Burner control unit with plug-in spring force connection terminals
Burner control unit BCU 580 controls, ignites and monitors gas
burners in intermittent or continuous operation. It can be used
for gas burners of unlimited capacity which are ignited by pilot
burners. The burners may be modulating-controlled or stagecontrolled. Its fast reaction to various process requirements
makes the BCU suitable for frequent cycling operation.
On industrial furnaces, it reduces the load on the central
furnace control by taking over tasks that relate to the burner,
for example it ensures that the burner ignites in a safe condition
when it is restarted.
The air control on the BCU..F1, F2 or F3 assists the furnace
control for cooling, purging and capacity control tasks.
The burner control unit has an interface via which an air valve
or actuator (IC20, IC40 or RBW) can be controlled for staged
or modulating burner capacity control.
The program status, the unit parameters and the level of the
flame signal can be read directly from the unit. The burners
or a connected control element can be activated manually
using the integrated Manual mode for setting and diagnostic
purposes.
Thanks to the optionally integrated valve proving system, the
valves can be checked for leaks by querying an external gas
pressure switch or it can be checked whether the gas valve
on the inlet side is closed.
Using the BCSoft program, the parameters, analysis and
diagnostic information can be read from a BCU via the
optionally available opto-adapter. All valid parameters are
saved on an integrated parameter chip card. The parameter
chip card can be removed from the old unit and inserted into
a new BCU to transfer the parameters, for example when
replacing the unit.
BCU 580 · Edition 11.155
Page 6
The monitored outputs for the actuator and valves are accommodated in a plug-in power module. This can simply be
replaced if necessary.
Once the plug-in power module has been removed, the parameter chip card and fuses are accessible.
The BCU can be installed on a DIN rail in the control cabinet.
Plug-in connection terminal strips on the BCU make it easier
to install and remove.
The external operator-control unitOCU is available as an
option for the burner control units. The OCU can be installed
in the control cabinet door instead of standard control units.
The program status, flame signal or fault messages can be
read on theOCU. For burner adjustment, the operating points
can be approached conveniently in Manual mode using the
operator-control unit.
The address for the fieldbus communication is set using three
code switches.
The optional bus module BCM500 makes it possible to con-
nect the BCU to a PROFINET network via a fieldbus interface.
Networking via the fieldbus enables multiple BCUs to be con-
trolled and monitored by an automation system (e.g.PLC). The
bus module is prepared for DIN rail installation. It is pushed
on to the BCU from the side.
Thanks to the operator-control unitOCU, display functions and operation of the BCU can be relocated to the control cabinet door.
BCU 580 · Edition 11.156
Page 7
Application
Bogie hearth forging furnace in the metallurgical industry
Intermittent shuttle kiln in the ceramics
industry
Walking beam furnace with overhead firing
BCU 580 · Edition 11.157
Page 8
Application
FCU 500
46
HT
49
50
P
V1V2
VAS
Process control (PCC)
PLC
ϑ1
A
123
38371817
BCU 580..C0F3
µC
10
4
41
42
43
13
14
57
9
5
ϑ2
1.1 Examples of application
1.1.1 Stage-controlled main burner
with alternating pilot burner
Control:
VAG
1
2
VR..L
VAS 1
V4
TZI/TGI
UVS
Main burner ON/OFF or High/Low
The main burner can be started with re-
duced capacity after the operating signal
from the pilot burner has been detected.
The pilot burner is switched off automati-
cally after the main burner has started
up. When the main burner is switched off,
the pilot burner automatically switches
on again. This reduces the main burner
start-up time.
The UV sensor monitors the flame signal
from pilot and main burners.
The BCU provides the cooling and purg-
ing processes.
02–0402–04 06–0806–08
ϑ1
1
ϑ2
2
t
BCU 580 · Edition 11.158
Page 9
Application > Examples of application
V1V2
VAS
Process control (PCC)
FCU 500
PLC
VAG
1.1.2 Stage-controlled main burner with
permanent pilot burner
Control:
Main burner ON/OFF or High/Low
The main burner can be started with
VAS 1
reduced capacity after the operating
signal from the pilot burner has been
detected. Pilot and main burners can be
V4
operated simultaneously. This reduces
the time required by the main burner
for starting up.
The BCU provides the cooling and purg-
ing processes.
HT
P
040402–04 06–0806–08
ϑ1
38371817
BCU 580..C0F3
46
µC
49
50
10
123
ϑ2
A
4
41
1
42
2
43
13
14
57
9
8
5
VR..L
ϑ1
1
ϑ2
2
TZI/TGI
t
BCU 580 · Edition 11.159
Page 10
Application > Examples of application
TZI/TGI
VAS
VAS 1
VAG
IC 40 + BVA
V1
V2
V3
V4
VAS 1
4
10
12
7
16
12
M
µC
BCU 580..C0F2
µC
38371817
123
FCU 500
Process control (PCC)
46
49
50
P
HT
A
ϑ1
9
13
14
15
57
85
53 55 51 52
4
41
42
43
1
2
ϑ2
t
1
2
040402–04 06–0806–08
ϑ1
ϑ2
PLC
1.1.3 Two-stage-controlled main burner
with permanent pilot burner
Control:
Main burner ON/OFF with ignition via
bypass
The main burner can be started with
minimum capacity after the operating
signal from the pilot burner has been
detected. When the operating state is
reached, the BCU issues the Enable signal for the maximum burner capacity.
Pilot and main burners can be operated
simultaneously. This reduces the time required by the main burner for starting up.
The BCU provides the cooling and purg-
ing processes.
BCU 580 · Edition 11.1510
Page 11
Application > Examples of application
FCU 500
HT
P
V1
VAS
Process control (PCC)
ϑ1
A
123
38371817
BCU 580..C0F1
46
µC
49
50
52 53 54 5556
V2
Control:
Main burner continuous
1.1.4 Modulating-controlled burner
VAG
VAS 1
The butterfly valve for air is moved to the
position for minimum capacity in order to
V4
start the main burner. The main burner
is started with minimum capacity after
the operating signal from the pilot burner
PLC
has been detected. The control system
controls the burner capacity via the butterfly valve for air after the operating
state has been signalled. Pilot and main
ϑ2
TZI/TGI
burners can be operated simultaneously.
This reduces the time required by the
main burner for starting up.
4
41
1
42
2
43
13
14
57
9
8
5
M
IC 20 + BVA
040402–04 06–0806–08
ϑ1
1
ϑ2
2
t
BCU 580 · Edition 11.1511
Page 12
Application > Examples of application
1.1.5 Flame control using the temperature
FCU 500..H1
5-8
STM
HT
18
HT
49
HT
49
BCU 580..D
µC
5
BCU 580..D
µC
5
8
8
M
In high temperature systems (temperature >750°C), the flame
may be controlled indirectly via the temperature.
As long as the temperature in the furnace chamber is below
750°C, the flame must be controlled by conventional methods.
If the temperature in the furnace chamber rises above the
spontaneous ignition temperature of the gas/air mixture
(>750°C), the FCU signals to the downstream burner control
units via the fail-safe HToutput that the furnace system is in
High temperature mode(HT). When the HTinput is activated,
the burner control units switch to High temperature mode.
They operate without evaluating the flame signal and their
internal flame control is non-functional.
If the furnace temperature falls below the spontaneous ignition temperature (<750°C), the FCU disconnects the HToutput
from the electrical power supply. As soon as the signal to the
HTinputs of the burner control units is no longer present, the
flame signals are once again monitored by a UVsensor or
ionization electrode.
In the event of a fault in a temperature monitoring component
(e.g. sensor discontinuity, sensor short-circuit) or in the event
of a mains failure, the flame control task is transferred to the
burner control units.
BCU 580 · Edition 11.1512
Page 13
BCU 580
BCM
BCU 580
BCM
BCU 580
BCM
PROFINET
2
1
2
1
2
1
BUS
FCU
P
HT
PLC
Application > Examples of application
1.1.6 PROFINET connection using bus module BCM
The bus system transfers the control signals from the automation system (PLC) to the BCU/BCM for starting, resetting,
controlling the air valve, purging the furnace or for cooling
and heating during operation. In the opposite direction, it
sends operating status, the level of the flame signal and the
current program status.
Control signals that are relevant for safety, such as the safety
interlocks, purge and HTinput, are transferred independently
of the bus communication by separate cables.
BCU 580 · Edition 11.1513
Page 14
Application > Examples of application
PZLPZHPZ
DGDGDG
min
4915 131450
DG
max
µC
DG
46
1
ϑ
2
3
FCU 500..F0
STM
DL
M
VAS
45
pu/2
P
>750°
47 4858
minDLPurge
PZLPDZ
DGDG
VAS
VAS
BCU 580..F3
BCU 580..F3
VR..L
VR..L
1.1.7 ON/OFF rotary impulse control
For processes which require a turndown
of more than 10:1 and/or those which
require heavy circulation of the furnace
atmosphere to ensure a uniform temperature, e.g. heat treatment furnaces
M
operating at low and medium temperatures in the metallurgical industry.
With ON/OFF cyclic control, the capacity
supplied to the process is controlled by
VAS
means of a variable ratio of the operating time to the pause time. In this type of
VAGVAS
control, the burner output pulse frequency always maintains full momentum and
results in maximum convection in the
furnace chamber, even with regulated
heating.
The pneumatic ratio control system con-
trols the gas pressure on the burner proportionally to the air pressure and thus
VAS
VAGVAS
maintains a constant air/gas ratio. At the
same time, it acts as a low air pressure
protection device.
The ignition and monitoring of the pilot/
main burners is ensured by burner control units BCU580.
The centrally checked safety functions
TE
such as pre-purge, tightness test, flow
detector and pressure switch check (gas-
min.
, gas
max.
, air
) are provided by the
min.
FCU500.
BCU 580 · Edition 11.1514
Page 15
Application > Examples of application
PZLPZHPZ
DGDGDG
min
4915 131450
DG
max
µC
DG
46
1
ϑ
2
3
FCU 500..F1
STM
DL
minDLPurge
M
PZLPDZ
VAS
45
pu/2
P
>750°
TC
0°➔90°
53
90°➔0°
54
55
47 4858
VAS
M
VAS
BCU 580..F3
BCU 580..F3
VR..L
1.1.8 Modulating burner control
For processes that do not require heavy
circulation in the furnace, e.g. aluminium
smelting furnaces.
This system is suitable for processes in
M
which infiltrated air may flow into the
furnace through switched off burners.
The capacity can be adjusted continu-
ously by activating the air control valve
(analogue or 3-point step signal).
VAS
The pneumatic ratio control system con-
trols the gas pressure on the burner pro-
VAGVAS
portionally to the air pressure and thus
maintains a constant air/gas ratio. At the
same time, it acts as a low air pressure
protection device.
The ignition and monitoring of the pilot/
main burners is ensured by burner control units BCU580.
VAS
VAGVAS
The centrally checked safety functions
such as pre-purge, tightness test, flow
detector and pressure switch check (gas-
min.
, gas
max.
, air
) are provided by the
min.
FCU500.
DGDG
BCU 580 · Edition 11.1515
VR..L
TE
Page 16
2 Certification
Certified to SIL and PL
For systems up to SIL 3 pursuant to EN 61508 and PL e pursuant to ISO 13849
EU certified pursuant to
– Gas Appliances Directive (2009/142/EC)
Meets the requirements of the
– Low Voltage Directive (2006/95/EC),
– EMC Directive (2004/108/EC)
FM approved
Factory Mutual Research Class: 7400 Process Control Valves.
Designed for applications pursuant to NFPA 85 and NFPA 86.
www.approvalguide.com
Eurasian Customs Union
The product BCU580 meets the technical specifications of the
Eurasian Customs Union.
ANSI/CSA approved
American National Standards Institute/Canadian Standards Association – ANSI Z21.20/CSA C22.2 No. 199
www.csagroup.org – Class number: 3335-01 and 3335-81.
BCU 580 · Edition 11.1516
Page 17
3 Function
3.1 Connection diagram
3.1.1 BCU580..F1 with ionization control in single-electrode
operation
Alternative flame control, see page20 (Flame control).
Detailed connection diagrams for actuators and frequency
converters, see from page71 (Capacity control)
Electrical connection, see page98 (Project planning information)
Explanation of symbols, see page119 (Legend)
I
ϑ1
A
p
u
PZL
GZL
2
Air
HT
P
Air
P70P69
P70ϑ2P70
P71
min
P72P72
P73
1 2 3 4
230V
911
c
121062
61
5 6 7 8
c
464565 66 67 6849 50 51
24V
DC
3,15AT
424143
17 18 37 38
2
1
max. 1 A;
24 V DC,
250 V AC
V4
V3
88
µC
13 14 15 57
53 54 55 56
V2
V1
mA
52
0.6 × I
N
L1
BCU 580..F1
(P40 = 2/3) => 51
0 V+24 V
N
BCU 580 · Edition 11.1517
Page 18
Function > Connection diagram
3.1.2 BCU580..F2
Alternative flame control, see page20 (Flame control).
Detailed connection diagrams for actuators and frequency
converters, see from page71 (Capacity control)
Electrical connection, see page98 (Project planning infor-
mation)
Explanation of symbols, see page119 (Legend)
I
ϑ1
A
Luft
P71
ϑ2
P72P72
Luft
min
(P69 = 13)
P73
p
HT
PP
0,6 × I
u
PZL
GZL
2
P70
P70
N
L1
1 2 3 4
464565 66 67 6849 50 51
52
61
5 6 7 8
c
230V
24V
DC
88
µC
BCU 580..F2
911
c
121062
3,15AT
3,15AT
AUTO
COM
2
1
424143
424143
max. 1 A;
max. 1 A;
24 V DC,
24 V DC,
250 V AC
250 V AC
17 18 37 38
17 18 37 38
V4
V4
V3
V3
V2
13141557
13 14 15 57
LO
HI
53 54 55 56
V2
V1
V1
mA
0 V+24 V
N
BCU 580 · Edition 11.1518
Page 19
Function > Connection diagram
3.1.3 BCU580..F3
Alternative flame control, see page20 (Flame control).
