Elster BK-G1.6, BK-G2.5, BK-G4, BK-G1.6T, BK-G4T Operating Instructions Manual

...
Page 1
Edition 12.09
F
NL
I
E
SK
D GB F NL I SK
03250886/002
www.docuthek.com
Operating instructions Diaphragm gas meters
BK-G1.6 to BK-G25 and BK-G1.6T to BK-G25T
Translation from the German © 2008 2010 Elster GmbH

Contents

Diaphragm gas meters BK-G1.6 to BK-G25 and
BK-G1.6T to BK-G25T . . . . . . . . . . . . . . . . . . . 1
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
Diaphragm gas meters BK-G1.6 to G25 . . . . . . 2
Type code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Part designations. . . . . . . . . . . . . . . . . . . . . . . . 2
Type label/Index plate. . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Tightness test. . . . . . . . . . . . . . . . . . . . . . . . . .
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . .
Interface for mechanical index . . . . . . . . . . . . . . 3
Interface for Absolute ENCODER index . . . . . . . 3
Diaphragm gas meters BK with integrated
Smart Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Smart Valve valve function . . . . . . . . . . . . . . . . 4
Maintenance/Removal. . . . . . . . . . . . . . . . . . . 4
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . 4
Diaphragm gas meters BK. . . . . . . . . . . . . . . . . 4
Diaphragm gas meters BK with explosion
protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Diaphragm gas meters BK with integrated
Smart Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Declaration of conformity . . . . . . . . . . . . . . . . 5
Diaphragm gas meters BK. . . . . . . . . . . . . . . . . 5
Diaphragm gas meters BK with explosion
protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Safety

Please read and keep in a safe place
Please read through these instructions carefully before installing or operating. Follow- ing the installation, pass the instructions on to the operator. These instructions can also be found at www.docuthek.com.
Explanation of symbols
, 1 , 2 , ... = Action
= Instruction
Liability
We will not be held liable for damages resulting from non-observance of the instructions and non- compliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualied gas technicians. Electrical interventions may only be carried out by qualied electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Transport
Diaphragm gas meters are always to be transported in the upright position. On receipt of the product, check that the delivery is complete (see Part desig- nations). Report any transport damage immediately.
Storage
Diaphragm gas meters are always to be stored in the upright position and in a dry place. Ambient tempera- ture: see Technical data.
GB
GB-1
Page 2
F
NL
I
E
SK

Checking the usage

m
3
,
-
BK-Gx
12 345 6 78
DE-07-MI002-PTB001
002545632734 1 imp =^ 0,01 m
3
class 1,5
NG-47001BM0443 DIN EN 1359:2007
Q
max
Q
min
M09 0102

Diaphragm gas meters BK-G1.6 to G25

Residential or commercial diaphragm gas meters BK for recording gas consumption values for natural gas, town gas, propane and butane, gases of the rst to third families pursuant to DIN EN 437:2003 (DVGW Code of Practice G260). If used for internal measurements which are not subject to statutory testing, the gas meter is also suitable for hydrogen, nitrogen, air and inert gases.
Potentially explosive atmosphere
Diaphragm gas meters that are labelled with and
GB
(see sticker next to the index) are suitable for operation in potentially explosive atmospheres of Category 2G (Zone 1) of Class II 2G c IIB (TÜV 09 ATEX 554884X), see [Declaration of conformity p.5].

Type label/Index plate

Diaphragm gas meters BK
BK-Gx
DE-07-MI002-PTB001
Q
max
Q
min
M09 0102
002545632734 1 imp =^ 0,01 m
class 1,5
12 345 6 78
NG-47001BM0443 DIN EN 1359:2007
,
-
3
3
m
Diaphragm gas meters BK with Absolute ENCODER index and integrated Smart Valve
BK-Gx
EN C OD ER VALV E
M09 0102
DE-07-MI002-PTB001
002545632734
,
NG-47001BM0443 DIN EN 1359:2007
class 1,5
3
m
-
This function is only guaranteed when used under the
specied operating conditions see [Technical data
p.4]. Any other use is considered as non-compliant.

