Emax EDRYHT0091, EDRYHT0134, EDRYHT0028, EDRYHT0246, EDRYHT0056 Instruction Manual

...
AIR DRYER INSTRUCTION MANUAL
0
Contents
GENERAL SAFETY INFORMATION ………………………… 1
DESCRIPTION ……………………………………………………2
INSTALLATION
………………………………………………… 3
OPERATION ………………………………………………………5
MAINTENANCE …………………………………………………6
FLOW SCHEMATIC
………………………………………………7
TROUBLESHOOTING……………………………………………8
AIR DRYER INSTRUCTION MANUAL
1
GENERAL SAFETY INFORMATION
1. This equipment is a pressure-containing device. Don’t exceed maximum
operating pressure as shown on equipment serial number tag.
2. This equipment requires electricity to operate. Install equipment in
compliance with national and local electrical codes.
3. Disconnect power supply to equipment when performing any electrical
service work.
READ PRIOR TO STARTING THIS EQUIPMENT
1. This equipment has been thoroughly checked, packed and inspected before
leaving out plant
2. This equipment is shipped to accommodate a forklift truck. When installing
this equipment, move it by means of a forklift. Never lift it by hooking on to the air inlet and outlet connections.
3. Air-cooled units – Free air flow - Ambient air should be free to flow across the
refrigeration condenser. Do not block either side of the cabinet. Leave at least
1.5m clearance for free airs flow. The ambient temperature is to be within the operating parameters of 2°C to 40°C.
AIR DRYER INSTRUCTION MANUAL
2
DESCRIPTION
Function
Compressed air enters the air-to-air heat exchanger and is pre-cooled by the chilled outgoing air. The air then enters the air-to-refrigerant heat exchanger where it is further cooled by the refrigeration system. As the air is cooled, water vapor condenses into liquid droplets. The air and entrained water droplets then enter the separator where liquid water is removed. In addition, the air is filtered of all solid particles three microns and larger. Clean, dry compressed air leaving the dryer minimizes maintenance and repair of pneumatic distribution, instrument and control, and actuation devices, reduces product contamination, and increases productivity.
Working flow
Compressed air, saturated with water vapor, enters the dryer and is pre-cooled by the outgoing refrigerated air in an air-to-air heat exchanger (pre-cooler). It is a shell and tube type with cold air in the shell and the warm air in the tube side. In the pre-cooler, the warm incoming air is pre-cooled and the outgoing refrigerated air is warmed, this reduces the amount of heat that will have to be removed later by the refrigeration system, providing a more energy efficient dryer. The Pre-Cooled air enters the evaporator, where heat from the compressed air is transferred to the cold refrigerant. The compressed air is therefore cooled to a predetermined temperature, allowing water vapor to condense into liquid droplets. The compressed air then flows to the moisture separator, where the
AIR DRYER INSTRUCTION MANUAL
3
condensed moisture, oil and solids are separated from the compressed air and discharged from the system by an automatic condensate drain trap. The cold compressed air, enters the shell side of pre-cooler. By removing heat from the incoming air, the outgoing air is reheated.
In the refrigeration system, the compressor compresses low temperature, low-pressure refrigerant into high temperature, high-pressure gas. The compressed refrigerant gas flows through the discharge line to a condenser , where the gaseous refrigerant is condensed into a high-pressure liquid, by exchanging heat to the cooling airflow. The high-pressure liquid refrigerant reduces to a low pressure, low temperature mixture of liquid and vapor after passing through the thermostatic expansion valve and evaporator as it takes heat from the compressed air. The low-pressure refrigerant gas leaves the evaporator and flows to the liquid refrigerant accumulator, ensuing that only gas is returned to compressor. The accumulator prevents liquid refrigerant from entering the compressor and causing severe damage to the compressor. Refrigerant travels through the suction line to the compressor where the refrigeration cycle again starts.
INSTALLATION
Mounting
1. A dry, well-ventilated area is the best location for installation of the dryer. It also should be in an area where the ambient temperature will not exceed 40°C or fall below 2°C.
2. A dryer should be kept at a distance from the air compressor in order to prevent
AIR DRYER INSTRUCTION MANUAL
4
the vibration of the compressor from interfering with the dryer’s operation.
3.Mount dryer on firm level surface.
4.Automatic drain outlet should be connected to the plant drainage system in order to prevent condensate from polluting plant.
5. For typical placement in a compressed air system, see drawing back.
Typical Piping connection
Three -valve bypass line should be installed before the dryer air inlet valve and after the dryer air outlet valve. This bypass valve always be install to permit the continued use of the plant compressed air system during any dryer maintenance or servicing operations.
Power and electrical connections
1. Be sure that voltage to unit is as marked on unit serial number tag.
2. Range of voltage fluctuation will not exceed 10% of rated voltage.
μ
Filter
(1 )
Refrigerated Dryer
Filter
(1 )
μ
μ
Filter
(0.01 )
Air compressor
Aftercooler
Receiver
Separator
(3 )
μ
μ
Dew point:3-10° Oil:0.003ppm w/w Solid:<0.01
C
Temperature:<45° Oil:5ppm w/w Solid:<3
μ
Dew point:3-10° Oil:1ppm w/w Solid:<1
C
μ
C
AIR DRYER INSTRUCTION MANUAL
5
3. Electrical entry in through electrical connection entry hole in electrical
enclosure. Connect power to proper terminals.
