Prestige Series - Edge-Lit LED Exit Series
Prestige Series - Edge-Lit LED Exit Series
Flat trim AC, AC/DC and Self-Powered models
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not use outdoors.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and at heights where it
will not readily be subjected to tampering by unauthorized personnel.
5. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
6. Do not use this equipment for other than intended use.
7. All servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
Installation Instructions
Turn off AC power.
Installation (Figure 1)
1. Remove the proper knockout in the back box for the entry of the AC
wires.
2. Assemble the recessed mount brackets to the back box (see figure
2). Install the bar hangers in the adjustment brackets . Mount the
back box so that it is flush with the ceiling surface.
3. Route AC unswitched circuit of rated voltage into the back box and
leave 6” of wire length.
4. Connect the incoming ground to the short ground wire provided in the
back box.
5. Electrical connection (Figures 3,4)
a. Connect the long ground lead with eyelet from the back box to the
trim plate assembly with the hardware provided.
b. Make the proper connections. Our system can accept input volt-
ages of 120 VAC to 347 VAC. For regular models connect the
purple (hot) and white (common) leads to the building utility (Figure 3). For models with diagnostic feature connect the white
(common), black (120 VAC) or orange (277 VAC) leads to the
building utility (Figure 4).
c. AC/DC Models only:
For DC portion: wire the Red lead (+) to the positive DC input voltage
and the Blue lead (-) to the negative DC input voltage. Note: DC input
voltage range is 6 volts to 24 volts.
6. Compress the retention springs (Figures 5) and insert the trim plate
assembly in the back box. Align to be flush with the back box or with
the ceiling.
Figure 1
Part List
1. Back box
2. Adjusment brackets (2)
3. Bar hangers (2)
Figure 2
4. Trim plate assembly
5. Clips (2)
6. Exit panel
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
07/09 750.1436 Rev. A
1/2
Prestige Series - Edge-Lit LED Exit Series
Exit panel installation (Figure 1)
1. Remove the exit panel form its carton, do not remove the protective
sleeve until the installation is complete.
2. Partially remove the protective sleeve at the top of the exit panel.
Push the exit panel, with the clips, into the slot in the trim plate
assembly until it snaps. Gently try to pull out the panel to ensure that
it is engaged in the trim plate assembly. Remove the protective
sleeve.
3. Energize AC circuit. Legend and green pilot indicator (self-powered
models), will illuminate.
Important:
the Exit panel can only be removed by lowering the trim plate
and pushing on the end clip located on the opposite side of the test
switch with a screwdriver.
Self Powered models
Manual testing (Figure 6)
Press test switch. Legend will flicker then will remain lit. On release,
external green LED will illuminate, and automatic charger will restore
battery to full charge.
Automatic testing and diagnostics (optional)
The models with the automatic testing and diagnostic option include a
micro-controller which tests the unit on a monthly basis and identifies as
well displays failures of the electrical components: battery, charger circuit, LED lamps.
Self-test
The self-test is performed every 30 days for 30 seconds, every 60 days
for 30 minutes, and annually for 90 minutes.
Diagnostic function (Figure 6)
The diagnostic function uses the pilot light LED indicator. Service is
required if the green LED changes color to red indicating that an alarm
condition is detected.
Red + DC
Blue - DC
DC wires
for remote
DC supply
Figure 3 (Regular models)
(Optional)
Red 347VAC
Orange 277VAC
Black 120VAC
White neutral
Figure 4
(Models with diagnostic feature)
Purple AC
White neutral
Back box
LED Strip
DC wires for
Fire alarm input
Red + Fire Alarm
Blue - Fire Alarm
Back box
Transformer
LED Strip
Pilot light
Green
Green
Red
Red
Red
Red
Status
Steady
Blinking
Steady on
One Blink
Two Blinks
Four Blinks
Diagnostic
Normal (AC On)
Auto Test
Battery Disconnect
Battery Failure
Charger Failure
LED Lamp Failure
Maintenance
None required. Models equipped with batteries: if AC supply is to be disconnected for 2 months or more, the battery must be disconnected (SelfPowered Models only).
Note — For safety reasons Nickel Cadmium batteries are shipped discharged. The unites may require 10 minutes of connection to AC supply
before start-up test procedure, and two to seven days to reach full
charge.
Figure 5
AC Pilot light / Test switch
Diagnostic light (optional)
Trim plate
Figure 6
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
07/09 750.1436 Rev. A
2/2