Detailed connection diagrams for actuators, see from
page71 (Capacity control)
Electrical connection, see page98 (Project planning infor-
mation)
Explanation of symbols, see page119 (Legend)
I
ϑ1
A
p
u
PZL
GZL
2
Air
HT
P
Air
P70P69
P70ϑ2P70
P71
min
P72P72
P73
1 2 3 4
230V
911
c
121062
61
5 6 7 8
c
464565 66 67 6849 50 51
24V
DC
3,15AT
424143
17 18 37 38
2
1
max. 1 A;
24 V DC,
250 V AC
V4
V3
88
µC
13 14 15 57
53 54
V2
V1
52
0.6 × I
N
L1
BCU 580..F3
0 V+24 V
N
BCU 580 · Edition 11.1519
Page 20
911
121062
61
1 2 34
ϑ1
5 6 7 8
424143
2
1
NL1
I
I
Z
911
121062
61
1 2 34
ϑ1
5 6 7 8
424143
2
1
NL1
UVS
1
2
3
911
121062
61
1 2 34
ϑ1
5 6 7 8
A
2
1
NL1
0 V
24 V
+ –
0–20 mA
UVD1
1
2
4
3
5
6
911
121062
61
1 2 34
ϑ1
5 6 7 8
A
2
1
NL1
0 V
24 V
+ –
0–20 mA
UVD1
1
2
4
3
5
6
Function > Connection diagram
3.1.4 Flame control
Ionization control in double-electrode operation
UVS control
UVD control
A voltage supply of 24 VDC is required to operate the UV
sensor for continuous operation UVD1.
The 0–20mA current output can be used to display the flame
signal. The cable to the control room must be screened. The
0–20mA current output is not required for normal operation.
Depending on Parameter79, the following connection diagrams apply, see also page69 (Pilot burner).
Alternating pilot burner (Parameter 79=0):
Permanent pilot burner (Parameter 79=1):
BCU 580 · Edition 11.1520
Page 21
Function
▼
3.2 BCU 580 program sequence
Parameters 48 and 49 = 0: High/Low control during operation,
cooling in standby
Example of application, see page10 (Two-stage-controlled
main burner with permanent pilot burner)
Switch on BCU 580
▼
In the event of fault signal: reset
▼
00
PO
A0
H1
02
External actuation of the air valve for purging
External actuation of the air valve for cooling
Pilot burner start-up with ϑ1signal
Wait until the running time has elapsed(P42)
Safety interlocks
Start-up position/standby
▼
Flame simulation check
▼
▼
▼
▼
▼
Safety time 1 t
running,
SA1
ignition in process,
valves V1 and V4 open
▼
If no flame detected:
max. 3 start-up attempts
or fault lock-out
▼
03
04
05
06
07
Flame proving period 1 t
FS1
▼
running(P95)
In the event of flame failure:
fault lock-out
▼
Pilot burner operation signalling contact closes
▼
In the event of flame failure:
restart or fault lock-out
▼
Main burner start-up with ϑ2signal
▼
Wait until the running time has elapsed(P42)
▼
Safety time 2 t
running,
SA2
valves for 1st gas stage (main burner) open.
▼
If no flame detected:
max. 3 start-up attempts
or fault lock-out
▼
Flame proving period 2 t
▼
running(P97)
FS2
In the event of flame failure: fault lock-out
BCU 580 · Edition 11.1521
Page 22
Function > BCU 580 program sequence
08
Main burner operation signalling contact closes,
minimum operating time tB starts(P61)
▼
In the event of flame failure:
restart or fault lock-out
▼
A8
External actuation of the air valve for capacity control
Controlled shut-down via ϑsignals for pilot and main
08
00
If min. operating time tB has elapsed:
operation signalling contact opens,
burners
▼
gas valves close and
running time (P42) starts to elapse
BCU 580 · Edition 11.1522
Page 23
4 Air control
VAS
M
PZLPZHPZ
PZLPDZ
TE
BCU 580..F3
FCU 500..F0
µC
P
DGDGDG
VAS
VAS
VAGVAS
VAS
VR..L
VR..L
DGDG
DG
minDGmax
4915131450
45
474858
>750°
pu/2
ϑ
1
46
2
3
DL
minDLPurge
BCU 580..F3
VAGVAS
VAS
M
PZLPDZ
BCU 580..F3
FCU 500..F0
µC
P
VR..L
VR..L
DGDG
4915 131450
45
47 4858
>750°
ϑ
1
46
2
3
DL
minDLPurge
BCU 580..F3
M
A central protective system such as the FCU500 takes over
air control. It monitors the static air pressure as well as the air
volume required for pre-purge, start-up and after the furnace
has been shut down. The air actuators (BCU..F1= actuators
IC20/40, BCU..F2= RBW actuators, BCU..F3= valve) are actuated for this purpose by the capacity control system of the BCU.
After being enabled by the protective system, the BCU can
start the burners. The capacity is controlled during operation
by an external temperature control system.
BCU 580 · Edition 11.1523
Page 24
V1
IC 20 + BVA
BCU 580..C0F1
µC
38371817
1 2 3
FCU 500
Process control (PCC)
46
49
50
P
HT
A
ϑ1
13
14
57
TZI/TGI
9
8
5
VAS
VAS 1
VAG
V2
V4
M
52 53 54 55 56
4
41
42
43
1
2
ϑ2
PLC
Air control
4.1 Capacity control
4.1.1 BCU..F1/F2
The BCU..F1/F2 activates a control element via the outputs for
capacity control (terminals 53 to56) for purging, cooling or
starting the burner. This control element moves to the required
position for the relevant operating situation.
As soon as there is a purge signal at terminal50 of BCU..F1/
F2, the control element is activated by the outputs for capacity
control to approach the position for pre-purge. The protec-
tive system (e.g. FCU500) starts the pre-purge time if there
is adequate air flow. After the elapse of the pre-purge time,
the control element moves to the ignition position. Once the
protective system (terminal46, safety interlocks) has issued the
enable signal, the pilot and main burners can be started by
the start-up signals at terminals1 and4. The control element
can be activated to control the burner’s capacity dependent
on parameters 48 and49.
Modulating control
Parameter 48 = 3
After the operating signal has been received from the burner
and after expiry of the delay time for the controller enable
signal (parameter44), the BCU issues the controller enable
signal via the output at terminal56. Access to the control element is thus transferred to an external temperature controller
(3-point step). The temperature controller controls the burner
capacity (air volume) on the basis of the required temperature.
Depending on the wiring of the temperature controller, the
actuator may be adjusted between maximum capacity and
ignition capacity or minimum capacity.
Depending on parameter40, an actuator IC20, IC40, IC50
or an actuator with an RBW interface can be actuated via
the outputs for capacity control. Detailed information about
parameter 40, see from page71 (Capacity control).
Staged control
P48 = 0, 1 or 2
Depending on parameters 48 and 49, the control element may
be activated either by the program or externally via the input
at terminal2, see also from page80 (Air actuator control).
BCU 580 · Edition 11.1524
Page 25
BCU 580..C0F3
µC
VAS
VAS 1
VAG
TZI/TGI
VR..L
V1V2
V4
10
UVS
38371817
1 2 3
FCU 500
Process control (PCC)
46
49
50
P
HT
A
4
ϑ2
9
13
14
57
5
41
42
43
ϑ1
1
2
PLC
Air control > Capacity control
4.1.2 BCU..F3
The BCU..F3 activates an air valve for purging, cooling or starting the burner. The required air capacity is released by the
air valve.
As soon as there is a purge signal at terminal 50 of BCU..
F3, the air valve is activated by the output at terminal 10. The
protective system (FCU500) starts the pre-purge time if there
is adequate air flow. After the elapse of the pre-purge time,
the air valve closes for ignition. Once the protective system
(terminal 46, safety interlocks) has issued the enable signal,
the burner can be started by the start-up signal at terminal1.
The gas valves for the 1ststage are opened and the burner is
ignited (on the BCU..C1 after a successful valve check). After
the operating signal has been received from the burner, the
gas valve for the 2
nd
stage opens.
Staged control
P48 = 0, 1 or 2
Depending on parameters 48 and 49, the control element may
be activated either by the program or externally via the input
at terminal2, see also from page80 (Air actuator control).
BCU 580 · Edition 11.1525
Page 26
5 Valve proving system
V2
p
u
V
p1
V1
PZ
p
u
2
The BCU500..C1 is fitted with an integrated valve proving
system. This allows either the tightness of the gas solenoid
valves and the pipework between them to be checked (tightness test) or the closed position of a solenoid valve (proof of
closure function) to be checked.
Once the test has been carried out successfully, the burner
enable signal is issued.
For details, see following chapterTightness test and page33
(Proof of closure function)
5.1 Tightness test
The aim of the tightness control is to identify an inadmissible
leak on one of the gas solenoid valves and to prevent burner
start. Gas solenoid valves V1 and V2 are tested as is the pipework between the valves.
European standards EN 746-2 and EN 676 stipulate tightness
controls for capacities over 1200kW (NFPA 86: from 117kW or
400,000 Btu/h).
The tightness control function satisfies the requirements of
EN1643, EN746-2, ISO13577-2 and NFPA86 for valve proving systems.
BCU 580 · Edition 11.1526
Page 27
VAS
VAS 1
VAG
V1V2
V4
13 1457
PZH
pu/2
45
V
p1
VAS
VAS 1
VAG
V1
V2
V3
V4
VAS 1
13 14 15 57
pu/2
45
PZH
V
p1
Valve proving system > Tightness test
5.1.1 Test instant
Depending on the parameter setting, the tightness control
checks the tightness of the pipework and the gas solenoid
valves before each start-up and/or after each shut-down of
the burner, see page89 (Valve proving system).
The gas line is always safeguarded by a gas solenoid valve
during this check.
Before burner start-up
The valve check is started when the start-up signalϑ1 is present
at terminal1. The BCU checks the tightness of the gas solenoid
valves and the pipework between the valves. The gas line is
always safeguarded by a gas solenoid valve during this check.
The pilot burner is ignited when pre-purge is ended and the
tightness has been checked successfully.
After burner shut-down
After the burner has been shut down, the BCU checks the tightness of the gas solenoid valves and the pipework between
them. Once the test has been carried out successfully, the
next burner start is enabled.
The BCU always conducts a tightness test if mains voltage is
available or if it is reset after a fault lock-out.
An additional bypass/relief valve must be installed in gas
sections with an air/gas ratio control. This ensures that the
test volume Vp1 can be vented during the tightness test with
the air/gas ratio control closed.
BCU 580 · Edition 11.1527
Page 28
Valve proving system > Tightness test
▼
START
V1
tL = P59
V1
tM = P56
p
u
pZ >
2
+
V2
V2
tL = P59
V2
tM = P56
+
Program AProgram B
pZ >
V1V2
–
OK
V2
PZ
pu/2
–
p
u
2
p
z
V1
+
V2
tL = P59
V2
tM = P56
p
u
pZ >
2
–
V1
OK
V1
tL = P59
V1
tM = P56
5.1.2 Program sequence
The tightness test starts by checking the external pressure
switch. If pressure pZ> pu/2, programA starts.
If pressure pZ < pu/2, programB starts, see page29 (Pro-
gram B).
Program A
Valve V1 opens for the opening timet
set in parameter59. V1
L
closes again. During the measurement time tM, the tightness
control checks the pressurepZ between the valves.
If pressurepZ is less than half the inlet pressurepu/2, valveV2
is leaking.
If pressure pZ is greater than half the inlet pressurepu/2,
valveV2 is tight. ValveV2 is opened for the set opening timetL.
V2 closes again.
During the measurement time tM, the tightness control checks
the pressurepZ between the valves.
If pressurepZ is greater than half the inlet pressurepu/2,
valveV1 is leaking.
If pressurepZ is less than half the inlet pressurepu/2, valveV1
is tight.
The tightness test can only be performed if pressurepd down-
stream of V2 is around atmospheric pressure and the volume
downstream of V2 is at least 5× higher than the volume
between the valves.
+
p
u
pZ >
2
–
V1
OK
BCU 580 · Edition 11.1528
V1
V2
–
p
u
pZ >
2
+
V2
OK
Page 29
Valve proving system > Tightness test
START
V1
tL = P59
V1
tM = P56
p
u
pZ >
2
+
V2
+
Program AProgram B
pZ >
V1V2
–
OK
V2
PZ
pu/2
–
p
u
2
p
z
V1
+
V2
tL = P59
V2
tM = P56
p
u
pZ >
2
–
V1
OK
Program B
Valve V2 opens for the set opening timetL. V2 closes again.
During the measurement time tM, the tightness control checks
the pressurepZ between the valves.
If pressurep
If pressure p
>pu/2, valveV1 is leaking.
Z
< pu/2, valve V1 is tight. ValveV1 is opened for
Z
the set opening timetL. V1 closes again.
During the measurement time tM, the tightness control checks
the pressurepZ between the valves.
If pressurep
If pressurep
<pu/2, valveV2 is leaking.
Z
>pu/2, valveV2 is tight.
Z
The tightness test can only be performed if pressurepd down-
stream of V2 is around atmospheric pressure and the volume
downstream of V2 is at least 5× higher than the volume
between the valves.
V2
tL = P59
V2
tM = P56
+
p
u
pZ >
2
–
V1
OK
BCU 580 · Edition 11.1529
V1
V2
tL = P59
tM = P56
–
pZ >
V1
V1
p
u
2
+
V2
OK
Page 30
P
13
144
5
p
u
/2
PZ
ϑ
1
pu/2
PZ
V
p1
V1V2
p
u
p
z
p
d
Valve proving system > Tightness test
▼
5.1.3 Test period tP
Depending on the burner capacity, the tightness of the gas
solenoid valves must be checked in accordance with the relevant application standard, e.g. EN676, EN746, NFPA85
and NFPA86.
The test period tP is calculated from:
– Opening times t
– Measurement times t
for V1 and V2,
L
for V1 and V2.
M
tP [s] = 2 x tL + 2 x t
M
5.1.4 Opening time tL
Standard EN1643:2000 allows a maximum opening time of
3s for the tightness test if the main gas valves are actuated
directly. If gas can flow into the combustion chamber when a
valve is opened, the gas volume must not exceed 0.083% of
the maximum flow rate.
is set using parameter56 to a value between 3 and 3600s–
see page90 (Measurement time Vp1).
