Installation instructions
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precaut ions shou ld al wa ys be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Make sure the area is NON-HAZARDOUS before installing or servic­ing the unit.
2. Turn off electrical power before and during installation and mainte­nance.
3. Before opening, turn off electrical power and wait until the unit is cool.
4. Do not install where the marked operating temperatures (T-Code) exceed the ignition temperature of the hazardous atmosphere.
5. Do not operate in ambient temperatures above those indicated on the rating labels.
6. Keep tightly closed when in operation.
7. Do not use outdoors.
8. Do not mount near gas or electric heaters.
9. Use caution when handling batteries. Battery acid can cause burns to the skin and eyes. If acid is spilled on the skin or eyes, flush acid with fresh water and contact a physician immediatly. Avoid possible shorting.
10. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
1 1. The use of accessory equipment not recommended by the manufac-
turer may cause an unsafe condition.
12. Do not use this equipment for other than intended use.
13. Servicing of this equipment should be performed by qualified service personnel.
1
2
4
3
8
5
7
Figure 1
Part List
1. Tamper-proof screw
2. Screw covers
3. Lens-legend
4. EXIT panel
5. Diffuser panel
6. Frame
7. Electronic module
8. Electronic module screws (4)
6
10
11
12
13
1
2
9. Back plate
10. Swivel
11. MR16 lamp
12. O-ring
13. Lens-emergency light
14. Knock-out covers
15. Junction box
Conduit
9
14
SAVE THESE INSTRUCTIONS
Installation Instructions
1. T urn off unswitched AC power .
a. Remove the lens-legend (3). Disconnect the lamps from terminal
block (see fig 4) and remove the electronic module (3). Four screws secure the electronic module to the housing.
b. Determine which holes in the housing will be used for AC wires. Sup-
port frame by two blocks of wood, maximum one inch apart. Strike knockouts with a hammer and screwdriver. Clear holes of burrs to allow proper installation of the fit ting. Install conduit fitting rated for Class I Div 2, on the housing. For Nexus option, install the liquid tight fitting, provided with the unit to route the data cable.
Conduit Entry
a. Install the unit on the wall with 4 screws (not provided). Use the ears
located on each side (see figure 2).
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
Figure 2
Fitting
k’out
ears
12/08 750.1377 Rev. B
1/2
b. Route unswitched AC circuit wires into the housing through conduit. c. Reinstall the electronic module inside the housing using the four
screws.
Junction Box Entry
a. Remove appropriate knock-outs on back plate for installa tion on ju nc-
tion box (see figure 3).
b. Route unswitchd AC circuit wires into the housing through large hole
in back plate.
c. Install the unit on the junction box (Rated for Class1 Div 2) with the
junction box screws.
d. Reinstall the electronic module inside the housing using the four
screws.
2. ELECTRICAL CONNECTIONS Auto-diagnostic models (refer to figure 4
a. Connect transformer primary wires to AC wires from building: white
wire with neutral; black (120Vac) or orange (277Vac) to line voltage. Unused primary wire must be insulated to prevent shorting. Con nect
green wire to the ground. b. Reconnect the lamps on terminal blocks (L1+/L1-). c. For units with remote capacit y , connect the remote head s DC+ to L1+
and DC- to L1-. d. Connect the battery to the charger board.
Nexus models:
See Nexus addendum for the details on electrical connect ion.
3. Lamps adjustment:
a. To access the lamps, remove the lens. Remove the lamps protec-
tors. Adjust the lamps in appropriate position. Put the lens back in
place.
4. Put the unit cover back in place. Make sure the unit is tightly closed.
5. Energize AC.
.):
SVXH Series – Class I, Div 2 Combo Unit
15
Figure 3
Figure 4
Manual Testing
Operate the magnetic “test switch” by holding the provided magnet where indicated near the LED display (see figure 5). This will initiate a one minute test. The DC lamps will illuminate for approximately one minute, then the unit will automatically return to stand by mode. Test can be cancelled by holding the magnet near the test switch again.
Automatic Testing
The unit will perform an automatic self-test of 1 minute every month, 10 minutes every 6 month and a 30 minutes self-test once a year.
Automatic Diagnostics
There are five diagnostic indicators: one externa l and four i nternal. Unit must be opened to gain access to internal indicators. External: Servicel alarm, “Service Required”. The LED will turn-on if any alarm condition is detected (see fig. 5). Internal: Battery Failure, Battery Disconnect, Charger Failure & Lamp Fail­ure. Steady ON if alarm condition ex ists.
Normal operation, No fault — “Service Required” is OFF. Faulty operation — “Service Required” is ON.
(see AD charger owner manual for more details)
Nexus models
Nexus models use two local indicators. One is a green LED for AC pilot lamp. The other is a bicolor LED (Service) which identifies and displays the Nexus status. See Nexus addendum for details.
Service Alarm
Figure 5
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com