OPERATION
Preparation for start-up
1. Be sure that voltage to unit, air inlet pressure, air inlet temperature, air
flow are as marked on unit serial number tag.
2. Blow off the compressed air lines for a few minutes to remove welding
slag.
Start-up
1. Check the low refrigeration pressure gauge, it should indicate higher than
0.25MPa.
2. If the voltage is at normal range, open electric control box and close air
switch.
3. Press the control button “ON” to start.
Operation
1. Take note of refrigerant gauge indication at normal range:
The low refrigeration pressure gauge should indicate
Refrigerant R22 R134a R404A R407C
L-Pessure
0.35~0.45MPa
0.18~0.25MPa
0.45~0.55MPa 0.30~0.40MPa
If pressure is below this range please contact local service.
AIR DRYER INSTRUCTION MANUAL
6
Notice proceeding
1. Note running of the refrigeration compressor. Check and remove
troubleshooting in time.
2. Don’t start-up and shutdown frequently, dryers should restarted after 10
minutes.
Shutdown
Close the dryer air inlet valve and press the control button to shut, then disconnect the power and close the water supply valve.
MAINTENANCE
Air-cooled condenser
Ambient air should be free to flow across the refrigeration condenser for heat exchanging. Do not locate the dryer in direct sunlight. Air-cooled condenser should be cleaned with compressed air periodically.
Compressed air
AIR DRYER INSTRUCTION MANUAL
7
Automatic condensate drain
Monthly flush out accumulated sludge and dirt in the automatic condensate
drain. Procedure for clean drains: a. Close manual valve ahead of drain. b. Depressurize drain by loosening shell bolt. c. Remove shell bolt and detach the shell, take filter core out and clean it with
brush and water.
d. Reassemble the core and the shell. Then open the manual valve ahead of drain.
Electric apparatus
Check parts in the electric apparatus box and removes troubleshooting in
time.
FLOW SCHEMATIC
Pre-cooler
Evaporator
Low refrigerant pressure gauge
Compressor
Air inlet
Air condenser
Air outlet
Temperature Switch
Expansion valve
filter
Drain
separator
Fan Motor Switch
Flow diagram
AIR DRYER INSTRUCTION MANUAL
8
TROUBLESHOOTING
POSSIBLE CAUSE (S) CORRECTIVE ACTION
Power failure Check power to unit Temperature switch is disconnected
Reset
Faulty wiring, loose terminals
Have electrician check electrical connections
Compressor motor damage
Have compressor check and replace
Contactor damage
Have contactor check and replace
Dryer not running
Refrigerant leaks
Leak test and repair, refrigerant to be re-filled.
Compressor run
discontinues
Lack of refrigerant Refrigerant to be re-filled.
Ambient temperature too high
Check minimum/maximum
temperature ranges Fan motor switch improperly set
Set properly
Air-cooled models – Dirty, clogged condenser fins, obstructed air flow across condenser
Clean condenser and check for
free air flow
Too much refrigerant Let out excessive refrigerant
Condense pressure
too high
Air in refrigerated cycle system Remove air in system
Condense pressure
too low
Fan motor switch improperly set
Set properly
Thermostatic expansion valve open degree too large
Adjust Thermostatic
expansion valve correctly
Evaporate pressure
too high
Thermostatic expansion valve damage
Replace Thermostatic
expansion valve
Evaporate pressure
too low
Refrigerant Leak Refrigerant to be re-filled. Compressor sounds
abnormally
Replace damaged component
System noise
Thermostatic expansion valve sounds
Check refrigerant capacity
and replace filter
AIR DRYER INSTRUCTION MANUAL
9
Excessive air flow
Check flow rate and select
dryer newly Freezing of moisture in evaporator because of refrigeration system improperly functioning
Adjust hot gas bypass valve
clockwise
Pipeline diameter too small Pipeline too long Pipeline elbows too many
Install new pipeline
Inlet/Outlet valve not open completely
Open inlet/outlet valve
completely
High pressure drop
across dryer
Pipeline leak Leak test Low inlet air pressure High ambient air temperature High inlet air temperature High air flow
Check Dryer Selection
Air bypass valve open Close air bypass valve
Refrigeration system
not functioning
properly
drain troubleshooting a. Manual valve not open b. Drain jam or damage Drain line higher than drain condensate outlet
Open manual valve
Clean and replace drain
Install condensate line Newly
Fuse burn off Replace fuse Condense pressure too high bring on high pressure switch open Ambient temperature too high Inlet temperature too high Air flow too high
Adjust working status or select
dryer newly
Evaporate pressure too low bring on low pressure switch open Ambient temperature too low Thermostatic expansion valve opening degree too small or jam Refrigerant leak
Adjust hot gas bypass valve
regulator clockwise
Adjust or replace thermostatic
expansion valve
Replace dryer/filter
Check leak
Electric component damage Replace damaged component
Stop at running
process
Compressor damage Replace compressor
Loading...