The required measurement time tM is calculated from:
Inlet pressure pu [mbar]
Leakage rate QL [l/h]
Test volume Vp1 [l]
Calculation of the test volume – see page30 (Test vol-
ume Vp1)
For one test volume V
between 2gas solenoid valves
p1
Adjustable using parameter56
t
M
[s] =
(
2 x pu x V
p1
Q
L
)
For a large test volume Vp1 with reduced testing time
Adjustable using parameter56
t
M
[s] =
0.9 x pu x V
(
p1
Q
L
)
Conversion into US units– see page117 (Converting units)
Leakage rate
The BCU tightness test ensures that the leakage rate QL is
<0.1% of the maximum flow rate Q
(N)max.
.
5.1.5 Measurement time t
The sensitivity of the tightness control in the BCU can be adjusted for each individual system by adapting the measurement timetM. The longer the measurement timetM, the greater
M
Leakage rate QL
[l/h]
Q
=
[m3/h] x 1000 [l/h]
(N)max.
1000 x 1 [m3/h]
the sensitivity of the tightness control. The measurement time
BCU 580 · Edition 11.1530
Test volume V
p1
Page 31
Valve proving system > Tightness test > Measurement time tM
▼
Test volume Vp1 is calculated from the valve volumeVV, added to the volume of the pipeVR for each additional metre in
lengthL.
V
L
= VV + L x V
p1
R
ValvesPipework
TypeVolume VV [l]DN
VAS 10.25100.1
VAS 20.82150.2
VAS 31.8200.3
VAS 61.1250.5
VAS 71.4401.3
VAS 82.3502
VAS 94.3653.3
VG 100.01805
VG 150.071007.9
VG 200.1212512.3
VG 250.215017.7
VG 40/VK 400.720031.4
VG 50/VK 501.225049
VG 65/VK 652
VG 80/VK 804
VK 1008.3
VK 12513.6
VK 15020
VK 20042
VK 25066
Volume per metre
V
[l/m]
R
The measurement time required for the test volumeVp1 must
be set on the basis of the calculation using parameter56.
For the calculation, see page32 (Calculation examples).
BCU 580 · Edition 11.1531
Page 32
BCU 570..C1
µC
131415
475848
TC
M
>750°
1
2
3
V
p1
VAS 665VAS 665
p
u
= 50 mbar
Q
(N) max.
=
200 m
3
/h
DN65
9.5 m
Valve proving system > Tightness test > Measurement time tM
Calculation examples
2 valves VAS 665,
distance L = 9.5 m,
inlet pressure pu = 50 mbar,
max. flow rate Q
Leakage
rate Q
=
L
Test volume V
see page30 (Test volume Vp1)
= 200 m3/h.
(N)max.
3
200 m
/h x 1000 l/h
1000 x 1 m
= 1.1 l + 9.5 m x 3.3 l/m = 32.45 l
p1
Measurement time for one test volume V
p1
Parameter 70 = 0
t
M
[ s ] =
2 x 50 mbar x 32.45 l
200 l/h
= 16.23 s
Set the next highest value (20s) using parameter56, see
page90 (Measurement time Vp1).
/h
= 200 l/h
3
BCU 580 · Edition 11.1532
Page 33
13
14
ϑ
1
V1V2
45
GZL
Valve proving system
5.2 Proof of closure function
The proof of closure function monitors the function of the gas
solenoid valveV1. The proof of closure function can be activated
using parameter51=4, see page89 (Valve proving system).
A limit switch on gas solenoid valveV1 signals the closed
position of the valve to the BCU (terminal45) for this purpose.
By checking the closed position using the proof of closure
function, the BCU complies with the requirements of NFPA85
(Boiler and Combustion Systems Hazards Code) and NFPA86
(Standard for Ovens and Furnaces).
5.2.1 Program sequence
When the start-up signalϑ1 is received at terminal1, the BCU
checks that valve V1 is in its closed position using the POC
switch. After a timeout time of 10s, a signal from the POC switch
(valve V1 is closed) must be received at terminal45. Otherwise,
the BCU performs a fault lock-out with fault messagec1.
As soon as the BCU has opened valve V1, it queries the open
position of the valve via the POC switch. If a signal is still received at terminal45 from the POC switch after a timeout time
of 10s, the BCU performs a fault lock-out with fault messagec8.
BCU 580 · Edition 11.1533
Page 34
6 BCSoft
The BCSoft engineering tool provides extended access to
theBCU. BCSoft makes it possible to set device parameters on
Windows-based PCs in order to adjust the BCU to the specific
application. In addition, BCSoft provides extended access to
the individual statistics and protocol functions.
In addition to the engineering tool BCSoft, an opto-adapter or
Bluetooth adapter is required to read the device parameters
in and out, see also page106 (BCSoft).
BCU 580 · Edition 11.1534
Page 35
7 Profinet
BCU 580
BCM
BCU 580
BCM
BCU 580
BCM
PROFINET
2
1
2
1
2
1
BUS
FCU
P
HT
PLC
Profinet is a manufacturer-independent, open standard for
industrial Ethernet. It covers the requirements for automation
technology (manufacturing automation, process automation,
drive applications with or without functional safety).
Profinet is a bus variant for fieldbus communication, optimized
for speed and low connection costs.
The basic function of Profinet is the exchange of process and
required data between an IOcontroller (e.g.PLC) and several
distributed IOdevices (e.g.BCU/FCU).
The signals from the IOdevices are read into the IOcontroller
cyclically. There, they are processed and are then output to
the IOdevices again.
In addition to cyclic data exchange, Profinet also provides
acyclic data exchange for events which are not constantly
repeated such as sending parameter settings and configuration data when the IOdevices start up or sending a diagnostic message from the IOdevice to the IOcontroller during
operation. The data read or written acyclically by read/write
services are specified by an index, see page44 (Indexes
for acyclic communication).
The technical properties of an IOdevice are described by the
manufacturer in a device master data file (GSDfile). The GSD
file contains the device image, the communications properties
and all fault messages from the IO device in text form which
are important for the configuration of the Profinet network
and the data exchange. The configuration is completed using
an engineering tool which is supplied by the manufacturer
of the IO controller. Modules defined in the GSD file may be
selected for configuration to include them in the system, see
also page37 (GSD file for PLC configuration).
BCU 580 · Edition 11.1535
Page 36
BUS
FCU
P
HT
56
BCUBCM
L1,
M
ϑ
PROFINET
53555254
90° ➔ 0
0 ➔ 90°
3PS
Temperature
controller
PLC
Profinet
7.1 BCU and bus module BCM
The optional bus module BCM 500 is required to integrate the
BCU in the Profinet system.
Control signals (for start, reset and air actuator control), signal
states from the device inputs and outputs and information
about the device status (operating states, flame signal and
current program step), warnings and faults can be transferred
via the bus module between the BCU (IOdevice) and PLC
(IOcontroller).
Bus module BCM500 has two RJ45 connection sockets for
connection to the fieldbus on its front. The connection sockets
are combined with an internal 2-port switch. This allows the
BCM500 together with the BCU to be integrated in various
network topologies (star, tree or line topology). Requirements
such as Auto Negotiation and Auto Crossover are satisfied.
Safety-related signals and interlocks (e.g. safety interlock) must
be wired independently of the fieldbus communication direct
to the BCU and the protective system (e.g.FCU).
All network components which connect the automation system
and the field devices must be certified for Profinet use.
For information on planning and the structure of a Profibus
network and the components to be used (e.g. cables, lines and
switches), see Profinet Installation Guide at www.profibus.com.
BCU 580 · Edition 11.1536
Page 37
Profinet
7.2 GSD file for PLC configuration
Before commissioning, the Profinet system must be configured
for data exchange using an engineering tool.
The device master data file (GSD) is required for the integration of the BCU in the configuration of the PLC. The GSD file
contains the device image and communications properties of
the BCU. Modules defined in the GSD file may be selected for
configuration to integrate the BCU, see page38 (Modules
for cyclic data exchange).
The GSD file for the bus module can be ordered at
www.docuthek.com. The steps required to integrate the file
are described in the instructions for the engineering tool for
your automation system.
For parameter settings on the BCU and code switch settings
on the BCM, see page96 (Fieldbus communication).
BCU 580 · Edition 11.1537
Page 38
Profinet > GSD file for PLC configuration
▼
7.2.1 Modules for cyclic data exchange
The modules for cyclic data exchange are defined in the GSD
file for the bus module BCM500. All modules required for
cyclic data exchange between the controller and the burner
control units BCU580 are shown in the following table. The
modules are assigned to the slots.
ModuleSlot
Input ad-
dress
Output
address
Inputs/outputs1n...n+2n
Burner 1 flame signal2n
Burner 2 flame signal3n
Status signal4n
Fault and warning signals5n...n+1
Remaining times6n...n+1
Only for BCU..C1. Slot 7 is not transferred with other
device versions.
BCU 580 · Edition 11.1538
Page 39
Profinet > GSD file for PLC configuration > Modules for cyclic data exchange
▼
“Inputs/outputs” module – slot1
The digital input and output signals from the burner control
units BCU560, BCU565 and BCU580 are included in this
module.
Input bytes (device ➔ controller)
The input bytes describe the digital signals which are transferred from the BCU (IOdevice) to the digital inputs of the PLC
(IOcontroller). The digital signals take up 2bytes (16bits).
Bit Byte nByte n+1Byte n+2
Burner 1 oper-
0
ating signal
Burner 2 oper-
1
ating signal
BCU system
2
fault
Max. capacity
reached1)
Min. capacity
reached
1)
menox ONBOOL
FreeBOOL
Air ONFreeBOOL
Format
3Fault lock-out Pre-purge ON FreeBOOL
Safety shut-
4
down
5Warning
6ON
Manual mode
7
1)
Only with three-point step control via bus.
DI ONFreeBOOL
Ready for operation
Burner 2 flame
signal
Burner 1 flame
signal
FreeBOOL
FreeBOOL
FreeBOOL
Output byte (controller ➔ device)
The output byte describes the digital signals which are output
by the PLC (IOcontroller) to the BCU (IOdevice). The digital signals to control the burner control unit BCU occupy 1byte (8bits).
Parallel to the bus communication, terminals 1 to4, 44 and
50 of the BCU can be wired. This allows the BCU to be controlled using the digital signals of the bus communication or
the inputs at the terminals.
In the event that the bus communication is faulty or interrupted
and during the initialization of the bus communication after
switching on, the digital signals are interpreted as“0”. If the
BCU is controlled using the inputs at the terminals during this
time, the normal program runs even if the bus communication
is faulty or interrupted.
Bit Byte nFormat
0 Reset
1Burner 1 start
2 External air ON
1)
1)
1)
BOOL
BOOL
BOOL
3 Pre-purge ONBOOL
4Burner 2 start
1)
BOOL
5 menox ONBOOL
2)
2)
BOOL
BOOL
6 Open control element, three-point step Open
7Close control element, three-point step Close
1)
Parallel to the bus communication, terminals 1 to 4 can be
wired.
2)
Only with three-point step control via bus.
BCU 580 · Edition 11.1539
Page 40
Profinet > GSD file for PLC configuration > Modules for cyclic data exchange
The flame signal for burner1 is transferred from the BCU to
the PLC as an analogue value using this module. The flame
signal occupies one byte with values from 0 to255 (=flame
signal from 0 to 25.5µA).
The flame signal for burner2 is transferred from the BCU to
the PLC as an analogue value using this module. The flame
signal occupies one byte with values from 0 to255 (=flame
signal from 0 to 25.5µA).
This module transfers the status signals from the BCU to
thePLC. The status signals occupy one byte (0to255). Every
status signal is allocated a code. The allocation is described
in the code table “GSD Codes BCU580”.
Bit Byte n
Data
type
FormatValue
0
1
2
3
Status signalsByteDEC
4
5
0 – 255
(see
Code table “GSD_
Codes_BCU580.xlsx”
at
www.docuthek.com)
6
7
BCU 580 · Edition 11.1540
Page 41
Profinet > GSD file for PLC configuration > Modules for cyclic data exchange
▼
“Fault and warning signals” module (device ➔
controller)– slot5
The fault and warning signals are transferred from the BCUto
the PLC using this module. The fault and warning signals occupy one byte each (0to255).
The allocation of the output codes to the fault and warning
signals is described in the code table “GSD Codes BCU580”.
The same allocation table applies to the fault signals and the
warning signals.
This module transfers the remaining times of various processes
from the BCU to thePLC. The remaining time occupies 2bytes.
Bit Byte nByte n+1
Data
type
FormatValue
0
1
2
3
Remaining timesWordDEC
4
0 – 6554
(0 – 6554 s)
5
6
7
BCU 580 · Edition 11.1541
Page 42
Profinet > GSD file for PLC configuration > Modules for cyclic data exchange
▼
“Remaining times of the valve proving system” module
(device➔controller)– slot7
Only for BCU..C1.
The module in BCU..C0 contains no information.
This module transfers the remaining time of the valve prov-
ing system from the BCU..C1 to thePLC. The remaining time
occupies 2bytes.
The valve check runs parallel to other time-related processes,
e.g. pre-purge. To display the remaining time of the valve
proving system separately, it is transferred separately.
Only for BCU..F2: terminal53 is used as an input.
Bit 6 has no function.
Terminal 68
Free
Terminal 42
Terminal 43
Terminal 55
Terminal 56
Terminal 57
Free
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
1)
BOOL
BOOL
BOOL
BOOL
BOOL
BCU 580 · Edition 11.1543
Page 44
Profinet > GSD file for PLC configuration
7.2.2 Indexes for acyclic communication
With the help of acyclic communication between the PLC
(IOcontroller) and BCU/FCU (IOdevices), it is possible to read
information on parameters, statistics and fault history on
an event basis (e.g. using system function block Siemens
FSB52RDREC).
The available data records differ in terms of their indexes.
The contents and description of the indexes are described in
the code table “GSD Codes BCU580” (download from www.
docuthek.com).
BCU 580 · Edition 11.1544
Page 45
8 Program step/status
▼
1)
DISPLAY
00
A0
P0
H0
01
A1
H1
A
A
A
02
A2
H2
03
A3
04
A4
H4
H5
06
A6
07
A7
Program step/status
Initializing
Cooling
2)
Pre-purge
Delay
Burner pause time t
Pre-ventilation
Delay
Approaching minimum capacity
Approaching maximum capacity
Approaching ignition capacity
Valve check
Safety time 1
Safety time 1
Delay
Flame proving period 1 t
Flame proving period 1 t
Burner 1 operation
Burner 1 operation
Delay
Delay
Safety time 2
Safety time 2
Flame proving period 2
Flame proving period 2
BP
2)
2)
2)
2)
FS1
FS1
BCU 580 · Edition 11.1545
Page 46
Program step/status
1)
DISPLAY
08
A8
H8
U I
– –
1)
In Manual mode, two dots blink on the display.
