Eltako EVA12-32A User guide

GB
28 032 411 - 2
Energy consumption indicator EVA12-32A with display
Only skilled electricians may install this electrical equipment otherwise there is the risk of re or electric shock!
Temperature at mounting location:
-10°C up to +55°C. Storage temperature: -25°C up to +70°C. Relative humidity: annual average value <75%.
! Note: Select english language!* Maximum current 32 A, standby loss
0.5 watt only.
Modular device for DIN-EN 60715 TH35 rail mounting. 1 module = 18 mm wide, 58 mm deep.
The energy consumption indicator EVA12 uses the current between input and out put to measure active energy in the same way as a single-phase power meter. It saves the consumption parameter in a nonvolatile memory.
Like all meters without declaration of conformity (e.g. MID), this meter is not permitted for billing.
Accuracy conforms to Class B MID (1%) like all Eltako single-phase energy meters, the inrush current is 20 mA.
In this way the energy consumption indicator reproduces exactly the reading on the billing energy meter installed at a different location in the building.
The display is subdivided into 3 elds.
Field 1: This display refers to the
cumulative value in eld 3.
|||| moving slowly to the right = Field 3
shows the cumulative consumption since last reset. This is the display standard mode.
H01 = Field 3 shows the consumption for
the last hour up to H24 = 24 hours ago.
D01 = Field 3 shows the consumption for
the last day up to D31 = 31 days ago.
M01 = Field 3 shows the consumption for
the last month up to M12 = 12 months ago.
Y01 = Field 3 shows the consumption for
the last year up to Y24 = 24 years ago.
Field 2: Instantaneous values of energy
consumption (active power) in watt (W) or kilowatt (kW). The display arrows on the left and right show the automatic change W and kW.
Field 3: Cumulative value in kWh. Dis play
up to 9,999 kWh with 3 decimal digits, from 10 kWh with 1 decimal digit and from 1000kWh without decimal digit.
* Press the left button MODE to scroll down the display options which are shown in eld 1: H01, D01, M01 and Y01 as described above. Finally, press MODE to show the abbreviation of the set language, e.g. GB for English, D for German and F for French.
Press the right button SELECT once within the display options to increment the indicated gure by 1. The corresponding value is indi­cated in eld 3.The last clock hour then becomes the hour before last, etc.
If the active language was selected with MODE, press SELECT to switch to a different language. Exit the new language setting by pressing MODE to activate the setting.
The program returns to the standard display mode automatically if MODE or SELECT are not operated for 20 seconds or if you press both buttons briey simultaneously.
Reset To start saving the values to the nearest hour, we recommend performing a reset at an opportune moment after installation. Hold down the buttons MODE and SELECT simultaneously for a further 3 seconds until RES appears. Then press SELECT briey to reset all memories. Afterwards the program returns automatically to standard display mode.
Error messages
F01 is shown in the display at incorrect
direction of current.
If the voltage drops below 170 V, F02 is
shown on the display.
Typical connection
Technical data
Operating voltage, 230 V, 50 Hz, extended range -20%/+15%
I
Reference current (Limiting current
5 (32) A
ref
I
)
max
Internal power consumption 0.5 W active power
Display active power LC display Accuracy class for ±1% B Inrush current according to 2O mA
accuracy class B Operating temperature -10/+55°C Protection degree lP50 for mounting in
distribution cabines with protection class IP51
Maximum conductor 6 mm cross section
Recommended 0,8 Nm (max. 1.2 Nm) torque
1)
The c arryi ng capaci ty of cable s and wires is dene d
in DIN VD E 0298-4 .
2)
The t orques for s crew termi nals are mentioned in
DIN EN 6099 9-1.
To avoid dama ges at the energy met er, the recommended torque values for each terminal must not be exceeded!
1)
2)
The strain relief clamps of the
terminals must be closed, that
!
means the screws must be tightened for testing the function of the device. The terminals are open ex works.
2
Must be kept for later use!
We recommend the housing for operating instructions GBA14.
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025 technical-support@eltako.de
eltako.com
13/2021 Subject to change without notice.