BK-G..A with Absolute ENCODER indexAE1/Z6 .5BK-G..A with Absolute ENCODER AE2 and
communications module ACM..............5
BK-G..E with electronic index ..............5
Diaphragm gas meters BK with integrated valve5
Maintenance/Removal...................6
Technical data .........................6
Declaration of conformity................7
ATEX legend ...........................8
Contact ...............................8
Safety
Safety
Please read and keep in a safe place
Please read through these instructionscarefully before installing or operating. Following theinstallation, pass the instructions on to the opera-tor. This unit must be installed and commissionedin accordance with the regulations in force. Theseinstructions can also be found at www.docuthek.com.
Explanation of symbols
• , , , ... = Action
▷= Instruction
Liability
We will not be held liable for damages resultingfrom non-observance of the instructions and non-compliant use.
Safety instructions
Information that is relevant for safety is indicated inthe instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualifiedgas technicians. Electrical interventions may only becarried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEMspare parts.
Transport
Diaphragm gas meters are always to be transportedin the upright position. On receipt of the product,check that the delivery is complete (see Part desig-nations). Report any transport damage immediately.
Storage
Diaphragm gas meters are always to be stored in theupright position and in a dry place. Ambient tempera-ture: see Technical data.
GB
GB-1
Page 2
F
NL
I
SK
Checking the usage
m
3
,
-
BK-G..M..
12345678
DE-07-MI002-PTB001class 1,5
NG-47001BM0443 DIN EN 1359:2007
Q
max
Q
min
002545632734 1 imp =^ 0,01 m
3
M12 0102
Diaphragm gas meters BK-G.6 to G5
Residential or commercial diaphragm gas metersBK for recording gas consumption values for naturalgas, town gas, propane and butane, as gases of thefirst to third families pursuant to DIN EN 437:2003(DVGW Code of Practice G260). If used for internalmeasurements which are not subject to statutorytesting, the gas meter is also suitable for hydrogen,nitrogen, air and inert gases.
BK with integrated “Smart Valve”
Not suitable for highly contaminated gases, e.g.town gas.
GB
Potentially explosive atmosphere
Diaphragm gas meters that are labelled with and
(see sticker near the index) are suitable for opera-tion in potentially explosive atmospheres, see page7(Declaration of conformity).
This function is only guaranteed when used under the
specified operating conditions– see page6 (Technicaldata). Any other use is considered as non-compliant.
Type code
CodeDescription
BK-GDiaphragm gas meter
.6
.54
6 06
5
M
C
A
E
B
T
Te
Chekker mechanical indexAbsolute ENCODER index
Indication of volume at base conditions
Temperature conversion:
Flow rate
0.016 – 2.5 m
0.025 – 4 m3/h
0.04 – 6 m3/h
0.06 – 10 m3/h
0.1 – 16 m3/h
0.16 – 25 m3/h
0.25 – 40 m3/h
Mechanical index
Electronic index
mechanical
electronic
Part designations
6
4
3
5
2
1
Diaphragm gas meter BK
Index with index plate Connectors
4Protective caps
52 x thermowells (optional)6Pressure test point with sealing sleeve (optional)
Type label/Index plate
Diaphragm gas meters BK-G..M..
BK-G..M..
DE-07-MI002-PTB001
Q
max
Q
min
M12 0102
3
/h
002545632734 1 imp =^ 0,01 m
class 1,5
12345678
NG-47001BM0443 DIN EN 1359:2007
,
3
3
m
-
Diaphragm gas meters BK-G..A.. with
Absolute ENCODER index
BK-G..A..
ENCODER VALVE Vs
M12 0102
DE-07-MI002-PTB001
class 1,5
002545632734
,
NG-47001BM0443 DIN EN 1359:2007
3
m
-
Diaphragm gas meters BK-G..E
BK-G..E..
Q
max
Q
min
M12 0102
002545632734
DE-07-MI002-PTB001
class 1,5
12345678
The following data is not specified on the type label/
index plate, but can be called up in the menu:– Cyclic volume V,– Specified centre temperature tsp(for meters with
temperature conversion only),– EN 1359 registration number (if available),– Firmware version.
