The A1120/40 meter Users Manual consists of a number of Chapters containing information
on Meter Hardware, Communications and Software Support. Each Chapter is self contained
so that for specific information, only that part of the manual needs to be referred to. Each
Chapter can therefore be distributed as a document in its own right.
Manual Numbering System
The manual numbering system is defined as follows:
Chapter 2 contains general information on the A1120/40 meter including configuration and
installation.
Chapter 3 - Software Support (M181 001 3)
This Chapter contains full documentation for Power Master Unit Software Support.
This includes Reading, Programming and Configuring the A1120/40 meter.
Chapter 4 - Communications (M181 001 4)
Operating and Installation Instructions for all types of communications including, RS232,
RS485 and GSM modems. General information and configuration data for setting up ASL,
GSM modems are also included.
13.2.2 Reverse Energy Flow .................................................................................................................... 20
13.2.3 Power Fail ..................................................................................................................................... 21
13.2.4 End of Billing Event ....................................................................................................................... 21
13.2.8 In Service Hours ............................................................................................................................ 22
13.2.9 Meter Errors................................................................................................................................... 22
29 DISPOSAL AND RECYCLING .....................................................................................................40
FIGURE 1- MODEL CODE................................................................................................................................ 41
FIGURE 1- MODEL CODE (CONTINUED) ........................................................................................................... 42
The instructions and information in this manual are provided in compliance with Section 6 of the
UK Health and Safety at Work Act, as amended by Schedule 3 of the Consumer Protection Act
1987.
The purchaser is responsible for making sure that everyone, whether in his employment or not,
who will be associated with the products supplied by Elster Metering Systems, and to which these
instructions and information apply, are made familiar with the contents of this manual.
This applies to all persons who may be involved in activities such as unpacking, inspecting,
testing, setting, cleaning, installing, commissioning, operating, maintaining, decommissioning or
disposing of the products.
Safety of Persons using Electrical Products
Employers have a duty to ensure, as far as is reasonably practicable, the Health, Safety and
Welfare at Work of all their employees. Employers must therefore ensure that employees are
informed, trained and supervised and use proper working procedures to ensure the safety of
themselves and others.
The information provided in this manual is intended to ensure that products are properly installed
and otherwise handled in order to maintain them in a safe condition.
In the UK, employers have duties under the Health and Safety at Work Act 1974 and the various
regulations stemming therefrom.
In countries outside the UK, employers should ensure proper compliance with the Health and
Safety Legislation that is applicable to them.
Putting into Service
Products supplied by Elster Metering Systems have been designed and manufactured, in
accordance with appropriate standards, to operate under specified conditions, when properly
installed.
The purchaser or delegated contractor is responsible for the "Putting into Service" of any Elster
Metering Systems products that have been supplied as "Non-connected". All related activities
must therefore be carried out with due regard to any applicable legislation, standards and good
practice.
Page 14
6 A1120/40 - Electronic Polyphase Meter
2 WARNINGS
WARNINGS
Internal Electronic Circuits
Parts of the internal electronic circuits of these meters are, due to technical necessity, connected to
PHASE VOLTAGES.
Dangerous voltages are present
A Terminal Cover Plate must always be fitted to the A1120/40 meter to protect the main meter
terminals. If the Terminal Cover Plate is not fitted to the A1120/40 meter, all supplies to the meter
must be isolated before a module, module peripheral equipment or external battery module is installed
or removed.
Failure to do so may result in electric shock.
Caution
Installation of a faulty module or module peripheral equipment may affect the main meter functionality.
Removal of the main cover invalidates the certification of certified meters.
Liquid Crystal Display
Liquid crystals are toxic. If a display is damaged, avoid contact with the liquid. If the liquid makes
contact with the skin it must be washed off immediately with water.
Seek medical advice.
Batteries
The meter contains an internal Lithium manganese dioxide primary cell. This battery is completely safe
under normal conditions. However, it must never be recharged, disassembled, heated above 100° C,
incinerated, or have the contents exposed to water.
Fire, explosion or severe burns may result if these instructions are disregarded.
In the interests of safety, environmental protection and possible legislation, Lithium batteries require
careful disposal. Before arranging for the disposal of these cells, users should satisfy themselves that
the proposed means of disposal is both safe and compliant with local legislation requirements.
Elster Metering Systems would like to draw the user's attention to the International Standard for
Lithium Batteries - IEC 60084-4 - which gives further information about the handling, storage, transport
and disposal of lithium cells.
Elster Metering Systems should be contacted by the user should difficulties arise in arranging proper
disposal. They will if practical help the user identify safe disposal means.
An optional External Battery Module supports the display and optical communications during power
outages. A non-rechargeable “alkaline” (alkaline zinc manganese dioxide) PP3 (IEC 6LR61) battery is
used.
This battery is completely safe under normal conditions. It must not be recharged, disassembled,
short-circuited, overheated or incinerated. It contains corrosive materials.
Used batteries should be disposed of in compliance with local legislation requirements.
3 COMPLIANCE WITH STANDARDS AND EUROPEAN DIRECTIVES
Meters are marked with the European CE mark, in accordance with the Marking Directive
93/68/EEC, to indicate compliance with the requirements of the EMC Directive 89/336/EEC.
Safety requirements for meters are addressed in specific metering standards outlined below.
The CE Mark does not denote compliance with the European Low Voltage Directive 73/23/EEC,
which specifically excludes electricity meters.
The A1120/40 meter measures active energy, according to the requirements of -
EN 62053-21/22:2003 for indoor kWh meters of Protective Class II and Accuracy Class 0.5s, 1 or 2
(MID) - Annex MI-003, kWh Class A, B or C.
The meter measures reactive energy in accordance with EN 62053-23:2003, Class 2 or Class 3.
Meters displaying OBIS Identification Codes meet the requirements of IEC 62056-61.
The degree of ingress protection is to IP53, IEC 60529:1989.
The meter complies with DIN 43857 Part 2 and Part 4 - dimensional requirements (except for the
top fixing centres).
The meter complies with the essential requirements of the EC Directive 2004/22/EC on Measuring
Instruments (MID).
The meter complies with the general requirements and particular requirements of EN 50470 Parts
1 & 3, and complies with Class M2 Mechanical environment and Class E2 Electromagnetic
Environment.
Devices for metering and billing electrical energy described in this manual are supplied for use in a
‘Fixed Installation’ only. Devices described are a ‘component of a system only’ and therefore outside
the scope of European Directives 2002/95/EC RoHS (Restriction of the Use of Certain Hazardous
Substances in Electrical Equipment) and 2002/96/EC WEEE (Waste Electrical and Electronic
Equipment).
4 APPROVALS
kWh/kvarh energy meters are approved by the Office of Gas and Electricity Markets
(OFGEM) in compliance with European and British metering legislation.
Page 16
8 A1120/40 - Electronic Polyphase Meter
5 INTRODUCTION
The A1120/40 has been designed to meet the changing needs of the Electricity Supply Industry.
The meter offers a ‘modular’ solution for remote communications, allowing the meter to be
integrated into an AMR system at any time. Flexibility in communications provides the Utility with
the means to employ the most cost effective communications method. The RJ11 connector
provides power for a modem removing any requirement for external connections.
The modem fits neatly under the terminal cover providing a high degree of protection against
fraud or tampering.
Communications are provided via the optical (IEC 62056-21) port and are supported by data
stream mode, allowing fast reading of meter data. The A1140 permits up to 90 days of load
profile data to be collected in less than 30 seconds. The RJ11 socket provides optional RS232
communications allowing remote access to the same data as the optical port. This port can be
multi-dropped, allowing access to up to 10 meters in a single installation. A further option allows a
pulsed output to be transmitted via the meter’s auxiliary terminals.
The meter is available in a number of variants that measure combinations of active energy, four
quadrant reactive energy and kVAh. Two customer defined registers can be used to summate
energy from any like unit registers. Instrumentation quantities to aid installation can be included in
the display sequence.
Firmware Version C allows 12 External Registers to display data from an external source such as
a gas or water meter. The registers are written to by an intelligent source via the RS232 port.
The meter offers extensive security data which includes a programming log with user ID.
Further security can be provided as an option with terminal cover and main cover removal
detection. As an alternative option, the latter detection switch can instead be used to allow the CT
ratio to be changed.
The Liquid Crystal Display (9.8mm) has large characters that can be viewed from a wide angle.
The display sequence is programmable and can be auto-cycle, step or utility. Displayed
information can have English language identifiers or OBIS (Object Identification System) codes.
The OBIS codes can be changed via the Power Master Unit.
TM
Power Master Unit software provides a user-friendly Windows
programming the meter and reading meter data.
The meters are approved to:
EN 62053-21/22 for kWh accuracy - Class 0.5s, 1 or 2
EC Directive 2004/22/EC (MID) - Class A, B or C
EN 62053-23 for kvarh accuracy - Class 2 or Class 3
The meter has an ingress protection rating of IP53 to IEC 60529:1989.
The following main variants of the meter (configured at manufacture) are available:
The main available manufacturing options of the meter are tabulated below:
Pulse Output
Load Profile
RS232 Port
Accuracy EN 62053 - 21/22(kWh)
2004/22/EC (MID)
A1120 A1140
Optional Optional
Not available Standard
Optional Optional
Class 0.5s, 1 or 2
Class A, B or C
Class 0.5s, 1 or 2
Class A, B or C
Features
•Accuracy kWh Class 0.5s, 1 or 2 (EN 62053 -21/22) kWh Class A, B or C (EC Directive 2004/22/EC [MID])
kvarh Class 2 or Class 3
• Comprehensive tariff structure
• Twelve external registers (Firmware Version C only)
• Large digit (9.8 mm register digits) Liquid Crystal Display
• IEC 62056-21 (formerly IEC 61107) optical communications port
• Internal clock and calendar with battery back-up
• 15 years product life
• Comprehensive security data
• Display of external register information
• Compact design
• DIN (BS) double insulated, glass filled polycarbonate case
• IP53 in accordance with IEC 60529 : 1989
Options
• RS 232 serial communications
• Load profiling (A1140)
• Module/battery carrier
• SO (EN 62053-31) or relay pulsed output
• Terminal cover removal detection switch
• Main cover removal detection or CT ratio programming switch
• Terminal cover with cut-out
• Read without power option (battery support)
• Optional (Extended) terminal cover and main cover with voltage disconnect protection
(See Figure 5)
Tariff Structure
• 8 time-of-use (TOU) registers
• 4 maximum demand registers
• 48 switching times
• 12 seasons
• 24 change of season dates
• 32 exclusion dates
• 13 end of billing date
Independent day control
Daylight saving
Deferred tariff
Tariff scheme CRC
Page 18
10 A1120/40 - Electronic Polyphase Meter
6 GENERAL DESCRIPTION
6.1 Basic Meter Types
LM… DIN/BS Termination
6.2 Current and Voltage Ratings
Unless otherwise indicated on the nameplate, the following meter ratings are available:
Voltage Current Frequency
3 Element Meters
*220 - 240V L-N
105 - 127V L-N
2 Element Meters
220 - 240V L-L
105 - 127V L-L
* Ratings available for Class 0.5s, CT operated variant
20 - 100A (Direct connected)
10 - 100A (Direct connected)
5 - 100A (Direct connected)
1 - 2A (CT operated)
*5 - 10A (CT operated)
1 - 10A (CT operated)
50 or 60Hz
Note - 105 - 127V meters and 60Hz meters are not OFGEM or MID approved.
6.3 System Connections
Meters can be supplied for direct connected or CT, 3 element (3 phase, 4 wire) or 2 element (3
phase 3 wire) applications and have the following connection capability:
Number of Elements Connection capability
3 * 3 phase, 4 wire
2 * 3 phase, 3 wire
* Connections available for Class 0.5s, CT operated variant
Meter nameplates (see Figure 3 for example) are marked with the rated current, reference
voltage, frequency and the relevant meter constant (pulses/kWh, pulses/kvarh).
Connection diagrams (See Figure 5A for examples) are shown underneath the terminal cover.
A Terminal Cover Plate must be fitted to protect the meter Main Terminals.
The A1120/40 meter measures active energy, in accordance with the requirements of -
EN 62053-21/22 for indoor kWh meters of protective Class II and accuracy Class 0.5s, 1 or 2,
EC Directive 2004/22/EC (MID) - Class A, B or C
The design of the meter ensures life long stability. There are no on-site adjustments.
The meter measures reactive energy in accordance of the requirements of EN 62053-23 for kvarh
meters for reactive energy Class 2 or Class 3.
Typical accuracy curves are shown in Figure 4.
6.6 Meter Case
The case is double insulated to protective Class II.
The case provides an ingress protection rating of IP53 in accordance with IEC 60529:1989.
