Status: 11.03.2016 • Errors excepted. Subject to technical changes.
3Clarification of signs
Installation, inspection, commissioning and troubleshooting of the device
must only be carried out by a competent electrician.
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-todate version of the manual is available.
Clarification of signs used in this manual
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER!
WARNING!
CAUTION!
ATTENTION!
ETSIn the ETS tables, the parameter default settings are marked by
... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
... indicates a situation which may lead to damage to property if it is
not avoided.
underlining.
4
1.Description
The Weather Station Suntracer KNX sl basic for the KNX building bus system
measures temperature, wind speed, brightness and recognises precipitation. All values can be used for the control of limit dependent switching outputs. States can be linked via AND logic gates and OR logic gates. Multi-function modules change input data
as required by means of calculations, querying a condition, or converting the data
point type.
The compact housing of the Suntracer KNX sl basic accommodates the sensors,
evaluation circuits and bus-coupling electronics.
Functions:
•Brightness measurement (current light strength) with 3 sensors. Separate
values, maximum or mixed value usable
•Wind measurement: The wind strength is measured electronically and thus
noiselessly and reliably, even during hail, snow and sub-zero temperatures.
Even turbulent air and rising winds in the vicinity of the device are recorded
•Precipitation detection: The sensor surface is heated, so that only drops and
flakes are recognised as precipitation, but not mist or dew. When the rain or
snow stops, the sensor is soon dry again and the precipitation warning ends
•Temperature measurement
•Frost protection for shading systems
•Switching outputs for all measured and computed values. Threshold values
can be adjusted per parameter or via communication objects
•8 AND and 8 OR logic gates, each with 4 inputs. All switching events as well
as 16 logic inputs (in the form of communications objects) can be used as
inputs for the logic gates. The output of each gate can be configured optionally
as 1-bit or 2 x 8-bit
•8 multi-function modules (computers) for changing the input data by
calculations, by querying a condition or by converting the data point type
Configuration is made using the KNX software ETS. The product file can be downloaded from the Elsner Elektronik homepage on www.elsner-elektronik.de in the “Service” menu.
1.0.1. Deliverables
•Weather station
•Stainless steel installation band for pole installation
•4×50 mm stainless steel roundhead screws and 6×30 mm dowels for wall
mounting. Use fixing materials that are suitable for the base!
•Size 6 Torx bit
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
5
1.1.Technical specification
HousingPlastic
ColourWhite / Translucent
AssemblySurface mount
Protection categoryIP 44
Dimensionsapprox. 62 × 71 × 145 (W × H × D, mm)
Weightapprox. 85 g
Ambient temperatureOperation -30…+50°C, storage -30…+70°C
Auxiliary supply12…40 V DC, 12…28 V AC. An appropriate power sup-
Auxiliary currentat 12V DC: max. 185 mA
Bus currentmax. 10 mA
Data outputKNX +/BCU typeIntegrated microcontroller
PEI type0
Group addressesmax. 2000
Assignmentsmax. 2000
Communication objects341
Temperature sensor:
Measurement range -30°C … +50°C
Resolution0.1°C
Accuracy±0.5°C at -30°C … +25°C
Wind sensor:
Measurement range0 m/s … 35 m/s
Resolution0.1 m/s
Accuracy±15% of the measurement value when incoming flow
Accuracy±15% of the measurement value at 35 lux … 150,000
ply unit can be purchased from Elsner Elektronik.
at 24V DC: max. 90 mA
at 24V AC: max. 82 mA
±1.5°C at -30°C … +45°C
is 45°…315°
(Frontal incoming flow corresponds to 180°)
4 lux at 256…2,645 lux
163 lux at 2,646…128,256 lux
762 lux at 128,257…150,000 lux
lux
The product conforms with the provisions of EU directives.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
6
2.Installation and start-up
2.1.Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
•National legal regulations are to be followed.
•Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
•Do not use the device if it is damaged.
•Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or
failure to follow the operating instructions voids any and all warranty and guarantee
claims.