GB-2
Page 3
F
NL
I
SK
Diaphragm gas meters with integrated valve
BK-G..
m
3
VALVE Vx
Valve variants:Vs = Smart ValveVp = bi-stable valve (prepayment meter)Note: up to 12.2011, all valve versions were sim-ply marked with the word VALVE on the type label/index plate.
ATEX identification
BK-G..M, BK-G..C, BK-G..MT, BK-G..CT
Elster GmbH, Strotheweg 1
BK
D-49504 Lotte, Germany
II -/2 G c IIB TX
TÜV 11 ATEX 090370 X
Use as follows:Category: internal: none, external: Category2(Zone1).
Please observe the following to ensure that neitherpersons nor the gas meter are damaged duringinstallation and operation:
–Note the max. allowable operating pressurep
and measuring rangeQlabel/Index plate).
– Note the permitted ambient temperaturetm and
gas temperaturetg, see page2 (Type label/Indexplate) or page 6 (Technical data).
–The gas meter is suitable for mechanical ambient
conditions of Class M1 of Directive 2004/22/EC.For gas meter versions BK..A, BK..E and BK..B,
ClassE2 for electromagnetic ambient conditions
also applies.
–When installing the diaphragm gas meterBK with
integrated valve, make sure that no dirt particlesget into the meter and thus into the valve.
– The yellow sealing sleeve protects the pressure
test point on the gas meter. It may only be openedfor connecting a pressure measuring line.
–Use seals made from tested materials. Elastomer
seals or asbestos-free flat seals from Elster arerecommended.
– For meters resistant to high temperatures, only
use seals tested to be resistant to high tempera-
tures.– Only use the seals once.–For installation and operation, note the applicable
national regulations and the directives of the gassupply company. For Germany, the valid DVGW
Code of Practice G600 (DVGW-TRGI) applies.–The gas meter marked with
in the equipotential bond when being installed ina potentially explosive atmosphere, e.g. by con-necting it to a grounded pipeline. Installation mustbe carried out in accordance with EN60079-14.
–The gas meter marked withmust be protected
from falling parts.
▷If the calibration seal has been damaged or re-
moved, the gas meter is no longer approvedfor measurements which are subject to statu-tory testing.
▷If the gas meter is stored or installed outdoors,
protect the site against rain. Condensing humid-
ity is permitted.
Remove protective caps.
▷
Installation in the horizontal position: connectors
must be pointing upwards.
▷Note direction of flow (arrow).▷The gas meter must not be in contact with ma-
sonry or other parts.
▷Ensure that there is sufficient installation space.▷Ensure unobstructed view of the index.▷
The seal faces on the screw unions must be
clean and damage-free.
GB-3
, see page2 (Type
max.
must be included
max.
GB
Page 4
F
NL
I
SK
▷For the compression of seals and the resulting
12
1
2
3
4
5
1
6
7
2
3
4
5
tightening torques for the screw unions, the sealmanufacturers’ specifications must be observed.
Tightening torques for the recommended flat
seals in conjunction with screw connectorspursuant to DIN 3376-1 and 3376-2, seewww.docuthek.com→Elster-Instromet→Prod-ucts → Gas measuring devices → Diaphragmmeters → Ergänzung für Betriebsanleitung BK,Verschraubungen und Anzugsmomente fürBK-G1,6 bis BK-G25 (Supplement for BK op-erating instructions, Screw unions and tighteningtorques for BK-G1.6 to BK-G25) (D).
Install the gas meter free of mechanical stress.
GB
▷
If a pulse sensor IN-Z6x is used for pulse tap-ping on the gas meter marked with – see Data sheet for pulse sensorIN-Z6x (D, GB)www.docuthek.com→Elster-Instromet→Prod-ucts→ Gas measuring devices→ Diaphragmmeters→ Pulse sensorIN-Z61 and the stand-ardEN 60079-14 (Explosive atmospheres).
Temperature test point
▷
Temperature sensors can be inserted into the
thermowells for measuring the gas temperaturein the meter housing.
1
4
▷
Use corrosion-resistant, seamless precision
2
3
5
steel tube pursuant to DINEN10305-4 (exter-nal diameter 6mm, material E235= 1.0308). Forother materials, use a suitable adapter and notethe Parker/EO recommendations.