The base is light beige coloured polycarbonate.
A separate phenolic terminal block conforms to DIN 43857 Part 2 and 4.
The extended terminal cover is moulded in light beige coloured polycarbonate.
An option with a cut-out is available.
The main cover is moulded in tinted, clear polycarbonate.
Figure 6 illustrates the outline and fixing dimensions.
The main cover is secured by two sealable screws. Two separate sealable screws secure the terminal
cover.
The terminal cover plate protects the meter main terminals.
An optional main cover prevents access to the voltage disconnect links (See Figure 5)
A holder for a module/battery that attaches to the base under the terminal cover is available as an
option.
7 OVER VOLTAGE OPERATION
The meter has been designed to withstand a phase - neutral voltage of √3 x 1.1 Uref (i.e. 440V
for 230V meters) for an indefinite period. When tested over a 12 hour duration the change in
meter error was less than 0.4%.
8 IMPORT ACTIVE REGISTRATION
Import Active registration can be configured at manufacture to one of the following:
Import Active Units Only – Import Active Units measures the sum of all phases, when the total
system flow is positive.
Positive (kWh [L
Power Flow Insensitive Mode - Power Flow Insensitive Mode allows the meter to increment its
main kWh register regardless of whether the system energy flow is import or export.
│(kWh [L
] + kWh [L2] + kWh [L3])│
1
] + kWh [L2] + kWh [L3])
1
Page 20
12 A1120/40 - Electronic Polyphase Meter
The Reverse Energy Event Alarm, Reverse Energy Count and Reverse kWh Register respond
only to reverse power flow and continue to function as in normal operation.
Theft Resistant Measurement - Theft Resistant Measurement mode measures the sum of the
modulus of each phase (│kWh [L
The Reverse Energy Event Alarm, Reverse Energy Count and Reverse kWh Register respond
only to reverse power flow and continue to function as in normal operation.
Note 1: Power Flow Insensitive Mode and Theft Resistant Measurement may not be allowed in
certain countries due to local regulations.
Note 2: Theft resistant measurement is not appropriate for meters connected to 3 phase 3 wire
systems.
9 TEST INDICATORS & ANTI-CREEP
Test Indicators
Two red test output LEDs (for kWh and kvarh) are provided which pulse in accordance to the
following configurations:
]│ + │kWh [L2]│ + │kWh [L3]│)
1
Import only meter - The LED pulses for forward system energy only
Import meter with Power Flow Insensitive enabled - The LED pulses for forward and reverse
system energy
Import meter with Theft Resistant measurement enabled – The pulsing LED reflects theft
resistant measurement.
Import/export meter - The LED pulses for import and export energy
See Section 25 (Technical Data) for LED specification.
Anti-creep
The Wh and
rating and accuracy class. For a 4 wire meter connected with less than 3 elements energised, the
value adjusts to maintain an appropriate current threshold level. Each Test Indicator LED is
continuously illuminated when the meter's anti-creep lock is operating for kWh and kvarh
respectively.
varh anti-cree
p threshold is set at manufacture to a value appropriate to the meter
10 FEATURES OF THE A1120/40 METER
The meter contains numerous features, combinations of which can be selected to provide the
required metering function. Main variants are selected at manufacture (See Section 5).
Programmable features are selected using Power Master Unit Software that runs on an IBM or
compatible PC.
This software is available from Elster Metering Systems and is described in M181 001 3.
Note: The features available will depend on the meter variant (See Section 5).
Total import and total export quantities are registered
separately. The measurement discrimination is such that,
as the power factor of any load from 0.05Ib to Imax is
varied over 360°, the import and export registers will never
advance together. The resolution of registration is 1mWh.
10.1.2 kvarh
Q1 kvarh Inductive Import
Q2 kvarh Capacitive Import
+Q
L
a
e
v
i
t
i
c
a
p
a
C
/
g
n
i
E
d
W
a
O
e
P
L
E
V
I
T
C
-P
A
T
R
O
P
X
E
e
v
i
t
c
u
M
I
R
R
d
n
I
/
g
n
i
g
g
a
C
A
T
E
I
V
R
E
T
R
O
P
Q1Q2
Q4
Q3
E
W
O
P
R
E
E
V
I
A
T
C
L
g
g
i
n
g
/
I
n
d
P
O
W
E
R
E
X
P
O
R
T
v
e
u
c
t
i
v
e
+P
a
c
i
t
i
L
e
a
d
i
n
g
/
C
a
p
-Q
Q3 kvarh Inductive Export
Q4 kvarh Capacitive Export
All four quadrants are registered separately. The resolution of registration is 1mvarh.
kvarh is derived using the phase shift method.
Note: The diagram shows a representation of the quadrants. The active quadrant can be shown on
the display.
10.1.3 kVAh
kVAh is derived from the measured kWh and kvarh values
The calculation uses the formula: kVAh = √ ([kWh]
There are two kVAh registers. These can each be configured to accept pulses from
any combination of quadrants e.g.
Q1 Q2 Q3 Q4
kWh * * kVAh - to match 2 electromechanical meters
kvarh * *
2
+ [kvarh]2 )
Note: Real and reactive energy for each phase is respectively summated prior to kVAh
calculation.
Page 22
14 A1120/40 - Electronic Polyphase Meter
10.1.4 Customer Defined Registers
Two Customer Defined (CD) Registers are provided. These are cumulative registers which can
be used throughout the tariff scheme and load profile data and are programmable to accept
consumption from any two of the following like-unit registers:
kWh import
kWh export
Q1 kvarh
Q2 kvarh
Q3 kvarh
Q4 kvarh
kVAh 1
kVAh 2
Examples of their use are:
CD Register 1 Total kWh kWh import + kWh export = Total kWh
CD Register 2 Total Import kvarh Q1 + Q2 = Total Import kvarh
The contents of the Customer Defined Registers can be viewed on the display.
11 TARIFF STRUCTURE
The tariff structure repeats year on year and comprises the following features:
8 Time-of-use (TOU) registers
4 Maximum demand registers
48 Switching times
12 Seasons
24 Change of season dates
32 Exclusion dates
13 End of billing dates
Daylight savings
Independent day control
Deferred tariff
Tariff scheme CRC
At least one Season must be programmed into the meter for TOU registers to be available.
Each TOU Register is independently time controlled so that registration can take place over a
restricted time period.
The contents of each TOU Register can be viewed on the display along with the active rate(s).
11.2 Demand Registers
The A1120/40 provides the rising demand value associated with each of the 10 registered
quantities specified in Section 11.1. The demand integration period can be 1, 2, 3, 4, 5, 6, 10, 15,
20, 30 or 60 minutes.
In A1140 meters the integration period used for the demand registers is the same as the load
profile integration period.
During any period, the rising demand value is calculated by measuring the energy consumed to a
point in a period, then scaling the measured value by a factor equal to the ratio of the demand
period to a total hour interval.
Rising Demand = Energy recorded in current period x 60
minutes in demand period
The contents of each Rising Demand Register can be viewed on the display.
11.2.1 TOU Maximum Demand Registers
p
The meter has 4 maximum demand registers, each with an independent source selectable from
one of the 10 rising demands.
The meter records the three highest maximum demand values (along with time and date stamp)
that can be sampled on a continuous basis (24-hour period) or over a restricted time period.
At the end of each billing period, the greatest of the three demands is added to a corresponding
cumulative maximum demand register.
The maximum demand registers are then set to zero.
Page 24
16 A1120/40 - Electronic Polyphase Meter
11.3 Switching Times
Up to 48 switching times can be set, each allocated to a specified season.
Each switching event can be enabled for any combination of days of the week.
These are the transition times when one or more TOU registers become active or inactive.
Each switching time is defined in hours and minutes. A 24-hour clock is used.
06:0018:00
Switching times
24 hours
The above diagram shows the tariff for TOU1 and TOU2. TOU1 is active from 06:00 to 18:00.
TOU2 is active from 18:00 to 06:00. It is possible for none or multiple TOU registers to be
programmed to be active at any particular time period.
11.4 Seasons and Change of Season Dates
Up to 12 Seasons may be specified and at least one Season must be programmed for the TOU
registers to be available. Each Season is activated by one or more Change of Season Dates.
Up to 24 Change of Season Dates are available,
each date specifying the start of a new Season.
These may refer to a different Season, or the
same Season may be used more than once in a
year.
The old Season ends at the instant the new
Season starts.
A new Season starts at 00.00 of the specified
day.
Start dates are specified as absolute (dd.mm)
dates.
The diagram shows three Seasons. Season 1 is
in operation from October to February, Season 2
from March to May and Season 3 from June to
September.
11.5 Exclusion Dates
There may be special days in the year when the tariff does not follow the normal pattern, e.g. public
holidays. These can be taken care of by invoking Exclusion Dates.
These dates will fall into one of three categories:
1 Dates which are fixed for every year e.g. December 25
2 Dates which fall on the same day of the month every year e.g. the first Monday in May
3 Dates which vary from year to year e.g. Easter Monday - defined using dd.mm.yy
For each Exclusion Date the meter may be programmed to:
- Use the switching times for a different weekday of the current season
- Use the switching times for the same weekday but a different season
- Use the switching times for a different weekday of a different season
11.6 End of Billing (EOB)
th
- programmed by absolute dd.mm
Time and Date Stamps for
the last three EOB records
End of Billing Reset
Programmed EOB
Automatically on programmed dates (13) or every midnight when auto reset is enabled
At a change of season date (24)
When the deferred tariff becomes active
Daily reset
Instantaneous E OB
When the Billing Reset p ushbutton is pressed
On command via the optical port
On command via the serial port (where fitted)
When a CT ratio programming event occurs
When the internal battery has failed at power up
When a snapshot of meter data is required to allow a bill to be prepared reflecting consumption to a
specified date, the End of Billing feature should be used.
See Section 13.3 for a description of the data captured.
A programmed Automatic End of Billing occurs at midnight.
More than one End of Billing request may occur at the same time (for example, a deferred tariff
introduced at the start of a new season), but only a single End of Billing event will take place. The
cause of each of the End of Billing events is recorded but the End of Billing Counter is only
incremented by one.
If an automatic End of Billing event should have occurred during a power down, then a billing
event will take place immediately following the next power up. If several requests were missed
then a single billing event is created, the cause reflecting all billing events that were missed.
If an End of Billing reset is required when the current tariff is manually overwritten by a new
current tariff, it should be manually requested as part of the communications session.
Page 26
18 A1120/40 - Electronic Polyphase Meter
Auto Reset initiates a Billing Reset every midnight. When Auto Reset is enabled there is an
option to inhibit the reset of the Maximum Demand Registers.
A message that a Billing Reset has been initiated is displayed with a code showing the cause of
the reset (See Figure 8, Display Table).
At each Billing Reset the oldest of the fifteen historical data records is overwritten. Time and date
stamps, together with causes are stored for the last three End of Billing events.
End of Billing Lock-out
A further End of Billing can be inhibited via the Power Master Unit for either:
- Up to 255 minutes
- Until the next midnight boundary
Note: This only inhibits instantaneous end of billing requests, either via the pushbutton or
communications setting, not programmed End of billing events.
11.7 Daylight Savings
The meter provides 2 Daylight Savings dates whereby the clock can be advanced by one or two
hours at the start of the summer and can be retarded by one or two hours at the end of the
summer.
The day on which a Daylight Saving occurs is programmable, with the choice of the first, second,
third, fourth or last specified weekday in a specified month.
The algorithm used will identify the correct calendar dates for the next 50 years.
All of the following will reflect Daylight Savings:
Automatic End of Billing
Switching times within the tariff definition
Time and date stamps (For firmware Version C meters, daylight savings time and date stamps
can be referenced to base time or daylight savings time)7.
Optionally load profile (A1140 only)
11.8 Independent Day Control
The meter has the facility to have a different switching program consisting of several switching
times running on different days of the week. An example of a switching program is below.
11.9 Deferred Tariff and Deferred Tariff Changeover Date
A second tariff can be programmed in the meter that will take effect from a programmed date.
An option to perform an End of Billing on the Deferred Tariff Changeover Date is available as part
of the deferred tariff structure.
11.10 Tariff/Display Scheme Verification
The meter generates a checksum (CRC-16) of the tariff/display scheme currently residing in the
meter. The checksum can be included as part of the display sequence, and also compared with a
tariff checksum generated by the Power Master Unit. This allows quick verification, either locally
or remotely, that the correct tariff/display scheme resides within the meter.
12 EXTERNAL REGISTERS (FIRMWARE VERSION C ONLY)
Firmware Version C of the A1120/40 has 12
External Registers that can be used to
display data from an external source such as
a gas or water meter. The registers are
accessed via an intelligent source (such as a
modem) and can be viewed on the A1120/40
meter display.