After unpacking the device, check it immediately for possible mechanical damage. If it
has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when assembled and after conclusion of all installation and operational start-up tasks and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2.Installation location
Select an installation position on the building where the sensors can measure wind,
rain and sunshine without hindrance. No structural elements should be mounted above the weather station, from which water could continue to drop on the precipitation
sensor even after it has stopped raining or snowing. The weather station should not be
shaded by structures or, for example, trees.
At least 60 cm of clearance must be left around the device. This facilitates correct wind
speed measurement without eddies. At the same time, this prevents spray (raindrops
hitting the device) or snow (snow penetration) from impairing the measurement. This
also prevents birds from biting it.
Please ensure that the extended awning does not cast shade on the unit, and that it is
protected from the wind.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
7
Abb. 1
There must be at least 60 cm clearance to
other elements (structures, construction
parts, etc.) below, to the sides and in front of
the weather station.
60 cm
Abb. 2
The weather station must be attached to a
vertical wall (or a pole).
wall
or
pole
90°
Abb. 3
The weather station must be mounted in the
horizontal (transverse) direction.
Horizontal
Temperature measurements can also be distorted by external influences such as warming or cooling of the building structure on which the sensor is mounted (sunlight, heating or cold water pipes). Temperature variations from such sources of interference
must be corrected in the ETS in order to ensure the specified accuracy of the sensor
(temperature offset).
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
2.3.Device design
Abb. 4
The weather station must be aligned in the direction of the façade which is to be shaded.
Abb. 5
1Programming LED
2a, b, c Brightness measurement
3Precipitation sensor in lid
4Temperature measurement
5Wind measurement
6Programming key on the underside of the housing (recessed),see Addressing the
equipment, page 13
ATTENTION!
Sensitive wind sensor.
•Remove the protective transport sticker after installation.
•Do not touch the sensor on the wind measuring element (no. 5).
4
5
1
2a
3
6
2b
2c
8
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
9
Abb. 6
Slacken both screws on the lid (top) and lower part (bottom) with a size 6 Torx screwdriver.
Abb. 7
Pull the lid and lower part completely apart.
This also releases the plug-in connection between the board in the lid and the socket in the
lower part.
Abb. 8
The device is installed with two screws. Break
off the two longitudinal holes in the lower
part of the housing.
Longitudinal holes
2.4.Installing the weather station
ATTENTION!
Even a few drops of water can damage the device electronics.
•Do not open the device if water (e.g. rain) can get into it.
2.4.1. Preparation for installation
2.4.2. Fitting the lower part with mounting
Now, first of all, assemble the lower part of the housing with the integrated mounting
for wall or pole installation.
Wall installation
Use fixing materials (dowels, screws) that are suitable for the base.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
10
Abb. 9 a+b
a) If the power lead is to be hidden when in-
stalled, it must emerge from the wall in
the vicinity of the rear of the housing
(marked area).
b) If the power lead is to be surface-moun-
ted, the cable guide is broken off. The
lead is then fed into the device at the underside of the housing.
Cable guide
Abb. 10
Feed the power lead through the rubber gasket.
Rubber
gasket
Drilling plan
ATTENTION! The printout of the data sheet does not have original size! A separate, dimensionally correct drilling plan is included ex works and this can be used as a template.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
11
Abb. 11
Dimensions in mm. Variations are
possible for technical reasons
A/B2× longitudinal holes 8 mm ×
5.5 mm
C Position of the cable outlet (rub-
ber gasket) in the housing
AB
C
Abb. 12
Feed the mounting band through the eyelets
in the lower part of the housing.
Abb. 13
Break the cable guide off.
Feed the power lead through the rubber gasket.
Cable guide
Rubber
gasket
Pole installation
The device is installed on the pole with the enclosed stainless steel mounting band.
2.4.3. Connection
The connector is in the lower part of the housing.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
2.4.4. Closing the installation
Abb. 14
Connect
KNX data (+|-) and
power supply (12…40V DC, 12…28V AC, 1|2)
to the connector.
The terminal assignment of the power supply
is polarity-independent.
-+12
-+12
KNXVoltage
Abb. 15
Push the lid on the lower part. This also makes the plug-in connection between the board
in the lid and the socket in the lower part.
Abb. 16
Screw the lid (top) and lower part (bottom) together.
12
2.5.Instructions for assembly and initial start-up
Remove all transport protection stickers present after installation.
