ASSEMBLY
Tools Needed
1. 13/64" drill bit 6. hammer
2. hand drill 7. fine half round file
3. tape measure 8. heavy duty pop rivet gun
4. fine tooth hacksaw (24-36 teeth per inch)
Packing List (included with A1100-010)
(1) valve assembly #A1100 (8) pop rivets #564412
(1) hose clamp #564421 (1) o-ring #480049
(1) warning plate #564420 (1) counter sink indenter #564416
(1) drop tube O-ring #561683 (1) Seal-All sealant #566726
(1) 572719 drill fixture
NOTICE: If this valve is to be used with coaxial Stage I drop tube assemblies, you must
order the appropriate special kit for proper assembly:
Standard coaxial (A0070 style) kit #493195
Self sealing coaxial (A0088 style) kit #493197
The A1100 Guardian can only be installed after the containment manhole has
been installed. Existing drop tube may be used only if:
1. Tube is in good condition without holes, cracks, or bends.
2. I.D. of tube will fit over the valve body diameter.
Step 1
: If already in place, remove the existing 4” cap, adapter and drop tube
assembly.
Step 2:
Find measurement A which is the distance from the top of the tank to
the top of the 4” riser pipe as shown in Figure 1.
If the tank has a manway, make sure to include the height of the manway when
finding measurement A as shown in Figure 2, A = J + H . Consult your tank diagram to determine the proper H dimension. If this dimension cannot be found,
use 6” as the H dimension (typical manway height is 5”-7”).
WARNING: Do not use electrical devices near gasoline vapors, as it could result in fire
or explosion.
AVERTISSEMENT: Ne pas utiliser d'appareils électriques à proximité des vapeurs
d'essence, car il pourrait provoquer un incendie ou une explosion.
WARNING: If the underground storage tank is equipped with a ball float vent
valve, make sure it is not extended below the positive shut-off point of the A1100, or
remove the float vent valve.
ATTENTION: Si le réservoir de stockage souterrain est équipé d'un flotteur évent de balle
vanne, assurezvous qu'il n'est pas prolongée en dessous du point d'arrêt positive de la
A1100, ou supprimer la vanne flotteur de ventilation.
TOP TUBE INSTALLATION PROCEDURE
2