Emax PDRCF1150115, PDRCF4600575, PDRCF1150058, PDRCF1150144, PDRCF4600288 Instruction Manual

...
Emax Air Dryer
R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S
EDRCF1150029 – EDRCF4602000
Instructions Manual
TABLE OF CONTENTS
1. Important safety notes - Please read .......................... 1
1.1. Transportation ............................................................... 1
1.2 Positioning ..................................................................... 1
1.3 Installation ...................................................................... 1
1.4 Before operating ............................................................ 1
1.5 Maintenance by an engineer ......................................... 1
1.6 Maintenance by the user ............................................. 1
2. Introduction ..................................................................... 2
3. Operation ......................................................................... 4
4. Technical specifications ................................................ 7
5. Diagrams ............................................................................. 8
6. General Arrangements ................................................... 18
7. Main Settings ................................................................ 18
8. Drawings ........................................................................ 19
9. Components location ................................................... 60
10. Troubleshooting ............................................................ 61
11. Warranty ......................................................................... 63
1
A)
When operating the air dryer the operator must apply safe working methods and observe all local safety
instructions and relevant regulations.
B)
Prior to installation, the dryer and the compressed air system are to be depressurized and disconnected
from the electrical main supply.
C)
The user is responsible for safe operating conditions. Parts and accessories must be replaced if inspection
shows that safe operation cannot be assured.
D)
Installation, operation, maintenance and repair are only to be authorized, trained and skilled engineers.
E)
The minimum and maximum values stated must be observed, as well as all of the safety precautions described
in this manual.
F)
If any statement in this manual does not comply with the local legislation, the strongest standard is to be applied.
1.1. Transportation
A)
Use care and caution when transporting the dryer. Avoid dropping and other physical abuse.
B)
A forklift can be used to transport the dryers provided the forks are long enough to support its full width or
length and caution is used throughout the move.
1.2. Positioning
A)
The dryer must be installed horizontally. A minimum of 20” clearance around the dryer is necessary to
allow a good ventilation and easy access for servicing.
B)
The ambient temperature in the room should not exceed 122°F and should not be below 39°F, taking the heat
radiated by the dryer into account.
C)
(40 watt for each liter/sec under ISO 7183-A condition or 18 watts for each SCFM under ISO 7183-B condition).
1.3. Installation
A)
In addition to the general mechanical construction procedures and local regulations, the following instructions
need to be emphasized:
1) Only authorized, trained and skilled engineers should install the compressed air dryer.
2) Safety devices, protecting covers or insulation in the dryers never to be dismantled or modified. Each pressure vessel or accessory installed outside the dryer with air above atmospheric pressure must be fitted with the required pressure relief safety valves.
1.4. Before Operating
A)
Review all safety precautions.
B)
The piping must have the correct diameter and be adapted to the operating pressure (see technical specification).
C)
Never operate the dryer at pressure above the maximum specified on the dryer label (check the technical specs too).
1.5. Maintenance by an Engineer
A)
Maintenance and repairs should only be performed when the air dryer is shut down and depressurized and when
the main power switch is turned off.
B)
Use only the appropriate tools for maintenance and repair.
C)
Before dismantling a part under pressure, disconnect the pressure sources and depressurize the system.
D)
Proceed carefully during maintenance and repair. Prevent dirt from entering by covering parts and orifices with
a clean cloth, paper or tape. A receiver should never be welded or modified in any way.
E)
Never leave tools, loose parts or cleaning rags in or on the air dryer.
F)
Before returning the dryer into service, check the setting of the control and safety devices as well as the pressure
and the temperature of the compressed air circuit.
1.6. Maintenance by the user
A)
Keep the dryer clean.
B)
Regularly check the correct operation of the condensate drain trap.
C)
Every six months, check and clean the drain strainer by undoing the access screw and rinsing the filter with tap
water to remove the trapped dirt from the inside.
I. IMPORTANT SAFETY NOTES – Please READ
2
D)
For air cooled dryers, clean the air condenser as soon as it’s dirty or clogged.
E)
For optional water-cooled condensers, use only clean water and install a water filter if needed.