The wind measurement value and thus also all wind switching outputs cannot be output until 35 seconds after the power is turned on.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
13
1 2
Abb. 17
1Programming button for teaching the device
2Programming LED (under the semi-transparent lid)
After the auxiliary voltage has been applied, the device will enter an initialisation phase
lasting a few seconds. During this phase no information can be received or sent via the
bus.
3.Addressing the equipment
The equipment is delivered ex works with the bus address 15.15.250. You program a
different address in the ETS by overwriting the address 15.15.250 or teach the device
using the programming button.
The programming button can be reached through the opening on the underside of the
housing; it is recessed by approx. 15 mm. Use a thin object to reach the key, e. g. a
1.5 mm² wire.
4.Maintenance
WARNING!
Risk of injury caused by components moved automatically!
The automatic control can start system components and place people in
danger (e.g. moving windows/awnings if a rain/wind alarm has been
triggered while cleaning).
•Always isolate the device from the mains for servicing and cleaning.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
14
The device must regularly be checked for dirt twice a year and cleaned if necessary. In
case of severe dirt, the sensor may not work properly anymore.
ATTENTION
The device can be damaged if water penetrates the housing.
•Do not clean with high pressure cleaners or steam jets.
Weather Station Suntracer KNX sl basic • Stand: 11.03.2016 • Technische Änderungen und Irrtümer vorbehalten.
15Transfer protocol
5.Transfer protocol
Units:
Temperatures in degrees Celsius
Brightness in Lux
Wind in metres per second
Air pressure in Pascal
Azimuth and elevation in degrees
5.1.List of all communications objects
Abbreviation flags:
C Communication
R Read
WWrite
T Transmit
UUpdate
No.TextFunction Flags DPT typeSize
1Software versionOutputR-CT[217.1] DPT_Version2 bytes
21Signal LED object 1s cycleInput-WC-[1.1] DPT_Switch1 bit
22Signal LED object 4s cycleInput-WC-[1.1] DPT_Switch1 bit
34Rain: Switching outputOutputR-CT[1.1] DPT_Switch1 bit
35Rain: Switching output with fixed
delays
36Rain: Switching delay to rainInput-WC-[7,005] DPT_TimePeri-
37Rain: Switching delay to no rainInput-WC-[7,005] DPT_TimePeri-
41Temperature sensor: MalfunctionOutputR-CT[1.1] DPT_Switch1 bit
42Temperature sensor: External meas-
urement
43Temperature sensor: Measurement
value
44Temperature sensor: Total measure-
ment
45Temperature sensor: Min./Max. meas-
urement query
46Temperature sensor: Minimum meas-
urement
47Temperature sensor: Maximum meas-
urement
48Temperature sensor: Min./Max. meas-
urement reset
51Temp. threshold value 1: Absolute
value
52Temp. threshold value 1: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch1 bit
OutputR-CT[1.1] DPT_Switch1 bit
odSec
odSec
Input-SKÜ[9.1] DPT_Value_Temp 2 bytes
OutputR-CT[9.1] DPT_Value_Temp 2 bytes
OutputR-CT[9.1] DPT_Value_Temp 2 bytes
Input-WC-[1.017] DPT_Trigger1 bit
OutputR-CT[9.1] DPT_Value_Temp 2 bytes
OutputR-CT[9.1] DPT_Value_Temp 2 bytes
Input-WC-[1.017] DPT_Trigger1 bit
Input/
Output
RWCT [9.1] DPT_Value_Temp 2 bytes
2 bytes
2 bytes
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
16Transfer protocol
No.TextFunction Flags DPT typeSize
53Temp. threshold value 1: Switching
delay from 0 to 1
54Temp. threshold value 1: Switching
delay from 1 to 0
55Temp. threshold value 1: Switching
output
56Temp. threshold value 1: Switching
output block
58Temp. threshold value 2: Absolute
value
Input-WC-[7.5] DPT_TimePeriod-
