4.3.1 PMSCF20 has provided 2 lens shields for masking the undesired
detection area. Each lens shield has 3 layers (Layer A / Layer B
/ Layer C), each layer includes 6 small segments and each small
segment can cover 30° detection angle. For example, to install
the detector at the height of 2.5m, the detection range can
reach up to 4m diameter if the complete lens shields has been
used, and up to 8m diameter if layer C has been cut, as well,
up to 14m diameter if layer B also has been cut, the detection
range can reach up to 20m diameter when no lens shield is
used.
4.3 Usage of lens shield
Problem Possible cause Suggested solution
Lighting
device
does not
turn on
1. Power does not
turn on.
2. Wired incorrectly.
3. Lux knob adjusted
incorrectly.
4. Malfunctioned
load.
1. Switch on the power.
2. Refer to wiring diagrams for
correct connection.
3. Check if Lux knob is set to
the correct position.
4. Replace the disabled load
with a new one.
Lighting
device
does not
turn off
1. Auto off time is
set too long.
2. Detector is
nuisance
triggered.
3. Wired incorrectly.
1. Set auto off time to a shorter
time and check the load is
switched off or not according
to the pre-set off time.
2. Keep away from detection
coverage to avoid activating
detector while doing the test.
3. Make sure load and wires
are connected correctly.
LED does
not turn
on
1. Time konb is not
set to Test.
2. Exceeding the
detection range.
1. Time knob must be located
to Test position.
2. Walk in the effective detection
range of 20m diameter.
Nuisance
triggered
There are heat
sources, highly
reflective objects or
any objects which
may be swayed in
the wind within the
detection coverage.
Avoid aiming the detector
towards any heat sources, such
as air conditionings, electric
fans, heaters or any highly
reflective surfaces. Make sure
there are no swaying objects
within the detection coverage.
4.3.2 Fixing lens shield: There is circular hook on the back of the
decorative frame and the lens shield is designed with a circular
groove. The lens shield can be fitted by joining the groove of
lens shield with its corresponding hook on the decorative frame
(See FIG.13).
FIG.12
FIG.14
FIG.13
4.4 Walk test
The purpose of conducting the walk test is to check and adjust the
detection coverage. Set Time knob to “Test”, then conducting a walk
test and Lux is disabled.
It takes approx. 60sec for detector to warm up after power is
supplied, then enters into normal operation to conduct a walk test.
NOTE
4.4.1 Tester must be within the detection coverage.
4.4.2 Switch power on.
4.4.3 PMSCF20 takes approx. 60sec to warm up with load and LED
on, then turns off after warming up time.
4.4.4 Walk from outside across to the detection pattern until LED
turns on for approx. 2sec then off, the next trigger should be
2sec interval (See FIG.14).
4.4.5 Adjusting lens shield for desired detection range.
4.4.6 Repeat step 4.4.4 and 4.4.5 until it meets user's demands.
Test procedure
5 TROUBLE SHOOTING
When PMSCF20 works abmormally, please check assumptive
problems and suggested solutions in following table that will hopefully
to solve your problem.
Φ4m
C
B
A
The whole lens shield is used.
Part of the lens shield is used.
30°
Φ20m
Φ8m
Part of the lens shield is used.
Φ14m
Φ20m
Φ4m
Φ8m
30°
Φ8m
A & B layers of the lens shield are used.
A layer of the lens shield is used.
Φ14m
The shadow part of the lens shields in the FIG.12 is refer to the
cut off parts.
NOTE
When the actual light level is out of the range 10 - 2000Lux,
detector will learning 25sec, then the red LED flashes quickly for
5sec. When the actual light level is below 10Lux, Lux value is set
to 10Lux, or is above 2000Lux, Lux value is set to
∞
(uncontrolled by lux setting).
Installer should be away from the detector to avoid affecting the
luminous flux that reaches the detector when learning Lux value.
10
300
100
2000
10
300
100
2000
10
300
100
2000
10
300
100
2000
10
300
100
2000
Adjust knob to
” “ from
other position
Adjust knob to
other position
from ” “
1sec after goes
back to ” “
FIG.11-A
FIG.11-B
LED flashes slowly for 25sec
& Load is off
W
W
W
W
LED and load off
Detector switches to AUTO
mode
LED flashes quickly for 5sec &
Load is off (the actual light
level range is out of 10 2000Lux)
LED and load keep on 5sec
(the actual light level range
is 10 - 2000Lux)
FIG.11-C
28-MLCHA420P-C
4.2.2 When the knob is set to “ ” originally, it should be adjusted
to other position more than 1sec, then goes back to “ ” (See
FIG.11-B).
4.2.3 Then the load is off. LED starts to flash slowly indicating entering
into learning mode. Learning will be completed within 25
seconds. Afterwards, the LED and load will keep on 5sec or
LED flashes quickly for 5sec and load is off to confirm successful
learning (See FIG.11-C).
4.2.4 After learning procedure, the detector returns to AUTO mode
with LED and load being off.
3.4.7 Restore the power supply.
FIG.10
Φ65mm
Power cable
Spring clips
3.4.6 Close up sensor’s two spring clips and insert sensor into the
drilled hole on ceiling (See FIG.10).
3.4.4 Please refer to illustration of FIG.5 - FIG.6 for correct wiring
and then screw the protection cap tightly and fit on the cable
clamp.
3.4.5 Each cable clamp have two groves, then can fitup the different
of diameter of cable (See FIG.9).
Big grovle
Big
grovle
Small grovle
Small
grovle
Big
grovle
Small
grovle
FIG.9
Connect a circular
cable of Φ5 Φ12.5mm
Connect two circular
cable of
Φ5 - Φ6mm
Connect a circular
cable of Φ3 - Φ5mm
Connect two circular
cable of
Φ3mm
Connect one or two
flat cable of 4 x 8mm
Range: Approx. 10sec to 60min
(Reaction is regardless of
Lux value)
Set delay
off time for
HVAC
Time 2
15m
10s 60m
30m
Set delay
off time for
lighting
Range: Approx.5sec to 30min
Test
: Test mode (Load and red LED
will be 2sec on, 2sec off)
: Short impulse mode for
staircase timer switch control
(Load will be 1sec on, 9sec off)
1s
Time1
5m
5s 30m
Test
15m
1s
4.1 Meter, Lux, Time1 and Time2 knob
Knob Function Knob setting
4 OPERATION AND FUNCTION
Meter+Set the
range of
sensitivity
Range: from “-”(Φ10m) to “+”
(Φ20m)
Lux
10
300
100
2000
Set the light
value for
switching
on load
Range : Adjustable from approx.
10Lux to “ ” (∞).
(learn): The actual ambient light
level (10 - 2000Lux) can
be read in.
Learning procedure:
4.2 Lux learning function with knob
4.2.1 Adjust the knob to “ ” when the ambient light level matches
with the desired value (See FIG.11-A).