Use water counter flow to clean condenser if need.
F)
Check the trouble-shooting list in case of maintenance troubles.
G)
Check operating pressures, temperatures and time settings after maintenance. If operating and safety devices
function properly, the air dryer may be used.
A) Manufacturer: B) Purpose of this dryer
1)
This refrigerated compressed air dryer has been designed to remove water vapor from industrial compressed air.
2)
This dryer has been designed for indoor operation.
3)
The minimum and maximum values stated must be observed, as well as the safety precautions described
in this manual.
C) Dryer label
The following label is affixed on the cabinet of the refrigerant compressed air dryer.
D) Working details
1)
Refrigerant circuit:
The refrigerant circuit can be divided in 3 parts:
a)
Low pressure section with an evaporator (heat exchanger)
b)
High-pressure section including: Condenser, liquid receiver, (if installed) and the filter dryer.
c)
Control circuit including: Compressor, Expansion valve, by-pass valve (if installed),
Fan pressure switch (if installed)
2)
For water - cooled dryers:
a)
Water valve
b)
Safety high pressure switch (if installed)
3)
The Refrigerant circuit operates as follows:
a)
The compressor compresses gaseous refrigerant to a high temperature.
b)
The hot refrigerant condenses in the condenser. Being liquefied it is stored in the liquid receiver (if installed).
c)
The liquid is taken out the storage vessel and injected in the evaporator (heat exchanger) by an expansion valve.
This expansion valve is protected by a filter, which removes particles and humidity that could be in the circuit.
d)
The injected liquid fills in the refrigerant section of the air / refrigerant heat exchanger and evaporates by taking out the calories from the compressed air. The gaseous refrigerant is sucked in the compressor and the cycle carries on.
e)
In order to keep the evaporation pressure steady, and thus the refrigerant temperature in the heat exchanger, a by-pass valve is injecting hot gaseous refrigerant in the circuit. On certain dryers, an automatic expansion valve regulates this.
4)
Compressed air circuit
a)
The saturated hot compressed air flows into the Economiser where it is pre-cooled by the out flowing dry chilled
air. In the cold zone of the air refrigerant section it continues to cool
2. INTRODUCTION TO THE DRYER
3
down to dew point and enters the separator where condensates are collected. The outgoing chilled air is then warmed up in the economizer by the hot incoming air.
b)
The condensates are collected after centrifugal separation and drained out through the automatic trap.
c)
As long as the compressed air temperature does not drop below dew point, there will be no condensation
in the air circuit.
5)
Refrigerant compressor
Being of the hermetic type, it requires no servicing.
6)
Condenser
a)
Th e air condensers are equipped with a helecoidal at the condenser refrigerant level.
On certain type of dryers, a water-cooled condenser can be fitted.
b)
In this case, a water valve being driven by the refrigerant circuit is taking care of its regulation.
7)
Refrigerant circuit protection
a) Klixon:
The single phase compressors are equipped with a klixon which is a thermal sensitive switch controlling the temperature of the compressor and possible over intensity. In case of malfunction, the klixon trips but switches on again automatically as soon as the compressor has cooled down.
b) High Pressure Security Switch:
Refrigerant line is considered as a pressure vessel. That is why it is protected against bursts by the help of manually reset switch. It is set to 362.5 psi for dryers working with R134a
c) Filter dryer:
A refrigerant circuit is a closed circuit and total water removal in the refrigerant circuit is
paramount in order to obtain a correct functioning.
d)
To avoid problems, the refrigerant circuit must be vacuumed before loading the refrigerant. It is equipped with a filter dryer, which also traps any solid particles, which may have migrated into the circuit during assembly.
e)
Water-cooled dryers have a safety high-pressure switch. In case of cooling water failure, the safety switch stops the dryer. When the safety switch has tripped out, it has to be manually resettled before switching on the dryer.
8)
Refrigerant circuit controls
a)
Liquid refrigerant injection: The liquid refrigerant is into the evaporator by a control valve. This valve is a
thermostatic or pressostatic one maintaining a constant overheats of the refrigerant in the evaporator(s).
b)
Constant evaporating pressure: In the dryers equipped with a by-pass valve, the evaporating pressure is kept constant by a controlled injection of hot gas from the high-pressure side into the low-pressure section of the circuit.