Sec
Input-WC-[7.5] DPT_TimePeriod-
2 bytes
2 bytes
Sec
OutputR-CT[1.1] DPT_Switch1 bit
Input-WC-[1.1] DPT_Switch1 bit
Input/
RWCT [9.1] DPT_Value_Temp 2 bytes
Output
59Temp. threshold value 2: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch1 bit
60Temp. threshold value 2: Switching
delay from 0 to 1
61Temp. threshold value 2: Switching
delay from 1 to 0
62Temp. threshold value 2: Switching
output
63Temp. threshold value 2: Switching
Input-WC-[7.5] DPT_TimePeriod-
2 bytes
Sec
Input-WC-[7.5] DPT_TimePeriod-
Sec
2 bytes
OutputR-CT[1.1] DPT_Switch1 bit
Input-WC-[1.1] DPT_Switch1 bit
output block
65Temp. threshold value 3: Absolute
value
Input/
Output
RWCT [9.1] DPT_Value_Temp 2 bytes
66Temp. threshold value 3: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch1 bit
67Temp. threshold value 3: Switching
delay from 0 to 1
68Temp. threshold value 3: Switching
delay from 1 to 0
69Temp. threshold value 3: Switching
output
70Temp. threshold value 3: Switching
Input-WC-[7.5] DPT_TimePeriod-
2 bytes
Sec
Input-WC-[7.5] DPT_TimePeriod-
Sec
2 bytes
OutputR-CT[1.1] DPT_Switch1 bit
Input-WC-[1.1] DPT_Switch1 bit
output block
72Temp. threshold value 4: Absolute
value
Input/
Output
RWCT [9.1] DPT_Value_Temp 2 bytes
73Temp. threshold value 4: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch1 bit
74Temp. threshold value 4: Switching
1298 Weekly timer period 22: 8-bit outputOutputR-CT[5.10] DPT_Value_1_U-
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
1 byte
count
1299 Weekly timer period 23: Switch-on
time
1300 Weekly timer period 23: Switch-off
time
1301 Weekly timer period 23: Switching out-
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
put
1302 Weekly timer period 23: 8-bit outputOutputR-CT[5.10] DPT_Value_1_U-
1303 Weekly timer period 24: Switch-on
time
1304 Weekly timer period 24: Switch-off
time
1305 Weekly timer period 24: Switching out-
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
count
1 byte
put
1306 Weekly timer period 24: 8-bit outputOutputR-CT[5.10] DPT_Value_1_U-
count
1 byte
1331 Calendar timer period 1: Start dateInputRWCT [11.1] DPT_Date3 bytes
1332 Calendar timer period 1: End dateInputRWCT [11.1] DPT_Date3 bytes
1333 Calendar timer period 1 sequence 1:
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
Switch-on time
1334 Calendar timer period 1 sequence 1:
Switch-off time
1335 Calendar timer period 1 sequence 1:
Switching output
1336 Calendar timer period 1 sequence 1:
8-bit output
1337 Calendar timer period 1 sequence 2:
Switch-on time
1338 Calendar timer period 1 sequence 2:
Switch-off time
1339 Calendar timer period 1 sequence 2:
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
OutputR-CT[5.10] DPT_Value_1_U-
1 byte
count
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
Switching output
1340 Calendar timer period 1 sequence 2:
8-bit output
OutputR-CT[5.10] DPT_Value_1_U-
count
1 byte
1341 Calendar timer period 2: Start dateInputRWCT [11.1] DPT_Date3 bytes
1342 Calendar timer period 2: End dateInputRWCT [11.1] DPT_Date3 bytes
1343 Calendar timer period 2 sequence 1:
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
Switch-on time
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
29Transfer protocol
No.TextFunction FlagsDPT typeSize
1344 Calendar timer period 2 sequence 1:
Switch-off time
1345 Calendar timer period 2 sequence 1:
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
Switching output
1346 Calendar timer period 2 sequence 1:
8-bit output
1347 Calendar timer period 2 sequence 2:
Switch-on time
1348 Calendar timer period 2 sequence 2:
OutputR-CT[5.10] DPT_Value_1_U-
