Emergi-Lite SV User Manual

Page 1
SV Series – Survive-All
Figure 1
Part List
1. Tamper-proof screws (6)
2. Clear cover
3. Screw gasket
4. Lamps
5. Electronic module
6. Battery
7. Battery strap or bracket
8. Backplate
9. Gasket
10. AC harness
11. Ground wire
12. Wire nut
13. J-box (not supplied)
14. J-box screws (not supplied)
15. Screw cover
Figure 2
knockout
for conduit
knockout for Nexus data cables
Emergency Light unit
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. All servicing should be performed by qualified service personnel.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Use caution when handling batteries. Avoid possible shorting.
5. Equipment should be mounted in locations and at heights where it
will not readily be subjected to tampering by unauthorized personnel.
6. The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
7. Caution: If optional Halogen cycle lamp(s), symbol (H—), are used in
this equipment, to avoid shattering: do not operate lamp in excess of rated voltage, protect lamp against abrasion and scratches and against liquids when lamp is operating, dispose of lamp with care.
8. Halogen cycle lamps operate at high temperatures. Do not store or
place flammable materials near lamp.
9. Do not use this equipment for other than intended use.
SV Series – Survive-All
SAVE THESE INSTRUCTIONS
Installation Instructions
1. Turn off unswitched AC power.
2. Open clear cover by removing the screws making sure not to loose the screw gaskets. Remove lamp protectors.
3. Remove the electronic module. Pull on the cover until snapping fea­tures disengage or use a screw driver by inserting it into the slots shown in figure 12 and prying the cover open.
4. Remove the battery in order to access the knockouts (k’out).
5. Install back plate:
Wall mounting on a junction (figure 2)
a. Route unswitched AC circuit wires into the junction box and leave
6” of wire length.
b. Remove the k’outs needed to mount back plate. Considering the
weight of the unit, it’s recommended to use key hole for additional securing(see fig.4). For Nexus wired option, install the liquidtight fitting, provided with the unit. Use the k’out located on the bottom of the unit.
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
10/13 750.1518 Rev. B
1/4
Page 2
c. Remove AC harness from electronic module. Wire to AC circuit
- 120 VAC OPERATION -
White wire - Common Black wire - 120V Line Green wire - Ground
-277 VAC OPERATION-
White wire - Common Orange wire - 277V Line Green wire - Ground
INSTRUCTIONS - HOOKUP
Unused primary wire must be insulated to prevent shorting
Figure 4
key-hole
Figure 5
Figure 3
To ensure watertightness:
install the screw gaskets
inside the unit, as shown. Put the screw in the lens
hole and than install the screw gasket.
wires using wire nuts (see figure 2). Refer to hookup instructions on page 2.
d. Install the gasket on the back plate. Feed AC harness and the
ground through the large hole in the backplate (see figure 2). Mount to J-box using the J-box screws (not provided). J-box
should be properly secured directly to a stud. Note: When back mounting the unit on uneven surface such as brick, silicone caulk should be used to prevent water from seeping in between the unit and the J-box.
Wall mounting with conduit
a. Remove k’out on top of the backplate for conduit entry and key
hole k’out to fix the backplate to the wall. For Nexus wired option,
install the two holes liquid tight fitting, provided with the unit, on
the bottom of the back plate. Don’t route data cables with AC
wires.
b. Install a liquid tight conduit fitting on the backplate. Conduit size:
1/2” NPT (not provided).
c. Install the unit on the wall using screws (not provided). d. Connect the conduit to fitting and route unswitched AC circuit
wires in the unit.
e. Remove AC harness from electronic module. Wire to AC circuit
wires using wire nuts. Refer to hookup instructions..