Type code

Code Description
BK Diaphragm gas meter
-G Size
1.6
2.5 4
6 10 16
25
Flow rate
0.016 2.5 m
0.025 4 m3/h
0.04 6 m3/h
0.06 10 m3/h
0.1 16 m3/h
0.16 25 m3/h
0.25 40 m3/h
T With temperature conversion

Part designations

4
2
3
1
1 Diaphragm gas meter BK
2 Index with index plate Connectors 4 Protective caps

Installation

WARNING
Please observe the following to ensure that neither persons nor the gas meter are damaged during installation and operation:
Note the max. allowable operating pressure p
3
/h
and measuring range Q plate p.2].
, see [Type label/Index
max.
Note the permitted ambient temperature tm and
gas temperature tg, see [Type label/Index plate p.2] or [Technical data p.4].
The gas meter is suitable for mechanical ambient
conditions of Class M1 of Directive 2004/22/EC. For gas meters with an Absolute ENCODER index, Class E2 for electromagnetic ambient conditions also applies.
Use seals made from tested materials. Elastomer
seals or asbestos-free at seals from Elster are recommended.
For meters resistant to high temperatures, only
use seals tested to be resistant to high tempera-
tures. Only use the seals once. For installation and operation, note the applicable
national regulations and the directives of the gas
supply company. For Germany, the valid DVGW
Code of Practice G600 (DVGW-TRGI) applies. If the calibration seal has been damaged or re-
moved, the gas meter is no longer approved for
measurements which are subject to statutory
testing.
If the gas meter is stored or installed outdoors, protect the site against rain. Condensing humidity is permitted.
1 Remove protective caps.
Installation in the horizontal position: connectors
must be pointing upwards.
Note direction of ow (arrow).
max.
GB-2
Page 3
F
NL
I
E
SK
The gas meter must not be in contact with ma-
sonry or other parts.
Ensure that there is sufcient installation space. Ensure unobstructed view of the index.
The seal faces on the screw unions must be clean
and damage-free.
For the compression of seals and the resulting tightening torques for the screw unions, the seal manufacturers specications must be observed.
Tightening torques for the recommended at seals
in conjunction with screw connectors pursuant to DIN 3376-1 and 3376-2, see www.docuthek.com
Elster-Instromet Products Gas measuring
devices Diaphragm meters Ergänzung für Betriebsanleitung BK, Verschraubungen und An- zugsmomente für BK-G1,6 bis BK-G25 (Supple- ment for BK operating instructions, Screw unions and tightening torques for BK-G1.6 to BK-G25) (D).
2 Install the gas meter free of mechanical stress.
The gas meter marked with must be included
in the equipotential bond when being installed in a potentially explosive atmosphere, e.g. by con- necting it to a grounded pipeline.
If a pulse sensor IN-Z6x is used for pulse tap- ping on the gas meter marked with see Data sheet for pulse sensor IN-Z6x (D, GB) www.docuthek.com Elster-Instromet Prod- ucts Gas measuring devices Diaphragm meters Pulse sensor IN-Z61 and the standard EN 60079-14 (Explosive atmospheres).

Tightness test

Check the pipework for leaks prior to installation of the gas meter, in case the pipework is tested with a greater test pressure than the max. allowable operating pressure p erwise, the installed gas meter may be damaged.
If a valve is integrated in the diaphragm gas meter BK, see [Type label/Index plate p.2], this must be opened for the tightness test.
Ensure the customers consumers are closed, see [Diaphragm gas meters BK with integrated
Smart Valve p.3].
1 Apply the test pressure slowly to the gas meter.
2
for the gas meter. Oth-
max.

Commissioning

Once the tightness test has been successfully com- pleted, the gas meter is ready for operation.
Slowly open the manual valve.

Interface for mechanical index

For pulse tapping, the pulse sensor IN-Z6x can be connected see Data sheet for pulse sensor IN-Z6x (D, GB) www.docuthek.com Elster-Instromet  Products Gas measuring devices Diaphragm meters Pulse sensor IN-Z61.

Interface for Absolute ENCODER index

Interface description for gas meters with ENCODER in- dex see Specication (D, GB) www.docuthek.com
Elster-Instromet Products Gas measuring
devices Diaphragm meters Encoder index Specication.
Diaphragm gas meters BK with integrated
Smart Valve
In the event that the diaphragm gas meter BK is t- ted with an integrated Smart Valve, see [Type label/ Index plate p.2], the gas supply can be connected or disconnected remotely.
WARNING
The network provider is responsible for the safe
remote shut-down and restart of the diaphragm gas meter:
The Smart Valve does not assume the safety
functions of a safety shut-off valve.
Depending on national regulations, a limited and
technically safe gas ow rate in the customers open consumer piping is allowed, see [Technical data p.4].
Assessment of the non-critical gas ow rate with
regard to amount and duration, which occurs when the valve is released, is to be dened by the network provider.
The minimum operating pressure on the inlet
must not be undershot, see [Technical data p.4]. Otherwise, when the valve is released and if the customers consumer piping is open at the same time, the valve may be completely opened.
GB
After the tightness test, slowly vent the gas meter.
GB-3
Page 4
F
NL
I
E
SK

