E-matic PMUSC Instruction Manual

FIG.5-A
PIR Minor Motion
PIR Major Motion Ultrasonic Minor
Motion Ultrasonic Major
Motion
FIG.4-B
Open office
14m
3.1.3 Examples of application
3.1.3.1 Ultrasonic sensor is less affected by humidity which is more suitable for using in the moisty environment (See FIG.5-A).
FIG.5-D
The shelves of
The cabinet. The stalls of
3.1.3.2 Ultrasonic sensor detects occupant based on
the Doppler Effect and it does not need to “see” directly the movement of occupant. In other words, it is able to detect the movement happened behind the obstacles (See FIG.5-B & FIG.5-C & FIG.5-D).
FIG.5-E
FIG.5-F FIG.5-G
3.1.3.3 Ultrasonic sensor is high sensitive in detecting
small movement, such as a minor motion of typing, hand waving, door opening, etc. (See FIG.5-E & FIG.5-F & FIG.5-G):
Light keeps off when no movement is detected.
Typing, light keeps on.
Open the door, light turns on.
3.1.4 Helpful tips for installation
Since the detector is in response to temperature, airflow and wind change, please avoid the following conditions:
Avoid aiming the detector toward the objects which may be swayed in the wind, such as curtain, tall plants, miniature garden, etc. (See FIG.6-A). Avoid aiming the detector toward the objects whose surfaces are highly reflective, such as mirror, monitor, etc. (See FIG.6-A). It is better to locate the detector at least 2m away from the glass gate or window for avoiding nuisance triggering because the shaking of glass could trigger the ultrasonic sensor (See FIG.6-D).
FIG.5-H FIG.5-I
FIG.5-J
3.1.3.4 Since ultrasonic sensor is high sensitive to the
small motion and does not require a direct view between the sensor and the movement, therefore, it is optimum for using in the spaces where frequently has less or small motion taken place, such as a conference room, an open plan office with partitions, a library, etc. (See FIG.5-H & FIG.5-I & FIG.5-J).
D2 D1 N
N L
Load
Power box
L
M/S R
Push button (N.O.)
Manual switch
Jumper
FIG.7
D2 D1 N LLN
N L
Load
Power box
Power box
N
L
M/S R
S S
Push button (N.O.)
Master Slave
FIG.8
3.2.1.2 Master / slave operation (See FIG.8).
Jumper
It is better to locate the detector at least 2m away from the source of airflow such as doorway, vents and air conditioning, etc. (See FIG.6-B & FIG.6-C & FIG.6-E). If airflow causes the detector false triggering, set ACC knob to ON position. After that, if the false triggering still exists, lower the ultrasonic sensitivity or select a more suitable location. The distance between two detectors must be at least 2m to avoid interference (See FIG.6-F). The direction of the ultrasonic sensor should aim to the main detection area to obtain the best coverage (See FIG.3).
FIG.6-E
>
2m
FIG.6-F
>
2m
FIG.6-D
>2m
Air duct
3.2 Wiring
3.2.1 For lighting (With jumper wire on D1 & L terminals).
3.2.1.1 One detector controls one load (See FIG.7).
FIG.6-BFIG.6-A FIG.6-C
Push button (N.O.)
Push button (N.O.)
D2 D1 N
Power box
L
M/S R
Jumper
N L
Ein
t
Staircase timer
Load
FIG.9
3.2.1.3 One detector controls staircase timer (Set time knob to ) (See FIG.9).
1s.
3.2.2 For HVAC (Remove jumper wire on D1 & L terminals) (See FIG.10).
D2 D1 N
N L
Load
Power box
L
M/S R
Push button (N.O.)
FIG.10
AC/DC
......
Presence Detector
PMUSC
INSTRUCTION MANUAL
TECHNICAL SPECIFICATIONS
ACC on / ACC off Switch
Adjustable from approx. 5sec to 30min, Test &
Adjustable from approx. 10Lux to 1000Lux
Select “ON” for activating or select “OFF” for deactivating air current compensation function
1s.