The registers are configured as three sets,
External set 1, External set 2 and External
set 3.
Each register set has four associated registers and has its own formatting options that can be
configured using the Power Master Unit (Number of digits, Number of decimal places and display
scale).
The Display shows Register 2 of External Set 1
Each register has 16 digits. The user is able to select English text or create an OBIS code for each of
the twelve external registers.
Page 28
20 A1120/40 - Electronic Polyphase Meter
13 SECURITY FEATURES
Password Protection
The A1120/40 meter uses a Password as part of the security algorithm. The passwords must be
entered in upper case. Password protection can be disabled at manufacture if required.
Four levels of access are available.
Entering the correct password for levels 0, 1, 2 and 3 allows the functions in Figure 9 to be
performed, higher levels giving access to the lower levels. Passwords may also be set to defaults
using the Power Master Unit.
It is important to note that the integrity of the A1120/40 meter passwords should always be
protected. This can be achieved by ensuring the ability to change passwords is controlled and only
made available to Administrative Personnel.
The level 3 password should be changed at regular intervals. It may be appropriate for no more
than 100 meters to be protected by the same level 3 password.
Calibration values, zeroing of registers etc. are protected by a security link that is removed at the
factory before the meter is sealed.
13.1 Data Retention
All cumulative register and time of use data is saved to non-volatile memory every time the power
to the meter fails and also every 2 hours. The data is recovered when power is restored to the
meter.
All data is retained for the nominal life of the meter.
13.2 Recordable Security Features
The following security features are available and can be included in the display sequence:
13.2.1 Phase Present/Phase Fail Indication
The meter detects and stores the number of phase fail events to a maximum of 65535.
The register will then roll over to 0. A time and date stamp of the three most recent events is
recorded. The phase fail threshold can be set between 0 and 250 V.
Phase indication on the display (L1, L2, L3) has the following options:
Indicator ‘on’ when phase present
Indicator ‘on’ when phase failed
Where a meter is to be used on a supply with less than 4 wires, it is possible to disable the
monitoring and display of phases L2 and L3.
13.2.2 Reverse Energy Flow
Reverse run event count
The meter detects and stores the number of reverse running events to a maximum of 65535. The
register will then roll over to 0.
A time and date stamp of the three most recent events is recorded.
The count and time and date stamps can be included in the display sequence.
An event is detected if the meter runs in reverse for a period greater than 5 seconds.
Reverse energy reading
Irrespective of whether the meter is set to import only power flow insensitive mode, reverse kWh
power flow will be independently recorded.
Theft Resistant Measurement
Theft Resistant Measurement mode measures the sum of the modulus of each phase
(│kWh [L
]│ + │kWh [L2]│ + │kWh [L3]│)
1
The Reverse Energy Event Alarm, Reverse Energy Count and Reverse kWh Register respond
only to reverse power flow and continue to function as in normal operation.
Reverse energy Alarm (Import only meter)
The reverse run indication, which responds to the total system power flow, can be inhibited if
required.
Per Phase Reverse Run Indication
Any phase in reverse run can be indicated on the Liquid Crystal Display by flashing the L
phase indicators.
L
3
13.2.3 Power Fail
A count of the cumulative number of power downs to a maximum of 65,535 is recorded.
The register will then roll over to 0.
A time and date stamp of the three most recent events is recorded. The count and time and date
stamps can be included in the display sequence.
13.2.4 End of Billing Event
A count of the number of end of billing events to a maximum of 65,535 is recorded.
The register will then roll over to 0. Time and date stamps together with the source of the billing
reset for the three most recent events is recorded. The count and time and date stamps can be
included in the display sequence.
The message ‘Reset’ is displayed each time an End of Billing event takes place.
13.2.5 Programming Event Log
, L2 or
1
A count of the number of programming events to a maximum of 65,535 is recorded. A time and
date stamp of the three most recent events together with the source (optical or RS232 data port)
is recorded. The identity of the programming user is also stored. The count and time and date
stamps can be included in the display sequence.
Note: Programming events are communications sessions where the meter configuration or data
has been changed. Reading data only does not count as a programming event.
Page 30
22 A1120/40 - Electronic Polyphase Meter
13.2.6 CT Ratio Programming
The CT ratio can be displayed as a ratio or as a scalar quantity. A count of the number of CT
Ratio reprogramming events to a maximum of 65,535 is recorded together with source (Optical or
RS232 port) and time and date stamps for the three most recent events. The identity of the
programming user is also stored. The count and time and date stamp can be included in the
display sequence.
Note: CT Ratio Reprogramming Events are communications sessions where the primary or
secondary value of the CT has been changed.
An End of Billing Reset can be requested with a CT ratio change.
A CT Programming switch can be fitted as a manufacturing option. The switch must be activated
in order to change the CT ratio. The switch is under the terminal cover and may be protected by a
paper seal.
13.2.7 Watchdog (Transient Reset)
A count of the number of watchdog resets to a maximum of 65,535 is recorded together with time
and date stamps for the three most recent events. The count and time and date stamps can be
included in the display sequence.
13.2.8 In Service Hours
The elapsed time counter records the cumulative time (to a resolution of 1 hour) the meter has
been powered up. The count can be included in the display sequence.
The amount of storage is in excess of 25 years.
13.2.9 Meter Errors
An alarm can be displayed if an error occurs. The alarm and error message
(See Figure 8, Display table) can be disabled via the Power Master Unit.
Access to the data is via the optical port, the RS232 data port or on the LCD.
A time and date stamp of the three most recent non-fatal error events is recorded where possible.
In the unlikely event that any of the above meter errors occur, a catastrophic failure has been
detected and the meter should be returned to Elster Metering for failure investigation.
13.2.10 Cover Removal Detection
Main Cover
As a manufacturing option the main cover can be fitted with a tamper switch to detect removal.
The number of times the cover has been removed to a maximum of 65,535 is recorded together
with the time and date stamps of the last three occurrences. The count and time and date stamps
can be included in the display sequence.
Note: The main cover removal option is not available when the meter is configured for CT Ratio
Programming Switch.
As a manufacturing option the meter can be fitted with a tamper switch to detect removal of the
terminal cover. The number of times the cover has been removed to a maximum of 65,535 is
recorded together with the time and date stamps of the last 3 occurrences.
The count and time and date stamps can be included in the display sequence.
13.2.11 Remaining Internal Battery Life
The A1120/40 provides a count of the number of hours of life left in the internal battery.
The count can be included in the display sequence.
The count is calculated by subtracting the amount of time the meter has been supported during
power outages from the initial battery life estimate.
13.3 Historical Data
At each End of Billing the following data is stored to historical registers:
Meter Data
• Cumulative Registers
• TOU Registers
• TOU MD Registers
There are 15 sets of historical registers
Event Data
• Reverse running count, last 3 time and date stamps
• Billing events count, last 3 time and date stamps
• Power failures count, last 3 time and date stamps
• Meter errors, last 3 time and date stamps of non fatal errors
• Watchdog resets count, last 3 time and date stamps
• Programming events count, last 3 time and date stamps
• Phase failures (L
• CT ratio programming events count, last 3 time and date stamps
• External battery failures count, last 3 time and date stamps
• Number of times the terminal cover has been removed, last 3 time and date stamps
• Number of times the main cover has been removed, last 3 time and date stamps
• In-service hours
• Internal battery life
Note that for Version C meters the Time and Date Stamps can be in Base Time or daylight
Savings Time.
, L2 or L3) count, last 3 time and date stamps
1
Page 32
24 A1120/40 - Electronic Polyphase Meter
E
D
R
Measurement
14 METER DISPLAY
14.1 Introduction
The A1120/40 meter is fitted with a high contrast liquid crystal display that can be viewed from a
wide angle. The main display characters are 9.8mm high.
The display can be configured using the Power Master Unit to display data with English
descriptors or OBIS (Object Identification System) format.
The Test Display with a description of the displayed legend (English or OBIS) is shown below.
English Identifier
OBIS Code
nglish
escription
everse Run
Register, Time,
Da te, Sec urity Da ta
Units of Quantity
M, k, W, V, A , r, h
Multiplier
X10, X100
Alarm
14.2 General
Display Resolution
he resolution of the display can be set at manufacture to 7, 6 or 5 digits.
T
The decimal point indicator can be configured to be a point or a comma and set to 0,
1 or 2 places.
The display is a window of this. e.g. 1 2 3 4 5 6 7 8 9 0 1 2 3. 4 5 6
Seven Digits Six Digits Five Digits
4 5 6 7 8 9 0
5 6 7 8 9 0. 1
6 7 8 9 0. 1 2
Phase
Indicators
5 6 7 8 9 0
6 7 9 9 0. 1
7 8 9 0. 1 2
Chevrons
Energy Flow
Dire ctio n
6 7 8 9 0
7 8 9 0. 1
8 9 0. 1 2
Units of Quantity and Multiplier
The Units of Quantity (Wh, kWh, MWh) and multiplier (x10,
x100) displayed are selectable by the Power Master Unit and
displayed in the top right corner of the display.
The display has two modes of operation, Default Mode and Utility Mode. Up to 40
displays can be made available for each mode of operation.
14.3.1 Default Mode
The Default Mode can operate in two ways, Auto-cycle or single step.
Auto-cycle
At power up the segment test pattern is shown. This will remain displayed for a period of 3
seconds.
The display will then sequence through the programmed displays, remaining on each display item
for one step duration time, called the Auto-cycle step duration
(2-30 seconds).
3 seconds
Step
Step mode is entered by a single press of the Display Pushbutton. The first display in the
autocycle sequence is displayed. Further presses of the pushbutton allow the consumer to step
through the autocycle display items, and then through the single step display items.
The display will default to autocycle mode at a programmed time after the last press of the display
pushbutton.
Next display 2-30 seconds
Display pushbutton press
Next display
Page 34
26 A1120/40 - Electronic Polyphase Meter
14.3.2 Utility Mode
It is necessary to break the seal on the Reset Pushbutton to enter ‘Utility’ mode.
The mode is entered by pressing the Reset Pushbutton. ‘Utility’ appears on the display.
Single presses of the Display pushbutton will then step through the utility displays.
The display will default to autocycle mode at a programmed time after the last press of the
Display Pushbutton, or if the Reset Pushbutton is again pressed.
Short press Reset Pushbutton
Press Display Pushbutton
Next display
14.3.3 English Display
Chevrons & Identifiers
The chevrons on the display have the following meaning:
Chevron/Description
Description
Import Security
Export
1 Import
2 Export
3 4 Security
5 6 7 -
The display identifiers give a description of the main register displayed.
Examples of the display are shown in Figures 7.
A full list of displays is given in Figure 8.
Identifiers
1 2 3 4 5 6 7
14.3.4 OBIS Display
The OBIS code gives a description of the main register displayed. OBIS Code
Chevron 7 indicates the register is active.
Examples of displays and a full list of displays are given in Figures 7
and 8 respectively.
A full list of displayable data items is given in Figure 8. Items available will depend on the meter
variant.
Segment Test Pattern
Cumulative Registers
Customer Defined Registers
Rising Demand Registers
TOU Maximum Demand
TOU Registers
Historical Registers
Security
Instrumentation
Phase Failure
CT Ratio
Tariff CRC
Meter Errors
Dial Test
For dial testing, the cumulative kWh and kvarh displays can be set to a higher resolution by using
the Power Master Unit.
The resolution of the display can be configured to 0, 1, 2, 3 or 4 decimal places
Note: If the display is configured for Wh with no multiplier set, the maximum resolution of the
display is 3 decimal places.
The meter will cease using dial test resolution when instructed by the Power Master Unit, or after
a programmable number of power cycles.
Display Indicators
System Reverse Run Indicator
Phase Failure Indication
Per Phase Reverse Run Indication
Error/Alarm
Energy Direction Indicators
Communications Indication
When communications are taking place the following indicators are displayed in the top left corner
of the display.
o Optical communication
r RS232 Communication
Figure 7 shows examples of the display. The indicators can be disabled via the Power Master
Unit.
Page 36
28 A1120/40 - Electronic Polyphase Meter
15 USING THE PUSHBUTTONS
Two pushbuttons can be provided as an option. Their use is as follows:
Default Display Mode
A short press of the display (right pushbutton) enters consumer display mode at the first display in
the autocycle display sequence. Single presses of the display pushbutton allow the user to step
through the consumer display sequence. The display will default to auto cycle mode at a
programmed time after the last press of the consumer display pushbutton.
Utility Display Mode
A short press of the Reset (left pushbutton) enters the utility display mode at the first display in
the utility sequence. Single presses of the display (right pushbutton) allow the user to step
through the utility display sequence. The display will default to auto cycle mode at a programmed
time after the last press of the display pushbutton, or if the Reset pushbutton is presses again.