2)
Air actuator (control element/valve) is open.
Program step/status
Burner 2 operation
Burner 2 operation
Delay
Remote control with OCU
Data transfer (programming mode)
Device Off
BCU 580 · Edition 11.1546
Page 47
9 Fault signalling
▼
Fault message (blinking)
Burner 1 flame simulation
No flame after safety time 1
Flame failure during flame proving period1t
Flame failure during burner 1 operation
Burner 2 flame simulation
Flame failure during safety time 2
Flame failure during flame proving period 2
Flame failure during burner 2 operation
Too many remote resets
Too many restarts
Too many restarts for burner 2
Controller enable output (terminal 56)
Simultaneous activation (terminals 51 and 52)
Actuator wiring (terminals 52 – 55)
Actuator feedback (terminal 52)
Simultaneous Min./Max. bus command
Non-fail-safe parameters (NFS) inconsistent
Fail-safe parameters (FS) inconsistent
Mains voltage
Faulty parameterization
Incompatible bus module
Power module defective
FS1
DISPLAY
01
02
03
04
05
06
07
08
10
11
12
20
21
22
23
24
30
31
32
33
35
36
Description
Flame simulation/flame signal before ignition
No flame formation to end of 1st safety time
Flame failure during operation
Flame simulation/flame signal before burner2 start
No flame formation to end of 2nd safety time
Flame failure during operation
Remote reset activated >5× in 15min.
> 5 restarts in 15 minutes
> 5 restarts in 15 minutes
Controller enable output incorrectly connected/supplied with
power from an external source
“Maximum capacity” and “Ignition capacity” position feedback
from butterfly valve set simultaneously
Faulty wiring of terminals 52 to 55
Maximum or ignition capacity is not constantly signalled back to
terminal52
“Open actuator” and “Close actuator” bus signals set simultaneously
NFS parameter range is inconsistent
FS parameter range is inconsistent
Operating voltage too high/low
Parameter set contains illegal settings
Device fuse F1 is defective
Leak found on inlet valve
Leak found on outlet valve
Reversed valve connection
Remote reset input activated >25s
Minimum timing cycle not observed
Faulty feedback signal of the control element position for ignition
capacity
Faulty wiring for multi-flame control
Flame amplifier error/device error
Error in processing internal data
Error at digital inputs
Error at digital outputs
Error when checking the SFR
Error when reading the EEProm
Error when writing to the EEProm
Shut-down without application error
Position for minimum capacity has not been reached after 255s
Position for maximum capacity has not been reached after 255s
Position for ignition capacity has not been reached after 255s
Bus module fault
Incorrect or defective PCC
Valve not closed
BCU 580 · Edition 11.1548
Page 49
Fault signalling
Fault message (blinking)
POC valve closed
Air monitor “no flow” state
Low air pressure
Low air pressure
Air flow during pre-purge
Waiting for connection
Invalid address
Invalid configuration
Invalid network name
Controller in STOP position
Burner 1 flame simulation
No flame after safety time 1
Flame failure during flame proving period 1
Flame failure during burner 1 operation
Burner 2 flame simulation
Flame failure during safety time 2
Flame failure during flame proving period 2
DISPLAY
8
0
1
2
,
4
,
6
,
8
P
0
1
2
3
4
A 1
A 2
A 3
A4
A 5
A 6
A 7
Description
Valve not open
Fault Air monitor “no flow” state check
Fault Air monitor operating check
3
,
5
,
Low air pressure during program step 2, 3, 4, 5, 6, 7 or8
7
,
Air flow failure during pre-purge
BCU waiting for connection to controller
Invalid or incorrect address set on bus module
The bus module has received an incorrect configuration from the
controller
Invalid network name or no address allocated in the network
name
Controller in STOP position
Burner 1 flame simulation while air valve open
No flame during safety time 1 while
Flame failure during flame proving period1 while
Flame failure during burner 1 operation while
Burner 2 flame simulation while
No flame during safety time 2 while
Flame failure during flame proving period2 while
air valve open
air valve open
air valve open
air valve open
air valve open
air valve open
Flame failure during burner 2 operation
BCU 580 · Edition 11.1549
A8
Flame failure during burner 2 operation while
air valve open
Page 50
10 Parameters
▼
Any changes to parameters will be saved to the parameter chip card.
NameParameter Value rangeDescription
Burner 1 FS1 flame signal switch-off
threshold
Burner 2 flame signal switch-off
thresholdFS2
Flame control04
High temperature operation06
Burner 1 start-up attempts07
Burner 2 start-up attempts08
010 – 20
020 – 20
0
1
2
3
4
5
6
7
8
0
2
3
1
2
3
1
2
3
Burner 1 FS1 flame signal switch-off threshold in µA
Burner 2 FS2 flame signal switch-off threshold in µA
Ionization
UVS
UVD
Ionization1 and UVS 2
Ionization1 and UVD 2
UVS 1 and ionization 2
UVD 1 and UVD 2
UVD 1 and ionization 2
UVD 1 and UVS 2
Off
Intermittent operation with UVS
Safety time during operation190; 1; 2Time in seconds1
Capacity control40
Running time selection41
Running time420 – 250
3
4
5
6
0
1
2
3
5
0
1
2
3
Off
Burner 1
Burner 2
Burner 1 and burner 2
Max. 5× in 15min. for burner1
Max. 5× in 15min. for burner2
Max. 5×
Off
With IC 20
With IC 40
With RBW
With air valve
Off; checking the positions for minimum/
maximum capacity
On; for approaching the positions for minimum/maximum capacity
On; for approaching the position for maximum capacity
On; for approaching the position for minimum capacity
Running time in seconds
if parameter 41 = 1, 2 or 3
in 15 min. for burner1 and burner2
Factory default
settings
BCU..F0 = 0
BCU..F1 = 1
BCU..F2 = 3
BCU..F3 = 5
0
0
30
BCU 580 · Edition 11.1551
Page 52
Parameters
▼
NameParameter Value rangeDescription
Low fire over-run43
Controller enable signal delay time tRF
Air actuator control48
Air actuator can be activated ex-
ternally on start-up
Air actuator in the event of fault50
Valve proving system51
Relief valve (VPS)52
440 – 250Time in seconds0
49
0
1
2
3
4
5
6
7
8
9
10
0
1
2
3
4
0
1
0
1
0
1
2
3
4
2
3
4
Off
Up to minimum capacity
1 s
2 s
3 s
4 s
5 s
10 s
20 s
30 s
40 s
Opens on external activation
Opens with gas stage 1
Opens with operating signal
Controller enable following operating sig-
nal or in standby
Opens with V4 pilot burner
Cannot be activated
Can be activated externally
Cannot be activated
Can be activated externally
Off
Tightness test before start-up
Tightness test after shut-down
Tightness test before start-up and after
shut-down
Proof of closure function
V2
V3
V4
Factory default
settings
1
0
0
1
0
2
BCU 580 · Edition 11.1552
Page 53
Parameters
▼
NameParameter Value rangeDescription
3
Measurement time Vp156
Valve opening time 1 tL1592 – 25Time in seconds2
Minimum operating time tB610 – 250Time in seconds0
Minimum pause time tBP620 – 3600Time in seconds0
Operating time in Manual mode67
Function of terminal 5068
Function of terminal 5169
Function of terminal 6570
Function of terminal 6671
Function of terminal 6772
Function of terminal 6873
5 – 25
30 – 3600
0
1
23
24
0
8
13
0
8
0
8
20
0
8
21
0
8
22
Time in seconds
in 5s steps
in 10s steps
Unlimited
5 minutes
Purge with Low signal
Purge with High signal
Off
AND with emergency stop (trm.46)
Max. capacity position feedback (IC40/
RBW)
Off
AND with emergency stop (trm.46)
Off
AND with emergency stop (trm.46)
LDS ignition position check
Off
AND with emergency stop (trm.46)
Multi-flame control (MFC) start-up condi-
tions
Off
AND with emergency stop (trm.46)
Multi-flame control (MFC) operating condi-
tions
Factory default
settings
10
1
24
0
0
0
0
0
BCU 580 · Edition 11.1553
Page 54
Parameters
NameParameter Value rangeDescription
Capacity control (bus)75
0
1
2
3
4
5
Off
MIN. to MAX. capacity; standby in position
for MIN. capacity
MIN. to MAX. capacity; standby in CLOSED
position
IGNITION to MAX. capacity; standby in
CLOSED position
MIN. to MAX. capacity; standby in position
for MIN. capacity; burner quick start
IGNITION to MAX. capacity; standby in
Factory default
settings
0
CLOSED position; burner quick start
Password770000 – 9999Four-digit number code1234
Burner application78
Pilot burner79
Fieldbus communication80
0
1
2
3
4
5
0
1
0
1
2
Burner 1
Burner 1 with pilot gas
Burner 1 and burner 2
Burner 1 and burner 2 with pilot gas
Two-stage burner 1
Burner 1 and two-stage burner 2
With shut-down
In continuous operation
Off
With address check
No address check
2
0
1
Safety time 1 tSA1942, 3, 5, 10Time in seconds5
Flame proving period 1 tFS1950 – 20Time in seconds2
Safety time 2 tSA2962, 3, 5, 10Time in seconds5
Flame proving period 2 tFS2970 – 20Time in seconds2
BCU 580 · Edition 11.1554
Page 55
Parameters
10.1 Scanning the parameters
During operation, the 7-segment display shows the program
step/status.
All the parameters of the BCU can be scanned in numerical
order by repeatedly pressing the Reset/Information button
(for 1s).
The parameter display is ended 60seconds after the last time
the button is pressed or by switching off theBCU.
The BCU indicates when the mains switch has been
switched off. The parameters cannot be scanned when the
BCU is switched off or when a fault message is displayed.
10.2 Flame control
The BCU is fitted with a flame amplifier which evaluates whether
an adequate flame signal is supplied by the burner using an
ionization electrode or UV sensor.
10.2.1 Switch-off threshold of the flame amplifier
Burner 1 FS1 flame signal switch-off threshold
Parameter 01
The sensitivity at which the burner control unit detects a flame
at burner1 can be set using parameter01.
In the case of UV control, this value can be increased, should
the burner to be monitored be influenced by other burners
for example.
During start-up
If the measured flame signal falls below the set value (2 to
20µA) during the start-up after elapse of safety time1, the BCU
performs a safety shut-down with subsequent fault lock-out
or up to two further start-up attempts. The number of start-up
attempts can be defined using parameter07, see page60
(Burner 1 start-up attempts).
During operation
If the measured flame signal falls below the set value (2 to
20µA) during operation after elapse of the safety time during
operation (parameter19), the BCU performs a safety shut-down
with subsequent fault lock-out or a restart. The restart function
can be defined using parameter09, see page67 (Restart).
Burner 2 flame signal switch-off thresholdFS2
Parameter 02
The sensitivity at which the burner control unit detects a flame
at burner2 can be set using parameter02.
In the case of UV control, this value can be increased, should
the burner to be monitored be influenced by other burners
for example.
BCU 580 · Edition 11.1555
Page 56
Parameters > Flame control
10.2.2 Flame control
Parameter 04
Parameter 04 = 0: flame control is performed with an ioniza-
tion electrode.
Parameter 04 = 1: flame control is performed with a UV sensor
for intermittent operation (UVS).
Parameter 04 = 2: flame control is performed with a UV sensor
for continuous operation (UVD).
Parameter 04 = 3: burner 1 flame control is performed with
an ionization electrode. Burner2 flame control is performed
with a UV sensor for intermittent operation(UVS).
Parameter 04 = 4: burner 1 flame control is performed with
an ionization electrode. Burner2 flame control is performed
with a UV sensor for continuous operation(UVD).
Parameter 04 = 5: burner 1 flame control is performed with
a UV sensor for intermittent operation(UVS). Burner2 flame
control is performed with an ionization electrode.
Parameter 04 = 6: burner1 and burner2 flame control is
performed with a UV sensor for intermittent operation(UVS)
on each burner.
Parameter 04 = 7: burner 1 flame control is performed with
a UV sensor for continuous operation(UVD). Burner2 flame
control is performed with an ionization electrode.
Parameter 04 = 8: burner 1 flame control is performed with
a UV sensor for continuous operation(UVD). Burner2 flame
control is performed with a UV sensor for intermittent operation(UVS).
and restarted automatically after an operating time of 24hours.
The restart does not meet the requirements of EN298 for UV
sensor continuous operation because the required self-test
(at least once per hour) is not performed while the burner is
operating.
This shut-down and subsequent restart are performed in the
same way as a normal controlled shut-down. This process
is controlled independently by the BCU and therefore it must
be checked whether the industrial process permits the pause
in heat supply it creates.
UV sensor for continuous operation
The reaction times of the BCU and UV sensor for continuous
operation are coordinated so that the set safety time during
operation (parameter 19) is not extended.
UV sensor for intermittent operation
For intermittent operation, the operating state of the complete
system is limited to 24h pursuant to EN298. To meet the requirement for intermittent operation, the burner is shut down
BCU 580 · Edition 11.1556
Page 57
t
SA1
t
Z
0406020300
t
t
FS1
t
SA2
0708
t
FS2
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
1
43
2
49
HT
Parameters > Flame control
▼
10.2.3 High temperature operation
Parameter 06
Operation of firing systems at temperatures above 750°C
The BCU..D1 and BCU..D2 have a fail-safe input with the function “High temperature operation”. If firing systems are operated above 750°C, the system is considered to be an item
of high temperature equipment (see EN746-2). Here, flame
control must be in operation until the furnace wall temperature
has exceeded 750°C.
Below 750°C, the flame is monitored by conventional means
(UV sensor or ionization electrode). In High temperature mode
(>750°C), the flame may be controlled via the temperature
using a safety temperature monitor(STM) in order to increase
the system’s availability. This means that no incorrect flame
signals, e.g. signals from a UV sensor which interprets reflected
UV radiation as extraneous signals, may lead to faults.