Auto Off Time Adjustment
Lux Adjustment
230V~±10% 50/60HzRated
Voltage
PIR + US, PIR only, US only, PIR or US
PIR: 360
o
circular, adjustable up
to Φ8m
US: 360
o
, adjustable up to 10m x
16m, it’s an oval shape 0
o
C to +45oC
Detection Range (H=2.5m)
Triggering Method selection
Class, IP20
Operating Temperature
Environmental Protection
1
1
1
PACKAGE CONTENTS
22
Lens shield
Detector
Pattern
Item
Quantity
Manual
Pattern
Quantity
1
Item
Junction box JB-46
Accessories for optional purchase
2 PRODUCT DESCRIPTION
2.1 Features
The Dual-Technology presence detector PMUSC integrates advanced PIR and Ultrasonic technologies in one unit. The combination of these technologies helps to eliminate false triggering problems even in difficult applications. It is suitable for indoor application which is ideal for using in home, open­plan office, multi-stall public restroom, conference room, under-ground parking lots, classroom, library, etc.
4
Non­dropping screw Φ3 x 18mm
US only or PIR/US:
When there is high level of minor motion or obstacle (furniture or partitions) existing in the monitored space, or it is a multi-stall space. For example, a multi-stall public restroom, an office with partitions, etc.
PIR+US:
If the precise detection is necessary, choose this triggering method which can reduce the false triggering problem. For example, a classroom, an open-plan office, etc.
Triggering mode application examples:
With its knobs and IR remote controller, the time, ultrasonic sensor sensitivity, Lux, ACC (air current compensation) function and PIR/US triggering method can be adjusted as user desired to match different application requirements and energy saving for switching light on and off.
2.2 Additional functions
2.2.1 Function of terminal R
Connect terminal R with push button (N.O. type) to manually control the load’s on / off. When the load is off, press (>1sec) the push button (N.O. type) to manually switch the load on. The load keeps on if the movement is detected constantly. The load can be automatically switched off if no movement is detected and the delay time has expired, or by pressing the push button again. When the load is off, the move­ment cannot trigger the load on, and the detector will return to the previous mode until detecting the last movement and the delay time has expired. Refer to FIG.7 for wiring connection.
PIR only:
If the monitored space is free of obstacle or has high level of airflow or the detection area is needed to be well specified. For example, a small-scale office with air-conditioning, a small conference room, etc.
FIG.1
2.2.2 Function of master / slave
14m
20% overlap
2.2.2.1 Compatible with slave detector to achieve this function. PMUSC can connect up to 10pcs slave detector which has the same detection range as PMUSCt o enlarge the detection range. Under this mode, load and LED perform according to the setting of the master detector (PMUSC). Slave detector works as a movement register to send signal to master detector.
2.3 Dimension:
PMUSC: Φ111.5 x 67mm (See FIG.2-A)
2.2.3 Advance switching off function
To enhance energy savings, the detector is able to turn off the controlled load prior to the set delay off time if it detected the passing through occupant. When the load is off, once the detector is triggered, the load will keep on. If no movement is detected again during 30sec to 3min, the load will on for
2.5min, and then off, even the time setting value is more than 3min.
FIG.2-A
Φ111.5
52
67
JB-46: Φ111.5 x 35mm (See FIG.2-D)
FIG.2-C
FIG.2-B
FIG.2-D
FIG.2-E
35
Φ111.5
Φ111.5
72
Φ111.5
43.5
90
SP-96: 62.5 x 50mm (See FIG.2-B)
Detector with power box cap SP-96 for flush mount:
Φ111.5 x 90mm
(See FIG.2-C)
Detector with junction box JB-46 for surface mount: Φ111.5 x 72mm
(See FIG.2-E)
50
62.5
3 INSTALLATION AND
WIRING
Please disconnect power completely and read the entire instruction manual carefully before installation.
3.1 Select a proper location
FIG.3
Side view
US 16m
PIR 8m
2.5m
PIR Minor Motion
PIR Major Motion
Ultrasonic Minor Motion
Ultrasonic Major Motion
3.1.1 The recommended installation height of this detector is 2 - 3m, and 2.5m is the optimal mounting height. The detection range of PIR sensor can reach up to Φ8m, and ultrasonic sensor is an oval shape of 8m x 10m with small movement (i.e. hand wave), and an oval shape of 10m x 16m with large movement (i.e. walk). The detection angle is 360° for both PIR and ultrasonic sensors (See FIG.3).