count
1 byte
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
Switch-off time
1349 Calendar timer period 2 sequence 2:
Switching output
1350 Calendar timer period 2 sequence 2:
8-bit output
OutputR-CT[1.1] DPT_Switch1 bit
OutputR-CT[5.10] DPT_Value_1_U-
count
1 byte
1351 Calendar timer period 3: Start dateInputRWCT [11.1] DPT_Date3 bytes
1352 Calendar timer period 3: End dateInputRWCT [11.1] DPT_Date3 bytes
1353 Calendar timer period 3 sequence 1:
Switch-on time
1354 Calendar timer period 3 sequence 1:
Switch-off time
1355 Calendar timer period 3 sequence 1:
Switching output
1356 Calendar timer period 3 sequence 1:
8-bit output
1357 Calendar timer period 3 sequence 2:
Switch-on time
1358 Calendar timer period 3 sequence 2:
Switch-off time
1359 Calendar timer period 3 sequence 2:
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
OutputR-CT[5.10] DPT_Value_1_U-
1 byte
count
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
Switching output
1360 Calendar timer period 3 sequence 2:
8-bit output
OutputR-CT[5.10] DPT_Value_1_U-
count
1 byte
1361 Calendar timer period 4: Start dateInputRWCT [11.1] DPT_Date3 bytes
1362 Calendar timer period 4: End dateInputRWCT [11.1] DPT_Date3 bytes
1363 Calendar timer period 4 sequence 1:
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
Switch-on time
1364 Calendar timer period 4 sequence 1:
Switch-off time
1365 Calendar timer period 4 sequence 1:
Switching output
1366 Calendar timer period 4 sequence 1:
8-bit output
1367 Calendar timer period 4 sequence 2:
Switch-on time
1368 Calendar timer period 4 sequence 2:
Switch-off time
1369 Calendar timer period 4 sequence 2:
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
OutputR-CT[5.10] DPT_Value_1_U-
1 byte
count
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
InputRWCT [10.1] DPT_TimeOfDay 3 bytes
OutputR-CT[1.1] DPT_Switch1 bit
Switching output
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
30Transfer protocol
No.TextFunction FlagsDPT typeSize
1370 Calendar timer period 4 sequence 2:
8-bit output
OutputR-CT[5.10] DPT_Value_1_U-
count
1 byte
1391 Logic input 1Input-WC-[1.2] DPT_Bool1 bit
1392 Logic input 2Input-WC-[1.2] DPT_Bool1 bit
1393 Logic input 3Input-WC-[1.2] DPT_Bool1 bit
1394 Logic input 4Input-WC-[1.2] DPT_Bool1 bit
1395 Logic input 5Input-WC-[1.2] DPT_Bool1 bit
1396 Logic input 6Input-WC-[1.2] DPT_Bool1 bit
1397 Logic input 7Input-WC-[1.2] DPT_Bool1 bit
1398 Logic input 8Input-WC-[1.2] DPT_Bool1 bit
1399 Logic input 9Input-WC-[1.2] DPT_Bool1 bit
1400 Logic input 10Input-WC-[1.2] DPT_Bool1 bit
1401 Logic input 11Input-WC-[1.2] DPT_Bool1 bit
1402 Logic input 12Input-WC-[1.2] DPT_Bool1 bit
1403 Logic input 13Input-WC-[1.2] DPT_Bool1 bit
1404 Logic input 14Input-WC-[1.2] DPT_Bool1 bit
1405 Logic input 15Input-WC-[1.2] DPT_Bool1 bit
1406 Logic input 16Input-WC-[1.2] DPT_Bool1 bit
1411 AND logic 1: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1412 AND logic 1: 8-bit output AOutputR-CT1 byte
1413 AND logic 1: 8-bit output BOutputR-CT1 byte
1414 AND logic 1: BlockInput-WC-[1.1] DPT_Switch1 bit
1415 AND logic 2: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1416 AND logic 2: 8-bit output AOutputR-CT1 byte
1417 AND logic 2: 8-bit output BOutputR-CT1 byte
1418 AND logic 2: BlockInput-WC-[1.1] DPT_Switch1 bit
1419 AND logic 3: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1420 AND logic 3: 8-bit output AOutputR-CT1 byte
1421 AND logic 3: 8-bit output BOutputR-CT1 byte
1422 AND logic 3: BlockInput-WC-[1.1] DPT_Switch1 bit
1423 AND logic 4: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1424 AND logic 4: 8-bit output AOutputR-CT1 byte