FCU 500..H1
5-8
STW
HT
18
BCU 580 · Edition 11.1557
BCU 580..D
µC
HT
49
BCU 580..D
HT
49
8
5
µC
8
5
M
When the HT input is activated (terminal49), the burner control
unit reverts to High temperature mode, i.e.: the BCU operates
without evaluation of the flame signal. The safety function
of the device-internal flame control system is deactivated.
In High temperature mode, the gas valves are opened and
the burners are started as usual without monitoring the presence of a flame.
The precondition for this operating mode is that an external
flame supervision device ensures the presence of the flame
in a fail-safe manner indirectly via the temperature. For this
purpose, we recommend a safety temperature monitor with
double thermocouple (DIN 3440). The flame must be monitored again by conventional means (UV sensor or ionization
electrode) in the event of sensor discontinuity or short-circuit,
failure of the safety temperature monitor or power failure.
Only if the temperature at the furnace wall has exceeded
750°C may voltage be applied to the HT input (terminal 49)
so as to activate High temperature mode.
Page 58
06070808
t
t
SA2tFS2
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
49
t
SA1
t
Z
04020301
t
FS1
t
W
L1
HT
08
08
t
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
49
L1
HT
Parameters > Flame control > High temperature operation
▼
If the temperature in the furnace chamber drops below 750°C,
Parameter 06 = 3 (BCU..D1)
the HTinput must be disconnected from the electrical power
supply and the furnace must then be operated with flame
control.
The BCU then responds, depending on setting:
Parameter 06 = 0
The High temperature mode function is switched off. Flame
control takes place dependent on the setting in parameter 04
(by ionization electrode, UVS sensor or UVD sensor).
Parameter 06 = 2 (BCU..D1)
Despite the HT input having been disconnected from the elec-
trical power supply, the burner remains in operation. The BCU
performs flame control again (recommended in the case of
ionization control or UV control withUVD).
The BCU switches off the burner once the HT input has been
disconnected from the electrical power supply and restarts
with flame simulation check (recommended in the case of UV
control withUVS).
BCU 580 · Edition 11.1558
Page 59
t
04 04
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
49
L1
HT
t
0808
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
49
L1
HT
Parameters > Flame control > High temperature operation
If no flame signal is present when High temperature mode is
deactivated, the burner control unit performs a fault lock-out,
regardless of parameter06.
Fault, pilot burner
Fault, main burner
BCU 580 · Edition 11.1559
Page 60
t
SA1
t
Z
04
t
0002
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
t
SA1
t
Z
t
SA1
t
Z
t
00 02
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
Parameters
10.3 Behaviour during start-up
10.3.1 Burner 1 start-up attempts
Parameter 07
Up to three start-up attempts are possible in certain conditions. In accordance with EN746-2, a restart may be conducted only if the safety of the installation is not impaired.
Note the requirements of the standards!
For FM and CSA approved units, it is only possible to select
one start-up attempt (P07=1).
This parameter defines the maximum number of possible
start-up attempts of burner1.
If no flame is detected during start-up, an immediate fault
lock-out (P07=1) or up to two additional start-up attempts
(P07=2,3) are performed depending on parameter07.
Parameter 07 = 1: 1 start-up attempt.
Parameter 07 = 2, 3: two or three start-up attempts.
If no flame is formed during the start-up so that at the end of
the safety timet
no flame signal is detected, the BCU closes
SA1
the gas valves and repeats the start-up. Each start-up attempt
begins with the parameterized start-up behaviour.
If the safety timet
elapses without a flame signal having
SA1
been detected, even after the last parameterized start-up
attempt, this will result in a BCU safety shut-down with sub-
sequent fault lock-out. The fault message 04 will flash in the
BCU display depending on the burner operating mode.
If no flame is formed during the start-up so that at the end of
the safety timet
no flame signal is detected, this will result
SA1
in a BCU safety shut-down with subsequent fault lock-out. The
fault message 04 will flash in the BCU display depending on
the burner operating mode.
BCU 580 · Edition 11.1560
Page 61
t
SA1
t
Z
04 06 02 03 00
t
t
FS1
t
SA2
06
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
1
43
2
t
SA2
t
SA2
t
SA2
t
SA1
t
Z
0406020300
t
t
FS1
06
t
W
06
06
05
05
t
W
5
13
V1
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
1
43
2
Parameters > Behaviour during start-up
10.3.2 Burner 2 start-up attempts
Parameter 08
Up to three start-up attempts are possible in certain conditions. In accordance with EN746-2, a restart may be conducted only if the safety of the installation is not impaired.
Note the requirements of the standards!
For FM and CSA approved units, it is only possible to select
one start-up attempt (P08=1).
This parameter defines the maximum number of possible
start-up attempts of burner2.
If no flame is detected during start-up, an immediate fault
lock-out (P08=1) or up to two additional start-up attempts
(P08=2,3) are performed depending on parameter08.
Parameter 08 = 1: 1 start-up attempt.
Parameter 08 = 2, 3: two or three start-up attempts.
If no flame is formed during the start-up so that at the end
of the safety timet
no flame signal is detected, the BCU
SA2
closes the gas valves and repeats the start-up. Each start-up
attempt begins with the parameterized start-up behaviour.
If the safety timet
elapses without a flame signal having
SA2
been detected, even after the last parameterized start-up
attempt, this will result in a BCU safety shut-down with sub-
sequent fault lock-out. The fault message 06 will flash in the
BCU display depending on the burner operating mode.
If no flame is formed during the start-up so that at the end of
the safety timet
no flame signal is detected, this will result
SA1
in a BCU safety shut-down with subsequent fault lock-out. The
fault message 06 will flash in the BCU display depending on
the burner operating mode.
BCU 580 · Edition 11.1561
Page 62
BCU 570
µC
V1
V2
14 1513
BCU 570
µC
V1
V2
V3
14 1513
Parameters > Behaviour during start-up
▼
10.3.3 Burner application
Parameter 78
This parameter enables the BCU to be adjusted to various
burner applications. In addition, an optional pilot gas valve
(V3) can be parameterized via which the burner is started with
a defined ignition capacity.
Parameter 78 = 0: burner 1. Two valves (V1,V2) are included for
the burner. These are connected to the valve outputs (terminals
13 and14). Valves V1 and V2 are opened in parallel to start
the burner in order to release the gas supply to the burner.
03020104
9
13
1
14
2
15
3
5
17-18
t
BP
SA1
FS1
t
t
t
Parameter 78 = 1: burner 1 with pilot gas. Three valves (V1, V2
andV3) are included for a burner with a pilot gas valve. These
are connected to the valve outputs (terminals 13, 14 and15).
Valves V1 and V3 open to start the burner. The burner is started
with a limited ignition capacity using gas valveV3. After the
elapse of the safety time t
(program step02), valve V2 opens.
SA1
Valve V3 limits the ignition capacity. After the elapse of the
flame proving period t
(program step04), it is closed again.
FS1
For this application, it must be ensured that the flame proving
period (P95) is set to a value ≥2s.
03020104
9
13
1
14
2
15
3
5
17-18
t
BP
BCU 580 · Edition 11.1562
SA1
FS1
t
t
t
Page 63
V1
V2
V4
14 5713
0302H10607
2
1
3
9
14
15
13
5
17-18
t
t
FS1
t
SA1
t
SA2
H8
t
FS2
08
t
RF
8
4
57
1
2
V1
V2
V3
V4
14 15 5713
0302H10607
2
1
3
9
14
15
13
17-18
t
t
FS1
t
SA1
t
SA2
H8
t
FS2
08
t
RF
4
57
5
8
1
2
Parameters > Behaviour during start-up > Burner application
▼
Parameter 78 = 2: burner 1 and burner 2. Three valves (V1,
V2 andV4) are included for a modulating burner with a pilot
burner. These are connected to the valve outputs (terminals
13, 14 and57). Valves V1 and V4 open to start the pilot burner.
Gas valveV2 releases the gas supply to the main burner.
For this application, it must be ensured that the flame proving
period(P97) is set to a value ≥2s.
Parameter 78 = 3: burner 1 and burner 2 with pilot gas. In this
application, the burner has an additional pilot gas valveV3.
The valves are connected to the valve outputs (terminals 13,
14, 15 and57). Valves V1 and V4 open to start the pilot burner.
The burner is started with a limited ignition capacity using
gas valveV3. After the elapse of the safety time t
step06), valve V2 opens (terminal14). Pilot gas valveV3 is
closed again after the elapse of the flame proving period t
(program step07).
BCU 580 · Edition 11.1563
(program
SA2
FS2
Page 64
BCU 570
µC
V1
V2
V3
14 1513
BCU 570..C1F1
µC
V1
V2
V3
V4
14 15 5713
040302H506
2
1
3
9
14
15
13
5
17-18
t
t
FS1
t
SA1
07
t
SA2
08
t
FS2
4
57
8
2
1
Parameters > Behaviour during start-up > Burner application
Parameter 78 = 4: two-stage burner 1. Three valves (V1, V2
andV3) are included for a two-stage-controlled burner. These
are connected to the valve outputs (terminals 13, 14 and15).
The burner can be started with minimum capacity. When the
operating state (program step04) is reached, the BCU issues
the Enable signal for the maximum burner capacity to gas
valveV2.
03020104
9
13
1
14
2
15
3
1
5
17-18
Parameter 78 = 5: burner 1 and two-stage burner2. In this
application, the burner has an additional pilot gas valveV3.
The valves are connected to the valve outputs (terminals 13,
14, 15 and57). Valves V1 and V4 open to start the pilot burner.
The burner is started with a limited ignition capacity using
gas valveV3. ValveV2 (terminal14) can be opened with the
operating signal (program step08) in order to operate burner2
at maximum capacity.
t
t
SA1
BP
t
FS1
t
BCU 580 · Edition 11.1564
Page 65
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2
5
13
V1
57
V4
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
1
43
2
17-18
Parameters > Behaviour during start-up
10.3.4 Safety time 1 t
SA1
Parameter 94
During the safety time 1 t
SA1
It can be set to 2, 3, 5 or 10s.
, the flame (pilot flame) is ignited.
10.3.5 Flame proving period 1 t
FS1
Parameter 95
Flame proving period 1 (t
) can be parameterized to enable
FS1
the flame on burner1 to stabilize after the elapse of safety
time1. Only when the flame proving period has elapsed will
the next program steps be initiated by the BCU. The flame
proving period can be set between 0 and 20s.
88
11
46
1
9
13
57
5
4
14
8
41
42
43
17-18
L1
ϑ1
V1
V4
1
ϑ2
V2
2
1
2
t
Safety time1 starts with the application of the ϑ1signal (terminal1). The valves open at the start of safety time1. The fuel
supply to burner1 is released so that a flame can form. If no
04 06 07 08 02 03 00
t
Z
t
SA1
t
FS1
t
SA2
t
FS2
flame is detected at the end of safety time1, the valves are
closed again. Depending on parameter07 (Burner1 start-up
attempts), the BCU reacts either with an immediate safety
shut-down with fault lock-out (P07=1) or with one or two additional start-up attempts (P07= 2 or3). The BCU will complete
a maximum of three start-up attempts.
Safety time1 must be determined on the basis of current national standards and regulations. The burner application and
the burner capacity are the main criteria for this.
If the ϑ1signal (terminal1) drops out during safety time1, the
valves will not be switched off until the end of safety time1.
BCU 580 · Edition 11.1565
Page 66
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2
5
13
V1
57
V4
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
1
43
2
17-18
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2
5
13
V1
57
V4
1
14
V2
2
ϑ1
ϑ2
8
4
88
1
46
11
9
41
42
L1
1
43
2
17-18
Parameters > Behaviour during start-up
10.3.6 Safety time 2 t
SA2
Parameter 96
During the safety time 2 t
, the flame on burner2 (main
SA2
flame) is ignited. It can be set to 2, 3, 5 or 10s.
10.3.7 Flame proving period 2 t
FS2
Parameter 97
Flame proving period 2 t
can be parameterized to enable
FS2
the flame on burner2 to stabilize after the elapse of safety
time2. Only when the flame proving period has elapsed will
the next program steps be initiated by the BCU. The flame
proving period can be set between 0 and 20s.
Safety time2 starts with the application of the ϑ2signal (terminal4). Valve V2 opens at the start of safety time2. The fuel
supply to burner2 is released so that a flame can form. If no
flame is detected at the end of safety time2, the valves are
closed again. Depending on parameter08 (Burner2 start-up
attempts), the BCU reacts either with an immediate safety
shut-down with fault lock-out (P08=1) or with one or two additional start-up attempts (P08= 2 or3). The BCU will complete
a maximum of three start-up attempts.
Safety time2 must be determined on the basis of current
national standards and regulations. The burner application
and the burner capacity are the main criteria for this.
If the ϑ1signal (terminal1) drops out during safety time2, the
valves will not be switched off until the end of safety time2.
BCU 580 · Edition 11.1566
Page 67
04
t
t
SB
04
88
ϑ
1
46
11
9
5
13
V1
57 V4
L1
42
41
t
SA
t
Z
04 04 02 03 01
t
t
FS
t
W
t
SB
1x
>2 s
88
ϑ
1
46
9
5
13
V1
57 V4
11
L1
42
41
Parameters
▼
10.4 Behaviour during operation
10.4.1 Restart
Parameter 09
This parameter determines whether the BCU initiates an im-
mediate safety shut-down with fault lock-out or an automatic
restart after a flame failure during operation. Excessive restarts
(max.5) can also be detected.
In accordance with EN746-2, a restart may be conducted
only if the safety of the installation is not impaired. A restart is
recommended for burners which occasionally display unstable
behaviour during operation.
The precondition for an automatic restart is that the burner
can restart (as intended in all operating phases). In this case,
it must be ensured that the program sequence started by the
BCU matches the application.
Parameter 09 = 0: Off.
If a flame failure occurs during operation (minimum operating
time of 2s), the valves are closed and the operation signalling
contact is opened within the safety time during operationtSB.
The burner control unit then attempts to restart the burner
once. If the burner does not function, a safety shut-down with
fault lock-out occurs. The display blinks and shows the fault
message.
A safety shut-down with subsequent fault lock-out takes place
in the event of flame failure during operation.
Parameter 09 = 1: burner 1. The restart function is active.
