Eltako DSZ15WD-3x5A User guide

Page 1
GB
and the corresponding phase conductor are indicated on the display
28 305 015 - 1
Three-phase energy meter DSZ15WD-3x5A with display and MID approval
Only skilled electricians may install this electrical equipment otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C. Storage temperature: -25°C up to +70°C. Relative humidity: annual average value <75%.
CT operated energy meter with settable CT ratio and MID. Maximum current 3x5A. Standby loss 0.5 watt per path only.
Modulair device for DIN-EN 60715 TH35 rail mounting in distribution cabinets with IP51 protection class. 4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With SO interface as standard. This three-phase energy meter measures active energy by means of the
current between input and output. The internal power consumption of 0.5 watt active power per path is neither metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 5A can be connected.
The inrush current is 10mA. The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power supply.
Power consumption is shown by a bar flashing at a rate of 10 times per kWh. On the right next to the display are the keys MODE and SELECT. Press them
to scroll through the menu. First the background lighting switches on. The display then shows the total active energy, the active energy of the resettable memory as well as the instantaneous values of consumption, voltage and current per phase.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a bridge over the terminals which are marked with 'JUMPER'. To adjust the CT ratio to the installed transformer, remove the bridge and reset the energy meter according to the the display guide, right on this manual. Then block it again with the bridge. Adjustable current transformer ratios: 5:5, 50:5, 100:5, 150:5, 200:5, 250:5, 300:5, 400:5, 500:5, 600:5, 750:5, 1000:5, 1250:5 and 1500:5.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false' and the corresponding phase conductor are indicated on the display.
Important! Before working on the current transformers disconnect the voltage paths of the energy meters.
Important! Before working on the current transformers disconnect the voltage paths of the energy meters.
Typical connection:
4-wire-connection 3x230/400V
Connect the current transformer terminals on the secondary part to the phase cunductors which are metered. These connections for the voltage supply of the energy meters must be secured according to the local installation regulations.
S0 output
.
Menu guidance
JUMPER
MODE
SELECT
K
K
K
k
L
L
l
k
k
L
l
l
Page 2
Technical data
Rated voltage, extended range 3x230/400V, 50 Hz,
-2O%/+15%
Reference current I
(Limiting current I
ref
) 3x0.05 - 5(6)A
max
Internal consumption active power 0.5W per path Display LC display 7 digits,
therefrom 1 digit after the decimal point Accuracy class ±1% B Inrush current according to accuracy class B 1OmA Operating temperature -25/+55°C Interface Pulse interface S0 according to DIN EN 62053-31,
potential free by opto-coupler,
max. 30V DC/2OmA and min. 5V DC,
impedance 100 ohms,
pulse length 30ms, 10Imp./kWh Terminal cover sealable Terminal cover claps Protection degree lP50 for mounting in distribution cabines
with protection class IP51
Maximum conductor cross section
1)
N and L terminals 16mm2,
S0 terminals and jumper terminals 6mm
Recommended torque
2)
L- and N terminals 1,5Nm (max. 2,0Nm)
S0 terminals and jumper terminals 0,8Nm (max. 1,2Nm)
EC type examination certificate 0120 /SGS0314 The energy meter is used indoors. Mechanical environmental conditions class M1 Electromagnetic environmental conditions class E2
1)
The carrying capacity of cables and wires is defined in DIN VDE 0298-4.
2)
The torques for screw terminals are mentioned in DIN EN 60999-1.
To avoid damages at the energy meter, the recommended torque values for each terminal must not be exceeded!
2
Must be kept for later use!
We recommend the housing for operating instructions GBA12.
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025 technical-support@eltako.de
eltako.com
23/2020 Subject to change without notice.