Eltako electronics DSZ12WDZ-3x5A Operating Instructions Manual

CT operated energy meter with settable CT ratio and MID. Maximum current 3x5A. Standby loss 0.5 watt per path only.
Modular device for DIN-EN 60715 TH35 rail mounting. 4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface. The directly measuring two-way three-phase energy meter measures active energy by means of the currents flowing between inputs and outputs. The internal power consumption of 0.5 watt active power per path is neither metered nor indicated.
The active energy will be added dependently on the sign. Energy consumption is displayed with a right arrow
and power supply
with a left Arrow
each over the active bar in the display.
3 phase conductors with max. currents up to 5A must be connected. The inrush current is 10mA. The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power supply.
Power consumption is shown by a bar flashing at a rate of 10 times per kWh. On the right next to the display are the keys MODE and SELECT. Press them to scroll through the menu. First the background lighting switches on. After that, the total active energy per reference and supply, the active energy of the resettable memory per reference and supply as well as the instantane­ous values of power, voltage and current per phase can be displayed.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a bridge over the terminals which are marked with 'JUMPER'. To adjust the CT ratio to the installed transformer remove the bridge and reset the energy meter according to the operation manual.
Then block it again with the bridge.
Adjustable current transformer ratios: 5:5, 50:5, 100:5,
150:5, 200:5, 250:5,
300:5, 400:5, 500:5, 600:5, 750:5, 1000:5, 1250:5 and 1500:5.
Error message (false)
When phase conductor is missing the bar 'false' appears and the corresponding phase conductor is also shown in the display.
Important! Before working on the current transformers disconnect the voltage paths of the energy meters.
Typical connection:
4-wire-connection 3x230/400V
Operating instructions:
The energy will be added dependently on the sign. Positive power in the energy meter stands for energy reference, a negative power for energy supply.
The S0 output can be changed in the menu so that either the energy supply (S0 in), the energy output (S0 out) or the balance thereof (S0 bidi) is trans­mitted.
Two-way three-phase energy meter DSZ12WDZ-3x5A with display and MID approval
GB
28 305 912 - 2
Only skilled electricians may install this electrical equipment otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C. Storage temperature: -25°C up to +70°C. Relative humidity: annual average value <75%.
Menu guidance DSZ12WDZ
EC DECLARATION OF CONFORMITY
File name FQKZ112
Product
Calibrated electronic two-way three-phase energy meter with display and MID approval
CT operated energy meter with settable CT ratio
Type designation DSZ12WDZ-3x5A
Technical data
Rated voltage, extended range 3x230/400V, 50 Hz,
-2O%/+15%
Reference current I
ref
(Limiting current I
max
) 3x5 (6) A
Internal consumption active power 0.5W per path
Display LC display 7 digits,
therefrom 1 digit after the decimal point
Accuracy class ±1% B
Inrush current according to accuracy class B 1OmA
Operating temperature -25/+55°C
Interface Pulse interface S0 according to DIN EN 62053-31,
potential free by opto-coupler,
max. 30V DC/2OmA and min. 5V DC.
impedance 100 Ohm,
pulse length 30ms, 10 Imp./kWh
Terminal cover sealable Terminal cover claps
Protection degree lP50 for mounting in distribution cabines
with protection class IP51
Maximum conductor cross section N and L terminals 16mm
2
,
S0 terminals 6mm
2
EC type examination certificate CH-MI003-08009
Mechanical environmental conditions class M2
Electromagnetic environmental conditions class E2
EC DECLARATION OF CONFORMITY
File name FQKZ112
Product
Calibrated electronic two-way three-phase energy meter with display and MID approval
CT operated energy meter with settable CT ratio
Type designation DSZ12WDZ-3x5A
EC type CH-MI003-08009 examination certificate
ELTAKO GmbH, D - 70736 Fellbach, herewith declares, on their own responsibility
that the energy meter which this certificate refers to, is in accordance with
the foll owing standards:
EN 50470 parts 1 and 3: October 2006 (electronic meters)
CLC/FprTR 50579 Directive 2004/22/EG of the European parliament and of the Council on measuring instruments
Annex I , essential requirements
Annex MI-003 , active electrical energy meters
Conformity Certification body METAS-Cert , no. 1259 assessment body CH-3003 Bern-Wabern
Issuer Eltako GmbH
Hofener Straße 54, D-70736 Fellbach
Ort, Datum Fellbach,14. November 2012
signed Ulrich Ziegler, General Manager
Eltako GmbH
D-70736 Fellbach
+49 711 94350000
www.eltako.com
28/2015 Subject to change without notice.
Must be kept for later use!
We recommend the housing for operating instructions GBA12.