Emergi-Lite SVX Combo User Manual

SVX Series – Survive-All Combination Unit
SVX Series – Survive-All Combination Unit
Emergency Light and Exit Sign
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Do not let power supply cords touch hot surfaces.
2. Do not mount near gas or electric heaters.
3. Use caution when handling batteries. Avoid possible shorting.
4. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
5. The use of accessory equipment not recommended by the manufac­turer may cause an unsafe condition.
6. Do not use this equipment for other than intended use.
7. All servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
Installation Instructions
1. Turn off unswitched AC power.
Canopy Mount
a. Remove canopy assembly from carton. Remove mounting plate
from canopy and retain securement screw.
b. Route unswitched AC circuit wires into the junction box and leave
6” of wire length.
c. Remove proper knockouts in canopy backplate for desired
mounting position.
d. Feed unswitched AC wires through large hole in canopy mount-
ing plate.
e. Make sure the securement screw is accessible (see fig.1 & 2 part
# 13). Use existing screws in junction box to secure canopy back­plate to the junction box.
f. Remove lens, exit panel and diffuser panel from the packaging.
Figure 1 (single face)
Part List
1. Tamper-proof screws short (6 per side)
2. Screw covers
3. Lens-legend
4. EXIT panel
5. Diffuser panel
6. Frame
7. Electronic module
8. Electronic module screws (4)
9. Backplate (single face sign)
10. Diffuser (double-face)
11. Lock-nuts (2)
12. Gasket washer (2)
13. Canopy securement screw
14. Canopy
15. Nipple assembly (2)
16. Canopy backplate
17. Junction box screws (not supplied)
18. Junction box (not supplied)
19. Nylon washer (2 for wall mount)
20. Junction box gasket (for wall mount)
21. Swivel
22. MR16 lamp
23. O-ring
24. Lens-emergency light
25. Knock-out cover
26. Canopy gasket (for end or ceiling mount)
Figure 2 (double face)
Emergi-Lite Tel: (888) 552-6467 ext. 547 or 255 Fax: (888) 867-1565 www.emergi-lite.com
02/08 750.1157 Rev. B
1/4
g. In order to access the knockouts of the frame, remove the 4 elec-
tronic module screw(s) holding the electronic module to the frame (see fig.3 & 4), disconnect the lamps from terminal block and remove the electronic module.
h. Determine which holes in the exit frame will be used for mounting
(see fig.1,2 & 5). Support frame by two blocks of wood, maximum one inch apart. Strike knockouts with a hammer and screwdriver. Clear holes of burrs to allow proper assembly of nipple/wire assembly.
i. Secure canopy to the frame using the provided nipple/wire
assembly. Make sure the gasket is between the canopy and frame, and the nuts inside the exit sign (see fig. 5).
j. Reassemble the elec tronic module inside the frame and do the
electrical connections inside the enclosure. Double face: diffuser (part 10 shown in fig. 2) to be removed in order to do the electrical connections (see page 3).
Wall Mount (Single Face Model Only)
a. Remove the backplate from the packaging. Determine the proper
knockouts to remove for mounting to a junction box (see fig.6).
b. Support area around knockouts with two blocks of wood. Strike
knockouts from the inside with a hammer and a screwdriver.
c. Remove the 4 electronic module scre w(s) holding the electronic
module to the frame (see fig.3 & 4),disconnect the lamps from ter­minal block and remove the electronic module.
d. Mount parts 11, 12, 15 & 19 to backplate, as shown in fig. 6, and
reinstall the backplate to the frame using the tamper-proof screws
(use the supplied bit). e. Do the electrical connections inside the junction box (see page 3). f. Attach the frame to the junction box, using the junction box sup-
plied screws. g. Use the hook provided with in the canopy to temporarly support
the electronic module on the frame. h. Complete electrical connections (see page 3).
SVX Series – Survive-All Combination Unit
Figure 3 (single face)
Figure 4 (double face)
Figure 5
Figure 6
Emergi-Lite Tel: (888) 552-6467 ext. 547 or 255 Fax: (888) 867-1565 www.emergi-lite.com
02/08 750.1157 Rev. B
2/4
Loading...
+ 2 hidden pages