Top view
US 10m
US 8m
360°
PIR Φ4m
PIR Φ8m
US 10m
US 16m
12m
7.5m
Classroom
Conference room
10m
8m
FIG.4-A
Dual-technology detector is capable of detecting occupant without directly seeing the moving person due to the high sensitivity of ultrasonic sensor. Ceiling mount will give an overall view of the entire room, and the detector should be mounted in the center of the room so that the detector can detect movement from anywhere of the monitored space. If you choose the PIR technology (PIR+US or PIR only) as triggering method, the detector should be located where the PIR sensor is able to see the occupant. In order to ensure good reliability of PIR sensor, an overlapping area is need to be considered while installing several sensors in a space.
3.1.2 Location of dual-technology detector (See
FIG.4-A & FIG.4-B).
CAUTION!
Switches complying with this standard are suitable for use at ambient temperature not normally exceeding 25°C, but occasionally reaching 35°C. A circuit breaker (250VAC, 10A) type C according to EN60898-1 shall be installed in the fixed wiring for protection. Do not mount on conductive surface. Do not open the enclosure frequently. Turn off power when change the light sources. Bulb burn of certain brands would cause high in­rush current which might damage the unit permanently.
Installation and assembly of electrical equipment must be carried out by skilled person. Contact a qualified electrician in the event of fault down.
Screw
Φ
3 x
14mm
2
Wood screw
Φ
4
x 25.4mm
Pattern
Quantity
11
Item
PMUSIR IR remote controller
Power box cap SP-96
+ U
LT
+
U
L
T
Time1
Time2
ON
ACC
OFF
ACC
PIR /US
PIR only
US only
PIR +US
IR-11T
Lux
Load (L )
Max. 10A (cosφ=1) for 250VAC Max. 3A (cosφ=0.4) for 250VAC Max. 5A for 30VDC
For lighting (with jumper wire):
For HVAC (remove jumper wire):
12 x (2 x 18W)
7 x (2 x 36W)
5 x (2 x 58W)
Energy saving Lamp: Max. 600VA /
400W (include
CFL and PL lamp)
<
<
<
Incandescent Lamp: Max. 2000W AC halogen Lamp : Max. 1000W LV halogen Lamp : Max. 1000VA
(600W) Fluorescent Lamp : Max. 900VA / 100μF 25 x (1 x 18W); 15 x (1 x 36W); 10 x (1 x 58W);
3.3.1.4 Assemble the detector with power box, then fix them with two screws (See FIG.11).
3.3.1.5 Put on the decorative frame and restore the power supply.
3.3.1.2 Pull out cables from European standard junction box (See FIG.12), then strip off 6 ­8mm of cable sheathing for wiring, and refer
to the wiring diagrams for correct cable
connections (See FIG.7 - FIG.10).
FIG.12
mm8 - 6
3.3.1.3 Fit the power box into European standard junction box then screw them with two screws (See FIG.13).
FIG.13
3.3.1 Flush mount with European standard junction
box
3.3.1.1 Take off the decorative frame (See FIG.11).
FIG.11
Non-dropping screw
Power box
Detector head
Decorative frame
3.3 Installation Procedure
NOTE
The direction of the ultrasonic sensor should aim to the main detection area to achieve the best detection coverage when detector is flush mounted with European standard junction box, and the fixing plate can be adjusted 45°.
2.2.2.2 2.5mm
2
power cables for D1, D2, L, N connection, and 1.5mm2 for master and slave connection. Refer to FIG.8 for wiring connection.
2.2.2.3 To get complete coverage in an open office area, install multi slave detectors with approx. 20% overlap ultrasonic detection range to adjacent ones (See FIG.1).
Dual-Technology
FIG.5-B FIG.5-C
W
RH % OK
RH %
OK
Dual-Technology Presence Detector
PMUSC
3.3.2 Surface mount
3.3.2.1 There are 7 pairs of fixing holes with various distances from 41mm to 85mm on the bottom cover of the combined junction box JB-46 which can be selected for different mounting applications (See FIG.14-A). To select two same figures on both ends for the corresponding fixing distance (See FIG.14-B).
FIG.14-A
80
80
8
5
8
5
7
0
7
0
6
0
6
0
63
63
53
53
41
41
80
80
8
5
85
7
0
70
60
6
0
63
63
53
53
41
41
A
B
Fixing holes
Fixing holes
FIG.16
80
85 70
60
63 53
41
80
85
70
6
0
63
53
41
FIG.17
Non­dropping screw
Non­dropping screw
3.3.2.4 Insert four non-dropping screws to the corresponding screw holes on detector’s fixing plate. Afterwards, those four screws will not drop off to provide convenient subsequent installation (See FIG.17).