1425 AND logic 4: 8-bit output BOutputR-CT1 byte
1426 AND logic 4: BlockInput-WC-[1.1] DPT_Switch1 bit
1427 AND logic 5: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1428 AND logic 5: 8-bit output AOutputR-CT1 byte
1429 AND logic 5: 8-bit output BOutputR-CT1 byte
1430 AND logic 5: BlockInput-WC-[1.1] DPT_Switch1 bit
1431 AND logic 6: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1432 AND logic 6: 8-bit output AOutputR-CT1 byte
1433 AND logic 6: 8-bit output BOutputR-CT1 byte
1434 AND logic 6: BlockInput-WC-[1.1] DPT_Switch1 bit
1435 AND logic 7: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
31Transfer protocol
No.TextFunction FlagsDPT typeSize
1436 AND logic 7: 8-bit output AOutputR-CT1 byte
1437 AND logic 7: 8-bit output BOutputR-CT1 byte
1438 AND logic 7: BlockInput-WC-[1.1] DPT_Switch1 bit
1439 AND logic 8: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1440 AND logic 8: 8-bit output AOutputR-CT1 byte
1441 AND logic 8: 8-bit output BOutputR-CT1 byte
1442 AND logic 8: BlockInput-WC-[1.1] DPT_Switch1 bit
1443 OR logic 1: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1444 OR logic 1: 8-bit output AOutputR-CT1 byte
1445 OR logic 1: 8-bit output BOutputR-CT1 byte
1446 OR logic 1: BlockInput-WC-[1.1] DPT_Switch1 bit
1447 OR logic 2: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1448 OR logic 2: 8-bit output AOutputR-CT1 byte
1449 OR logic 2: 8-bit output BOutputR-CT1 byte
1450 OR logic 2: BlockInput-WC-[1.1] DPT_Switch1 bit
1451 OR logic 3: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1452 OR logic 3: 8-bit output AOutputR-CT1 byte
1453 OR logic 3: 8-bit output BOutputR-CT1 byte
1454 OR logic 3: BlockInput-WC-[1.1] DPT_Switch1 bit
1455 OR logic 4: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1456 OR logic 4: 8-bit output AOutputR-CT1 byte
1457 OR logic 4: 8-bit output BOutputR-CT1 byte
1458 OR logic 4: BlockInput-WC-[1.1] DPT_Switch1 bit
1459 OR logic 5: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1460 OR logic 5: 8-bit output AOutputR-CT1 byte
1461 OR logic 5: 8-bit output BOutputR-CT1 byte
1462 OR logic 5: BlockInput-WC-[1.1] DPT_Switch1 bit
1463 OR logic 6: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1464 OR logic 6: 8-bit output AOutputR-CT1 byte
1465 OR logic 6: 8-bit output BOutputR-CT1 byte
1466 OR logic 6: BlockInput-WC-[1.1] DPT_Switch1 bit
1467 OR logic 7: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1468 OR logic 7: 8-bit output AOutputR-CT1 byte
1469 OR logic 7: 8-bit output BOutputR-CT1 byte
1470 OR logic 7: BlockInput-WC-[1.1] DPT_Switch1 bit
1471 OR logic 8: 1-bit switching outputOutputR-CT[1.2] DPT_Bool1 bit
1472 OR logic 8: 8-bit output AOutputR-CT1 byte
1473 OR logic 8: 8-bit output BOutputR-CT1 byte
1474 OR logic 8: BlockInput-WC-[1.1] DPT_Switch1 bit
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
32Parameter setting
6.Parameter setting
6.0.1.Behaviour on power failure/power restoration
Behaviour on bus or auxiliary power failure
The device sends nothing.
Behaviour on bus or auxiliary voltage restoration and following programming
or reset
The device sends all measurement values as well as switching and status outputs according to their send pattern set in the parameters with the delays established in the
"General settings" parameter block. The "Software version" communications object is
sent once after 5 seconds.
6.0.2.Storage of threshold values
For threshold values that are specified via a communication object, a starting value
must be entered for the first commissioning. It is valid until the first communication of
a new threshold value.