Billing Reset
A Billing Reset can be initiated by holding both of the pushbuttons pressed for approximately 3
seconds. The billing reset pushbutton can be disabled by using the Power Master Unit.
As a further option, a message that a billing ‘reset’ has been initiated can be displayed.
External Battery Support (Optional)
Pressing either pushbutton allows the displays to be read and optical communications to be
established during power outages (See Appendix D).
16 COMMUNICATIONS
Communications with an A1120/40 can be established via the IEC 62056-21(formerly 1107) port
or via the optional RS232 Port. A symbol can be displayed in the top left corner of the display
which gives an indication of the type of communications currently taking place.
16.1 Optical Communications Port
A bi-directional infra red communications port is provided to allow
reading of all stored data (measurement, diagnostic and current
personality) and programming of "personality" data. Data Stream Mode
(See Section 16.3) allows a fast method of retrieving all data from the
meter.
The port is accessible through the front of the main cover and interfaces
to a hand held unit or computer. In normal operation the port only
operates when the meter is powered from the a.c. supply.
An optional battery (See Section 20) supports the port during power
outages. This facility is limited to reading data only.
An RJ11 connector provides RS232 communications. The port allows access to the same data as
the optical port, using the same protocol. The port operates at speeds of up to 9600 baud. Data
Stream Mode (See Section 16.3) allows a fast method of retrieving all data.
The RS232 port supports multi drop mode, allowing up to 10 meters (RS232) or 32 meters
(RS485) to be accessed from a PC (See Appendix B).
16.2.1 Modem Power Supply
The RS232 port allows different modules to be added that can support different means of
communications (PSTN, Ethernet, GSM etc).
An isolated internal d.c. supply to power the modem is provided via the RJ11 socket
Nominal Voltage: ≥+6V with mean load ≤500mA
The power is sufficient to support a GSM modem
16.2.2 Resetting the Power Supply
If a modem is installed which draws too much power from the meter, a transient reset occurs and
the modem power supply is disabled to prevent continuous resetting of the meter. On early
versions of A1120/40 meter only, the RS232 port may also be disabled. The power supply (and
RS232 port on early versions of the meter) can be re-enabled using the PMU via the IEC 1107
port or by using the following sequence:
Step to the ‘GSM signal strength’ display in the Utility Display section of the meter
Press the display and utility pushbuttons together for several seconds until ‘PSU On’ is displayed
If the meter generates another reset, an alternative modem should be fitted and the power supply
re-enabled as above.
16.3 Data Stream Mode
Data stream mode allows fast reading of all metering data (90 days of 30 minute, one channel
data in 30 seconds). To achieve this, the meter and modem device must be configured to 8 bits,
no parity, 1 stop bit (Selectable via the Power Master Unit).
Page 38
30 A1120/40 - Electronic Polyphase Meter
17 PROGRAMMING THE METER
The meter can be programmed via the optical port or via the RS232 port. The optical port can be
connected either directly to a PC (IBM compatible) or to a Hand Held Unit. In both cases an IEC
62056-21 (formerly 1107) Probe is required.
Information for the meter is first prepared on forms within the Power Master Unit Software (Refer
to Master Unit Software M181 001 3).
The meter does not check to ensure that reprogramming has been completed, therefore at the
end of a reprogramming session all data should be read back to confirm the meter is
programmed correctly.
If communications fail during programming a failure message is displayed.
Each time the meter is reprogrammed, the programming counter is incremented and the time and
date of the event is recorded. The user who created the scheme in the PMU is recorded.
Note: The programming counter does not increment when a 'Set time' or 'Time and date
adjustment' only is programmed to the meter.
18 REAL TIME CLOCK AND CALENDAR
The clock uses the notation 00:00 to 23:59. The calendar automatically caters for leap years.
Note: - For time stamps 00:00 indicates the start of the day and 24:00 the end of the day.
The time base for the clock is a programmable option. It can be derived from either the a.c.
supply frequency or from a crystal controlled oscillator.
When the clock is synchronised to the mains frequency, it maintains synchronisation for
variations of up to +/- 5% of nominal mains frequency. Outside these limits the meter switches to
the crystal oscillator and then switches back to mains when the frequency is back within limits.
Crystal calibration achieves an internal accuracy of better than 0.5 of a second per day at
reference temperature. In the event of a supply failure a backup battery supports the crystal
oscillator, which maintains timekeeping.
There are two methods of adjusting the meter clock:
1. The time and date of the clock may be set via the IEC 62056-21 optical port or RS232
communications port (if fitted) provided the correct (level 2 or higher) password is used.
2. If a request for a small adjustment (-7.5 minutes to +7.5 minutes) to the current setting is
made (with appropriate password), this adjustment will be applied by shortening or
lengthening subsequent demand periods by 5 seconds until the whole of the adjustment has
been achieved.
The A1120/40 has an internal battery that supports the clock and calendar.
An optional external battery that supports the reading of meter data and display facilities during
power outages can be provided.
19.1 Internal Battery
In the event of an a.c. failure, an internal battery (a Lithium ‘coin’ cell) supports the real time
clock.
The battery is soldered onto the printed circuit board.
The meter can be programmed to initiate one of the following courses of action should the supply
fail and the battery become exhausted. When the supply returns: -
a. Freeze the TOU registers and increment the total cumulative registers only
b. Assume the last known time and continue to use the TOU registers
See Section 29 for battery disposal.
19.1.1 Internal Battery Monitoring
The battery provides support for the life of the meter. The following functions are provided on the
Battery Monitor: -
Elapsed Time - The total amount of battery support time is monitored. The elapsed time counter
decrements to represent the use/shelf life of the battery.
Remaining Time - The remaining battery life is calculated by subtracting the elapsed time from
the expected time. The remaining life may be read via the optical or RS232 communications port
and its value optionally included in the display sequence.
If the remaining time falls to zero, a ‘flag’ is set which can be read by via the optical port or RS232
port.
Failed Battery - The occurrence of total battery fail is monitored each time the meter is
energised. A flag is set and the time and date recorded when the meter last powered down.
Page 40
32 A1120/40 - Electronic Polyphase Meter
20 MODULE/BATTERY CARRIER
A Special housing can be supplied as an option for a Module or External Battery. Molex Connector
20.1 Communications Module
Simple installation
Snap in position
Sealable (under the terminal cover)
Connects to the meter via a 'RJ11' connector
Refer to Chapter 3 (M181 001 3) Communications Modules
20.2 External Battery Module
Simple installation
Snap in position
Sealable (under the terminal cover)
Connects to the meter via a 'Molex' connector
Refer to Appendix D, External Battery Module
21 OUTPUT
An optional output can be provided. This output can be set at manufacture to one of the following
options:
SO output, floating, customer configurable pulse duration/value
Care should be taken in selecting the combination of pulse width and pulses/unit.
Avoid combinations that may give insufficient spacing between pulses at maximum load.
To ensure correct operation a maximum of 10 pulses/sec should not be exceeded.
When the meter is in anti-creep mode the output does not pulse.
Rate Indication
The output can be sourced (using the Power Master Unit) to provide indication of an active rate.
The output becomes low impedance if any one of a selected combination of TOU or MD TOU tariffs
is activate.
Page 42
34 A1120/40 - Electronic Polyphase Meter
21.2 Test Indication (Manufacturing option)
The output can be configured at manufacture to generate pulses that replicate the kWh LED or
the kvarh LED.
This option is desirable if meter accuracy verification must be performed without using optical
pickups. When configured in this way the auxiliary output pulse width and LED pulse width are
the same (approximately 6 ms).
22 ADDITIONAL VOLTAGE TERMINALS
As an option the A1120/40 can be supplied with additional terminals that allow external
equipment to be powered from the meter (See Figure 5).
WARNING
Connections made to these terminals will only be protected by the installation’s main fuse cutout.
The installer must ensure that additional local protection is provided for any circuits connected
to these terminals.
23 LOAD PROFILE RECORDING (A1140)
Ty pical Loa d Profi le Recording
4 Demand Values
(kW, kvar, kVA,
Customer Defined)
Demand Period End
The A1140 can be programmed to record up to four values from any of the rising demand registers
at the end of each integration period. Up to 300 days of 30 minute data can be stored for a single
channel. The number of day's storage is reduced if Instrumentation Profiling is configured, the
Number of Channels stored is increased or the Integration Period is reduced.
Channels Days
1 300
2 300
3 265
4 205
(30 minute integration period)
Power
Master Unit
Readings
Proprietary
Software
Readings
Integration period - 1, 2, 3, 4, 5, 6, 10, 15, 20, 30, 60 minutes. Common with the demand period.
Load profile data is stored with reference to either base time or daylight saving time.
•Base Time - Daylight savings have no effect on the demand period and 48 periods are stored
(assuming 30 minute integration period).
•Daylight savings time - When the clock advances, 46 periods will be stored. When the clock
retards, 50 periods will be stored (assuming 30 minute integration period).
Status information is also stored with each integration:
•Load profile event indication with time and date stamps – Power up, Power down, Time
change, Configuration change, New day, Daylight savings, Forced end of demand.
•Load profile status indication per period – Transient reset, Time synchronisation, Data
change, CT ratio change, Internal battery failure, Reverse run, Phase failure (one or more
phases).
When storage is full, new data overwrites the oldest stored data.
Using Data Stream Mode (9600 baud rate), 90 days of single channel, 30 minute demand period
data can be read in less than 30 seconds.
Two methods of reading load profile data are provided:
• Number of day’s data up to and including the current day
• From day x up to and including day y.
Load profiles can be transferred to the Power Master Unit and viewed in Readings.
24 INSTRUMENTATION
The A1120/40 calculates the following instrumentation values:
Volts (Phase A, B, C)
Current (Phase A, B, C)
Watts (Phase A, B, C, System)
Phase Angle (Phase A, B, C)
Phase Rotation (Phase A, B, C)
Power Factor (Phase A, B, C, System)
Frequency (Phase A, B, C)
Instrumentation values can be included in the display sequence.
Page 44
36 A1120/40 - Electronic Polyphase Meter
25 TECHNICAL DATA
Current: Standard Range (direct connected)
Extended Range (direct connected)
Standard Range (CT operated)
Extended Range (CT operated)
Frequency
Reference Voltage
Voltage Operating range
System Connection - 2 element meter
- 3 element meter
Short Circuit Current
Burden of Voltage Circuits 230V
Burden of Current Circuits (10 – 100A meter)
Burden of CT Operated Meters
Insulation
Impulse Withstand
Display 9.8mm characters, high contrast, wide viewing angle
Meter Constant (pulsing LED output) 1,000 p/kWh (kvarh) Direct connected
Pulse Output Specification
SO Output (12 kV isolation)
100mA Relay Output (12 kV isolation)
300mA Relay Output (12 kV isolation)
Product Life
Certified Life
Temperature
Humidity
Maximum Dimensions
Weight
Accuracy Class kWh
kWh
kvar
Case DIN 43857 Part 2 and Part 4 (except for top fixing centre)
Terminals Main
Auxiliary
20 - 100A, 10 - 100A
5 - 100A
1 - 2A, 5 - 10A
1 - 10A
50 or 60Hz
220V - 240V (L – N)
220V - 240V (L – L)
105V - 127V (L – N)
105V - 127V (L – L)
±20%
3 phase 3 wire
3 phase 4 wire
2 phases of 3 phase 4 wire
2 phase 3 wire
1 phase 3 wire
1 phase 2 wire
30 Imax
0.8W, 1.3VA
4VA @ 100A/phase [max]
0.22VA per phase
4kV RMS
12kV 1.2/50μs 40 ohm source
10,000p/kWh (kvarh) CT Operated
Approximately 6ms Pulse width
27V d.c. 27 mA, IEC 62053-31 (Transistor Output)
230V a.c or d.c, 100mA
230V a.c 300mA
15 years
10 years
Operational range: -25° C to +65° C
Storage Range: -25° C to +85° C
Condensing (See note below)
Annual Mean 75% (95% for 30 days spread over one year)
233mm (High) x 174 mm (Wide) x 50mm (Deep)
904 grams
EN 62053-21/22 - Class 0.5s, 1 or 2
EC Directive 2004/22/EC (MID) - Class A, B or C
EN 62053-23 - Class 2 or Class 3
IP53 to IEC 60529:1989
EMC Directive 89/336/EEC
8.2mm bores, M6 Terminal Screws – max torque 2.8 N m
9.0mm bores, M6 Terminal Screws – max torque 2.8 N m
9.5mm bores, M6 Terminal Screws – max torque 2.8 N m
3.2 mm bores, M3 Terminal Screws – max torque 0.45 N
Note: Sample meters have successfully passed the “Damp heat cyclic” test given in section 6.3.4 of
EN50470-1. However, for maximum operational life, it is recommended that installation sites are
chosen where condensation is unlikely to occur.
