disabled.
28 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Set the baud rate for network connec-
Page 36
10 Troubleshooting Guide
No Heat/ No Cool/ No Fan (Common Problems)
Possible Cause Corrective Action
Blown fuse or tripped circuit breaker. Replace fuse or reset breaker.
Furnace power switch set to OFF. Turn switch to ON.
Furnace blower compartment door or panel is loose or not properly installed.
Table 10-1 - No Heat/ No Cool/ No Fan (Common Problems)
No Heat
Possible Cause Corrective Action
Pilot light not lit. Re-light pilot.
System switch not set to HEAT.
Loose connection to thermostat or system. Verify thermostat and system wires are securely attached.
Furnace Lock-Out Condition. Heat may also be intermittent.
Replace door panel in proper position to engage safety interlock or door switch.
Press the SYSTEM button one or more times to select HEAT and
press to raise the temperature setpoint above room temperature.
Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently, contact the furnace manufacturer or your HVAC contractor for assistance.
Heating system requires service or thermostat requires replacement.
Table 10-2 - No Heat
Diagnostic: Press the SYSTEM button to select HEAT and press to raise the temperature setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation described on Section 10.1., Reset Operation. If the thermostat does not click after being reset, contact your HVAC contractor or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or your HVAC contractor to verify the heating is operating correctly.
Installation Menu Troubleshooting Guide • 29
Page 37
No Cool
Possible Cause Corrective Action
System Switch not set to COOL.
Press the SYSTEM button to select COOL and press to lower the temperature setpoint below room temperature.
Loose connection to thermostat or system. Verify thermostat and system wires are securely attached.
Diagnostic: Press the SYSTEM button to select COOL and press to lower the temperature setpoint below room temperature. Within a few seconds the thermostat should make a soft click sound. This sound
Heating system requires service or thermostat requires replacement.
usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation described on Section 10.1., Reset Operation. If the thermostat does not click after being reset, contact your HVAC contractor or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or HVAC contractor to verify the heating is operating correctly.
Table 10-3 - No Cool
No Heat or No Cool
Possible Cause Corrective Action
Thermostat may be in Load Shed (a Control Event is in progress).
Table 10-4 - No Heat or No Cool
Wait for the Control Event to end.
Heat, Cool, or Fan Runs Constantly
Possible Cause Corrective Action
Fan set to ON. Change Fan to AUTO.
Check each wire connection to verify they are not shorted or touching
together. No bare wire should stick out from under terminal screws. Try Possible short in wiring, thermostat, or HVAC system.
resetting the thermostat as described on Section 10.1., Reset Operation.
If the condition persists, the manufacturer of your system or HVA C
contractor can instruct you on how to test the HVAC system for correct
operation. If the system operates correctly, replace the thermostat.
Table 10-5 - Heat, Cool, or Fan Runs Constantly
Blank Display and/or Keypad Not Responding
Possible Cause Corrective Action
Voltage spike or static discharge. Use the Reset Operation described on Section 10.1., Reset Operation.
Table 10-6 - Blank Display and/or Keypad Not Responding
30 • Commercial Communicating Programmable Thermostat I&O Manual 026-1729 Rev 2 15-NOV-2016
Page 38
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (Narrow or Wide Temperature Swing)
Possible Cause Corrective Action
Digital thermostats normally provide precise temperature control
The location of the thermostat and/or the size of the heating system may be influencing the cycle rate.
Table 10-7 - Furnace (Air Conditioner) Cycles Too Fast or Too Slow (Narrow or Wide Temperature Swing)
and may cycle faster than some older mechanical models. A faster cycle rate means the unit turns on and off more frequently, but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, choose Economy for slow cycle in the menu.
Second and Third Stage Won’t Come On
Possible Cause Corrective Action
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the fir st sta ge of the system.
Table 10-8 - Second and Third Stage Won’t Come On
Wait for the second or third stage to come on.
10.1.Reset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can cycle the thermostat power by unplugging the thermostat from the baseplate for a few seconds then plugging the thermostat back onto the mounting plate.
Reset Operation Troubleshooting Guide • 31
Page 39
Page 40
Page 41
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the produc ts or services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selecti on, use or maintena nce of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.
026-1729 15-NOV-2016 Emer son is a trademark of Emerson Electric Co. ©2016 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.