3.3.2.5 Refer the FIG.11 to assemble the detector head with the power box, and then refer to the wiring diagrams (See FIG.7 - FIG.10) for correct cable connections.
3.3.2.6 Put on the decorative frame and restore power supply.
3.3.3 Flush mount
3.3.3.1 To install detector, please drill a hole with diameter of 65mm on ceiling board and keep the power cable outside. Please strip off 6 ­ 8mm of cable sheathing for wiring (See FIG.18).
FIG.18
NO. A B
The distance between A and B
1 2 3 4 5 6 7
41 53 60 63 70 80 85
41 53 60 63 70 80 85
41mm 53mm 60mm 63mm 70mm 80mm 85mm
FIG.14-B
FIG.15
3.3.2.2 To feed power cables through the side of junction box, please use the cutting pliers to break the side cable entry knockouts, then insert cables into junction box and feed through it. Please strip off 6 - 8mm of cable sheathing for wiring (See FIG.15).
3.3.2.3 Choose two proper knockouts to fix the junction box JB-46 on the surface of ceiling board with two wood screws (See FIG.16).
30 - 35mm
6 - 8mm
Φ=65mm
30 - 35mm
6 - 8mm
Cable entry knockout
Drill a hole with
Φ =65mm on the
ceiling
Green LED does not turn on
1. Ultrasonic sensor is not chose as the triggering method (US only; PIR/US; PIR+US).
2. Exceed the valid detection range.
1. Choose ultrasonic sensor as the triggering method.
2. The movement should be in the valid detection range (10m x 16m).
Nuisance triggering
There are heat sources, airflow, highly reflective objects or any objects which may be swayed in the wind within the detection coverage.
Avoid aiming the detector toward any heat sources, such as air conditioning, electric fans, heaters or any highly reflective surfaces. Make sure there are no swaying objects within the detection coverage.
Lighting device does not turn off
1. Auto off delay time is set too long.
2. Detector is nuisance triggered.
3. Incorrect wiring.
1. Set auto off delay time to a shorter time and check if the load is switched off or not according to the preset off delay time.
2. Keep the objects which may cause nuisance triggering away from detection coverage to avoid activating detector while doing the test.
3. Refer to wiring diagrams (See FIG.7 - FIG.10).
Red LED does not turn on
1. PIR sensor is not chose as the triggering method (PIR only; PIR/US; PIR+US).
2. Exceed the valid detection range.
1. Choose PIR sensor as the triggering method.
2. The movement should be in the valid detection
range (Φ8m).
5
TROUBLE SHOOTING
Problem
Possible cause
Suggested solution
When PMUSC works abnormally, please check assumptive problems and suggested solutions in following table that will hopefully to solve your problems.
Lighting device does not turn on
1. Power does not switch on.
2. Incorrect wiring.
3. The ambient light level is too high.
4. Malfunctioned load.
1. Switch on the power.
2. Refer to wiring diagrams (See FIG.7 - FIG.10) and check if the load is malfunctioned.
3. Set Lux value above the ambient light level then trigger the detector and check if the load is switched on or not.
4. Replace the disabled load with a new one.
6 OPTIONAL ACCESSORY
FIG.24
PMUSIR
+ ULT
+
ULT
Time1
Time2
ON
ACC
OFF
ACC
PIR /US
PIR only
US
only PIR +US
IR-11T
Lux
NOTE
Wire connections in reverse in between N and L will cause lower sensitivity of ultrasonic sensor.
The following conditions may cause lower sensitivity of PIR sensor: On very foggy days, the sensitivity may be less due to moisture collecting on the lens. On very hot days, the sensitivity will be lower as high ambient temperature can be close to body temperature. On very cold days when wearing heavy clothing, and especially if the facial area is covered, maybe appear less sensitive.
The Effects to PIR sensitivity:
NOTE
Do not attempt to open or repair the unit without qualified electrician while it is malfunctioned. Cleaning: Wipe with dry cloth only. Soap or rough cloth may damage the detector lens.
The following conditions may cause lower sensitivity or false triggering of ultrasonic sensor: Set ACC knob to ON: The airflow will cause false trigger to ultrasonic sensor. To reduce the possibility of false trigger, the dual technology sensor is designed with air current compensation (ACC) function which is able to reduce the sensitivity of ultrasonic sensor approx. 10% ~ 40% varied with the strength of airflow. Ultrasonic sensitivity will be affected by the materials such as carpet, sound absorbable cotton, curtain, etc. since they are sound wave absorber. Low ambient temperature might slightly decrease ultrasonic sensitivity and also reduce the detection range.