Remove the meter from its packaging and inspect for damage.
Check that there is no movement or loose parts within the meter enclosure.
If damage has been sustained in transit, an immediate claim should be made to the Transport
Company, and a report sent to the Elster Metering Systems branch office or agent.
WARNING
Removal of the main cover seals will invalidate certification.
The meter type and rating must be correct for the intended application.
26.2 Handling
Once removed from the packaging, meters must be treated with care and not subjected to
excessive shock or mechanical vibration.
Care should be taken to avoid marking or scratching the meter case and polycarbonate cover.
26.3 Storage
If the meter is not required for immediate use, it should be returned to the original packing
(including plastic bag) and stored in a clean, dry environment.
Storage temperature: -25° C to +85° C
26.4 Installation Site
The installation site should be a dry indoor environment and, as far as is practicable, away from
direct sunlight and free from mechanical shock and vibration.
26.5 Electromagnetic Compatibility (EMC)
The A1120/40 meter has been designed and tested for compliance with the EMC Directive.
It is, however, the responsibility of the installer for ensuring that a system conforms to the
Directive.
Page 46
38 A1120/40 - Electronic Polyphase Meter
In order to assist the installer the following guidelines are given: -
1. Keep a.c. circuits and d.c. circuits separated by a minimum of 50mm where possible
2.Where a.c. and d.c. circuits must cross, do so at right angles to each other
3. The cables for each circuit must be bunched together to minimise the loop
4. area enclosed
5. The cables for the pulsing output must use a twisted pair. Where the environment is
electrically hostile, screened twisted pair cable may be required. The screen must be
connected to earth at one point only
6. Ancillary equipment must also be CE marked
7. If interposing relays are used (a.c. or d.c.) then these must be correctly and adequately
suppressed
26.6 Fixing and Connection
WARNING
Installation must always be carried out by appropriately trained and qualified personnel in
accordance with normal metering custom and practice.
The installer is responsible for the choice of connecting cables which must be appropriate for the
voltage and current rating of the meter and for ensuring that the supply is properly fused. For
direct current meters, 25mm
to the meter rating. i.e. 100A fuse for a 100A meter. Failure to do so may result in damage or fire.
Connections to the auxiliary voltage terminals will only be protected by the installation’s main fuse
cut-out. The installer must ensure that additional local protection is provided for any circuits
connected to these terminals.
Refer to the connection diagrams inside the terminal cover, paying particular attention to the
auxiliary terminal configuration.
Isolate all circuits before carrying out the installation.
Refer to the nameplate to ensure that the correct meter is being installed.
Failure to comply with these instructions may result in damage, fire and/or electric shock.
2
cables are recommended. Meters must be protected by fuses equal
To mount the meter on the meter board
Remove the meter terminal cover.
Fix a 5mm dia. x 13mm long round headed wood screw into the meter board to accommodate the
keyhole fixing aperture at the back of the meter. Note that a choice of two fixing points is available
for the upper fixing screw (see figure 6). Leave the shank of the screw projecting from the board by
4.5 mm.
Hang the meter on the screw and align it to be vertical.
Secure the lower end of the meter to the board using two 5mm dia. x 13mm long round head
screws through the lower mounting holes in the area of the terminal chamber.
Tighten screws just sufficiently to prevent movement of the meter.
Do not over-tighten the screws or the meter base may be damaged.
For connecting to the large diameter terminals, strip back the cable insulation by 26mm.
Fully insert cables into the terminals so that the insulation butts up into the counter-sunk recesses
in the bottom face of the terminal block.
Using a Number 2 Phillips or flat blade screwdriver, tighten the M6 terminal screws to a torque of
between 2.2N m (minimum), 2.8N m (maximum).
Auxiliary terminal connections should be completed with appropriately sized cable.
The M3 terminal screws should be tightened using a Number 1 Phillips or flat blade screwdriver
to a maximum torque of 0.45N m.
Where connections are taken from the auxiliary voltage terminals, appropriate fuses should be
incorporated to protect these circuits.
If a battery (for read without power) is installed in the module housing, the battery must be
connected before mains supplies are energised.
It is also recommended that connections to the meter’s RJ11 connector are made with the meter
supplies isolated.
27 COMMISSIONING
WARNING
Commissioning must only be carried out by appropriately trained and qualified personnel.
Check that the supply rating on the meter nameplate corresponds to the system rating.
Removal of the meter cover seals will invalidate certification.
With the system de-energised, check the cable connections are secure and correct to the wiring
diagram fitted under the terminal cover
Refit and seal the terminal cover. Energise and load the system
At power-up, ensure all segments of the LCD show in the test pattern
Check that the display is cycling through the display sequence
Check that the LED test indicators are illuminated or flashing
Check the operation of the pulse output (if fitted)
Check operation of the RS232 port (if fitted)
Carry out load checks as necessary
Page 48
40 A1120/40 - Electronic Polyphase Meter
28 MAINTENANCE
No maintenance is necessary during the meter's normal working life.
29 DISPOSAL AND RECYCLING
Liquid Crystal Display
Liquid crystals are toxic. If a display is damaged, avoid contact with the liquid. If the liquid makes
contact with the skin it must be washed off immediately with water. Seek medical advice.
Recycling Materials
The following meter materials are recyclable: polycarbonates, metals and printed circuit board
(see Safety Warning in Section 2).
Major plastic parts are marked with recycling information. On the disposal of a meter, every
endeavour should be made to comply with local environmental legislation regarding recovering
materials and waste disposal.
Batteries
If the main cover is re
exposed.
This battery is completely safe under normal conditions. However, it must never be
disassembled, heated above 100°C, incinerated, nor have the contents exposed to water.
Fire, explosion or severe burns may result if these instructions are disregarded.
In the interests of safety, environmental protection and possible legislation, Lithium batteries
require careful disposal.
Before arranging for the disposal of these cells, users should satisfy themselves that the
proposed means of disposal is both safe and compliant with local legislation requirements.
Elster Metering Systems would like to draw the user's attention to the International Standard for
Lithium Batteries - IEC 60084-4. - which gives further information about the handling, storage,
transport and disposal of Lithium cells.
The user should contact Elster Metering Systems should difficulties arise in arranging proper
disposal. They will if practical, help the user identify safe disposal means.
An optional battery may be housed in a module housing attached to the meter.
The battery is a non re-chargeable, alkaline zinc manganese dioxide, PP3 size. Where local
legislation places restraint on the disposal of this type of battery, the requirements of that
legislation should be obeyed.
moved from the meter then a Lithium manganese dioxide battery will be
PRODUCT/TERMINATION
Polyphase, BS/DIN termination L M
SERVICE TYPE
3Ph 4W for use on:
3Ph 3W
CURRENT RANGE
Direct Connected 20A – * (* is any multiple of Ib up to 100A maximum) A
Direct Connected 10A – * (* is any multiple of Ib up to 100A maximum) B
Direct Connected 5A – * (* is any multiple of Ib up to 100A maximum) C
CT Operated 1A – 2A L
CT Operated 5A – 10A M
CT Operated 1A – 10A N
Direct Connected (10A - 100A) -40ْ to 70ْ C operation P
VOLTAGE
220 - 240V (L - N) (See note 2 for Ref voltage ranges) A
220 - 240V (L - L) (See note 2 for Ref voltage ranges) (LM2****** variants only) B
105 - 127V (L - N) (See note 2 for Ref voltage ranges) Not OFGEM Approved C
105 - 127V (L - L) (See note 2 for Ref voltage ranges) (LM2****** variants only) Not OFGEM Approved D
ACCURACY CLASS
50 Hz Cl.1 kWh, Cl.2 kvarh (IEC 62053-21, 23 see note 1) B
50 Hz Cl.2 kWh, Cl.3 kvarh (IEC 62053-21, 23 see note 1) C
60 Hz Cl.1 kWh, Cl.2 kvarh (IEC 62053-21, 23 see note 1) Not OFGEM Approved E
60 Hz Cl.2 kWh, Cl.3 kvarh (IEC 62053-21, 23 see note 1) Not OFGEM Approved F
HARDWARE - SWITCHES
No tamper detect switches N
Two tamper detect switches B
Terminal cover tamper detect switch and CT ratio programming protection switch C
HARDWARE - BUTTONS
No buttons N
Two buttons B
Backlit LCD with no buttons C
Backlit LCD with twom buttons D
HARDWARE - BATTERY
No external battery connection
External Battery connection. Note! External battery module cannot be fitted when an RS232 comms module is fitted B
Supercapacitor/External battery/RS485 module connection C
OPERATIONAL MODES
Import kWh only
Import kWh, Q1 and Q4 kvarh
Import kWh, Q1, Q2, Q3, Q4 kvarh and Imp kVAh
Imp/Exp kWh
Imp/Exp kWh, Q1, Q2, Q3, and Q4 kvarh
Imp/Exp kWh and Imp/Exp kVAh
Imp/Exp kWh, Q1, Q2, Q3, Q4 kvarh and Imp/Exp kVAh
Import kWh only (Power Flow Insensitive)
Import kWh, Q1 and Q4 kvarh (Power Flow Insensitive)
Import kWh, Q1, Q2, Q3, Q4 kvarh and Imp kVAh (Power Flow Insensitive)
Import kWh only (Theft Resistant Measurement)
Import kWh, Q1 and Q4 kvarh (Theft Resistant Measurement)
Import kWh, Q1, Q2, Q3, Q4 kvarh and Imp kVAh (Theft Resistant Measurement)
TARIFFS
A1120 Multi Rate
A1140 Multi Rate (with load profile)
A1120 Multi Rate with password protected register zeroing and zero level time shift
A1140 (with load profile) Multi Rate with password protected register zeroing and zero level time shift
AUXILIARY OUTPUT
No Output N
SO output, floating, 2 aux terminals. 12 kV isolation (Configurable pulse duration/value) 27V DA only
SO output, floating, 2 aux terminals. 12 kV isolation, replicating centre LED (kWh) 27V DA only
SO output, floating, 2 aux terminals. 12 kV isolation, replicating left hand LED (kvarh) 27V DA only
Relay output, floating, 2 aux terminals. 12 kV isolation (Configurable pulse duration/value) 230V AC, DC
Relay output, floating, 2 aux terminals. 12 kV isolation, replicating centre LED (kWh) 230V AC, DC
Relay output, floating, 2 aux terminals. 12 kV isolation, replicating left hand LED (kvarh) 230V AC, DC
300mA Relay output, floating, 2 aux terminals, 12kV isolation, indicating tariff/MD state, 230V a.c only
COMMUNICATIONS
No Serial Comms N
RS232 serial Comms Note! RS232 Comms module cannot be fitted when an external battery module is fitted R
OTHER OPTIONS
Standard (Extended) Terminal cover B
Standard (Extended) Terminal cover with cut-out C
Standard (Extended) Terminal plus 9.0mm main terminal bores D
Short Terminal Cover E
Standard (Extended) Terminal cover with additional voltage terminals F
Standard (Extended) Terminal cover with cut-out and additional voltage terminals G
Standard (Extended) Terminal cover plus 9.0 mm mail terminal bores and additional voltage terminals H
Standard (Extended) Terminal cover plus 9.5 mm main terminal bores J
Standard (Extended) Terminal cover and main cover with voltage disconnect protection
Standard (Extended) Terminal cover with slotted head screws
Standard (Extended) Terminal cover with cut-out and slotted head screws
Short terminal cover with slotted head screws
TYPE (nameplate)
MODEL
max
example:
L M 3 A A B N N B B B N N B - A N
3 2
N
B
C
D
E
F
G
H
J
K
L
R
S
T
P
A
R
S
D
U
T
K
L
M
P
B
C
D
E
Figure 1 - Model Code
Page 50
42 A1120/40 - Electronic Polyphase Meter
VERSION
8 TOU Registers, 4 MD Registers, 15 Historical Registers, DSM - see Note 4 - A
8 TOU Registers, 4 MD Registers, 15 Historical Registers, DSM, DLS time stamps and 12 external registers - Note! All new customers from November 2007 - see
Note 4
8 TOU Registers, 4 TOU Registers, 15 Historical Registers, DSM, DLS Time stamps, 12 External Registers and Daily Billing F
8 TOU Registers, 4 TOU Registers, 15 Historical Registers, DSM, DLS Time stamps, 12 External Registers - Note! Register zeroing by use of "Register Zeroing Tool"
is NOT available in this option
Revision Suffix
Firmware 2-01178-Q (Version A only). Enhanced GPRS and COP 10 Q
Firmware 2-01322-K (Version C) Enhanced GPRS and COP 10 K
Firmware 2-01340-B (Version F) Daily Billing B
Firmware 2-01345-A (Version G) Enhanced GPRS & COP 10. No register zeroing Z
SPECIAL ADDITIONS FIRMWARE
None N
Additional Firmware Function for ESCOM only (Phase angle definition as A1700 A
SPECIAL ADDITIONS HARDWARE
NONE N
Notes
Note 1: CURRENT RATINGS
IEC/EN 62052-11 defines only Basic, Reference and Maximum currents as follows:
Basic Current (Ib) Direct ConnectedStandard values: 5, 10, 15, 20, 30, 40, 50A Exceptional
Reference Current (In) CT Operated Standard values: 1, 2, 5A
Exceptional values: 1.5, 2.5A
Direct Connected Maximum current (Imax) shall preferably be an integral multiple of Ib.