9)
Condensate drain - trap assembly
Dismantling the drain is easy because it can be isolated from the air circuit under pressure with a ball valve. The drain has to be depressurized before being dismantled.
10)
Heat Exchanger Modular design
a)
The dryers are equipped with a compact Mono Bloc Heat Exchanger module. This assembly has been specially designed to dry compressed air and is made of:
1)
An Economiser which pre-cools the entering hot air with the out flowing cold air.
2)
An air/refrigerant exchanger cooling down the compressed air.
3)
A centrifugal separator concentrating all condensates and requiring no maintenance.
11) Accessories
a) Dew point indicator: Located on the control panel, it displays the value of the pressure dew point. b) Temperature switch: Located inside the dryer, this temperature switch is adjustable from 32 °F up to 95 °F c) Energy Saving Device: (ESD) This device helps dryer save energy when there is not any compressed air flow in the dryer. (Please see the models have standart and optional in next page) d) Filter change alarm on the front panel
4
3.1. Operation
A)
Control panels:
The control panel of the dryer includes the following elements:
1) Dewpoint indicator (Standard)
2) Filter change Alarm**
3)
Start / Stop Button
1) Dewpoint indicator (Standard)
2) Start Light
3) N/A
4) Filter change Alarm**
5) Main Switch
Triphase
ESD3
PDRCF4600575 - PDRCF4601200
1) ESD3 (Standard)
5) EMERGENCY STOP
ATTENTION : DN-US range dryers have low pressure drop according its competitors. Do not use DN-US range dryers together with other dryers which have higher pressure drop without getting the confirmation from our technical team.
** IMPORTANT NOTE: The Dryer has two Compressed Air Filter inside. It is better to change filter element for the best efficiency when the alarm light is active. It is recommended to keep replacement filter elements in your stock in order to replace them when needed.
1
5
1
2 3
Monophase
Dew point
indicator
DN120-US - DN130-US
Monophase
Dew point
indicator
PDRCF1150029 - PDRCF2300288
3. OPERATION
2 3
1 4 5
5
3.2. During Operation
Regularly check the digital temperature controller ESD3 or dew point indicator on dryer.
B) Start up and shut-down
Warning:
Avoid leaving the dryer off when compressed air is still flowing through it.
C) Starting for the first time or after a long stop
1) Set the rotary switch to “I” This preheats the dryer and turns the drain system on. It is recommended to leave the dryer power on permanently so the crankcase heater runs continuously.
3) Follow the daily starting and shut down procedure.
D) Daily starting and shut-down
1) Push on the green button to start the dryer.
2) The start light will indicate that the dryer is running.
3) To stop the dryer, first stop the airflow (either shut-down the air compressor or close the inlet/outlet or by-pass valve) When the air flow is stopped set the rotary switch on 0 Set it again on I in order to keep the preheating on.
4)
IMPORTANT NOTE!
Avoid leaving the dryer stopped when compressed air is still flowing through it.
5) To switch the already preheated dryer on again, simply push the green start button.
E) Digital Temperature Control technical features (ESD3)
ESD3:
PLC clear text multilingual indication of alarms, maintenance and running hours + Energy Saving Device automatic switching OFF at no load and ON when warm compressed air is entering. (Please see the ESD3 manual which is given with Dryer)
2)
IMPORTANT NOTE!
After a long stop of the dryer it is MANDATORY to allow a preheating period of minimum
4 hours
before starting again, to avoid any compressed air flow during preheating.
Emax Air Dryer
RE F RIG ERATED TYPE COMP R ESSE D AIR DRYERS
Technical Specifications
& Diagram
7
Model
Capacity
(CFM)
Connection
Size
Voltage
Total
Electric
Power
Refrigerant
Type
Pressure
Drop
Max Work
pressure
(bars)
Max
Ambient
Temperatu
Max inlet
Temp.
