Eltako WSZ15DE-32A User guide

GB
Single-phase energy meter
WSZ15DE-32A without MID
Only skilled electricians may install this electrical equipment otherwise there is the risk of re or electric shock!
Temperature at mounting location:
-20°C up to +55°C. Storage temperature: -25°C up to +70°C. Relative humidity: annual average value <75%.
Maximum current 32 A. Standby loss 0.4 watt only.
Modular device for DIN-EN 60715 TH35 rail mounting. 1 module = 18mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface. This single-phase energy meter measures
active energy by means of the current between input and output. The internal power con­sumption of 0.4 watt active power is neither metered nor indicated. Like all meters without declaration of conformity (e.g. MID), this meter is not permitted for billing.
Every 30 seconds, the display switches for 5 seconds from the accumulated active energy in kWh to the momentary consumption in watts.
1 phase conductor with a max. current up to 32 A can be connected.
If the anticipated load exceeds 50%, main­tain an air gap of ½ pitch unit to the devices mounted adjacently. If necessary, use spacer DS12.
The inrush current is 20 mA. The display can only be read when the power
supply is on. However, the consumption is saved to a non-volatile memory and is dis­played immediately after power restoration.
Two N terminals for secure cross wiring of several counters.
The digital display has 7 digits. Two decimal places are indicated up to 99999.99 kWh.
Above 100000.0 kWh there is only one decimal place. Power consumption is shown by a bar ashing at a rate of 1000 times per kWh.
Error message
In case of a wrong connection, a LED is blinking on the display.
Protection degree lP50 for mounting in distribution cabines with protection class IP51
Maximum L terminals 16 mm conductor N and SO terminals cross section 1) 6 mm
Recommended torque 2)
Typical connection
L terminals 1,5 Nm (max. 2,0 Nm) N and S0 terminals 0,8 Nm (max. 1,2 Nm)
Mechanical class M1 environmental conditions
Electromagnetic class E2 environmental conditions
1)
The carrying capacity of cables and wires is dened in
DIN VDE 0298-4.
2)
The torques for screw terminals are mentioned in DIN
EN 60999-1.
To avoid damages at the energy meter, the recom­mended torque values for each terminal must not be exceeded!
Technical data
Rated voltage 230 V, 50 Hz, Extended range -2O%/+15%
5 (32) A
Reference current (Limiting current
Internal consumption 0.4 W
I
ref
I
)
max
Active power Display active power LC display
7 digits,therefrom 1 or 2 digits after the decimal point
Accuracy class ±1% B Inrush current according 2O mA
Must be kept for later use!
We recommend the housing for operating instructions GBA14.
to accuracy class B Operating temperature -25/+55°C Interface potential free by opto-coupler,
max. 30 V DC/2O mA and min. 5 V DC, pulse interface S0 according to DIN EN 62053-31, impedance 100 ohms,
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025 technical-support@eltako.de
eltako.com
pulse length 30 ms, 2000 Imp./kWh
50/2020 Subject to change without notice.