
H
TEL 888 935 3605:( ) -
FAX 888 867 1565:( ) -
FPDL-32
EMERGILITE BRAND
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. - To prevent electrical shock, do not mate unit connector until installation is complete andCAUTION
power is supplied to the unit.A.C.
2. - This fixture provides more than one power supply output source. To reduce the risk of
CAUTION
electrical shock, disconnect both normal and emergency sources by turning off the A.C. Branch circuit
and by disconnecting the unit connector.
3. The battery is sealed, non-maintenance, and is not replaceable in the field. Please contact manufacturer for information on service. Do not attempt to service the battery please.
4. . The product is for use with grounded, UL Listed, indoor fixtures except in
DO NOT USE OUTDOORS
heated air outlets or hazardous locations.
5. The product requires an unswitched A.C. Power source of either 120 or 277 volts. Properly cap the
unused A.C. Lead.
6. Do not mount near gas or electric heaters.
7. The product should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
8. The product will cold strike and operate one 2 through 4 (20-40W) instant start, rapid start, U shape
or circline, T8 through T12 fluorescent lamps, T5 28W fluorescent lamps, including energy saving and
long compacts for 90 minutes at reduced light output.
9. The product is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts
with one lamp operating in the emergency mode.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this equipment for other than intended use.
12. Install in accordance with the National Electrical Code and local regulations.
13. Installation and servicing should be performed by qualified personnel.
14. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility
before final installation.
15. The battery is sealed,non-maintenance,and is not replaceable in the field. Please contact
manufacturer for information on service. Do not attempt to service the battery please.
16. The rated operating time in the emergency mode with battery is 1-1/2 hours and the recharge
time shall not be less than 24 hours.
′′
SAVE THESE INSTRUCTIONS
CONTAINS NICKEL-CADMIUM
BATTERY.MUST BE RECYCLED
OR DISPOSED OF PROPERLY.
Page 1
Ni - Cd

INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. Power is off and the battery
connector is disconnected.
1. MOUNTING THE FPDL-32
1
Remove the ballast channel cover. Mount the FPDL-32 in the ballast channel at least away from the A.C. Ballast(s).
1
2
When battery packs are remote mounted, the remote distance can not exceed of the distance from ballast to
lamp specified by the A.C. Ballast manufacturer. For example, if the A.C. Ballast manufacturer recommends no
more than 25¡remote distance, then the battery pack should not exceed 12 . Under no circumstances should
/
1
¡
/
2
2"
/
the battery pack exceed a distance of 50¡from the lamp.
2. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance
with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
3. INSTALLING THE LIGHTED
Recessed Troffer Fixture
7
punch a / hole ( / knockout). Insert the / bushing into the hole. Push the plastic tube through the bushing.
8"
1
2"
Route the leads of the through the plastic tube. Connect the LED wires from the unit to the
iolet Brown
(V to Red, to White/Red). Push the entire assembly back into the tube until the lens collar rests against the plastic
tube. The plastic tube should be adjusted so that the is within / of the fixture lens. The
must be visible after installation. Refer to
Strip Fixture -
Select a convenient location on the fixture so the can be seen after installation.
Allow for proper clearance inside the fixture and drill or punch a1/2" hole. Remove the nut from the
. Push the housing into the1/2" hole and secure with the nut. Connect the LED wires
from the .
TBTS
TBTS
(Violet to Red, Brown to White/Red)
- Select a convenient location with proper clearance in the ballast cover and drill or
7
8"
INDICATOR LIGHT INDICATOR LIGHT
1
INDICATOR LIGHT INDICATOR LIGHT
4"
Illustration 1.
TBTS
TBTS
Refer to Illustration 2.
Illustration 1
Recessed Troffer Fixture
FPDL-32
PLASTIC TUBE
7/8 BUSHING
TBTS
4. WIRING THE A.C. INPUT
A. The and A.C. Ballast be on the same branch circuit.FPDL-32 must
B. The requires an A.C. Power source of either 120 or 277 volts. Select the proper voltage lead
and cap the unused lead.
C. When the is used with a switched fixture, theA.C. Input to the must be connected ahead of the
FPDL-32 FPDL-32
fixture switch. Refer to for switched and unswitched fixture wiring diagrams.
unswitchedFPDL-32
Illustration 3
FIXTURE
BALLAST CHANNEL COVER
FIXTURE LENS
Illustration 2
Strip Fixture
FIXTURE
TBTS
FPDL-32
OBSERVE PROPER POLARITY
Page 2