BCU 580 · Edition 11.1567
Page 68
06
05
07
08
08
t
t
SA2
t
FS2
1x
t
W2
t
SB
>2 s
88
5
13
V1
57
V4
1
14
V2
2
ϑ1
ϑ2
8
4
1
46
11
9
41
42
L1
1
43
2
17-18
Parameters > Behaviour during operation > Restart
Parameter 09 = 2: burner 2.
Taking into account national standards and requirements,
it must be clarified whether the option may be used.
Parameter 09 = 5: max. 5× in 15 min. for burner2.
Parameter 09 = 6: max. 5× in 15 min. for burner 1 and2.
If a flame failure occurs during operation (minimum operating time of 2s), valve2 is closed and the operation signalling
contact is opened within the safety time during operationtSB.
The burner control unit then attempts to restart burner2 once. If
burner2 does not function, a safety shut-down with fault lockout occurs. The display blinks and shows the fault message.
Parameter 09 = 3: burner 1 and burner 2.
Parameter 09 = 4: max. 5× in 15min. for burner1. The restart
function is active and is also monitored. In certain conditions,
it is possible that the restart function is repeated continuously without a safety shut-down with subsequent fault lockout being performed. The BCU has a safety shut-down with
subsequent fault lock-out option if more than 5restarts are
performed within a period of 15minutes.
BCU 580 · Edition 11.1568
Page 69
Parameters > Behaviour during operation
10.4.2 Minimum operating time tB
Parameter 61
A minimum operating time (0 to 250s) may be defined to
ensure that the heating equipment operates stably.
If the minimum operating time is active, burner operation
will be maintained until the set time has elapsed even if the
start-up signal fails.
The minimum operating time starts as soon as the program
step for operation/controller enable (display08) has been
reached.
If the start-up signal drops out before the start of operation/
controller enable, e.g. during pre-purge, the burner control
unit reverts directly to the start-up position (standby) and the
burner is not ignited.
The minimum operating time can be cancelled by switching
off the BCU or if a safety shut-down occurs.
10.4.3 Pilot burner
Parameter 79
04060708020300
P79 = 1
t
SA1
t
FS1
t
SA2
t
FS2
88
1
4
9
13
14
15
57
ϑ1
ϑ2
V1
V2
V3
V4
t
If a burner with a pilot burner is used, this parameter can be
used to define whether the pilot burner is shut down 1second
before the end of the second safety timet
or operates
SA2
continuously.
Parameter 79 = 0: with shut-down.
Parameter 79 = 1: in continuous operation.
BCU 580 · Edition 11.1569
Page 70
Parameters
10.5 Safety limits
Parameter19 can be used to adjust the safety limits (safety
time during operation) to the system requirements.
10.5.1 Safety time during operation
Parameter 19
Parameter 19 = 1; 2: time in seconds.
The safety time during operation is the time that the BCU needs
to stop the fuel supply after a flame failure during operation or
an interruption at the safety current inputs (terminals 45 to51
and 65 to68). The safety time can be set to 1 or 2s. Prolonging the safety time during operation increases the installation
availability in the case of brief-duration signal fades (e.g. fades
of the flame signal).
In accordance with EN298, the maximum reaction time to a
flame failure must not exceed 1s. In accordance with EN746-2,
the safety time of the installation during operation (total closing
time) may not exceed 3s.
The requirements of national standards and regulations must
be satisfied.
BCU 580 · Edition 11.1570
Page 71
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
PE
L1
N
3PS
3 2 116674812 1115 13
S3S4
S11
S10
0°
90°
M
IC 20
PE
S1S2
90°➔0°
0°➔90°
S1
MinMax
Parameters
▼
10.6 Air control
10.6.1 Capacity control
Parameter 40
The BCU is fitted with an interface for connecting air actuators.
The BCU..F1/F2 activates a control element via the outputs for
capacity control (terminals 53 to56) for purging, cooling or
starting the burner. This control element moves to the required
position for the relevant operating situation.
The BCU..F3 activates an air valve for purging, cooling or starting the burner via the output at terminal10. The required air
capacity is released by the air valve.
Using parameter40, you can set which actuator is used for
capacity control (actuators IC20, IC40, RBW or air valve).
Parameter 40 = 0: Off; no capacity control (no air actuator).
Parameter 40 = 1: with IC20.
The interface is configured to the requirements of actuators
IC20, IC20..E, IC50 or IC50..E.
Alternatively, comparable three-point step actuators may be
used.
IC20
The positions for maximum capacity, ignition capacity and
minimum capacity can be set using the actuator. It is checked
whether the relevant position has been reached using terminal52. If the position is not reached within the timeout
time of 255s, the BCU will display fault message A , A or
A (maximum, ignition or minimum capacity not reached), see
page47 (Fault signalling).
BCU 580 · Edition 11.1571
Page 72
0°90°
S4
S1S3
Burner control range
Butterfly valve setting range
Control range
Move to ignition position
Ignition pos.
Min.
pos.
Closed
pos.
Max. pos.
MIN
MIN
MIN
MAX
MAX
MAX
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
3PS
0°90°
S4
S2
S1S3
Burner control range
CLOSED
Butterfly valve setting range
Control range
Move to ignition position
Ignition pos.
Max. pos.
OPEN
S4
S2
Min.
pos.
Closed
pos.
MIN
MIN
MAX
MAX
Parameters > Air control > Capacity control
▼
In the event of a fault, the actuator is moved to the position set
via camS4 for minimum capacity via the output at terminal54.
The control system is enabled for operation via the controller enable output (terminal56). During the controller enable
procedure, the actuator can be adjusted infinitely between the
positions for maximum and minimum capacity by an external
three-point step controller or using bus signals. There is no
timeout active in this case.
If bus control is active (parameter75), the controller enable output (terminal56) has a different function. The wiring between
the BCU and the 3-point step controller can be adjusted so
that the control range of the actuator is between the positions
for maximum and ignition capacity.
The minimum position which can be reached is the closed
position.
Manual mode
In Manual mode, the actuator can be moved between the
positions for maximum and minimum capacity in 3-point step
operation. No timeout is active when approaching these positions. The controller enable output (terminal56) is not active
and not checked.
BCU 580 · Edition 11.1572
Page 73
20 19 183 2 1674812 11
S3
S4
S1 0
OUT
0°
➔
90°
0°
90°
90°
➔
0°
IC 20..E
S1
S2
517
++
IN
OK
R
R
PE
A
D
A
D
R
1 2 3 4 5 6
ON
µC
131516
M
PE
L1
N
S1
MinMax
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
3PS
Parameters > Air control > Capacity control
▼
IC20..E
procedure, the actuator can be adjusted infinitely between the
positions for maximum and minimum capacity by a controller
(0(4)–20mA, 0–10V) using the setpoint device on terminals 17
and18 or the bus signal. There is no timeout active in this case.
If bus control is active (parameter75), the controller enable output (terminal56) has a different function. The wiring between
the BCU and the 3-point step controller can be adjusted so
that the control range of the actuator is between the positions
for maximum and ignition capacity.
Manual mode
In Manual mode, the actuator can be moved between the
positions for maximum and minimum capacity in 3-point step
The positions for minimum capacity, maximum capacity and
ignition capacity can be set using the actuator. When the
appropriate position has been reached, this information is
signalled back via terminal52. If no signal is received that the
position has been reached within the timeout time of 255s,
a safety shut-down of the BCU will be performed and a fault
message (A , A or A ) will be displayed, see page47 (Fault
signalling). In addition, the actuator will be moved to the set
position for minimum capacity using the output at terminal54.
The control system is enabled during operation via the controller enable output (terminal56). During the controller enable
BCU 580 · Edition 11.1573
operation. No timeout is active when approaching these positions. The controller enable output (terminal56) is not active
and not checked.
Page 74
N
19 1816 15 1412 11 108 75 42 1
A
AC
D
DC
mA
L N
22 21 20
53 54 55 56
52
123464565 66 67 6849 50 51
17 18 3738
13 14 15
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
t [s]
t [s]
t
1
t
2
t
3
t
4
t
5
t
6
DI 1
DI 2
Purge
Closed
Ignition
High
fire
Parameters > Air control > Capacity control
▼
IC 40
Parameter 40 = 2: with IC40.
To ensure that the actuator IC40 can be operated on the BCU..
F1, P40=2 (capacity control) must be set. The operating mode
of actuator IC40 may be parameterized to11 or27.
of the BCU will be performed. A fault message (A
, A or A )
will be displayed, see page47 (Fault signalling).
If a controller enable is active, the control system is enabled
for operation via the outputs at terminals 53 and55.
Operating mode 11
Operating mode 11 allows cyclic operation (ON/OFF and OFF/
Low/High/OFF).
The actuator IC moves to the “High fire” position during the
controller enable procedure. There is no timeout active in
The positions for maximum capacity and ignition capacity
can be set using the actuator. Terminal51 checks whether the
position for maximum capacity has been reached. Terminal52
checks the position for ignition capacity. If the position is not
reached within the timeout time of 255s, a safety shut-down
BCU 580 · Edition 11.1574
this case.
BCUIC40 (operating mode 11)
Signal at
terminal
PositionButterfly valve position
5553
OFFOFFClosedClosed
ONOFFIgnition
ONON
High-fire
rate
Minimum/Ignition capacity
High-fire rate
OFFONPurgeMaximum capacity
Page 75
t [s]
t [s]
t
1
t
2
t
3
t
4
t
5
t
6
0–20
mA
DI 1
DI 2
Purge
Closed
Ignition
Parameters > Air control > Capacity control
▼
Operating mode 27
During the controller enable procedure, the actuator IC40
can be adjusted infinitely between the positions for maximum
and minimum capacity using its analogue input (terminals18
and19). There is no timeout active in this case.
BCUIC40 (operating mode 27)
Signal at
terminal
PositionButterfly valve position
5553
OFFOFFClosedClosed
ONOFFIgnition
ONON0 – 20 mA
Minimum/Ignition capacity
Any position between mini-
mum and maximum capacity
OFFONPurgeMaximum capacity
Fault
In the event of a fault, there will be no signal at terminals
53 and55 so that the actuator moves to the closed position.
When approaching the closed position, no timeout of 255s
is active since no feedback input is checked. This may result
in a situation where the program is continued in the case of
a request for the closed position, without the butterfly valve
being closed. The outputs at terminals56 (controller enable)
and54 (closed position) on the BCU are non-functional and
are not activated.
Manual mode
In Manual mode, no external controller is enabled. The actuator can be moved to the positions for maximum capacity or
ignition capacity by the user. 3-point step operation is not possible. No timeout is active when approaching these positions.
BCU 580 · Edition 11.1575
Page 76
N
M
R B W
90°➔0°
0°➔90°
L1
RBW
COM
HI
LO
AUTO
53 54 55 56
52
1234645
65
66
67
68
17183738
131415
BCU 580..F2
3,15AT
µC
4950 51
88
c
c
4142
24VDC
56911
1210762
61
N
M
+ F -
0°➔90°
L1
mA
A
D
OUT
+
-
RBW
COM
HI
LO
AUTO
53 54 55 56
52
1234645
17183738
131415
BCU 580..F2
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
65
66
67
68
4950 51
PLC
Parameters > Air control > Capacity control
▼
RBW
Parameter 40 = 3: with RBW.
The actuator can be moved to the positions for maximum ca-
pacity (contact COM to HI) and minimum capacity (contact COM
to LO) using the interface and by closing the various contacts.
reports that it has reached the position for minimum capacity via a signal to terminal52. The simultaneous activation
of terminals 51 and52 results in a fault lock-out of theBCU.
If parameter 41 = 0, the system monitors the movement to
the positions for maximum and minimum capacity with a
timeout time of 255s. Reaching the relevant position immediately triggers the program continue switch conditions. If
reaching the position is not signalled within the timeout time
of 255s, a safety shut-down of the BCU will be performed.
A fault message (A or A ) will be displayed, see page47
(Fault signalling).
If parameter 41 = 1, the system does not monitor whether the
positions for minimum and maximum capacity are reached. In
this case, a running time of up to 250s must be defined using
parameter42, see page78 (Running time). The program
continue switch conditions are then controlled dependent on
this time.
If a fault occurs, the actuator is moved to the position for minimum capacity.
Manual mode
In Manual mode, no external controller is enabled during the
The RBW actuator reports that it has reached the position for
controller enable procedure. The actuator can be moved to
the positions for maximum capacity or ignition capacity by
the user. 3-point step operation is not possible. No timeout is
active when approaching these positions.
maximum capacity via a signal to terminal51. The actuator
BCU 580 · Edition 11.1576
Page 77
BCU 580..F3
µC
VAS
VAS 1
VAG
TZI/TGI
VR..L
V1V2
V4
10
9
13
14
57
8
5
Parameters > Air control > Capacity control
Parameter 40 = 5: with air valve.
The positions for maximum capacity and ignition capacity can
be set using the air valve. If the air valve is closed, the ignition capacity is reached, if it is open, the maximum capacity
is reached.
Parameter 42 (Running time) can be used to adjust the behaviour of slow opening and closing air valves so that the
system can be set to ignition position before a start-up is
initiated. Parameter 41 (Running time selection) must be set
to 1 to adjust this behaviour.
See page 78 (Running time) and (78 (Running time selection)).
BCU 580 · Edition 11.1577
Page 78
Parameters > Air control
10.6.2 Running time selection
Parameter 41
Parameter 41 = 0: Off; checking the positions for minimum/
maximum capacity. A signal that the positions for minimum
and maximum capacity have been reached is returned and
monitored with a timeout time of max. 255s. When the position
has been reached, the BCU will initiate the next program step.
Parameter 41 = 1: On; for approaching the positions for minimum/maximum capacity. The Running time set using parameter42 is activated for approaching these positions. After this
time has elapsed, the BCU will initiate the next program step.
Parameter 41 = 2: On; for approaching the position for maximum capacity. The Running time set using parameter42 is
activated for approaching the position for maximum capacity.
After this time has elapsed, the BCU will initiate the next program step. Approaching the position for minimum capacity
is signalled and monitored.
Parameter 41 = 3: On; for approaching the position for minimum capacity. No signal is returned that the position for minimum capacity has been reached. The Running time set using
parameter42 is activated for approaching the position for
minimum capacity. After this time has elapsed, the BCU will
initiate the next program step. Approaching the position for
maximum capacity is signalled and monitored.
