Emergi-Lite Lux-Ray LED Battery User Manual

Lux-Ray LED - Emergency lighting
WARNING:
Risk of Shock.
Disconnect Power before Installation.
Figure 1
Back plate
Junction box
Pin guide
Inside cover
not supplied
Install ground wire here
Figure 2
Conduit (not supplied)
Back plate
Quick connect
Liquid tight fitting (not supplied)
Thread 1/2-14
Install ground
wire here
a. Battery-operated (self-powered) and AC-only units: connect
Cap the unused wire with a wire connector. b. Units for normal lighting: connect the wire input marked “nor-
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
1. All servicing should be performed by qualified service person­nel.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Use caution when handling batteries. Avoid possible shorting.
5. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized per­sonnel.
6. The use of accessory equipment not recommended by the man­ufacturer may cause an unsafe condition.
7. Do not use this equipment for other than intended use.
c. DC-remote units: connect the wire input "6-12 VDC" to the
d. Units with dual-mode lighting: normal and emergency self-
e. Units with dual-mode lighting: normal and emergency DC-
f. Units with dual AC circuit: both primary and secondary cir-
DO NOT cap together the unused wires.
Lux-Ray LED - Emergency lighting
the wire input marked “emergency lighting” to the un­switched AC line. Install the ground wire on the back plate. Connect the neutral (white) wire. For 120Vac connect black wire; for 277Vac connect orange wire.
mal lighting” to the AC line. Identify the wires by color as above. Cap the unused wire with a wire connector.
DC remote wires. The building emergency circuit must pro­vide 6-volt or 12-volt maximum. Connect red wire to the pos­itive and blue wire to the negative of the DC emergency line.
powered: follow instructions a-b.
remote: follow instructions b-c.
cuits must have the same voltage value: 120/120Vac or 277/ 277Vac. Follow instructions a and b.
SAVE THESE INSTRUCTIONS
Installation Instructions
1. Turn off the building emergency circuit and the breaker of the AC circuit for normal lighting.
2. Remove the back plate from the package.
3. Open the inside cover by turning it. Identify the wires by using the labels attached to them.
4. Choose the proper mounting below and continue to step 5.
Junction box mounting (Figure 1)
Knockout the desired holes in the back plate. Make the electri­cal connections as shown in point 5. Route the wire connectors through the large knockout and mount the back plate to the junction box.
Conduit entry mounting (Figure 2)
Remove plug on the back plate and knock out the desired holes in the back plate to secure the unit on the wall. Install the con­duit and supply wires. For wet location: install a liquid tight fitting with teflon tape. Use wire nuts provided with the unit. Bigger wire nuts might interfere with internal components.
5. Electrical connections
Depending on the model of equipment selected, the electrical connections may require one or two independent power supply circuits, as described further on.
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
02/13 750.1712 Rev. A
1/2
Lux-Ray LED - Emergency lighting
Battery
Backplate
Housing
+
-
Hook and tighten the security wire
Figure 3
Connect battery
Figure 4
Housing
Back plate
Steady on
Battery
Two Blinks
Charger Failure
Three Blinks
Lamp Failure
Battery Failure
One Blink
red
red
red
red
green
Blinking
Testing Mode
Steady
AC On
green
Disconnect
Figure 5
6. Close the inside cover and tighten the screw.
7. Remove the unit housing from the package. Units with DC­remote power: go to step 8 (see figure 3).
a. Units with battery back-up: plug the battery connector in the
slot. The connector is polarized, do not force-fit . Correct installation has the positive red wire at the left (see figure 3).
b. Units with dual AC circuit: connect the orange wire labeled
“VOLTAGE SELECTOR” to one of the two wires labeled AC VOLTAGE (black: 120V; orange: 277V). Cap the unused wire with a wire connector.
8. Hook the security wire to the backplate and tighten the screw (see figure 3).
9. Align the unit housing over the back plate and press until it snaps in place (see figure 4).
10. Energize the circuits. Units with battery back-up will have the test button illuminated.
Testing the emergency lights
Allow the unit to charge for 24 hours before testing. Press the test button. The unit will light in emergency mode for one minute. To abandon the test press the test button again.
Testing the normal lighting
Turn the AC power on: the unit will light. Units equipped with photo-switch: mask the small circular window with the finger: the unit will light. Uncover the window: when
exposed to ambient light the unit will turn off.
Maintenance
None required. WARNING: Hold the housing in your hand and open the unit with a flat head screwdriver. When replacing the housing assembly
ALWAYS hook and tighten the security wire.
Disconnect the battery if the emergency power supply is disabled for two months or more.
Self-diagnostics / self-test (battery units)
1. Once supplied with power the unit will automatically initiate self­diagnostic routines and a self-test calendar as follows:
a. Verifies battery connection, battery failure, charger board
failure and lamps failure. b. Executes one-minute monthly self-test. c. Executes a 30-minute self-test every 6th month. d. Executes a 90-minute self-test every 12th month.
2. The LED pilot light is bi-color and indicates the following status: a. Green color: AC-on / self-test b. Red color: Service alert (see figure 5)
Emergi-Lite Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
3. Transfer time delay (TD option)
This function acts when the AC power was restored: it keeps the emergency lights "on" for a period of: 5, 10 or 15 minutes (factory­set). If the battery depletes before the end of the time delay, the lamps turn off and the unit goes in stand-by mode.
02/13 750.1712 Rev. A
2/2