Direct Connected A1120/A1140 meters may have Imax values up to a maximum of 100A
CT Operated shall have maximum currents of 1.2 In, 1.5 In and 2 In
CT Operated A1120/A1140 meters may be:
1 - 2A (suitable for use as 1 - 1.2A, 1 - 1.5A, or 1 - 2A)
5 - 10A (suitable for use as 5 - 6A, 5 - 7.5A, or 5 - 10A)
1 - 10A (suitable for use with any of the above 6 ratings)
EN 50470-1 (MID) defines basic values or Itr from which Imin, Iref and Imax can be derived
Basic values of Itr Direct Connected 0.5, 1, 1.5, 2A
Basic values of Itr CT Operated 0.05, 0.1, 0.25
Imin, Iref and Imax have been chosen so that the following relationships are met
Direct Connected, Class A Imin <
CT Operated, Class A Imin <
Direct Connected, Class B Imin <
CT Operated, Class B Imin <
Note 2: VOLTAGE RATINGS
Of the values IEC/EN 62052-11 defines for reference voltages, the following may be accepted
Ref Voltages for meters not connected through current transformers
Meters with marked currents and voltages other than the above values CANNOT be provided when the nameplate
shows the IEC/EN Standard Number.
If a valid requirement exists for meters with marked values within the acceptable ranges, but not listed above, specific
arrangements to provide nameplates not showing the IEC/EN standard must be made.
Note 3: TEST INDICATOR OUTPUT VALUES
The following values are to be used for the Test Indicator LED outputs:
Voltage connections Voltage Links shown in open position Main cover removal or CT ratio programming switch
on a CT Meter. (whole current meters only) Terminal cover removal switch
Optional additional
Voltage terminal on
whole current meter
to connect external
battery
Molex connector
Element 1 Element 2 Element 3 Neutral Auxiliary
Terminals RJ 11
1 2 3 4 5 6 7 8 9 10 12 20 21
RJ 11 and Auxiliary Terminals
Auxiliary Terminals
RJ11 Socket
6 5 4 3 2 1
Main cover with voltage disconnect protection.
Note that this cover cannot be used if voltage terminals are fitted.
Terminal & RJ11 Numbering
Terminal RJ11
1
2
3
4
5
6
7
8
9
10
12
Auxiliary 20 positive
Element 1 - Line in
- Voltage terminal
- Line out
Element 2 - Line In
- Voltage Terminal
- Line Out
Element 3 - Line In
- Voltage Terminal
- Line Out
Neutral In
Neutral Out
21 negative
1
2
3
4
5
6
Rx (Input)
Tx (Output)
Rx (Input)
No Connection
Zero Volts
Modem Power Supply (+) Output
See Warning in Section 22 regarding protection for additional voltage terminals.
Description Units OBIS Display Code English Display
Segment Test - - - - Current Time - 0.9.1 - - Current Date - 0.9.2 - - -
Cumulative
Total Import kWh kWh 1.8.0 CUM 1 Total Export kWh kWh 2.8.0 CUM 2 Q1 kvarh kvarh 5.8.0 CUM - 1
Q2 kvarh kvarh 6.8.0 CUM - 2
Q3 kvarh kvarh 7.8.0 CUM - 3
Q4 kvarh kvarh 8.8.0 CUM - 4
kVAh 1 kVAh D.8.0 CUM - kVAh 2 kVAh E.8.0 CUM - Customer Defined 1 * A.8.0 CUM - Cd 1
Customer Defined 2 * B.8.0 CUM - Cd 2
Rising Demand
Total Import kW kW 1.4.0 DEM 1 Total Export kW kW 2.4.0 DEM 2 Q1 kvar kvar 5.4.0 DEM - 1
Q2 kvar kvar 6.4.0 DEM - 2
Q3 kvar kvar 7.4.0 DEM - 3
Q4 kvar kvar 8.4.0 DEM - 4
kVA 1 kVA D.4.0 DEM - kVA 2 kVA E.4.0 DEM - CD 1 * A.4.0 DEM - Cd 1
CD 2 * B.4.0 DEM - Cd 2
Cumulative MD (1-4)
Total Import kW kW 1.2.(1 - 4) CUM MAX DEM - 1 - 4
Total Export kW kW 2.2.(1 - 4) CUM MAX DEM - 1 - 4
Q1 kvar kvar 5.2.(1 - 4) CUM MAX DEM - 1 - 4
Q2 kvar kvar 6.2.(1 - 4) CUM MAX DEM - 1 - 4
Q3 kvar kvar 7.2.(1 - 4) CUM MAX DEM - 1 - 4
Q4 kvar kvar 8.2.(1 - 4) CUM MAX DEM - 1 - 4
kVA 1 kVA D.2.(1 - 4) CUM MAX DEM - 1 - 4
kVA 2 kVA E.2.(1 - 4 CUM MAX DEM - 1 - 4
1 - 4 CD 1 * A.2.(1 - 4) CUM MAX DEM - 1 - 4
1 - 4 CD 2 * B.2.(1 - 4) CUM MAX DEM - 1 - 4
Maximum Demand (1-4)
1 - 4 Import kW kW 1.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Import Time - 1.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Import Date - 1 .6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Export kW kW 2.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Export Time - 2.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Export Date - 2.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q1 kvar kvar 5.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q1 Time - 5.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q1 Date - 5.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q2 kvar kvar 6.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q2 Time - 6.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q2 Date - 6.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q3 kvar kvar 7.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q 3 Time - 7.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q3 Date - 7.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q4 kvar kvar 8.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q4 Time - 8.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 Q4 Date - 8.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 kVA 1 kVA D.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 kVA 1 Time - D.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 kVA 1 Date - D.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 kVA 2 kVA E.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 kVA 2 Time - E.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 kVA 2 Date - E.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 CD 1 * A.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 CD 1 Time * A.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 CD 1 1 Date * A.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 CD 2 * B.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 CD 2 Time * B.6.(1 - 4) MAX DEM - 1 - 4
1 - 4 CD 2 Date * B.6.(1 - 4) MAX DEM - 1 - 4
Note 1 * Identifier Chevron Index
Figure 8 - Display Table
Page 60
52 A1120/40 - Electronic Polyphase Meter
Description Units OBIS Display Code English Display
External Registers
Register Set 1 (1-4) - User selectable Cum - S1 - (1 - 4)
Register Set 2 (1-4) - User selectable Cum - S2 - (1 - 4)
Register Set 3 (1-4) - User selectable Cum - S3 - (1 - 4)
Security
Program Event Count - C.2.0 - 4 1
Program Event Time - C.2.0 - 4 1
Program Event Date - C.2.0 - 4 1
CT Ratio Change Count - C.72.0 - 4 2
CT Ratio Change Time - C.72.0 - 4 2
CT Ratio Change Date - C.72.0 - 4 2
Phase Fail Event Count - C.54.0 - 4 3
Phase Fail Event Time - C.54.0 - 4 3
Phase Fail Event Date - C.54.0 - 4 3
Power Fail Event Count - C.7.0 - 4 4
Power Fail Event Time - C.7.0 - 4 4
Power Fail Event Date - C.7.0 - 4 4
Rev Run Event Count - C.53.0 - 4 5
Rev Run Event Time - C.53.0 - 4 5
Rev Run Event Date - C.53.0 - 4 5
End Billing Count - 0.1.0 - 4 7
End Billing Time - 0.9.6 - 4 7
End Billing Date - 0.9.7 - 4 7
Main Cov RemCount - C.70.0 - 4 8
Main Cov Remove Time - C.70.0 - 4 8
Main Cov Remove Date - C.70.0 - 4 8
Term Cov Rem Count - C.71.0 - 4 9
Term Cov Remove Time - C.71.0 - 4 9
Term Cov Remove Date - C.71.0 - 4 9
Est Battery Life Remain - C.6.0 - 4 10
In Service Hours - C.8.0 - 4 11
Active Tariff CRC - C.80.1 - 4 CrC1
Deferred Tariff CRC - C.80.4 - 4 CrC4
CT Ratio - 0.4.2 4 Ct
EOB Events (All Meters) Code (HEX) Dis play
Program Date or Midnight 01 rESEt
Change of Season 02 rESEt
Deferred Tariff 04 rESEt
Serial Port Command 08 rESEt
Optical Port Command 10 rESEt
Billing Pushbutton Press 20 rESEt
CT Programming Event 40 rESEt
Battery Fail 80 rESEt
Meter Errors -
Power fail data - FF 0040 Error 0040
Period backup data error - FF 0080 Error 0080
ROM checksum error - FF 0100 Error 0100
I2C Bus error - FF 0200 Error 0200
Internal battery life
exceeded
Internal battery fail - FF 0800 Error 0800
Description Units OBIS Display Code English Display
Note 1 Identifier Chevron Index
Historical (Most recent only)
Total Import kWh kWh 1.8.0.1 CUM - H1
Total Export kWh kWh 2.8.0.1 CUM - H1
Q1 kvarh kvarh 5.8.0.1 CUM - H1
Q2 kvarh kvarh 6.8.0.1 CUM - H1
Q3 kvarh kvarh 7.8.0.1 CUM - H1
Q4 kvarh kvarh 8.8.0.1 CUM - H1
Import kVAh kVAh D.8.0.1 CUM - H1
Export kVAh kVAh E.8.0.1 CUM - H1
Customer Defined 1 * A.8.0.1 CUM - H1
Customer Defined 2 * B.8.0.1 CUM - H1
Historical MD’s
1 - 4 Import kW kW 1.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Import Time - 1.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Import Date - 1.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Export kW kW 2.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Export Time - 2.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Export Date - 2.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q1 kvar kvar 5.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q1 Time - 5.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q1 Date - 5.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q2 kvar kvar 6.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q2 Time - 6.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q2 Date - 6.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q3 kvar kvar 7.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q 3 Time - 7.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q3 Date - 7.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q4 kvar kvar 8.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q4 Time - 8.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 Q4 Date - 8.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 kVA 1 kVA D.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 kVA 1 Time - D.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 kVA 1 Date - D.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 kVA 2 kVA E.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 kVA 2 Time - E.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 kVA 2 Date - E.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 CD 1 * A.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 CD 1 Time * A.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 CD 1 Date * A.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 CD 2 * B.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 CD 2 Time * B.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
1 - 4 CD 2 Date * B.6.(1 - 4).1 MAX DEM - H1 (1 - 4)
Historical Registers
CUM MD 1- 4 Import kW kW 1.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD 1 - 4 Export kW kW 2.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD Q1 1 - 4 kvar kvar 5.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD Q2 1 - 4 kvar kvar 6.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD Q3 1 - 4 kvar kvar 7.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD Q4 1 - 4 kvar kvar 8.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD kVA 1 1 - 4 kVA kVA D.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD kVA 2 1 - 4 kVA kVA E.2.(1 - 4) 1 CUM MAX DEM - H1 (1 - 4)
CUM MD CD 1 1 - 4 * A.2.(1 - 4).1 CUM MAX DEM - H1 (1 - 4)
CUM MD CD 2 1 - 4 * B.2.(1 - 4).1 CUM MAX DEM - H1 (1 -4)
TOU 1 - 8 Import kWh kWh 1.8.(1 - 8).1 TOU - H1 (1 -8)
TOU 1 - 8 Export kWh kWh 2.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 Q1 kvarh kvarh 5.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 Q2 kvarh kvarh 6.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 Q3 kvarh kvarh 7.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 Q4 kvarh kvarh 8.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 kVAh 1 kVAh D.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 kVAh 2 kVAh E.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 CD 1 * A.8.(1 - 8).1 TOU - H1 (1 - 8)
TOU 1 - 8 CD 2 * B.8.(1 - 8).1 TOU - H1 (1 - 8)
Rev Run Count - C.53.0.1 - 4 H1 5
Phase Fail Count - C.54.0.1 - 4 H1 3
Power Fail Count - C.7.0.1 - 4 H1 4
Program Count - C.2.0.1 - 4 H1 1
CT Ratio Change Count - C.72.0.1 - 4 H1 2
Main Cover Remove Count - C.70.0.1 - 4 H1 8
Term Cover Remove Count - C.71.0.1 - 4 H1 9
End Billing Count - 0.1.0.1 - 4 H1 7
In Service Hours - C.8.0.1 - 4 H1 11
Estimated Battery Life - C.6.0.1 - 4 H1 10
Figure 8 - Display Table (continued)
Page 62
54 A1120/40 - Electronic Polyphase Meter
Description Units OBIS Display Code English Display
Note 1 Identifier Chevron Index
Instrumentation
Volts Phase A V 32.7.0 - - Ins A
Volts Phase B V 52.7.0 - - Ins B
Volts Phase C V 72.7.0 - - Ins C
Current Phase A A 31.7.0 - - Ins A
Current Phase B A 51.7.0 - - Ins B
Current Phase C A 71.7.0 - - Ins C
Watts Phase A kW 21.7.0 - - Ins A
Watts Phase B kW 41.7.0 - - Ins B
Watts Phase C kW 61.7.0 - - Ins C
Watts Phase System Import kW 1.7.0 - - Ins
Watts Phase System Export kW 2.7.0 - - Ins
Phase Angle Phase A - 81.7.4 - - Ins A
Phase Angle Phase B - 81.7.15 - - Ins B
Phase Angle Phase C - 81.7.26 - - Ins C
Phase Rotation - C.90.0 - - Ins
Power Factor Phase A - 33.7.0 - - Ins A
Power Factor Phase B - 53.7.0 - - Ins B
Power Factor Phase C - 73.7.0 - - Ins C
PF Phase System - 14.7.0 - - Ins
Frequency Phase A - 34.7.0 - - Ins A
Frequency Phase B - 54.7.0 - - Ins B
Frequency Phase C - 74.7.0 - - Ins C
Level 2 (Correct level 2 password [Read and Program])
All data listed in level 0 and 1
Correction to the time and date
End of Billing
Time set
Level 3 (Correct level 3 password [Read and Program])
All operations listed in levels 0, 1 and 2
Programming
Setting the passwords for Levels 1, 2 and 3
Protocol Timeouts
Figure 9 – Password Access Levels
Page 64
56 A1120/40 - Electronic Polyphase Meter
APPENDIX A - Checking kWh and kvarh Registration Accuracy
WARNING
Only trained and competent personnel, familiar with meter test procedures should carry out the
following operation.