PDRCF11500 29 29 1/2" 115 0.42 R134a <3 232 122 140
PDRCF11500 58 58 3/4" 115 0.68 R134a <3 232 122 140
PDRCF11501 15 115 1 1/ 2" 115 0.93 R134a <3 232 122 140
PDRCF11501 44 144 1 1/ 2" 115 1.28 R134a <3 232 122 140
PDRCF23002 88 288 2" 230 1.94 R134a <3 232 122 140
PDRCF46002 88 288 2" 460 1.94 R134a <3 232 122 140
PDRCF46005 75 575 3" 460 3.01 R134a <3 232 122 140
PDRCF23005 75 575 3" 230 3.01 R134a <3 232 122 140
PDRCF46008 50 850 3" 460 4.31 R134a <3 232 122 140
PDRCF46012 00 1200 3" 460 5.68 R134a <3 232 122 140
PDRCF46016 00 1600 3" 460 R134a <3 232 122 140
PDRCF46020 00 2000 3" 460 R134a <3 232 122 140
For All Models
Maximum Pressure 232 PSI
Maximum Ambient Temperature 122 F
Minimum Ambient Temperature 40F
Maximum Inlet Temperature 140 F
8
5.1
AIR FLOW DIAGRAMS
EDRCF1150029
-
EDRCFR1150144
M
IMPORTANT NOTICE:
5: Only From Dryer PDRCF1150115 to PDRCF1150144 9: Only from Dryer PDRCF1150115 to PDRCF1150144
9
10
5.2
ELECTRICAL DIAGRAMS
Dryair DN10-US - Dryair DN30-US
Electrical Circuit
12
Dryair DN40-US - Dryair DN80­US
Electrical Circuit
15
Dryair DN100-US - Dryair DN110-US
Electrical Circuit
16
Dryair DN140-US - Dryair DN170-US
Electrical Power Circuit
Emax Air Dryer
RE F RIG ERATED TYPE COMP R ESSE D AIR DRYERS
General Arrengements
Main Settings
Drawings
18
Model
Drya ir DN10-US
1 * GKO50X + 1 * GKO50Y
MKO50 KIT
16.26
14.29
21.93
70.40
Drya ir DN20-US
1 * GKO50X + 1 * GKO50Y
MKO50 KIT
16.26
14.29
21.93
70.40
Drya ir DN30-US
1 * GKO50X + 1 * GKO50Y
MKO50 KIT
16.26
14.29
21.93
70.40
Drya ir DN40-US
1 * GKO150X + 1 * GKO150Y
MKO150 KIT
18.62
17.83
32.76
112.20
Drya ir DN50-US
1 * GKO150X + 1 * GKO150Y
MKO150 KIT
18.62
17.83
32.76
116.60
Drya ir DN60-US
1 * GKO150X + 1 * GKO150Y
MKO150 KIT
18.62
17.83
32.76
121
Drya ir DN70-US
1 * GKO500X + 1 * GKO500Y
MKO500 KIT
21.77
19.80
34.41
171.60
Drya ir DN80-US
1 * GKO500X + 1 * GKO500Y
MKO500 KIT
21.77
19.80
34.41
182.60
Drya ir DN90-US
1 * GKO500X + 1 * GKO500Y
MKO500 KIT
21.77
19.80
34.41
189.20
Drya ir DN 100 - US
1 * GKO851X + 1 * GKO851Y
MKO851 KIT
26.69
25.51
45.55
352
Drya ir DN 110 - US
1 * GKO1210X + 1 * GKO1210Y
MKO1210 KIT
26.69
25.51
45.55
363
Drya ir DN 120 - US
1 * GKO1210X + 1 * GKO1210Y
MKO1210 KIT
37.32
28.66
53.94
484
Drya ir DN 130 - US
1 * GKO1210X + 1 * GKO1210Y
MKO1210 KIT
37.32
28.66
53.94
506
Drya ir DN 140 - US
1 * GKO1820X + 1 * GKO1820Y
MKO1820 KIT
37.32
31.42
57.48
594
Drya ir DN 150 - US
1 * GKO1820X + 1 * GKO1820Y
MKO1820 KIT
37.32
31.42
57.48
627
Drya ir DN 160 - US
1 * GKO2700X + 1 * GKO2700Y
MKO2700 KIT
45.79
30.63
67.91
862.40
Drya ir DN 170 - US
1 * GKO2700X + 1 * GKO2700Y
MKO2700 KIT
45.79
30.63
67.91
902
Superheat of thermostatic expansion valve
Evaporating pressure
Fan pressure switch
Security
(*)
high pressure switch
Security
(**)
low pressure switch
Drain timer
(***)
Low pres. High Temp. switch
(****)
Water flow valve (if water condenser)
41OF - 50OF
29.7 psi
130 - 174 psi
362.5 psi
23.2 psi
1 min. - 5- sec. 5 min. - 4- sec.