After this, a threshold value once set per parameter or via a communication object is
retained until a new threshold value is sent via a communication object. The last threshold value set by communication object is saved in the device, so that it is retained
during a power outage and is available once again when power is restored.
6.0.3.Malfunction objects
Malfunction objects are sent after every reset and, additionally, after changes (i.e. at
the beginning and end of a malfunction).
6.1.Rain
Activate the rain sensor in order to use objects and switch outputs.
Use rain sensorNo • Yes
Set, in which cases delay times received are to be kept per object. The parameter is
only taken into consideration if the setting by object is activated further down. Please
note that the setting "After power restoration and programming" should not be used
for the initial start-up, as the factory settings are always used until the first call (setting
via objects is ignored).
Maintain the
delays received via communication objects • never
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• after power restoration
• after power restoration and
programming
33Parameter setting
Select whether the special rain output is to be used with fixed switching delay. This
switching output has no delay on rain recognition and 5 minutes delay after it is dry
again.
Use rain output with fixed
switching delay
No • Yes
Set the delay times. If the delays are defined using objects, then the times set here are
only valid up to the first call.
Delays can be set via objects
(in seconds)
Delay on rainnone • 1 s … • 2 h
Delay on no rain
(after drying of the sensor)
No • Yes
5 min • 1 h… • 2 h
Define the send pattern for the rain switch output and specify the object value for the
event of rain.
Switching output sends• on change
Send cycle
(if sent periodically)
Object value(s) with rain0 • 1
• on change to rain
• on change to no rain
• on change and periodically
• on change to rain and periodically
• on change to no rain and periodically
5 s ... 2 h; 10 s
6.2.Temperature measurement value
First of all set whether the temperature sensor malfunction object is to be used and correct, if necessary, the output of the measurement value by specifying an offset (e.g. in
order to compensate malfunction sources).
Use malfunction objectNo • Yes
Offset in 0.1°C-50… 50; 0
Then set the mixed value calculation if desired.
Use external readingNo • Yes
Ext. Reading proportion of the total reading
(if external reading is to be used)
All following settings refer to the total measured value
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
5% • 10% • 15% • ... • 50% • ... • 95% • 100%
34Parameter setting
Specify the send pattern for the total measured value.
Send pattern• never
on change of
(if sent on change)
Send cycle
(if sent periodically)
• periodically
• on change
• on change and periodically
0.1°C • 0.2°C • 0.5°C • 1.0°C • 2.0°C • 5.0°C
5 s … 2 h; 10 s
6.3.Temperature threshold values
Activate the temperature threshold values required (maximum four) The menus for the
further setting of the threshold values are then displayed.
Threshold value 1No • Yes
Threshold value...No • Yes
Threshold value 4No • Yes
6.3.1.Temperature threshold value 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and programming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Maintain the
threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and programming
Select whether the threshold value is to be specified per parameter or via a communication object.
Threshold value setpoint usingParameter • Communications object
When the threshold value per parameter is specified, then the value is set.
Threshold value in 0.1°C-300 … 800; 200
When the threshold value per communication object is specified, the starting
value, object value limit and type of change to the threshold value are then set.
Start threshold value in 0.1°C
valid until first call
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
-300 … 800; 200
35Parameter setting
Object value limit (min) in 0.1°C-300 … 800
Object value limit (max) in 0.1°C-300 … 800
Type of threshold changeAbsolute value • Increase/decrease
Step size
With both of the methods for specifying the threshold values the hysteresis is set.
Hysteresis settingin % • absolute
Hysteresis in % of the threshold value
(for setting in %)
Hysteresis in 0.1°C
(for absolute setting)
0 … 50; 20
0 … 1100; 50
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits.