SV Series – Survive-All
Pole or I-beam mounting (Option)
a. Universal bracket (part 16 on figure 4) is an accessory and needs
to be ordered separately. Remove knockouts on top of the back-
plate for conduit entry.
b. Install a liquidtight conduit fitting on the backplate. Conduit size:
1/2” NPT.
c. Install the universal bracket as shown in figure 4. Don’t install the
gasket (9). Note: this type of installation is not NSF certified for
food processing areas.
d. Unit can be installed using steel banding for routing around the
poles and I-beam. Standard banding ¾" in width or less can be
used (not provided). It can also be mounted on Superstrut®
metal framing (1 5/8" channel series) using 1/4" bolt (not pro-
vided). Holes are placed at 9" apart horizontally.
e. Connect the conduit to fitting and route unswitched AC circuit
wires in the unit.
f. Remove AC harness from electronic module. Wire to AC circuit
wires using wire nuts.Refer to hookup instructions.
6. Complete electrical connection:
Standard product:
a. Re-install batteries and electronic module as shown on figure 5.
See figure 6 for batteries wiring diagram.
b. Connect transformer harness to AC harness.
Cold weather option:
a. Connect battery heater (18) to thermostat (19) and to AC harness
(10) (see figure 7).
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
10/13 750.1518 Rev. B
2/4
Page 3
b. Refer to figure 8 for 120VAC input voltage and to figure 9 for
Figure 6
Figure 7
Figure 8
120V
Figure 9
277V
277VAC . Use wire t aps provided with the hardware kit to connect battery heater. Unused wires must be insulated to prevent short­ing.
c. Re-install the batteries. Battery heater is placed between the bat-
tery and the backplate. See figure 6 for battery
wiring diagram.
Re-install the electronic module as shown on figure 5.
d. Connect transformer harness to AC harness.
7. For unit with remote capacity, connect remote heads to termi­nal L+ and L- (see figure 11).
Calculation of total allowable remote capacity of unit: Maximum remote lamp power = unit capacity minus the total power of lamps included with unit.
8. Snap electronic module on backplate.
9. Adjust lamp aiming.
10.Install the lens by using the 6 tamper-proof screws (1). To insure water tightness, gasket screws (x6) have to be installed from the inside (see figure 3). Tighten the screws approxi­mately 5 Lb.-Ft. DO NOT OVER TIGHTEN.
11.For food processing areas, in order to avoid food accumula­tion, screw caps have to be installed (provided with the hard­ware kit).
12.Energize AC. Lamps will turn on for few minutes.
13.See page 4 for testing procedure.
SV Series – Survive-All
Nexus:
For connections related to Nexus system, refer to Nexus Adden­dum.
FOR COLD WEATHER
OPTION ONLY
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
10/13 750.1518 Rev. B
3/4
Page 4
Unit testing
Figure 10
Magnetic test
LED Status
Figure 11
Figure 12
Manual Testing
Operate the magnetic test switch by holding the provided magnet near the status LED, where indicated. This will initiate a one minute test and the lamps will illuminate. At the end of the test, the unit will automatically return to stand by mode. Test can be cancelled by holding the magnet near the test switch again.
Automatic Testing and diagnostics
The automatic testing and diagnostic function includes a micro­controller which self-tests the unit on a monthly basis and identi­fies as well displays failures of the electrical components: battery, battery charger and lamps.
Self-test
The self-test is performed every month for 1 minute, every 6 months for 30 minutes, and annually for 90 minutes.
Diagnostic function
The diagnostic function uses an external red LED indicator. Service is required if the red LED is present indicating that an alarm condition is detected (See fig. 10).
SV Series – Survive-All
o
o Green Steady On AC On o Red Steady On Battery Disconnect
-o Red Blinking Battery Failure
o-o Red Two Blinks Charger Failure
o-o-o Red Three Blinks Lamp Failure
For Nexus models, refer to “Nexus addendum” and for additional infor­mation about the Nexus system, go to “www.nexus-system.com”. For more information about the AD function, please consult the web site for this user manual: “AD with Single LED Status User Manual”
Food processing facilities
Screw covers are available in the hardware kit. These covers have to be installed on screws to avoid any food accumulation. Note: some detergent used in food processing industry can affect durability of Polycarbonate lens. Install unit on even wall surface to insure watertightness and avoid any gaps between the gasket and the wall.
Maintenance (All Models)
None required. If AC supply to the unit is to be disconnected for 2 months or more, the battery must be disconnected.
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com