▷Install pipes free of mechanical stress.
6
7
8Screw on the union nut by hand as far as it will
go.
▷
At the same time, press the end of the pipe firmlyagainst the stop.
9Mark the position of the union nut and tighten
with about 1½ turns.
Secure each of the temperature sensors using
the capstan screw provided.
Connecting the pressure measuringline
WARNING
In order to ensure that the gas meter is tight:
–The pressure test nipple must not be twisted,
bent, or otherwise manipulated.
– When installing, always secure the pressure test
nipple using a suitable spanner.
▷
Functional safety and reliability are ensured only ifthe material combination of the screw connectorand the pressure line are intermatched.
▷
Only use the olive and the attached union nutsupplied. The olive is secured to the sealingsleeve.
▷
When re-ordering, use original Parker EO pro-gressive ring fittings PSR/DPR.
▷When re-installing, the union nut will be turned
to the original position and then further tightenedthrough approx. 30°.
Once the installation and tightness test are com-
plete, see page4 (Tightness test), protect thepressure test point against external access withthe sealing sleeve and the seal.
Tightness test
▷
Check the pipework for leaks prior to installationof the gas meter, in case the pipework is testedwith a greater test pressure than the max. al-lowable operating pressure pmeter. Otherwise, the installed gas meter maybe damaged.
▷If a valve is integrated in the diaphragm gas me-
terBK, see page2 (Type label/Index plate), thismust be opened for the tightness test.
▷Ensure the customer’s consumers are closed.
GB-4
max.
for the gas
Page 5
F
NL
I
SK
Apply the test pressure slowly to the gas meter.
2
2
BK-G..E with electronic index
For further commissioning of diaphragm gasmeter BK-G..E with electronic index – see Elec-tronic index operating instructions (D, GB) →www.docuthek.com→ Elster-Instromet→ Prod-ucts→ Gas measuring devices→ Diaphragm me-ters→ Smart Metering.
▷If a pressure measuring line has been retrofitted
to the diaphragm gas meter, check this connec-tion for tightness.
3
Diaphragm gas meters BK with integratedvalve
In the event that the diaphragm gas meterBK is fittedwith an integrated valve, see page3 (Diaphragm gasmeters with integrated valve), the gas supply can beconnected or disconnected remotely.Unless otherwise agreed, the valve is open on delivery
GB
as standard.
4 After the tightness test, slowly vent the gas meter. 5 If a pressure measuring line has been retrofitted
to the diaphragm gas meter, protect the pressuretest point against external access with a sealingsleeve and a seal.
WARNING
– The network provider is responsible for the safe
remote shut-down and restart of the diaphragmgas meter.
– The integrated valve does not assume the func-
tions of a safety shut-off valve.
... with valve variantVp
Commissioning
Once the tightness test has been successfully com-pleted, the gas meter is ready for operation.
▷Slowly open the manual valve.
BK-G..M with mechanical index
For pulse tapping, the pulse sensorIN-Z6x can beconnected – see Data sheet for pulse sensorIN-Z6x(D, GB)→ www.docuthek.com→ Elster-Instromet→ Products→ Gas measuring devices→ Diaphragmmeters→ Pulse sensorIN-Z61.
BK-G..A with Absolute ENCODERindexAE/Z6
Interface description for gas meters withENCODER index– see Specification (D, GB)→ www.docuthek.com→ Elster-Instromet→ Prod-ucts→ Gas measuring devices→ Diaphragmmeters→ Smart Metering→ SpecificationM-BUSorSCR+.
BK-G..A with Absolute ENCODER AE andcommunications module ACM
If the diaphragm gas meter BK-G..A is fitted withcommunications module ACM – for further commis-sioning see Communications module ACM M-BUSWIRE, ACM SCR+ WIRE... or Communications mod-ule ACM WAVE SYSTEM RF operating instructions (D,GB, NL) → www.docuthek.com→ Elster-Instromet→Products→ Gas measuring devices→ Diaphragmmeters→ Smart Metering.