The Effects to ultrasonic sensitivity:
All rig hts res erved . No repro ducti on, copy, o r transmission of this priduct may be made without writing permission.
1. Pressing “ ” button to activate the air current compensation function which is confirmed by the green LED keeping on for 5sec.
2. Pressing “ ” button to deactivate the air current compensation function which is confirmed by the green LED flashing for 5sec.
ACC on/off control function
1. By pressing “ ” button, load will be
switched off 8hrs, it is confirmed by
flashing of detector’s LEDs.
2. Exit off mode and return to Auto mode either by pressing “ ” again or to re­ supply power to detector after it is off.
3. Load (for lighting control) can be lead to on mode by pressing “ ” button under off mode.
Load off
1. Press “ ” button to enter into short impulse mode, both LED and load are controlled by Lux under this mode.
2. If the triggering method is “PIR+US”: Both PIR and ultrasonic sensors are triggered, the load and LEDs will be on for 1sec, and then off. The next trigger­ ing should be 9sec interval.
3. If the triggering method is “PIR/US”: Either PIR or ultrasonic sensor is triggered, the corresponding LED and load will be on for 1sec, and then off. The next triggering should be 9sec interval.
4. If the triggering method is “PIR only”: Only PIR sensor is triggered, the red LED and load will be on for 1sec, and then off. The next triggering should be 9sec interval.
5. If the triggering method is “US only”: Only ultrasonic sensor is triggered, the green LED and load will be on for 1sec, and then off. The next triggering should be 9sec interval.
6. Loadhas no reaction in short impulse mode.
Short impulse mode
1. By pressing “ ” button, load will be
switched on 8hrs, it is confirmed by
flashing of detector’s LEDs.
2. Exit on mode and return to Auto mode either by pressing “ ” again or to re­ supply power to detector after it is off.
3. Load (for lighting control) can be lead to off mode by pressing “ ” button under on mode.
Load on
4.3.5 To repeat above mentioned procedures to adjust the settings of detector either by knobs or IR remote controller and conduct the walk test until the detector’s detection coverage meets your demand.
FIG.23-A
FIG.23-B
Walk type for PIR sensor
Walk type for ultrasonic sensor
4.2.3 Fixing lens shield: There is a circular groove on the back of the decorative frame and the lens shield is designed with a circular hook. By coupling the hook into the groove, the lens shield is fixed (See FIG.22-A & FIG.22-B).
FIG.22-A
FIG.22-B
Decorative frame
Circular groove
Circular hook
NOTE
4.3 Walk test (uncontrolled by Lux)
It takes approx. 30sec for detector to warm up with load on after power is initially supplied or resupplied after power failure, then the detector enters into normal operation to carry out a walk test. During which, red and green LEDs will permanent on for 30sec if no IR setting value is stored in detector. Reversely, the red and green LEDs will flash for 30sec if any setting value has been stored in the detector. Re-supplied after power failure, detector works according to the previous settings.
The purpose of conducting the walk test is to check whether the triggering method (PIR, ultrasonic) is set correctly or not and to adjust the detection coverage. Procedures of conducting the walk test (Lux controller is disabled):
4.3.1 Set the time knob to “Test” position.
4.3.2 Adjust the position of meter knob for matching the sensitivity of ultrasonic sensor as you desired. The detection coverage of PIR sensor can be adjusted by using the lens shield.
4.3.3 Set the ACC knob to OFF position.
4.3.4 Select the desired trigger method (i.e. PIR+US, PIR only, US only or PIR/US). Step 1: Switch on the power supply and it takes approx. 30sec for detector to warm up with load and LED on for 30sec, afterwards they will turn off. Step 2: To walk within the desired detection coverage of detector (Refer to FIG.23-A & FIG.23-B). Step 3: When its PIR sensor is triggered by move­ ment, the red LED turns on for 2sec, then turns off; when its ultrasonic sensor is triggered by movement, the green LED turns on for 2sec then turns off. When choosing PIR+US as triggering method, both red and green LEDs will turn on for 2sec then turn off if both sensors have been triggered by move­ ment.
6.1 It is recommended warmly to purchase our high quality IR remote controller PMUSIR for easy convenient and safe operation on PMUSC.
Button Function
US
US
1. By pressing “ ” “ ” buttons to set the sensitivity of ultrasonic sensor. Each time the user presses the button, the sensitivity of ultrasonic sensor would increase or decrease 10% with indication of green LED flashing.
2. By pressing “ ” button to increase the sensitivity of ultrasonic sensor.
3. By pressing “ ” button to decrease the sensitivity of ultrasonic sensor.
4. When the sensitivity of ultrasonic sensor is at its highest or lowest level which is confirmed by green LED keeping on for approx. 2sec.
Sensitivity adjustment of Ultrasonic sensor
US
US
US
US
US
By pressing “ ” button, the detector is set to activate its load on only when the ultrasonic sensor of it detects the move­ment, and the green LED will flash to confirm the successful setting of this mode. To exit this mode by selecting other mode.
Ultrasonic only function
US
1. Pressing “ ” button to activate the air current compensation function which is confirmed by the green LED keeping on for 5sec.
2. Pressing “ ” button to deactivate the air current compensation function which is confirmed by the green LED flashing for 5sec.
ACC on/off control function
PIR only function
By pressing “ ” button, the detector is set to activate its load on only when the PIR sensor of it detects the movement, and the red LED will flash to confirm the successful setting of this mode. To exit this mode by selecting other mode.
US
By Pressing “ ” button, the detector is set to activate its load on when either PIR sensor or ultrasonic sensor is triggered by movement. When PIR is triggered, the red LED will flash; when ultrasonic sensor is triggered, the green LED will flash. To exit this mode by selecting other mode.
PIR or Ultrasonic mode
US
US
By pressing “ ” button, the detector is set to activate its load on when both PIR sensor and ultrasonic sensor detect the movement, and both red and green LEDs will flash. To exit this mode by selecting other mode.
PIR & Ultrasonic mode
US
Button Function
Time setting for Time / Time1 or Time2
By pressing “ ” “ ” to select the load desired to set the delay off time value. Either “ ” or “ ” is pressed, LED flashes 2sec, and then press the corres­ponding time value button to set it, which is confirmed by 2sec flashing of detector’s LED.
Time1
Time1
Time2
Time2
1. By pressing “ ” button to enter into test mode. Both load and LEDs are uncontrolled by Lux value.
2. If the triggering method is “PIR+US”: Both PIR and ultrasonic sensors are triggered, the load and LEDs will be on for 2sec, and then off. The next trigger­ ing should be 2sec interval.
3. If the triggering method is “PIR/US”: Either PIR or ultrasonic sensor is triggered, the corresponding LED and load will be on for 2sec, and then off. The next triggering should be 2sec interval.
4. If the triggering method is “PIR only”: Only when PIR sensor is triggered, the red LED and load will be on for 2sec, and then off. The next triggering should be 2sec interval.
5. If the triggering method is “US only”: Only when ultrasonic sensor is triggered, the green LED and load will be on for 2sec, and then off. The next triggering should be 2sec interval.
6. Loadhas no reaction in test mode.
Test mode
Time2
Time1
Select load for time setting
By pressing “ ” to set the delay off time value of load, and “ ” to set the delay off time value of load. “ ” is invalid if the detector has only one load.
Time2
Time2
Time1
Load for lighting control (Relay)
Lux value adjustments for lighting control
By pressing corresponding button, the selected light level threshold for switching on the connected load can be set.
By pressing “ ” button,PMUSIR is unlocked; thereafter it can be used to make settings. The PMUSIR will lock auto-matically if there is no operation occurred in 2min counting from the last operation.
By pressing “ ” button,PMUSIR can be locked and no adjustments are workable (except “ ” button).
Lock PMUSIR
Button Function
Unlock PMUSIR
Reset
By pressing “ ” button, detector is controlled by potentiometers, and it can delete all the MEMO data.
Automatic read-in of actual light level function for lighting control
Actual light level can be read-in as threshold for switching the correspond­ing light if the provided Lux values do not match user's requirement. The steps are as below: Push “ ” button till detector's red and green LEDs flashing to enter into learning mode, learning time is 10sec. Then the ambient light level is read in confirmed by LED on to indicate IR learning successfully. Then it returns to Auto mode. If the ambient light level is out of the range of 5 ­1000Lux, detector will learn for 10sec, then LEDs flash quickly for 5sec to indicate IR learning unsuccessfully, but below Lux value will be stored: 1000Lux if the actual light level is above 1000Lux, and 5Lux if the actual light level is below 5Lux.
1. By pressing “ ” button, both loads and detector's LEDs have no reaction if no settings are stored in PMUSIR.
2. When time of Time1, Time2 and Lux are set by PMUSIR already, press “ ” button more than 3sec to store the settings successfully. By pressing “ ” button less than 1sec, the stored settings can be duplicated to a new detector.
3. Remove the battery more than 5sec, all the settings will be deleted. It needs to be reset after replacing the battery.
Store and duplicate the values of Time1, Time2, and Lux set by PMUSIR
6.2 Push button function:
Due to our policy of continuous improvement we reserve the right to change specification without prior notice. Errors and omissions excepted. These instructions have been carefully checked prior to publication. However, no responsibility can be accepted by E-Matic for any misinterpretation of these instructions.
E-Matic Energy Management Solutions Distributed by: Challenger Security Products 10 Sandersons Way, Blackpool, FY4 4NB
Tel: 01253 791888, Fax: 01253 791887
Email: enquiries.ematic@adivision.co.uk www.e-matic.co.uk
Ematic_PMUSC_Instructions_Rev01
4.2 Usage of lens shield for PIR sensor
4.2.1 PMUSC has provided 2 lens shields for masking the undesired detection area of PIR sens or. One lens shield has 2 layers with 6 small units each, and 30° of detection angle can be covered by each unit. For example, to inst all the detector at the height of 2.5m, the detection range ca n reach to 2m diameter if the complete lens shield has been used; and up to 6m diameter i f only the A layer of lens shield has been used ( See FIG.21-A & FIG.21-B).
4.2.2 After user choosing the desired dete ction area, the needless lens shield should be removed (See FIG.21-C).
Φ2m
A
B
FIG.21
30°
Φ6m Φ8m
The shadow part of the lens shields in the FIG.21-A & FIG.21-B & FIG.21-C is needed to be cut off. The ultrasonic sensor is unaffected by the lens shield.
Knob (Ex-factory setting)
Function Knob setting
4 OPERATION AND
FUNCTION
4.1 Setting of Lux, Time, Meter, ACC and PIR/US knobs
Lux
1000
300
10
100
Set the light value for switching on load
Range: Approx. 10Lux to 1000Lux User can set the knob according to their requirement for application. The marked values are for reference only.
Time
15m
5m
5s
30m
Test
1s.
Range: Approx. 5sec to 30min Test: Test mode (Load and red and/or green LED will 2sec on, 2sec off). Test mode is uncontrolled by Lux. : Short impulse mode for staircase timer switch control (Load and red and / or green LED will 1sec on, 9sec off).
1s.
Set delay off time
Set the sensitivity of ultrasonic sensor
-” = Min. (Approx. an
oval shape of 2m x 3m). “+” = Max. (Approx. an oval shape of 10m x 16m).
Meter
4x6m
7x8m
+
-
3.3.3.2 Break the two rubber gask ets on the power box cap with screwdriver, then put the power cable through them (See FIG.19).
FIG.19
Cable entry
P
ower box cap
Non-dropping screw
Rubber gasket
3.3.3.3 Refer to wiring diagrams for correct cable connections, then cover the power box cap back and screw it tightly.
FIG.20
3.3.3.5 Switch on the power supply.
Φ=65mm
Power cable
Spring clips
ACC
OFF ON
Reduce the false trigger problem caused by airflow.
ON : Activate the ACC function. OFF: Deactivate the ACC function. Remark: Under ACC ON status, the detection coverage of ultrasonic sensor will be reduced.
Knob (Ex-factory setting)
Function Knob setting
PIR only US only
PIR/US PIR+US
Select triggering method
PIR/ US: Load will turn on when either PIR or ultrasonic sensor is triggered. PIR+US: Load will turn on when both PIR and ultrasonic sensors are triggered, and after the load is on, either PIR or ultrasonic sensor detects movement, the load keeps on. PIR only:Load will turn on only when PIR sensor is triggered. US only: Load will turn on only when ultrasonic sensor is triggered.
The whole lens shield is used.
Φ6m
30°
Φ6m Φ8m
Φ2m
A layer of the lens shield is used.
Part of the lens shield is used.
Part of the lens shield is used.
3.3.3.4 Insert detector’s two spring clips into the drilled hole, then push it upwards (See FIG.20).
Loading...