10.6.3 Running time
Parameter 42
This parameter can be used to adjust the behaviour of slow
opening and closing air valves. The running time starts when
the air actuator is switched off. A restart of the burner after a
controlled shut-down, a start-up attempt, restart, cooling or
purging is delayed until the end of the running time. After the
running time has elapsed, the burner is started if the start-up
signal(ϑ) is applied.
The time should be adjusted such that the system can be set
to ignition position, i.e. that the air actuator is closed before
a start-up is initiated.
BCU 580 · Edition 11.1578
Page 79
BCU 580..F3
µC
VAS
VAS 1
VAG
TZI/TGI
VR..L
V1V2
V4
10
9
13
14
57
8
5
Parameters > Air control
10.6.4 Low fire over-run
Parameter 43
The low fire over-run (tKN) is applicable to systems with a pneu-
matic air/gas ratio control system and On/Off control. Using
the low fire over-run function reduces the O2 content in the
furnace atmosphere.
00 A8
t
KN
88
L1
11
46
ϑ
1
9
5
13
14 V2
57 V4
2
10
41
1
42
2
43
V1
A
t
Parameter 43 = 0: Off. No low fire over-run is performed. The
gas circuit is closed immediately owing to a quick closing gas
valve in the case of On/Off control. The air circuit is closed
more slowly. The air flowing in during this time increases the
O2 content in the combustion chamber.
Parameter 43 = 1 (only for BCU..F1/F2): up to minimum capacity.
The burner is not immediately switched off after the start-up
signalϑ (terminal1) has been removed. During low fire overrun, the control element is moved to the position for minimum
capacity and the gas valves remain open until the flame fails
or the position for minimum capacity is reached. If the flame
is extinguished, this does not result in a fault.
Parameter 43 = 2, 3, 4, 5, 10, 20, 30 or 40 (only for BCU..F3):
time in seconds. During this time, the gas valve remains open.
The air valve is closed with deactivated start-up signal(ϑ).
This means that the burner is initially adjusted down to low
fire and then switched off completely. Flame control is still
operational. It must be ensured that no excess gas occurs.
10.6.5 Controller enable signal delay time t
RF
Parameter 44 (only on BCU..F1/F2)
The controller enable signal is delayed by 0, 10, 20 or 30 up
to 250s using parameter44.
If the BCU has successfully started the burner, after the elapse
of the safety time and the flame proving period, if parameterized, the controller enable signal to the external temperature
controller is delayed. The BCU shows program statusH8. After
the elapse of the delay timetRF, the burner operation signalling
contact (terminals 17,18) is closed and the controller enable
output (terminal56) activated. The display changes to08.
BCU 580 · Edition 11.1579
Page 80
t
SA1
t
Z
04020300 A0
t
t
FS1
t
SA2
t
FS2
A80607
2
10
∨
53
A
88
ϑ1
46
1
ϑ2
4
11
9
5
37-38
13
V1
1
2
14 V2
14 V3
57 V4
17-18
8
M
t
SA1
t
Z
04020300A0
t
t
FS1
t
SA2
t
FS2
00A000A8A6A7
2
10
∨
53
A
88
ϑ1
46
1
ϑ2
4
11
9
5
37-38
13
V1
1
2
14 V2
14 V3
57 V4
17-18
8
M
Parameters > Air control
▼
10.6.6 Air actuator control
Parameter 48 = 1: opens with gas stage1.
Parameter 48
In cyclic operation, parameters 48 and 49 on BCU..F1, F2 and F3
determine the behaviour of the air actuator during burner start.
Parameter 48 = 0: opens on external activation.
The air actuator opens at the same time as safety timet
SA2
begins and the main burner starts.
This setting together with parameter 49= 0, see page83
(Air actuator can be activated externally on start-up), is required for burners on which the air/gas ratio is controlled by
a pneumatic air/gas ratio control system and which need
to be started at low-fire rate, e.g. on two-stage-controlled
burners, see page10 (Two-stage-controlled main burner
with permanent pilot burner). In this case, activation of the air
actuator during burner start via the input at terminal2 must
be prevented.
External control allows switchover between low fire and high
fire during operation.
BCU 580 · Edition 11.1580
Page 81
t
SA1
t
Z
04020300A0
t
t
FS1
t
SA2
t
FS2
00A000A80607
2
10
∨
53
A
88
ϑ1
46
1
ϑ2
4
11
9
5
37-38
13
V1
1
2
14 V2
14 V3
57 V4
17-18
8
M
t
SA1
t
Z
04020300
t
t
FS1
t
SA2
t
FS2
080607
88
ϑ1
46
1
ϑ2
4
11
9
5
37-38
13
V1
1
2
14 V2
14 V3
57 V4
17-18
8
56
mA
t
SA1
t
Z
04020300A0
t
t
FS1
t
SA2
t
FS2
00A000080607
2
53
A
17-18
M
56
mA
88
Parameters > Air control > Air actuator control
▼
Parameter 48 = 2: opens with operating signal.
This setting is required in the case of two-stage main burners
which are switched ON/OFF via the ϑ2input.
The air valve opens simultaneously with the operating signal
for the main burner. The air valve can be activated externally
via the input at terminal2 for cooling the burner in the start-up
position/standby. This function is not available during burner
start-up and during operation.
Parameter 48 = 3: controller enable following operating signal
or in standby.
This parameter is used to activate modulating capacity control
on BCU..F1 and F2. The controller enable signal is issued via
the output at terminal 56 in the start-up position (standby)
and during operation.
The air actuator can be opened in standby via the input at
terminal2 for this purpose. Cooling is then only possible in
the start-up position/standby. The controller enable signal is
suspended during cooling.
BCU 580 · Edition 11.1581
Page 82
t
SA1
t
Z
A4A2A300A0
t
t
FS1
t
SA2
t
FS2
00A000A8A6A7
2
10
∨
53
A
88
ϑ1
46
1
ϑ2
4
11
9
5
37-38
13
V1
1
2
14 V2
14 V3
57 V4
17-18
8
M
Parameters > Air control > Air actuator control
Parameter 48 = 4: opens with V4 pilot burner.
The air valve opens with the start-up fuel rate. The air valve can
be activated externally via the input at terminal2 for cooling
the burner in the start-up position/standby.
BCU 580 · Edition 11.1582
Page 83
02
00A0
00
t
SA2
A807
04
t
t
FS2
0688
A
37-38
2
10
43
13
5
V1
1
14
V2
1
46
11
9
8
2
4
42
1
2
t
SA1
t
Z
t
FS1
A0
00
03
ϑ
1
ϑ
2
∨
53
M
A2
00A0
00
t
SA2
A8A7
A4
t
t
FS2
A688
A
37-38
2
10
43
13
5
V1
1
14
V2
1
46
11
9
8
2
4
42
1
2
t
SA1
t
Z
t
FS1
A0
00
A3
ϑ
1
ϑ
2
∨
53
M
Parameters > Air control
10.6.7 Air actuator can be activated externally on start-up
Parameter 49
Parameter 49 = 0: cannot be activated.
During start-up, the air actuator remains closed. The air actuator cannot be activated externally.
Parameter 49 = 1: can be activated externally.
The air actuator can be activated externally via the input at
terminal2 during start-up. Parameter48 must be set to0 for
this purpose, see also page80 (Air actuator control).
10.6.8 Air actuator in the event of fault
Parameter 50
This parameter decides whether the air actuator can be ac-
tivated externally via the input at terminal2 in the event of a
fault lock-out.
Parameter 50 = 0: cannot be activated. The air actuator remains closed in the event of a fault lock-out. It cannot be
activated externally via the input at terminal2.
Parameter 50 = 1: can be activated externally. The air actuator
can be activated externally via the input at terminal2 during
a fault, e.g. for cooling.
BCU 580 · Edition 11.1583
Page 84
0°90°
S4
S1S3
Burner control range
Butterfly valve setting range
Control range
Move to ignition position
Ignition pos.
Min.
pos.
Closed
pos.
Max. pos.
MIN
MIN
MIN
MAX
MAX
MAX
PE
L1
N
3 2 116674812 1115 13
S3S4
S11
S10
0°
90°
M
IC 20
PE
S1S2
90°➔0°
0°➔90°
S1
MinMax
YY+
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
Parameters > Air control
▼
10.6.9 Capacity control (bus)
Parameter 75
Controlling the burner capacity using the fieldbus is only pos-
sible with bus module BCM500 connected and enabled (P80=
1 or2).
The output at terminal 56 has a different function.
Parameter 75 = 0: Off. No capacity control possible using
the fieldbus.
Parameter 75 = 1: MIN. to MAX. capacity; standby in position
for MIN. capacity. The control range while the burner is operating is between the positions for minimum capacity(S4) and
maximum capacity(S3). The burner is ignited in the position
for ignition capacity(S1). When the burner is switched off, the
actuator is moved to the position for minimum capacity(S4).
This operating mode can be achieved with an actuator IC20,
RBW or alternatively with a comparable three-point step actuator.
If the air supply is stopped on a heated furnace with the
burner switched off, the controls may be damaged by the
hot furnace atmosphere as a result of the lowest possible
position of the butterfly valve, limited byS4.
IC 20
Switching cam setting for ignition capacity, minimum and
maximum capacity as well as pre-purge and standby:
S1: for ignition capacity of the burner.
S3: for maximum capacity of the burner and pre-purge.
S4: for minimum capacity of the burner and standby.
BCU 580 · Edition 11.1584
Page 85
0°90°
S4
S2
S1S3
Burner control range
CLOSED
Butterfly valve setting range
Control range
Move to ignition position
Ignition pos.
Max. pos.
OPEN
S4
S2
Min.
pos.
Closed
pos.
MIN
MIN
MAX
MAX
PE
L1
N
3 2 116674812 1115 13
S3S4
S11
S10
0°
90°
M
IC 20
PE
S1S2
90°➔0°
0°➔90°
S1
MinMax
Y-
Y+
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
Parameters > Air control > Capacity control (bus)
▼
Parameter 75 = 2: MIN. to MAX. capacity; standby in CLOSED
position. The control range while the burner is operating is between the positions for minimum capacity(S2) and maximum
capacity(S3). The burner is ignited in the position for ignition
capacity(S1). When the burner is switched off, the actuator is
moved to the closed position(S4).
This operating mode can be achieved with an actuator IC20
or alternatively with a comparable three-point step actuator.
If the air supply is stopped on a heated furnace with the
burner switched off, the controls are protected from the
hot furnace atmosphere as a result of the butterfly valve
being in the closed position (limited byS4). Check whether
the burner can cope without cooling in this situation.
IC 20
Switching cam setting for ignition capacity, minimum and
maximum capacity as well as pre-purge and standby:
S1: for ignition capacity of the burner.
S2: for minimum capacity of the burner.
S3: for maximum capacity of the burner and pre-purge.
S4: for the closed position of the butterfly valve and standby.
BCU 580 · Edition 11.1585
Page 86
0°90°
S4
S1S3
Move to ignition position
Burner control range
CLOSED
IGNITION
Butterfly valve setting range
Control range
Ignition pos.Max. pos.
OPEN
Min.
pos.
Closed
pos.
MINMAX
MAX
PE
L1
N
3 2 116674812 1115 13
S3S4
S11
S10
0°
90°
M
IC 20
PE
S1S2
90°➔0°
0°➔90°
S1
MinMax
YY+
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
Parameters > Air control > Capacity control (bus)
▼
Parameter 75 = 3: IGNITION to MAX. capacity; standby in
CLOSED position.
The control range while the burner is operating is between the
positions for minimum capacity(S1) and maximum capacity(S3).
The burner is ignited in the position for minimum capacity(S1).
When the burner is switched off, the actuator is moved to the
closed position(S4).
This operating mode can be achieved with an actuator IC20,
RBW or alternatively with a comparable three-point step actuator.
If the air supply is stopped on a heated furnace with the
burner switched off, the controls are protected from the
hot furnace atmosphere as a result of the butterfly valve
being in the closed position (limited byS4). Check whether
the burner can cope without cooling in this situation.
IC 20
Switching cam setting for ignition capacity, minimum and
maximum capacity as well as pre-purge and standby:
S1: for minimum capacity and ignition capacity of the burner.
S3: for maximum capacity of the burner and pre-purge.
S4: for the closed position of the butterfly valve and stand-
by.
BCU 580 · Edition 11.1586
Page 87
S4
S2
S3
S1
0°90°
Move to ignition position
Burner control range
Butterfly valve setting range
Control range
Max. pos.
OPEN
Ignition
pos.
Reversing direction of rotation
for quick start
Min.
pos.
Closed
pos.
MIN
MIN
MIN
MAX
MAX
PE
L1
N
3 2 116674812 1115 13
S3S4
S11
S10
0°
90°
M
IC 20
PE
S1S2
90°➔0°
0°➔90°
S1
MinMax
S2
Y-
Y+
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
Parameters > Air control > Capacity control (bus)
▼
Parameter 75 = 4: MIN. to MAX. capacity; standby in position
for MIN. capacity; burner quick start.
The control range while the burner is operating is between
the positions for minimum capacity(S4) and maximum capacity(S3). The burner is ignited in the position for ignition capacity(S1). Switching cam S2 (reverse direction of rotation) ensures
that the position for ignition capacity is approached without
pre-purging first (quick start). When the burner is switched off,
the actuator is moved to the position for minimum capacity(S4).
This operating mode can be achieved with an actuator IC20
or alternatively with a comparable three-point step actuator.
If the air supply is stopped on a heated furnace with the
burner switched off, the controls may be damaged by the
hot furnace atmosphere as a result of the lowest possible
position of the butterfly valve, limited byS4. If pre-purge is
active, considerably lower air capacity than the maximum
air capacity will be used for purging.
IC 20
Switching cam setting for ignition capacity, minimum and
maximum capacity and reverse direction of rotation to approach the position for ignition capacity:
S1: for ignition capacity of the burner.
S2: for reversing the direction of rotation to approach the posi-
tion for ignition capacity.
S3: for maximum capacity of the burner and pre-purge.
S4: for the closed position of the butterfly valve and standby.
BCU 580 · Edition 11.1587
Page 88
S2
S3
S1
S4
0°90°
Move to ignition position
Burner control range
CLOSED
IGNITION
Butterfly valve setting range
Control range
OPEN
Max. pos.Ignition
pos.
Reversing direction of rotation
for quick start
Min.
pos.
Closed
pos.
