GB
28 032 615 - 1
Single-phase energy meter
WSZ15DE-32A without MID
Only skilled electricians may install this
electrical equipment otherwise there is
the risk of re or electric shock!
Temperature at mounting location:
-20°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity:
annual average value <75%.
Maximum current 32 A. Standby loss 0.4 watt
only.
Modular device for DIN-EN 60715 TH35 rail
mounting. 1 module = 18mm wide and 58mm
deep.
Accuracy class B (1%). With S0 interface.
This single-phase energy meter measures
active energy by means of the current between
input and output. The internal power consumption of 0.4 watt active power is neither
metered nor indicated. Like all meters without
declaration of conformity (e.g. MID), this meter
is not permitted for billing.
Every 30 seconds, the display switches for
5 seconds from the accumulated active energy
in kWh to the momentary consumption in
watts.
1 phase conductor with a max. current up to
32 A can be connected.
If the anticipated load exceeds 50%, maintain an air gap of ½ pitch unit to the devices
mounted adjacently.
If necessary, use spacer DS12.
The inrush current is 20 mA.
The display can only be read when the power
supply is on. However, the consumption is
saved to a non-volatile memory and is displayed immediately after power restoration.
Two N terminals for secure cross wiring of
several counters.
The digital display has 7 digits. Two decimal
places are indicated up to 99999.99 kWh.
Above 100000.0 kWh there is only one decimal
place.
Power consumption is shown by a bar ashing
at a rate of 1000 times per kWh.
Error message
In case of a wrong connection, a LED is blinking
on the display.
Protection degree lP50 for mounting
in distribution
cabines with
protection class IP51
Maximum L terminals 16 mm
conductor N and SO terminals
cross section 1) 6 mm
Recommended torque 2)
Typical connection
L terminals 1,5 Nm
(max. 2,0 Nm)
N and S0 terminals 0,8 Nm
(max. 1,2 Nm)
Mechanical class M1
environmental conditions
Electromagnetic class E2
environmental conditions
1)
The carrying capacity of cables and wires is dened in
DIN VDE 0298-4.
2)
The torques for screw terminals are mentioned in DIN
EN 60999-1.
To avoid damages at the energy meter, the recommended torque values for each terminal must not be
exceeded!
Technical data
Rated voltage 230 V, 50 Hz,
Extended range -2O%/+15%
5 (32) A
Reference current
(Limiting current
Internal consumption 0.4 W
I
ref
I
)
max
Active power
Display active power LC display
7 digits,therefrom
1 or 2 digits after
the decimal point
Accuracy class ±1% B
Inrush current according 2O mA
Must be kept for later use!
We recommend the housing for
operating instructions GBA14.
to accuracy class B
Operating temperature -25/+55°C
Interface potential free by opto-coupler,
max. 30 V DC/2O mA
and min. 5 V DC,
pulse interface S0 according
to DIN EN 62053-31,
impedance 100 ohms,
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
pulse length 30 ms,
2000 Imp./kWh
50/2020 Subject to change without notice.
2
2