Smart Valve valve function

The Smart Valve is switched remotely by the data
management system. The valve rst switches to the
Released position. From the Released position, the
valve automatically switches to the Open position, if the downstream installation is tight.
Released
The “Smart Valve” opens an internal bypass and
releases a minimum gas ow into the customers closed consumer piping. Pressure equalisation takes place between the inlet and outlet side of the valve.
Open
Following pressure equalisation, the valve automati-
GB
cally opens by spring force and fully releases the gas supply. If consumers of the customer are open, pressure equalisation cannot occur and the valve remains in the Released position and continues to release only the minimum gas ow rate of the bypass.
Closed
The valve and the bypass are closed in the event of
remote shut-down.
All valve positions are kept de-energised.

Maintenance/Removal

Gas meters BK-G1.6 to 25 from Elster are mainte- nance-free.
When used for custody transfer measurements,
recalibration must be carried out in accordance with national Directives. If the screw unions are loosened for maintenance
work or retesting, replace the seals.
After the gas meter has been removed, immedi-
ately close the connectors with protective caps, in order to prevent an ingress of dirt particles.

Technical data

Diaphragm gas meters BK

Gas type: natural gas, town gas, propane and butane, as gases of the rst to third families pursuant to DINEN 437:2003 (DVGW Code of Practice G260). Max. allowable operating pressure p [Type label/Index plate p.2]. Max. allowable measuring range Q [Type label/Index plate p.2]. Max. allowable ambient temperature range tm, see [Type label/Index plate p.2]. Max. allowable storage temperature range: -25 to +60°C. Gas temperature tg, where the measuring error still
lies within the error limits set out in the Directive, see [Type label/Index plate p.2]. If no gas temperature tg is specied on the index plate, tg = tm applies.
Diaphragm gas meters BK with explosion
protection
Max. allowable ambient temperature range tm/gas temperature range tg: -20 to +55°C, for constraints see [Type label/Index plate p.2].
Diaphragm gas meters BK with integrated
Smart Valve
Opening time from closed to open/released state: 4 s, closing time: 0.5 s. Min. operating pressure: 17.5 mbar. Allowed leakage ow in the customers piping: valve released: max. 13 l/h at 35 mbar, valve closed: max. 5 l/h.
, see
max.
min./Qmax.
, see
WARNING
A certain amount of gas may remain in the gas meter. Taking into consideration the risk of explo- sion, it is important to adopt safety measures, e.g.:
Following removal of the gas meter, purge it thor-
oughly with inert gas.
For transporting the gas meter with gas residue,
use a vehicle with an open or a ventilated loading area.
GB-4
Page 5
F
NL
I
E
SK

Declaration of conformity

Diaphragm gas meters BK

We, the manufacturer, hereby declare that the prod- uct BK, marked with No. DE-07-MI002-PTB001/DE- 07-MI002-PTB002, complies with the requirements of the listed Directives and Standards. Directives:
2004/22/EC (MID)
Standards: DIN EN 1359:2007 (EN 1359:1998 / A1:2006) The relevant product corresponds to the tested type
sample. The production is subject to the surveillance proce-
dure pursuant to 2004/22/EC, Annex D, Physika-
lisch-Technische Bundesanstalt (German National
Metrological Institute), Notied Body 0102.
Elster GmbH
Conformity with Directive 2004/22/EC is declared
by afxing the following markings:
0102
M...
After the M, the year of construction is given.
Diaphragm gas meters BK with explosion
protection
We, the manufacturer, hereby declare that the prod-
uct BK, marked with II 2G c IIB, complies with the
requirements of the listed Directives and Standards.
Directives: 94/9/EC
Standards: EN 13463-1:2001, EN 13463-5:2003 and
EN 1127-1:2007
The production is subject to the conformity assess-
ment procedure pursuant to 94/9/EC, Annex VIII,
Declaration of conformity No. TÜV 09 ATEX 554884 X, TÜV NORD CERT GmbH, Notied Body 0044.
Elster GmbH
GB
= Marking of explosion protection
II = Equipment group ll for general industries (with
the exception of mines)
2G = Equipment category for gases, hazes and va-
pours for Zone 1
c = Constructional safety explosion protection
type
IIB = Explosion group The unit is not a source of heat and therefore not
labelled with a temperature class.
Scan of the Declarations of conformity see
www.docuthek.com
GB-5
Page 6
GB
F
NL
I
E
SK

Contact

Elster GmbH Postfach 129, D-55248 Mainz-Kastel Steinern Straße 19-21, D-55252 Mainz-Kastel