A1 Introduction
Various methods of checking the accuracy of registration of the A1120/40 meter are available.
Methods using the LED test indicators and Register advances are described below.
A2 Checking Meter Accuracy Using the LED Test Indicator
The LED test indicators are configured at manufacture to pulse for import kWh and import kvarh
(import only meter) or pulse for import plus export kWh and kvarh (import/export or power flow
insensitive meters).
A2.1 Comparing the number of LED pulses with substandard meter register advance
What you will need
Suitable test equipment with a sensor to detect LED pulses
A suitable substandard meter (set to the same system configuration as the meter under test)
A counter for counting the number of LED pulses
Checking registration
In orde
seconds.
1. Connect the test equipment and a suitable load to the meter, then power up the meter
2. The right hand Test LED pulses for kWh
r to achieve a rep
eatability of 0.1% the test time at any load needs to be a minimum of 60
3. Run the test for a suitable duration and check the amount the substandard has advanced and
the number of pulses detected
Calculate the registration by dividing the number of pulses by the meter constant.
e.g. 994
1000 (meter constant)
Compare this kWh advance with the amount the substandard has advanced.
A2.2 Comparing LED pulses with substandard meter pulses
This method may be used where the test equipment has the facility to calculate meter errors
based on the pulse output from a substandard meter. It will be necessary to set the pulse value of
the meter under test (shown on the meter nameplate) into the meter test equipment.
The duration of each test must be at least 60 seconds
The number of LED pulses should be greater than:-
Itest x V x Pf x N x K
1000 x 60 V = System voltage
Pf = Power factor of test load
N = Number of system elements
K = LED pulse value, impulses/kWh
Itest = Test current
A3 Checking Meter Registration Accuracy from Register Advances
For these methods the advance of the meter register is used rather than the LED Test Indicator.
A3.1 Using the 'Dial Test' values on the meter display
Meters may be set to show cumulative kWh and kvarh registers
with increased resolution by using Power master Unit instructions
via the optical or RS232 port. Dial test displays can be programmed
to 0, 1, 2, 3 or 4 decimal places.
Import
The display resolution will revert to normal when a further appropriate instruction (Setting power
down count to zero) is received, or after a programmable number of power cycles.
What you will need
A suitable supply and load or a meter test bench.
Substandard meter with a kWh (kvarh) display.
For each measured quantity:
1. Connect the meter and substandard meter to the supply
2. Instruct the meter to show register to suitable dial test resolution
3. Record initial values of the meter and substandard meter registers
4. Apply a suitable load to cause a significant register advance
5. Switch off the load to stop the register advancing. Leave the supply connected
6. Record the final register readings, compute the advances and compare the meter advance
with the substandard advance
Page 66
58 A1120/40 - Electronic Polyphase Meter
r
APPENDIX B - RS232 Multi-drop Mode
A1120/40 meters allow up to 12 meters to be connected in RS232 multi-drop configuration. Twoway RJ11 adaptors will be required to link each meter in the chain.
B1 RS232 Multi-drop Installation Procedure
The connection diagram for RS232 multi-drop mode is shown below
1. Observe all Safety Warnings, Warnings, Precautions for handling electrostatic discharge sensitive devices and EMC Guidelines in Section 2
2. Remove the terminal cover from the meters. If the terminal cover plate is not in place, switch
off all supplies to the meter.
3. Connect a two-way RJ11 adaptor to the RJ11 port of the first meter in the multi-drop chain
4. Connect an RS232 cable from the PC to the first port of the RJ11 as shown below
5. Connect a Flat Pin Cable to the second port of the RJ11 adaptor
6. Replace the terminal cover and fit appropriate seals
7. Connect a two-way RJ11 adaptor to the RJ11 port of the second meter in the multi-drop chain
8. Connect the flat pin cable from the first meter to the RJ11 adaptor of the second meter in the
multi-drop chain
9. Connect a Flat Pin Cable to the second port of the RJ11 adaptor
10. Replace the terminal cover and fit appropriate seals
11. Continue as steps 7 to 10 to the next meter
12. When all multi-drop connections are made and all terminal covers are in place, switch on the
supplies
A1120/40 meters allow up to 12 meters to be connected in RS485 multi-drop configuration. Twoway RJ11 adaptors will be required to link each meter in the chain.
PC
1:
2:
3: B
4: A
5: A1
6: B1
7: VC D
8: Gnd
Gnd
+V
Standard 9-25 Way Lead
25-way D type
Amplicon
8 7 6 5 4 3 2 1
RJ11
6 5 4 3 2 1
White
Black
+VDC 7 4 2 3
25-way D type
Blue
Yellow
6 5 4 3 2 1
White
Black
+VDC 7 4 2 3
25-way D type
AmpliconAmplicon
8 7 6 5 4 3 2 18 7 6 5 4 3 2 1
RJ11
Yellow
B lue
Next Meter
Page 68
60 A1120/40 - Electronic Polyphase Meter
APPENDIX D - External Battery Module
D1 External Battery Module
An External Battery Module can be fitted as an option which allows reading of meter data via the
optical port and access to the display facilities during power outages. The battery is housed in the
Module Carrier that fits below the meter terminal cover.
The Battery Module connects to the meter via a special ‘Molex’ connector.
The 'Molex' connector is optional. The use of the External Battery Module must be specified at
the time the meters are ordered.
External Battery Status
The battery voltage is monitored to detect if it has failed. A new battery install date can be
programmed and can be read back from the meter.
Using the External Battery Facility during Power Outages
The External Battery facility will only operate when power has been removed from the meter.
The module is energised by pressing the display pushbutton.
Once the module has been energised-
Displays can cycled in the normal way using the pushbuttons
Meter data can be read via the optical port (note that the communications session will always be
completed before power is removed)
External Battery Module power will be removed from the meter if the 'No button time-out'
(programmable from 10 to 120 seconds using the Power Master Unit) has expired.
Read Section 2 (Warnings) before installing the Battery Module.
Check that the terminal cover plate is in place before installing the module.
If the terminal cover plate is not in place, all supplies to the meter must be isolated.
For correctly installed 3 phase 4 wire meters, one of the battery connections will be at 'Mains
Neutral' potential. Under fault conditions, this connection could be raised to a 'Fatally
Dangerous Potential'.
For 3 phase 3 wire meters, one of the battery connections will be at 'Mains Phase Potential'.
The External Battery Module and its connection leads are double insulated. No attempt
should be made to modify the assembly or open the module housing. A replacement
assembly must be used if the battery becomes exhausted.
Failure to follow these instructions may result in electric shock or death.
Installing the Module
1. Read the Warnings above
2. Remove the meter terminal cover
3. If the terminal cover plate is not in place, do not attempt to install the module unless all
supplies to the meter have been isolated
4. Clip the Battery Module over the Terminal Block as shown in Section D1
5. Connect the 'Polarised Molex connector' to the 'Molex socket' making sure the cable is
routed in the recess by the 'Terminal Block Screw Holder' as shown in Section D1
6. Replace the terminal cover
Technical Information
Battery Type (Alkaline zinc manganese dioxide) +9 Volt PP3 (IEC 6LR61)
Battery Life 5 years with one reading session each month
The instructions and information in this manual are provided in compliance with Section 6
of the UK Health and Safety at Work Act, as amended by Schedule 3 of the Consumer
Protection Act 1987. The purchaser is responsible for making sure that everyone, whether
in his employment or not, who will be associated with the products supplied by Elster
Metering Systems, and to which these instructions and information apply, are made
familiar with the contents of this manual.
This applies to all persons who may be involved in activities such as unpacking,
inspecting, testing, setting, cleaning, installing, commissioning, operating, maintaining,
decommissioning or disposing of the products.
Safety of Persons using Electrical Products
Employers are reminded that they have a duty to ensure, as far as is reasonably
practicable, the Health, Safety and Welfare at work of all their Employees. Employers must
therefore ensure that employees are informed; trained and supervised and use proper
working procedures to ensure the safety of themselves and others.
The information provided in this manual is intended to ensure that products are properly
installed and otherwise handled in order to maintain them in a safe condition.
In the UK, employers have duties under the Health and Safety at Work Act 1974 and the
various regulations stemming therefrom.
In countries outside the UK, employers should ensure proper compliance with the Health
and Safety Legislation which is applicable to them.
Putting into Service
Products supplied by Elster Metering Systems have been designed and manufactured, in
accordance with appropriate standards, to operate under specified conditions, when
properly installed. The purchaser or delegated contractor is responsible for the "Putting
into Service" of any Elster Metering Systems products which have been supplied as
"Non-connected".
All related activities must therefore be carried out with due regard to any applicable
legislation, standards and good practice.
This Chapter covers the operation and installation of the ASL A1120/40 GSM modem and
Technolog A1120/40 GSM modem. Both modems are housed in a secure carrier that fits under
the meter terminal cover.
Before installing a module or module peripheral equipment, read the Safety Warnings,
Warnings, Precautions for handling electrostatic discharge sensitive devices and EMC
Guidelines below.
2 WARNINGS, CE MARKING AND EMC
SAFETY WARNINGS
Dangerous voltages are present
If the Terminal Cover Plate is not fitted to the A1120 meter, all supplies to the meter
must be isolated before a module or module peripheral equipment is installed or
removed.
Failure to do so may result in electric shock or death.
When installing or removing a module, be aware that multi-drop terminals may be
energised from other A1120 meters.
Caution
Installation of a faulty module or module peripheral equipment may affect the main meter
functionality.
2.1 Handling
Observe precautions for handling electrostatic discharge sensitive devices
When handling communications modules and module peripheral equipment described in
this manual, observe electrostatic discharge precautions at all times.
CAUTION
Avoid touching connector pins and printed circuit boards on communications modules and
module peripheral equipment where the PCB is exposed.
Failure to adhere to this instruction may result in electrostatic damage, contamination or
corrosion.
A1120/40 meters and their internal modules delivered to customers for use in European
Economic Area (EU & EFTA) countries are CE marked to indicate compliance with the
requirements of the Electromagnetic Compatibility Directive.
