Emergi-Lite Prestige DX User Manual

Prestige DX & DXN - Die Cast Aluminum LED Exit Series
Prestige DX & DXN - Die Cast Aluminum LED Exit Series
AC, AC/DC, Self-Powered and Nexus
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Do not use outdoors.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
5. The use of accessory equipment not recommended by the manufac­turer may cause an unsafe condition.
6. Do not use this equipment for other than intended use.
7. All servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
Figure 1
Part List
1. Back cover
2. Canopy
3. Canopy plate
4. Junction box (not supplied)
5. Junction box screws (not supplied)
6. Securement screw
7. Canopy screws
8. Diffuser Panel
9. Exit door
Installation Instructions
1. Turn off AC unswitched power.
2. Route AC unswitched circuit of rated voltage into electrical box and leave 6” of wire length.
3. Separate the housing assembly, back cover and exit door, using a screwdriver (see fig. 3).
Canopy mount
a. Separate the canopy plate from the canopy assembly and retain
the securement screw (see fig. 2).
b. Remove the proper knockout in the canopy plate for desired
mounting position.
c. Feed the AC unswitched wires through the large hole in the can-
opy plate. Use the junction box screws to secure the canopy plate to the junction box. Ensure the location for securement screw is accesible.
d. To knock out the chevrons, remove the diffuser panel. Support
the door around the chevrons with two blocks of wood. Strike arrow knockouts from the inside with a hammer and screwdriver. Re-install the diffuser panel using the securement clips (see fig.
3).
e. Determine which side of the exit frame will be used for mounting.
Break out the appropriate rectangular section at the canopy mounting position (see fig. 3). Make sure edges are free from burrs.
f. Secure the canopy to the exit housing by guiding flange on the
canopy into the rectangular hole in the side (or top) of the hous-
Figure 2
Screwdriver slot
Figure 3
Break out positions
Securement clips
Emergi-Lite Tel: (888) 552-6467 ext. 547 or 255 Fax: (888) 867-1565 www.emergi-lite.com
04/07 750.0895 Rev.C
1/3
Prestige DX & DXN - Die Cast Aluminum LED Exit Series
ing. Use the canopy screws to fasten the canopy to the housing (see fig. 2).
g. Route the AC supply wires and ground wire from the exit through
the rectangular hole in the exit housing and through the slot in canopy. Make the proper connection. Our system can accept input voltages from 120 to 347 VAC. Therefore, connect the pur­ple (hot) and white (common) leads to the building utility (see fig.
5). For master exit sign wiring, connect the orange (277 VAC) or the black (120 VAC) and the white (neutral) to the building utility. Feed the excess wire into the junction box.
Note — For the Nexus models wiring, go to the section “Nexus Models” (see fig. 7).
h. Mount the exit/canopy assembly to the canopy mounting plate by
guiding the two tabs on the canopy plate into the slots in canopy. Use the securement screw to fasten the canopy to the mounting plate (see fig. 2). Go to step 3.
Figure 4
Regular wiring
Master exit wiring
Wall Mount
a. No canopy required. Determine the proper knockout in the back
Purple AC
White Neutral
cover for mounting. Support the area around knockout with two blocks of wood. Strike knockouts from the inside with a hammer and screwdriver (see fig. 4). Follow the chevrons knockout proce­dure in the Canopy mount section, step e.
b. Route the AC unswitched wires through the large hole in the back
cover.
c. Mount the back cover to the junction box using the junction box
screws.
d. Make the proper connections. Our system can accept input volt-
ages from 120 to 347 VAC. Therefore, connect the purple (hot)
LED Strip
and white (common) leads to the building utility. For master exit sign wiring, connect the orange (277 VAC) or the black (120 VAC) and the white (neutral) to the building utility. Feed excess wire
Figure 5
into the junction box (see fig. 5) Note — For the Nexus models wiring, go to the section “Nexus
Models” (see fig. 7).
4. Snap the two halves of clampshell together.
5. Energize AC. Sign will illuminate.
6. Units with vandal resistant options, refer to fig. 6.
AC/DC Models
Refer to fig. 5 for AC & DC wiring. For DC portion — Wire the Red lead (+) to the positive DC input volt-
age and the Blue Lead (-) to the negative DC input voltage. Note: DC input voltage range is 6 volts to 48 volts.
Figure 6
Nexus models
Refer to figure 7 for the wiring of Nexus models. These units can accept an input voltage of 120 or 277 VAC: 120 VAC — Connect the black (120 VAC) lead and white (neutral) lead to the building utility. Insulate the orange wire. 277 VAC — Connect the orange (277 VAC) lead and white (neutral) lead to the building utility. Insulate the black wire. Feed excess wire into the junction box. Leave as much space as possible between the live voltage cabling and
the unsheathed low voltage data cabling. Run the double insulation of data cables past the line cabling section and only strip back the last 30mm of the data cable sheathing.
Emergi-Lite Tel: (888) 552-6467 ext. 547 or 255 Fax: (888) 867-1565 www.emergi-lite.com
Orange (277)
Black (120)
White Neutral
Red + DC
Blue - DC
Canopy
Transformer
DC wires for
remote DC supply
Vandal resistant screws (4) for Vandal resistant (with or without shield) Typical front & back on single or double sided units.
04/07 750.0895 Rev.C
2/3