HP Series Remote Heads for Hazardous Locations
WARNING:
Risk of Electrical Shock.
Disconnect Power before Installation.
Figure 1
Lamps
Cover
Back box
Conduit hub
entries(3)
Hook
HP Series Remote Heads for Hazardous Locations
Class I Division 2, Class II, Division 2 Groups F & G, Class III
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always
be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. All servicing should be performed by qualified service personnel.
2. Do not mount near gas or electric heaters.
3. Equipment should be mounted in locations and at heights where it will
not readily be subjected to tampering by unauthorized personnel.
4. The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
5. Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
Installation Instructions
1. Remove the cover from the back box (See figure 1).
2. Select the entry point on the back box for the conduit and open one of
the knockouts (top or side).
3. Install the conduit fitting rated for Class 1 Div2 (provided).
4. For daisy-chain (input/output) wiring: open a second knockout and
install the conduit fitting rated for Class 1 Div2 (provided).
Wall or Ceiling mount
Install the unit to the wall or ceiling with 4 screws (not included).
Column mount (option)
a. The universal mounting bracket is an accessory ordered separately
(See figure 2).
b. The bracket can be installed using steel banding for routing around
the column. Standard banding (not provided) must be maximum
3/4-in in width. The bracket can also be mounted on a Superstrut®
metal framing (1 5/8-in channel series) using 1/4-in bolts (not
provided). Holes are placed at 9-in apart horizontally.
c. Install the bracket, observing the indicator: TOP.
d. Screw the unit onto the bracket with the 4 screws, washers and
nuts included in the bracket kit.
5. Route the wires from the wire conduit(s) through the conduit fitting(s)
and into the back box.
THE COLUMN MUST BE
WARNING:
Maximum mounting height
as per UL924 standards
LED Lamp wattage Maximum mounting height
6 - Watts 30 Feet
10 - Watts 50 Feet
15 - Watts 60 Feet
ANCHORED TO THE FLOOR
AND CEILING.
.
Emergi-Lite® Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
11/17 750.0024 Rev. A
1/2

6. Thread the wire conduit(s) tightly into the conduit fitting(s) ensuring a
Figure 3
Two screws
Nut
(located on both sides
of the lamp head)
water-tight seal. If necessary, seal with silicone or equivalent caulking
(not provided) to prevent water from leaking into the cabinet.
FAILURE TO ENSURE A WATER-TIGHT
WARNING:
7. Take the unit cover with lamps and hang it temporarily from the hook
located inside the back box.
Attach one of the ground wires to each screw located on the nut of the
8.
conduit fitting.
9. Connect the left over ground wire(s) to the incomming wire conduit
ground wire.
10. Respecting the proper polarity {red (+) and black (-)}, connect the lamp
wires to the emergency circuit (low-voltage 12-24Vdc) using wire nuts.
11. Verify that the gasket is installed and well aligned in the groove of the
cover.
12. Unhook and install the cover onto the back box with the lamp heads
pointing downwards. Tighten the four screws to prevent water
infiltration.
WARNING:
13. Adjust the lamp head assemblies:
- Rotation: hold the lamp assembly and turn it to either side.
- Tilting: hold the lamp assembly and tilt it up or down.
If the lamp heads become loose: tighten the screws located on each side
of the lamp heads and the nut located at the base of the bracket
(See figure 3). Warranty: For the complete warranty information, please
refer to the landing page of our website (http://www.emergi-lite.com/usa/).
INSTALLATION OF THE CONDUIT(S) AND
FITTING(S) WILL VOID THE MANUFACTURER
WARRANTY.
SCREWS MUST BE TORQUED TO AT LEAST
12INLB TO ENSURE A WATER-TIGHT SEAL
BETWEEN THE COVER AND HOUSING.
HP Series Remote Heads for Hazardous Locations
Emergi-Lite® Tel: (888) 552-6467 Fax: (800) 316-4515 www.emergi-lite.com
11/17 750.0024 Rev. A
2/2