MINMAX
MAX
PE
L1
N
3 2 116674812 1115 13
S3S4
S11
S10
0°
90°
M
IC 20
PE
S1S2
90°➔0°
0°➔90°
S1
MinMax
S2
Y-
Y+
53 54 55 56
52
123464565 66 67 68495051
17183738
131415
BCU 580..F1
3,15AT
µC
88
c
c
4142
24V
DC
56911
1210762
61
Parameters > Air control > Capacity control (bus)
Parameter 75 = 5: IGNITION to MAX. capacity; standby in
CLOSED position; burner quick start.
The control range while the burner is operating is between the
positions for ignition capacity(S1) and maximum capacity(S3).
The burner is ignited in the position for ignition capacity(S1).
Switching cam S2 (reverse direction of rotation) ensures that
the position for ignition capacity is approached without prepurging first (quick start). When the burner is switched off, the
actuator is moved to the closed position(S4).
This operating mode can be achieved with an actuator IC20
or alternatively with a comparable three-point step actuator.
If the air supply is stopped on a heated furnace with the
burner switched off, the controls are protected from the
hot furnace atmosphere as a result of the butterfly valve
being in the closed position (limited byS4). Check whether
the burner can cope without cooling. If pre-purge is active,
considerably lower air capacity than the maximum air
capacity will be used for purging.
IC 20
The position for maximum capacity is achieved by the controller
enable output (terminal56).
Switching cam settings S1, S2, S3 and S4:
S1: for minimum capacity and ignition capacity of the burner.
S2: for reversing the direction of rotation to approach the po-
sition for ignition capacity. The actuator will move to the
position for ignition capacity without reaching the position
for maximum burner capacity.
S3: for maximum capacity of the burner and pre-purge.
S4: for the closed position of the butterfly valve and standby.
BCU 580 · Edition 11.1588
Page 89
PZL
PZH
4913
1
450
ϑ
1
V1V2
45
GZL
Parameters
10.7 Valve check
10.7.1 Valve proving system
Parameter 51
Parameter 51 is used to define whether and at what time in
the BCU program sequence the valve check is activated. This
allows either the tightness of the gas solenoid valves and the
pipework between them to be checked (tightness test) or the
closed position of a solenoid valve (proof of closure function)
to be checked. If the proof of closure function is activated, the
closed position of the gas solenoid valve at the inlet side is
checked using a POC switch.
Parameter 51 = 0: Off. No valve check is activated.
Parameter 51 = 1: tightness test before start-up.
Parameter 51 = 2: tightness test after shut-down. With this
setting, a tightness test is also performed after a fault is reset
and after mains on.
Parameter 51 = 3: tightness test before start-up and after
shut-down.
An additional bypass valve must be installed in gas sections
with an air/gas ratio control. The valve allows the closed air/
gas ratio control to be bypassed during the tightness test.
Parameter 51 = 4: proof of closure function (POC).
A signal is sent to the BCU via the POC switch on the gas
solenoid valve on the inlet side before burner start-up stating
that the valve is closed. After burner start-up, the signal must
drop out to indicate to the BCU that the valve is open.
BCU 580 · Edition 11.1589
Page 90
V
2
V3
V4PZVAS
p
u
/2
14151345
5
7
V
p
1
V2
V3
V4
14 15
57
P
13
1
4
4
5
p
u
/2
PZ
ϑ
1
pu/2
PZ
V
p1
V1V2
Parameters > Valve check
10.7.2 Relief valve (VPS)
Parameter 52
One of the valves connected to terminal 14, 15 or57 can be
selected to discharge the test volume during a tightness test.
Parameter 52 = 2: V2. The test volume is discharged via the
valve connected to terminal14.
Parameter 52 = 3: V3. The test volume is discharged via the
valve connected to terminal15.
Parameter 52 = 4: V4. The test volume is discharged via the
valve connected to terminal57.
10.7.3 Measurement time V
p1
Parameter 56
The required measurement time must be determined ac-
cording to the requirements of the appropriate application
standards, e.g. EN1643.
The required measurement time for the tightness test of Vp1
can be set using parameter56. The possible settings are 3s,
5 to 25s (in 5s steps) or 30 to 3600s (in 10s steps).
See also page30 (Measurement time tM).
BCU 580 · Edition 11.1590
Page 91
Parameters > Valve check
10.7.4 Valve opening time 1 tL1
Parameter 59
This parameter is used to define the opening time for the
valves (2 to 25s) which are opened to fill or discharge the test
volume between the gas valves. If the preset opening timetL
= 2s is inadequate (e.g. if slow opening valves are used) to
fill the test volume or reduce the pressure between the valves,
bypass valves can be used instead of the main valves.
The opening time may be longer than the 3s permitted by the
standard (EN1643:2000) if
– the gas volume which flows into the combustion chamber
is equal to, or less than, 0.083% of the maximum flow
rate
and
– if bypass valves are used.
BCU 580 · Edition 11.1591
Page 92
Parameters
10.8 Behaviour during start-up
10.8.1 Minimum pause time tBP
Parameter 62
A minimum pause time tBP (0 to 3600s) can be defined to
achieve stable operation of the burners.
If a signal is applied to terminal 1 (burner start-up) or terminal 2
(cooling) during the minimum pause time, status displayDelay
H0
will appear.
BCU 580 · Edition 11.1592
Page 93
Parameters
10.9 Manual mode
If the Reset/Information button is pressed for 2s during
switch-on, the BCU reverts to Manual mode. Two dots blink
on the display. The BCU is now operating in Manual mode
independently of the status of the inputs of the burner1 startup signal (terminal1), controlled air flow (terminal2), remote
reset (terminal3) and the burner2 start-up signal (terminal4).
The functions of the safety-relevant inputs such as controller enable/emergency stop (terminal46) are retained. The
manual start-up of the BCU can be initiated in Manual mode
by pressing the Reset/Information button. Each time the button is pressed again, the BCU moves to the next step of the
program sequence and stops there, for example for adjusting
an actuator or the gas/air mixture.
Actuator IC20, IC 40 and RBW
08
Following controller enable (status display
actuator can be opened and closed as required. By holding the
button, the actuator is first opened further. The BCU indicates
A
with blinking dots. Once the button has been released,
the actuator stops in the relevant position. Pressing it again
will result in closing the actuator to the position for minimum
capacity. The BCU indicates A with blinking dots. A change
of direction takes place each time the button is released and
pressed again. When the actuator has reached its final position, the dots disappear.
), a connected
10.9.1 Operating time in Manual mode
Parameter 67
Parameter 67 determines when Manual mode is terminated.
Parameter 67 = 0: Manual mode is not limited in time.
If this function has been selected, operation of the burner may
be continued manually in the event of failure of the control
system or the bus activation.
Parameter 67 = 1: the BCU will terminate Manual mode 5minutes after the last time the button is pressed. It then moves
abruptly back to the start-up position (standby).
If the unit is switched off or a power failure occurs, Manual
mode on the BCU will be terminated regardless of parameter67.
BCU 580 · Edition 11.1593
Page 94
Parameters
10.10 Functions of terminals 50, 51, 65, 66, 67 and
68
The BCU is informed via terminal50 by a separate automation
system that purging is currently being performed.
Terminals 51, 65, 66, 67 and 68 can each be assigned a logical AND gating with one of the inputs for the safety functions
(terminals 46–50) using an appropriate parameter. If AND
gating is required, the input concerned can be enabled.
Terminal51 can also be used as a feedback input for the
maximum capacity position when operated with IC40/RBW.
10.10.1 Function of terminal 50
Parameter 68
The BCU..F1, F2 or F3 supports centrally-controlled pre-purge
or post-purge. In the case of multiple burner applications,
burners with mechanical combustion air supply are used.
The air for combustion and pre-ventilation is supplied by a
central fan controlled by a separate automation system. The
automation system sends a signal to terminal 50 during purging. At this point, the BCU opens the air actuator (actuator, air
valve) regardless of the status of the other inputs. The display
shows
Parameter 68 = 23: purge with Low signal.
Parameter 68 = 24: purge with High signal.
P 0
.
10.10.2 Function of terminal 51
Parameter 69
Parameter 69 = 0: Off.
Parameter 69 = 8: AND with input at terminal46 (emergency
stop).
Parameter 69 = 13: Max. capacity position feedback (IC40/
RBW), see page76 (Parameter 40 = 3: with RBW.).
10.10.3 Function of terminal 65
Parameter 70
Parameter 70 = 0: Off.
Parameter 70 = 8: AND with input at terminal46 (emergency
stop).
BCU 580 · Edition 11.1594
Page 95
B
CUBCU
FCU
µC
5455
53
+24V
M
L1
L1
54 55
53
M
6666
Parameters > Functions of terminals 50, 51, 65, 66, 67 and 68
10.10.4 Function of terminal 66
Parameter 71
Parameter 71 = 0: Off.
Parameter 71 = 8: AND with input at terminal46 (emergency
stop).
Parameter 71 = 20: LDS ignition position check.
The BCU does not perform a burner start-up, restart or start-up
attempt until the butterfly valve is in ignition position. To ensure
that the burners only start with the start-up fuel rate, the FCU
issues an enable signal to start the burner via terminal 66 to
the BCU with setting P71=20. In addition, the safety interlocks
must have been enabled by theFCU.
10.10.5 Function of terminal 67
Parameter 72
Parameter 72 = 0: Off.
Parameter 72 = 8: AND with input at terminal46 (emergency
stop).
10.10.6 Function of terminal 68
Parameter 73
Parameter 73 = 0: Off.
Parameter 73 = 8: AND with input at terminal46 (emergency
stop).
BCU 580 · Edition 11.1595
Page 96
Parameters
10.11 Password
Parameter 77
The password is designed to protect the parameter settings.
To prevent unauthorized changes to parameter settings, a
password is stored in parameter77 (0000to9999). Changes
to parameter settings can only be made once this number has
been entered. The password can be changed using BCSoft.
Note the effect of parameter settings on the safe functioning
of your system.
10.12 Fieldbus communication
Parameter 80
Fieldbus communication can be activated using parameter80
when bus module BCM500 is connected.
A device name must be entered in the automation system for
the unique identification of the control unit (BCU/FCU) in the
Profinet IOsystem.
Parameter 80 = 0: Off. Parameterization access using BCSoft
via Ethernet is still possible.
Parameter 80 = 1: with address check. The device name on
delivery for the BCU580 is “not-assigned-bcu-580-xxx”. The
expression “not-assigned-” must be deleted or may be replaced with an individual name. The sequence xxx must be
identical to the address set on the BCM500 using the code
switches (xxx= address in the range 001 toFEF).
Parameter 80 = 2: no address check. The device name can
be selected as specified by the automation system.
BCU 580 · Edition 11.1596
Page 97
11 Selection
Q W CO C1 F1 F2 F3 U0 D0 D1 K0 K1 K2 E
BCU 580
= standard, = available
Order example
BCU 580WC1F1D0K1E
11.1 Type code
CodeDescription
BCUBurner control unit
5Series 500
80Version for pilot and main burners
Q
W
C0
C1
F1
F2
F3
U0Ionization or UV control in case of operation with gas
D0
D1
K0
K1
K2
EIndividual packaging
Mains voltage: 120 V AC, 50/60 Hz
230 V AC, 50/60 Hz
No valve proving system
With valve proving system
Capacity control:
interface for actuator IC
interface for RBW actuators
air valve control
Digital input:
none
for high temperature operation
No plug-in terminals
Plug-in terminals with screw connection
Plug-in terminals with spring force connection
BCU 580 · Edition 11.1597
Page 98
12 Project planning information
12.1 Installation
Installation position as required.
The BCU mounting is designed for horizontally aligned
35× 7.5mm DINrails.
If the DINrail is aligned vertically, end clamps are required (e.g.
Clipfix35 by Phoenix Contact) to prevent the BCU from slipping.
12.2 Commissioning
Do not start the BCU until the parameter settings and wiring
are correct and the faultless processing of all input and output
signals complies with the local standards.
Environment
Install in a clean environment (e.g. a control cabinet) with an
enclosure ≥IP54, whereby no condensation is permitted.
BCU 580 · Edition 11.1598
Page 99
Project planning information
12.3 Electrical connection
The BCU is designed for connection to a 1-phase system. All
inputs and outputs have a one-phase mains supply. Other
connected burner control units must use the same phase of
the mains supply.
The national standards and safety requirements must be satisfied. If the BCU is operated in ungrounded/IT systems, an insulation monitoring device must be provided to isolate it from the
mains in the event of a fault. The cabling of the safety circuits
(e.g. pressure switches, gas valves) outside enclosed installation spaces must be protected from mechanical damage
and stress (e.g. vibration or bending) as well as short-circuits,
short-circuits to ground and cross-circuits.
Signal and control line for screw terminals max. 2.5mm2
(AWG12), for spring force terminals max. 1.5mm2 (AWG16).
Do not route BCU cables in the same cable duct as frequency
converter cables or cables emitting strong fields.
External electrical interference must be avoided.
12.3.1 OCU
Cables for signalling and telecommunications systems are
recommended for wiring the supplied plug connectors:
Cable length max. 10 m, 4-pin,
min. 0.25 mm
max. 0.34mm
2
(AWG 24),
2
(AWG22).
BCU 580 · Edition 11.1599
Page 100
17183738
N
max. 1A;24VDC,250VAC
BCU 580
3,15AT
µC
88
c
c
0 V+24 V
4142
24V
DC
911
121062
61
230V
1 2 3 4
L1
ϑ1
P70ϑ2P70
P70P69
P73
P72P72
HT
p
u
2
GZL
PZL
P71
0,6 × I
N
464565 66 67 6849 50 51
5678
13141557
V1
V2
V3
V4
A
53545556
P
M
I
Project planning information > Electrical connection
12.3.2 Safety current inputs
Actuation of the safety current inputs only with switchgear featuring mechanical contacts. If switchgear with semi-conductor
contacts is used, the safety current inputs must be connected
using relay contacts.
To safeguard the safety current inputs, the fuse must be designed so that the sensor with the lowest switching capacity
is protected.
The cabling outside enclosed installation spaces must be
protected from mechanical damage and stress (e.g. vibration
or bending) as well as short-circuits, short-circuits to ground
and cross-circuits.
Calculation
IN = current of the sensor/contactor with the lowest switching
capacity
Suitable fuse = 0.6 × I
N
BCU 580 · Edition 11.15100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.