113OF
159.5 psi
(*)
Available up to Dryair DN40-US and above
(**)
Available up to Dryair DN140-US and above
(***)
1 min. - 5 sec. (up to DN100-US and above)
5 min. - 4 sec. (up to DN90-US and above)
(****)
Available up to Dryair DN140-US and above
7. MAIN SETTINGS
6. GENERAL ARRANGEMENTS
19
Dryair DN10-US - Dryair DN30-US
8. ED and ID DRAWINGS
20
Dryair DN40-US - Dryair DN60-US
21
Dryair DN70-US - Dryair DN90-US
22
Dryair DN100-US - Dryair DN110-US
23
Dryair DN140-US - Dryair DN150-US
24
Dryair DN160-US - Dryair DN170-US
25
Dryair DN30-US
26
Dryair DN50-US
27
Dryair DN70-US
28
Dryair DN80-US
29
Dryair DN110-US
30
Dryair DN140-US
31
Dryair DN160-US
32
Dryair DN170-US
60
9. COMPONENTS LOCATION
61
Problem
Possible Cause
Repair
Comments
Dryer is switched on, indicator light is lit but the refrigerant compressor does not turn on.
The connection has inverted phases
Invert two phases
3-phase dryers are equipped with a phase controller to avoid the fans from turning in t he opp osite direction.
Refrigeration unit is not functioning
Check refrigeration compressor
Seve ral factors can cause compresso r f ailure. A qualified refrigeration technician needs to check all the electrical and refrigerant circuit and controls.
The refrigerant high pressure protection has tripped
The refrigerant safety high pressure switch has tripped.
The dryer is pr otect ed agains t exc essively high refrigerant pressure. If the condenser efficiency has reduced, the switch will trip. Manually reset the switch.
In case of water cooled con­densers, check the water control valve
Excessive ambient temperature
Be sure that dryer is working in temperatures lower than the design conditions. Designed conditions and correction factors are described in this manual.
A h igh ambi ent temp erature may c ause the refrigerant system to operate at higher than normal pres sur es. Resul ts will be higher than normal evaporator temperature. lmportant: adequate air circulation around the dryer, and proper ventilation in the equipment room should guarantee a low eno ugh ambient tem peratu re.
Dryer is switched on, but the refrigerant compressor does not turn on.
Excessive temperature on crankcase of compressor.
Allow time to compressor to cool down. Reason may be a possible incorrect adjustment of hot gas bypass valve or shortage of refrigerant
Compressor is protect ed aga ins t overly hi gh temperatures of the crankcase by a thermal switch.
Excessive compressed air inlet temperature.
Be sure that dryer is working in temperatures lower than design conditions.
The dryer is designe d for working in calculated con ditions (see descrip tion in this m anual ). If co nditio ns are excee ded, the dryer will be overflowed, dew point will go up and protecting devices can switch off.
Clogged condenser fins or clogged water condenser.
Possible high crankcase temperature
Possible loss of phase
Possible low voltage causing overload trip Possible failed compressor
Clear fins or water condenser of all obstructions.
The clogged fins in the condenser will restrict the air passage and reduce the refrigeration capacity, caus ing high tempe rat ure in t he evapo rator. Same will occur if water condenser is clogged with mud or dirt. Air condenser and water condenser should be per iodi cally chec ked and cl eaned. Protect w ater cir cuit by an a dapt ed f ilter.
Too much compressed air flow.
Check actual flow through the dryer.