This compliance has been demonstrated by subjecting representative samples of the
product, installed in accordance with the instructions and guidelines given in this document,
to the tests prescribed in the following standards:
EN 61036: 1996, Alternating current static watt-hour meters for active energy
(Class 1 and 2)
EN 50081 - 1: 1992, Electromagnetic compatibility generic emission standard -
Part 1: Residential, Commercial and Light Industry
EN 50082 - 1: 1992, Electromagnetic compatibility generic immunity standard -
Part 1: Residential, Commercial and Light Industry
EN 60687 1992, Alternating current static watt-hour meters for active energy -
(Class 0.2s and 0.5s)
The user can therefore be confident that, provided the guidelines and instructions are
properly followed, all units installed will satisfy the requirements for residential, commercial
and light industrial premises.
Elster Metering Systems holds on record the appropriate Declaration of Conformity and
supporting documentation, against which the CE mark is affixed.
The A1120/40 meter has been designed and tested for compliance with the EMC and other
applicable directives.
It is, however, the responsibility of the installer to ensure that an installed system conforms to
the directives.
In order to assist the installer the following guidelines are given:
1. Keep a.c. circuits and d.c. circuits separated by a minimum of 50mm where ever possible
2. Where a.c. and d.c. circuits cross, they must do so at right angles to each other
3. The cables for each circuit must be bunched together to minimise the loop area enclosed
4. Where the environment is electrically hostile, screened twisted pair cables may be required.
The screen must be connected to earth at one point only
5. Ancillary equipment must also be CE marked
Recommended transmission distances for RS232 and RS485 are shown
below:
The RS232 or RS485 incoming cable should always be connected to the first meter in the
multi-drop chain.
Connecting a cable to a meter in the middle of a chain is not recommended.
GSM (Global System for Mobile) Communications Modems are ideally suited for use in remote
areas where it is not practical to connect to a PSTN telephone network. The modems can be
used in any area that provides GSM coverage.
Two types of GSM modems have been developed for use with the A1120/40 meter:
Technolog A1120/40 GSM Cello Modem
ASL A1120/40 GSM Modem
The modems have been custom designed for use with the A1120/40 meter and can be installed
beneath the meter terminal cover.
GSM modems can be used with the Service provider of your choice.
Meters can be multi-dropped if required (See Section 4.2.1 for multi-drop Installation).
About the SIM
The SIM Card must be provided by the by the Network Service Provider (O2, Orange, Vodafone
etc) with the following settings:
Data enabled
Air baud rate: 1200 - 9600 (the SIM baud rate must be configured to match the meter serial port
baud rate)
Transparent (no error correction) or non-transparent (error correction)
The preferred settings for the A1120 are - 9600 baud, non-transparent
SIM security pin disable
It is a requirement that the SIM Card Pin Security Number for all types of GSM modem
is disabled on installation. If the pin security number is enabled and the modem is
powered down, a site visit will be necessary to re-enter the pin number.
The GSM system allows full verification of all data received when configured in nontransparent mode.
Antenna
There is a wide range of antennae, each with their own characteristics for use with
GSM modems. It is therefore important to choose an antenna most suitable for your
installation.
The antenna should be mounted vertically in a position where it is possible to receive good
mobile phone reception from your Service Provider. Signal strength may be tested by using the
monitor on a mobile telephone providing the mobile uses the same service provider as the SIM
in the GSM.
It is recommended that the antenna is mounted at least 1 metre from the installation.
Up to 10 meters can be connected in multi-drop configuration from a single modem.
The maximum transmission distance is 12 metres. Each meter will require a two-way RJ11
adaptor to link to the next meter in the chain.
4.1.1 RS232 Multi-drop Installation Procedure
The connection diagram for RS232 multi-drop mode is shown below.
Each meter in the chain will require an RJ11 two-way adaptor.
1. Observe all Safety Warnings, Warnings, Precautions for handling electrostatic discharge sensitive devices and EMC Guidelines in Section 2
2. Remove the terminal cover from the meters. If the terminal cover plate is not in place,
switch off all supplies to the meter.
3. Connect a two-way RJ11 adaptor to the RJ11 port of the first meter in the multi-drop chain
4. Connect the modem to the first port of the adaptor
5. Connect a Flat Pin Cable to the second port of the RJ11 adaptor
6. Replace the terminal cover and fit appropriate seals
7. Connect a two-way RJ11 adaptor to the RJ11 port of the second meter in the multi-drop
chain
8. Connect the flat pin cable from the first meter to the RJ11 adaptor of the second meter in
the multi-drop chain
9. Connect a Flat Pin Cable to the second port of the RJ11 adaptor
10. Replace the terminal cover and fit appropriate seals
11. Continue as steps 7 to 10 to the next meter
12. When all multi-drop connections are made and all terminal covers are in place, switch on
the supplies
A1120/40 meters allow up to 32 meters to be connected in multi-drop configuration.
This configuration allows transmission over longer distances of up to 1.2km.
Each meter in the chain will require an Amplicon line driver to convert RS232 communications
to RS485. The first meter in the chain will require a two-way RJ11 adaptor.
Power Master Unitiii _________________________________________________________________
Power Master Unit Meter Compatibility
Variants of the A1120/40 Meter that can be
programmed with the Power Master Unit are
shown opposite. This manual is for use with the
A1120 meter and the A1140 load profile meter
only.
See the list below for details of meter variants.
To program an A1700 (Vision) meter or PPM see
manual M120 001 6.
To program an A120 or A140 single phase meter,
see Manual M130 001 3.
For programming meters it is strongly
recommended that only one meter variant is
selected at a time.
If more than one type of meter is selected and a
Scheme is created, scheme parameters applicable
to the lowest specification of meter only will be
programmed to the meter.
A1120/40 Meter Variants
LM******** - A
LM******** - C
LM*******B -
LM*******C LM*******D LM*******E -
LM*******F -
LM*******G LM*******H -
Times always show UTC/GMT
Times (as selected) show GMT/BST
Import (Wh)
Import (Wh), Q1 and Q4 (varh)
Import (Wh), Q1 and Q4 (varh), VA 1
Import/Export (Wh)
Import/Export (Wh), Q1, Q2, Q3, Q4 (varh)
Import/Export (Wh), VA 1/2
Import/Export (Wh), Q1, Q2, Q3, Q4, (varh), VA 1/2
A1120/40 Versions
Page 95
iv A1120/1140 Programmable Polyphase Meter Users Manual
What you will Need (Recommended Minimum Specification)
Pentium 3 Processor
256 MB RAM
CD ROM
60 MB free hard disk space
SVGA Display
The Power Master Unit has been developed as a 32-bit Windows™ application.
As such it should present no problems running on most configurations of Windows NT 4, Windows
2000 and Windows XP.
Several third party software packages (such as CHIRPS) are included in the Power Master Unit. Refer
to their operating instructions/authoring company's to determine their levels of Windows compatibility.
The performance and operation of the Power Master Unit Software will inevitably depend on the way
Windows has been set up on a given PC. There are a number of limitations when using a “single user”
application in a fully networked environment and where the operating system controls the interaction
between an application and the resources of the computer. Wherever possible it is recommended that
the Power Master Unit machine is set to single application/single user mode with all local permissions,
etc. set.
Operating recommendation
It is recommended that the Master Unit is operated using a mouse.
Portable computers should use an external mouse fitted to the mouse port.
The Power Master Unit can be operated from the keyboard if required.
Installing the Software
Before beginning installation, make sure all other programs are closed.
If upgrading the Master Unit to a later version, ALWAYS make a back up of the database prior to
beginning the upgrade.
The installation can be halted by clicking on the "Cancel" button on the bottom right of the screen.
To install the software, follow the instructions below:
InstallShield
Click on the Install Software hypertext link in the
Read Me. The InstallShield Wizard will run.
After a short time the screen opposite is displayed.
If the Power Master Unit is not already on your PC a
prompt will be displayed to continue.
Click Upgrade Power Master Unit, Next to continue.
Power Master Unitv _________________________________________________________________
Read Me
If a new installation is being installed a Read Me screen is displayed.
Note: The Read Me contains important information on the Master Unit installation.
Please familiarise yourself with the contents before proceeding with the installation.
Click Next to continue.
Type of Installation
The following types of installation can be
selected:
1. New Installation
2. Upgrade PMU 16 bit -> PMU 32 bit
3. Upgrade PMU 32 bit -> later version 32 bit
Select your option and click Next to continue.
Note: If New Installation is selected and a 16
or 32 bit version of the Master Unit is already
installed on your PC, a warning will be
displayed to select an upgrade option or
completely uninstall the Master Unit.
Choose Destination
The Power Master Unit will be installed in the
selected folder. The default destination is
C:\ELSTER\PMU\.
Use the Browse button to select another folder.
Click Next to continue.
A prompt is displayed if it is OK to overwrite the
installation. Click Yes.
Page 97
vi A1120/1140 Programmable Polyphase Meter Users Manual
Click the installation options required.
The Master Unit can be installed in the default
directories or a directory of your choice by using
the Browse buttons.
Click Next to continue.
Note: For an upgrade it is recommended all
installation options are selected and Use copy of
existing database.
Flag Probe Selection
Various probes can be used to communicate with
meters via the optical 'FLAG' communications
port. These probes are one of two basic types:
Probe with DTR disabled
Probe with DTR enabled
It is important to choose the correct probe for
your installation, as optical communications will
not be available if the wrong probe is selected.
Power Master Unitvii _________________________________________________________________
Select Program Folder
This allows the program to be stored on the Start Menu in the folder name of your choice.
You may select a folder already on your system or select a new folder. When you have chosen the
folder:
Click Next to continue.
Start Copying Files
Before the files are copied to your PC, a
summary of the files you have selected to
install is displayed. Before continuing,
check they are the options you require.
Click Next to continue.
Installation Complete
The files are copied to your PC.
Click Finish.
Note 1: The Power Master Unit must have a
printer attached for correct installation.
If a printer is not available a generic print driver
may be used.
Page 99
viii A1120/1140 Programmable Polyphase Meter Users Manual
Me ter Ide nt ifi ers
Passwords
Tari ff /D ispl ay
Deferred Tariff /Display
Deferred Tariff Setup
Billing Dates
Meter Constants
Relay Setup
Load Profiling
Me ter Op tion s
User Interface Options
Tim e & Dat e
Register Values, Historical Registers, Load Profile Data, Instrumentation Prof ile Data, Sec urity Data, Hardware Confi guration
Me ter Ident ifie rs, P asswor ds, Tari ff, Def erred Ta riff, Bi llin g Da tes, D ispla y, Mete r Co nstan ts, C usto mer Regis ters, Relay Setup,
Load P rofiling, , A1120 Options, A1120 UI Options, Time & Date
Scheme Man ager
Quick Send
Readings
As Scheme Editor +
Cu rren t Value s
Historical Registers
Instantaneous Values
Me ter Ph ysi cal Inf o
Instrumentation Values
Meter M ana ger
Meter Information Editor
Connection (C omms)Type
Elements
Re lays
Load Profile
Co mmun icat ion
OS & Telephone Number
Identifiers
Utility Codes
Passwords
Examine Meter Readings
Systems Administration
Changing Pas swords
Defining a New User
File Locations
Meter Connection Setup
Co mms S erve r S etup
Back-up Database
Time Set M ode
Language
Power Master Unit1 _________________________________________________________________
Power Master Unit
1.1 Power Master Unit Introduction
This section gives the basics on how to use the Power Master Unit software.
The Power Master Unit (Referred to in this manual as the Master Unit) software is a menu driven
package designed to support all variants of Elster Metering Systems:
A1700 (PPM) Polyphase Commercial and Industrial Meters
A1120/40 Light Industrial and Commercial Meters
A120/140 Electronic Single-phase Domestic Meters
Power Master Unit meter compatibility does not allow different meter types to be programmed by the
same scheme, therefore a separate manual support's each application. This manual supports A1120
and A1140 meters only. For information on how to program the A1700 and PPM meters, see manual
M120 001 6.
To program A120/140 meters, see manual M130 001 3.
The key features of the Master Unit software are:
Menu driven, using Microsoft
process of setting up a meter for any particular application.
Programming structure to ensure that, if an attempt is made to program a feature that is not present in
a meter, erroneous data cannot be programmed.
All other features are programmed normally.
®
Windows based operating software to guide the user through the
The Software permits:
Reading and Programming directly through the optical port
Reading and Programming through the serial port either directly or via a modem
Reading and Programming indirectly via a Hand Held Unit (HHU) through the optical port
Transferring information to and from a HHU
1.2 Prerequisites
This tutorial assumes you are comfortable with the 'Microsoft Windows' environment.
The Master Unit is Windows™ compatible, but if you are uncertain of the Windows structure, it is worth
spending a little time familiarising yourself with the 'Brief Tour of Microsoft Windows' in the Windows
manual before entering the software.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.