Prestige Series - Edge-Lit LED Exit Series
Prestige Series - Edge-Lit LED Exit Series
Flat trim AC, AC/DC and Self-Powered models
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not use outdoors.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and at heights where it will
not readily be subjected to tampering by unauthorized personnel.
5. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
6. Do not use this equipment for other than intended use.
7. All servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
Installation Instructions
Turn off AC power.
Installation
1. Remove the proper knockout in the back box for the entry of the AC
wires.
2. Assemble the bar hangers (3) to the adjustment brackets (2) and the
adjustment brackets to the back box (see fi gu re 2). In stall the bar
hangers in the adjustment brackets . Mount the back box so that it is
flush with the ceiling surface.
3. Route AC unswitched circuit of rated voltage into the back box and
leave 6” of wire length.
4. Follow directions on the panel for chevron placement. (Note: for single sided units with clear background place chevron on back of
panel).
5. Connect the incoming ground to the short ground wire provided in the
back box.
6. Electrical connection
a. Connect the long ground lead from the back box to the ground
lead from the trim plate assembly with the hardware provided.
b. Make the proper connections (see figure 3). Our system can
accept input voltages of 120 V AC to 347 VAC. For regular models
connect the purple (hot) and white (common) leads to the building
utility (Figure 3).
c. AC/DC Models only:
For DC portion: wire the red lead (+) to the positive DC input voltage
and the blue lead (-) to the negative DC input voltage. Note: DC input
voltage range is 6 volts to 24 volts.
Figure 1
Part List
1. Back box
2. Adjusment brackets (2)
3. Bar hangers (2)
Slots to receive
retention
springs
4. Trim plate assembly
5. Exit panel
Figure 2
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
04/11 750.1541 Rev. A
1/2
Prestige Series - Edge-Lit LED Exit Series
7. Compress the retention springs (Figures 4) and pass them through
the slots on the back box (1) (see figure 2) and push the trim plate
assembly into the back box. Align to be flush with the back bo x or
with the ceiling.
8. Plug battery (self powered models only).
Self Powered models
Manual testing
Press test switch (see figure 5). Legend will flicker then will remain lit. On
release, external green LED will illuminate, and automatic charger will
restore battery to full charge.
Maintenance
None required. Models equipped with batteries: if AC supply is to be disconnected for 2 months or more, the battery must be disconnected (SelfPowered Models only).
Note — For safety reasons Nickel Cadmium batteries are shipped discharged. The unites may require 10 minutes of connection to AC supply
before start-up test procedure, and two to seven days to reach full
charge.
Red + DC
Blue - DC
Figure 3 (Regular models)
Purple AC
White neutral
Back box
Figure 4
AC Pilot light / Test sw itch
Figure 5
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
Trim plate
04/11 750.1541 Rev. A
2/2