This dryer is designed for a maximum air flow at desi gn condit ions. If too much air is pum ped into the dryer, water removal capacity may not be sufficient, resulting in liquid carryover down stream. Chec k the r ated outpu t the air comp ressor.
Faulty electrical wiring
Inspect the circuit
The compressor-on light should be wired into the refrigerant compressor circuit. See wiring diagrams in this manual.
One electrical protection has tripped.
Reset the protection or replace the blown fuse.
The dryer is prot ected against high amp draw by fuse and/or overload relay that can trip in case of need. Reset or replace fuse once, but do not persist if it trips again, request assistance from a qualified refrigeration contractor.
Dryer is switched on but fan is not running.
Fan has to run if refrigerant high pressure reaches upper set point.
Check that compressed air flows through the dryer. Check that fan blades are free to move. Check the fan pressure switch.
Fan operates automatically to keep refri gerant pressure below the maximum value. The fan can stop if pressure is under the recommended setting.
When compressor starts, it vibrates a lot and makes mechanical noise.
Compressor is slugging liquid refrigerant at start up.
Be sure the pre-heating period of at least 2 hours is respected
Refrigerant may move between recei vers when refrigerant com pressor is stopped and not heated, especially if stopped for a long time. This migration may cause liquid shock (slugging) in valves specially on large dryers containi ng more refrigerant
10. TROUBLESHOOTING
62
Problem
Possible Cause
Repair
Comments
Water in system
Compressed Air Inlet and outlet connections are reversed.
Check inlet and outlet connections.
This dryer is designed for air flow in one dire ction only. Inlet and outlet directions are identified on the dryer.
Drain system is clogged or inoperative.
Restore a free flow of water condensate. Check water evacuation.
Drain system is timed solenoid valve, pneumati cally assisted which has to be adjusted in accordance with values listed in this manual. The Solenoid valve includes a strainer that has to be periodically checked and cleaned. Membranes of pneumatically assisted drain have to be checked or replaced every 6 months.
Bypass system is open
Check the valves
Impo rtant: B ypas s piping should be i nstalled around the dryer so the dryer can be isolated for serv ice without shuttin g down the ai r supply. During dryer operation, valves must be set so all air goes into the system. Check tightness of the bypass system.
Free moisture remains in pipe lines.
Blow out the system
Before the dryer is first started all free moisture should be blown out of the system.
Excessive air flow
Check actual flow through the dryer.
This dryer is designed for a maximum air flow. If too much air is pumped into the dryer, water removal capacity may not be sufficient, resultingin liquid Carry over downstream. Check the rated flow of the air compressor .
Excessive free moisture
Check the separator and drain system and compressor after cooler ahead of the dryer.
In some system there may be an accumulation of free moisture in the line ahead of the dryer. If this moisture is pumped into the dryer intermittently, the water removal capacity may not be sufficient. A water separator should be installed in the line before the dryer.
Excessive compressed air inlet temperature.
Be sure that dryer is working lower than design conditions
The dryer is designed to work for calculated design conditions. Should the conditions be exceeded, the dryer will be overflowed, dew point will go up and protecting devices can switch off.
Clogged condenser fins
Clear fins of all obstructions
The clogged fins in the condenser will restrict air passage and reduce refrigerant capacity causing water downstream. Fins should be peri odically checked and cleaned.
Shortage of refrigerant
Fix the leak and add a charge of refrigerant.
Loss of refrigerant will cause improper functioning. A qualified, refrigeration specialist should perform the n ecess ary repai rs, or factory sh ould be contacted if the unit is in warranty.
Refrigeration system is not functioning
Check to be certain refrigerant compressor is running
To c heck if the com pres sor is runni ng, check compressor-on light. lt is possible for the fan to be operating but not the compressor. Compressor not running can be caused by several taeters. A qualified refrigeration technician should che ck all refr igerant and electr ical con trols
Excessive pressure dew point
Readjust refrigerant evaporating pressure
The refrigerant pressure adjustme nt s hould be done by a qualified refrigeration engineer. This is a very sensitiye device and incorrect settings may create other failures.
