Elster Solutions ELIR1 Users manual

Litenode™ wireless node
DRAFT
Single load RME-GEN
Installation instructions IL42-5047A
Description
Part of the DimOnOff wireless control technology, Litenode relays are suitable for general purpose lighting control applications that add intelligent functions and networkability to any light fixture. The relay provides continuous retroactive 0 V to 10 V (sink/source) for all types of ballasts and drivers and provide power to external sensors (optional).
• intelligent distributed control, metering, and monitoring
• NEMA C136-41
• 5- and 7-pin with continuous retroactive 0 V to 10 V dimming
Unless otherwise programmed, the relay will turn on the fixture approximately 10 seconds after power is restored to the relay.
The yellow LED will blink when power is properly applied.
Using DimOnOff software, test the communications link with the relay.
Before you install
• This device is to be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult a qualified electrician.
• Use this device only with NEMA C136-41 or C136-10 certified receptacles.
Use authorized utility procedures to install or service this device. Dangerous voltages are present. Disconnect power at the circuit breaker or fuse when servicing, installing, or removing the light fixture. Equipment damage, personal injury, or death may result if safety precautions are not followed.
Litenode™ wireless node 2
DRAFT
Installation
Use authorized utility procedures to install or service this device. Dangerous voltages are present. Disconnect power at the circuit breaker or fuse when servicing, installing, or removing the light fixture. Equipment damage, personal injury, or death may result if safety precautions are not followed.
If you are uncertain about any part of these instructions, consult a qualified electrician.
The node input and output are low voltage (24 VDC). Consult local building codes and regulations for information regarding low-voltage installation.
1 To avoid fire, shock, or death, be sure to turn off power at the circuit breaker or fuse. Verify that power
is off before proceeding.
2 Connect lead wires according to the wiring diagram as follows:
- Line voltage wiring: Remove 5/8-inch (1.6 cm) of insulation from each circuit conductor. Make sure
that the ends of the conductors are straight. Connect lead wires from relay to line per the appropriate wiring diagram as follows. Twist strands of each lead tightly and, with circuit conductors, push firmly into the appropriate wire connector. Screw connectors on clockwise making sure that no bare conductor shows below the wiring connectors. Secure each connector with electrical tape.
- Class II warning: Connect low-voltage wires from relay to fixture per appropriate wiring diagram
as follows. Twist strands of each lead tightly, and with circuit conductors, push firmly into appropriate wire connector. Screw connectors on clockwise, making sure that no bare conductor shows below the wire connectors. Make sure to cap-off unused low-voltage wires. Secure each connector with electrical tape.
3 Restore power at circuit breaker or fuse.
RME-GEN wiring
Line wires on C-136 socket supplied by others
Color Gauge
Line in Black 14
Neutral/line 2 White 14
Line out Red 14
DC control wires on C-136 socket supplied by others
0Vto10V+out Purple 18
0 V to 10 V- ground out Gray 18
Digital in 13 VDC to 30 VDC Orange 18
VCC 24 VDC 50 mA Brown 18
Loading...
+ 2 hidden pages