ELT Sensor CD-300, CD-300G, CD-300L, CD-300LG Operation Manual

ELT SENSOR Corp.
1 / 5
General
CD-300(G)and CD-300L(G) Transmitter type
4-20mA Current output module or 0-10V, 2-
10V Voltage output module(Jumper select)
These models give 3 wired input power (2
PWR lines, 1 Common GND line).
Features
Non-Dispersive Infrared(NDIR) technology
Either of four (2 Set of Analog Voltage or
2 set Current) output can be chosen by
Jumper. (4~20mA/2~10V/0~20mA/0~10V)
Customer could select multiple functions
-. Factory calibration mode is available.
-. 10 minutes manual recalibration or weekly
Auto-Calibration is settable.
Simple maintenance (S-300(G) sensor is
detachable from main board, which gives
easier manipulation on sensor module.)
Size : 123 x 69 x 40 (mm)
Carbon Dioxide (CO) Transmitter
(3-wired type) Operation Manual
CD-300(G) / CD-300L(G)
CD-300(G)
CD-300L(G)
(with LCD Display)
Version 2.72
ELT SENSOR Corp.
2 / 5
CD-300(G)/CD-300L(G)
Transmitter Specifications
General Performance
Operating Temperature range
-10 ~ 60
Operating Humidity range
0 ~ 95% RH (Non-condensing)
G:0~99% RH(Non-condensing)
Storage Temperature
-30 ~70
CO₂ Measurement
Sensing Method
NDIR (Non-dispersive Infrared)
Measurement Range
0 to 2,000 / 3,000 / 5,000 / 10,000ppm
(Jumper selectable)
(2%/3%/5%/7% are available)
Accuracy
±30ppm ±5%
Response Time(90%)
150 seconds
Sampling Interval
3 sec.
Operation mode selection
Factory calibration mode should be used
(Automatic calibration mode is only Indoor Air
Quality Monitoring).
Two manual recalibration methods are
available with manual recalibration by change
of J2 & J4 or by using TRB-100ST Jig (TRB-
100ST Jig : On Sale)
Electrical Data
Input Power
24VDC ± 20% (3-Wired)
Output Signals
4 ~ 20mA or 2 ~ 10VDC
0 ~ 20mA or 0 ~ 10VDC
, (Jumper selectable
-voltage output or current output)
Dimensions (unit : mm)