High pressure drop
Excessive compressed air flow or too law air inlet pressure.
Check actual pressure and flow through the dryer.
This dryer is desi gned for a maximum air flow. If t oo much air is pump ed i nto t he drye r, water r emoval c apac ity may not be sufficient , re sulti ng in l iquid ca rr y- over d ownst ream. Chec k the ra ted flow of the air com pressor .
Freeze up
Check that compressor room ambient,
Frosting of the Iines is an indic ation that controls are set too low. The fol lowing should be done by an e xp erie nced ref rig era ti on te chn ici an.
Fan switch could have failed in closed position keeping fan on.
Controls may be adjusted in the fields by means of the hot gas by pass valve . This is to be done by a qualified refrigerant technician.
The unit will not run or cycles off and on.
Clogged heat exchanger
Clean heat exchanger with areverse air flow.
Dryer are supposed to be used with compressed air free of any aggressive contami nants . Som e contamination may require extra maintenanc e of the heat exchanger.
Line disconnect switch is open.
Close the start or disconnect switch.
If the dryer is not operating, check the disconnect switch or circui t breaker to be certai n it is on.
Fuse or breaker is open
Replace fuse or reset breaker.
The fuse to the power line s hould be checked and replaced if needed. Never replac e a burnt fuse with an oversized fuse.
Faulty refrigerant compressor or controls.
Determine the cause and make correction
Failure of compressor to run may be c aused by several factors. A qualified refrigeration specialist should check all electrical and refrigeration controls, or factory should be contacted if unit is in warranty.
Excessive compressed air inlet temperature.
Design conditions and correction factors are described in this manual. Be sure that dryer is working in ambient temperatures below design conditions.
The dryer is designed for working into calculated design conditions. Shoul d th e co nditi ons be exce eded, the dryer will be overflowed, dew point will go up and protecting devices may trip.
63
Problem
Possible Cause
Repair
Comments
The unit will not run or cycles off and on.
Excessive ambient temperature
Designed conditions and cor­rection factors are described in dryer . Be sure that dryer is working lower than design conditions.
A high ambient temperature may cause the refrigerant system to operate at higher than normal pressures. Results will be a higher than normal evap orator temperature. Important: there should be adequate air circulation around the dryer, and proper ventilation in the equipment room should guarantee a low enough ambient temperature.
Clogged condenser fins
Clear fins of all obstructions.
The clogged fins in the condenser will restrict the air passa ge and reduce the refri geration capaci ty, cau sing high tem perat ure in the eva por ator. Fins should be periodically checked and cleaned.
Shortage of refrigerant
Fix the leak and add a charge of refrigerant.
Loss of refrigerant will cause improper functioning. Dryers are equipped with a temperature switch which maintains the amount of r efrigerant to maintain proper cooling of the compressor. A shortage of refrigerant may cause suction line to become very hot, causing the temperature switch to trip. A qualified refrigeration speci alist should perform the necessary repairs.
Error sign occurs on digital temperature control device
The dew point is too low or too high.
Check refrigerant gas and make sure that the working conditions are within the cor­rect range.
If there is not enough refrigerant gas or if the working temperature and inlet temperatures are very high, the dew point will increase.
Refrigerated Dryer
WARRANTY POLICY
When used under the conditions recommended the heat exchanger will be warranted for five (5) years. This warranty is limited to the replacement of the heat exchangers,
Some restrictions as outlined below concerning misuse, abuse or accident. The standard equipment external float drain and automatic drain carry a 90-day warranty. This warranty will apply to equipment installed, operated and maintained in accordance with the procedures and recommendations as outlined in the owner’s manual published by Emax During the life of this warranty, Emax will repair or replace (at Polar airs option) any defective part or assembly free of charge if such defect occurred in normal service and was not due to apparent misuse, abuse or accident.. Customer is responsible for shipping charges. This Warranty is not transferable. Any warranty service performed in the field must be authorized by EMAX air Unauthorized service voids the warranty and any resulting charges will not be paid by Emax Polar air makes no other warranties or guarantees, expressed or implied. Polar air assumes no liability for
indirect or consequential damages
.
Loading...