▷
Should the diaphragm gas meter BK be orderedwith a valve Vp, but without control electronics to
be complemented by a third party, the technical
data of the control interface is to be requestedfrom Elster GmbH and observed.The manufacturer of the control electronics is
▷
responsible for creating the conditions requiredfor safe operation of the valve. Instructions on
commissioning and operation are to be takenfrom the operating instructions for the control
electronics.
... with valve variantVs (Smart Valve)
WARNING
–Depending on national regulations, a limited and
technically safe gas flow rate in the customer’s
open consumer piping is allowed, see page6
(Technical data).
–Assessment of the non-critical gas flow rate with
regard to amount and duration, which occurswhen the valve is released, is to be defined bythe network provider.
–The minimum operating pressure on the inlet
must not be undershot, see page6 (Technical
data). Otherwise, when the valve is released and
if the customer’s consumer piping is open at the
same time, the valve may be completely opened.
“Smart Valve” valve function
▷
The “Smart Valve” is switched remotely bythe data management system. The valve first
switches to the “Released” position. From the
“Released” position, the valve automatically
switches to the “Open” position, if the down-stream installation is tight.
GB-5
Page 6
F
NL
I
SK
Released
▷
The “Smart Valve” opens an internal bypass and
releases a minimum gas flow into the customer’sclosed consumer piping. Pressure equalizationtakes place between the inlet and outlet sideof the valve.
Open
▷Following pressure equalization, the valve auto-
matically opens by spring force and fully releasesthe gas supply. If consumers of the customer areopen, pressure equalization cannot occur andthe valve remains in the “Released” position andcontinues to release only the minimum gas flowrate of the bypass.
GB
Closed
▷
Thevalveandthebypassare closedin the event
of remote shut-down.
▷All valve positions are kept de-energized.
Maintenance/Removal
Gas meters BK-G1.6 to 25 from Elster are mainte-nance-free.
▷When used for custody transfer measurements,
recalibration must be carried out in accordancewith national directives.
▷
If the screw unions are loosened for maintenancework or retesting, replace the seals.
▷After the gas meter has been removed, immedi-
ately close the connectors with protective caps,in order to prevent an ingress of dirt particles.
WARNING
A certain amount of gas may remain in the gasmeter. Taking into consideration the risk of explo-sion, it is important to adopt safety measures, e.g.:
– Following removal of the gas meter, purge it thor-
oughly with inert gas.
– For transporting the gas meter with gas residue,
use a vehicle with an open or a ventilated loadingarea.
–The indexes must not be opened in an explosion-
hazard area even for maintenance and repair.Opening of the service cover on the electronicindex, e.g. to change the battery, is permitted–see operating instructions for “Electronic indexfor diaphragm gas meters BK..E”.
Technical data
Diaphragm gas meters BK
Gas type: natural gas, town gas, propane and butane,as gases of the first to third families pursuant toDINEN437:2003 (DVGW Code of PracticeG260).Max. allowable operating pressureplabel/index plate.Max. allowable measuring rangeQtype label/index plate.
Transitional flow rate Qt = 0.1 x Q
Max. allowable ambient temperature rangetm, seetype label/index plate.Max. allowable storage temperature range:
-25 to +60°C.Gas temperature tg, where the measuring error stilllies within the error limits set out in the Directive, seetype label/index plate. If no gas temperature tg isspecified on the index plate, tg = tm applies.Cyclic volume V, see type label/index plate.Base temperature tb (for meters with temperatureconversion only), see type label/index plate.Specified centre temperature tsp (for meters with tem-perature conversion only), see type label/index plate.For BK..E.., the cyclic volume V and the specifiedcentre temperaturetsp are not stated on the indexplate, but can be called up in the display using themenu.
Diaphragm gas meters BK with pressure testpoint
Pressure test point: 24° olive fitting to ENISO8434-1,L6x M12x1.5-St.
Diaphragm gas meters BK with explosionprotection
Max. allowable ambient temperature rangetm/gastemperature rangetg: -25 to +55°C; for constraints,see type label/index plate.
Diaphragm gas meters BK with integrated
“Smart Valve”Vs
Not suitable for highly contaminated gases, e.g.town gas.Opening time from closed to open/released state: