Quick Start Guide Flatpack PS System
356803.103, v4-2006-10
7
4. Mount all Flatpack rectifier modules in the power shelves
o Push all rectifiers firmly inwards ⎯ one module at a time, allowing a 2s delay ⎯
to plug them in the shelf. Lock their handles. Refer also to page 3 in this guide
o Mount blanking panels over unused positions
5. Ensure that the MCU controller and all rectifier modules are working: LEDs are ON
o Verify correct operation, by monitoring the modules’ LED lamps and display:
No alarms are present on rectifiers; The MCU controller displays fuse alarms
6. Connect a PC to the PS system (to facilitate operation)
o Plug the correct serial cable between the PC and the MCU controller
o Start WinPower Silver on the PC (click on Start>All Programs>Eltek>WinPower Silver)
o Configure equal communication parameters on the MCU and the PC.
Refer to chapter “
Installing WinPower Silver ⎯ PC Application
”, page 9, if required
7. Measure and adjust DC output voltage
o Read the DC output voltage on the controller’s display
o With a multi-meter, measure the DC output voltage at the most accessible point, e.g.
between the common DC rail and the lower connection of one of the priority load MCBs
o If required, adjust the voltage using the controller’s front keys or via WinPower Silver
8. Verify the alarm relays are working correctly (alarm relay test)
o Run the alarm relay test using the controller’s front keys (refer to page 8) or via
WinPower Silver (click the “General Information” button; then the “Relay Test” tab)
9. Make sure the System Setup is in accordance with configuration
o Verify system settings using the controller’s front keys or via WinPower Silver
o Use the opportunity to enter site related information, type of batteries, etc. (Click
the “General Information” button; then the “Site Information” tab)
Load Adjustments
Power is ON!
Now, you can begin with stage III, where you will adjust again the output voltage to the
battery voltage, and connect the batteries and the load. Carry out the following:
10. Adjust DC output voltage to equal measured battery voltage
o Measure the battery voltage is within range (check connections have correct polarity)
o Adjust DC output voltage — using the controller’s front keys (refer to page 8) or via
WinPower Silver— to equal the measured battery voltage.
(Important adjustment to avoid arcing when connecting the batteries)
11. Unplug all rectifiers but one, and connect the battery fuses /MCBs
(CAUTION: Have only one rectifier connected, when switching ON the battery fuses.
Thus, avoiding damaging all rectifiers, due to possible incorrect polarity connections, etc.)
o Disconnect all rectifiers but one, by unlocking the handles and pulling them partially
out (fan housing visible). Do NOT physically remove them from the power shelves
o Switch ON all battery fuses or MCBs
12. Adjust DC output voltage again to equal the nominal battery voltage
o Adjust DC output voltage — using the MCU’s front keys or via WinPower Silver — to
equal the nominal battery voltage (or the nominal load voltage, when not using batteries)
13. Plug in again all rectifiers, and verify the rectifiers’ current sharing
o Connect all rectifiers again by pushing them firmly inwards ⎯ Repeat step 4, in stage II
o Wait for about 2 min., and check — reading the LED bar graph on the rectifiers’ font
panel — that each of the rectifiers delivers the same output current. A ±5 % deviation is
acceptable. (Each LED represents 3A approx.)
14. Connect the load breakers and verify that no alarms are displayed
o Switch ON all load MCBs/ fuses
o Verify correct operation: rectifiers and controller display no alarms
Commissioning
Device
hazard
Device
hazard
III