PMSCF Instructions Rev02
4. Secure the cable by re-screwing the cable clamp. Fix the terminal cover back
5. Press the side springs up, hold them and mount the sensor into the ceiling hole (see Figure 3)
After finishing the fitting operation, you can adjust the detection area and working state of PIR sensor
■
OPERATION MODE:
WALK TESTING:
When the mains supply is switched on to the PMSCF, the PMSCF sensor will enter into a “WARM-UP” period for approximately 1
minute and then automatically change to “AUTO MODE”. While sensor is in the AUTO MODE, you can then carry out a Walk-Test
by placing the LUX control to day position () and the TIME control to minimum (-). Once the PMSCF sensor receives a valid
trigger signal (such as movement of a person) within its detection area, the lamp(s) (load) will be turned on for the pre-set period
of time. You will be able to determine the detection area by walking slowly.
Please Note: Movement across the detection area is more effective than movement directly toward or away from the sensor.
(Refer Fig.4A). If movement is towards or away from the sensor, not across, the detection range will be reduced. (Refer Fig. 4B)
After completing the walk-test, set the LUX DIAL to the required night position to ensure PMSCF only operates at night or
required light level and set TIME DIAL to the desired “ON’ time.
ADJUSTING THE LUX CONTROL LEVEL:
The Lux control module has a built-in photocell that detects daylight and darkness.
() position denotes that the lamp(s) (load) will be turned on by PIR during day and night.
( ) position denotes that the lamp(s) (load) will be turned on by PIR only at night.
You can set to operate the unit at the desired level by adjusting the LUX knob
ADJUSTING THE DURATION TIME:
The duration time is “the length of time that the PMSCF switches the load ‘on’ after activation”. The duration time can be adjusted
from (10±5) seconds to (30±3) minutes. Rotating the TIME knob from (+) to (-) will reduce the duration time.
Note: Once the lamp(s) (load) has been triggered by the PIR sensor any subsequent detection will start the timed period again
from the beginning.
■ ATTENTION:
1. Before any electrical work, ensure mains supply cable is isolated by switching off and removing the relative fuse.
2. There are not any servicing parts inside, do not attempt to modify or service the unit.
3. It is normal that the load will delay several seconds to be turned on when power on.
Fig. 4(B) Not
Good
Fig. 4(A)
Good
Figure 3