When the following conditions apply, the
output is
(LV = Threshold value)
Delays can be set via objects
(in seconds)
Delay from 0 to 1 none • 1 s … 2 h
Delay from 1 to 0none • 1 s … 2 h
Switching output sends• on change
Cycle
(if sent periodically)
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
No • Yes
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
5 s ... 2 h
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
Use switching output blockNo • Yes
Analysis of the blocking object• At value 1: block | At value 0: release
Blocking object value before first call 0 • 1
Action when locking• Do not send message
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• At value 0: block | At value 1: release
• send 0
• send 1
36Parameter setting
Action upon release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
The behaviour of the switching output on release is dependent on the value of the parameter "Switching output sends" (see "Switching output")
Switching output sends on changedo not send message •
Switching output sends on change to 1do not send message •
Switching output sends on change to 0do not send message •
Switching output sends on change and
periodically
Switching output sends on change to 1 and
periodically
Switching output sends on change to 0 and
periodically
Status object/s send/s
If switching output = 1 send 1
If switching output = 0 send 0
Send switching output status
If switching output = 1 send 1
If switching output = 0 send 0
6.4.Frost alarm
If necessary, activate the parameter frost alarm.
Use frost alarmNo • Yes
Set which conditions are valid for the frost alarm. The frost alarm is active in cold outdoor temperatures in combination with precipitation.
Start frost alarm when
an external temperature of (in 0.1 °C)
is not reached.
during or until (in hours)
after precipitation.
End frost alarm when
an external temperature of (in 0.1 °C)30 ... 100; 50
for more than (in hours)
is exceeded.
-50 ... 40; 20
1 ... 10; 5
1 ... 10; 5
Define the send pattern and the object value.
Send pattern• on change
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• on change to frost
• on change to no frost
• on change and periodically
• on change to frost and periodically
• on change to no frost and periodically
37Parameter setting
Send cycle
(if sent periodically)
Object value with frost0 • 1
5 s … 2 h; 1 min
6.5.Brightness measurement value
Sensor 1-3
Give the brightness sensors 1-3 a nomenclature and set the transmission behaviour for
the measurement values.
Sensor nomenclatureS1 [Free text]
Send pattern• never
at and above change in %
(if sent on change)
Send cycle
(if sent periodically)
Total measurement
Select the type of the total measurement and set the transmission behaviour for the
total measurement.
Type of total measured value• Mixed value from all 3 sensors
Sensor 1-3 share in %
(if total measured value is a mixed value)
Send pattern• never
at and above change in %
(if sent on change)
Send cycle
(if sent periodically)
• periodically
• on change
• on change and periodically
1 ... 100; 20
5 s ... 2 h
• Maximum value of the 3 sensors
0...100; 33
• periodically
• On change
• on change and periodically
1 ... 100; 20
5 s ... 2 h
6.6.Brightness threshold values sensor 1-3 and
brightness threshold values total
Activate the required brightness threshold values at the individual sensors and at the
total threshold value (in each case a maximum of four). The menus for the further setting of the threshold values are then displayed.
Threshold value 1No • Yes
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
38Parameter setting
Threshold value...No • Yes
Threshold value 4No • Yes
6.6.1.Threshold values 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and programming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Maintain the
threshold values and delays received via
communication objects
Select whether the threshold value is to be specified per parameter or via a communication object.
Threshold value setpoint usingParameter • Communications object
When the threshold value per parameter is specified, then the value is set.
Threshold value in kLux1000 … 150000; 60000
• never
• after power supply restoration
• after power supply restoration and
programming
When the threshold value per communication object is specified, the starting
value, object value limit and type of change to the threshold value are then set.
Start threshold value in Lux
valid until first call
Object value limit (min.) in Lux1000 … 150000
Object value limit (max.) in Lux1000 … 150000
Type of threshold changeAbsolute value • Increase/decrease
Increment in Lux
(upon increase/decrease change)
1000 … 150000; 60000
1000 • 2000 • 5000 • 10000 • 20000
With both of the methods for specifying the threshold values the hysteresis is set.
Hysteresis settingin % • absolute
Hysteresis in % of the threshold value
(for setting in %)
Hysteresis in Lux
(for absolute setting)
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
0 … 100; 50
0 … 150000; 30000
39Parameter setting
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits.
When the following conditions apply, the
output is
(LV = Threshold value)
Delays can be set via objects
(in seconds)
Delay from 0 to 1 none • 1 s … 2 h
Delay from 1 to 0none • 1 s … 2 h
Switching output sends• on change
Cycle
(if sent periodically)
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
No • Yes
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
5 s ... 2 h
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
Use switching output blockNo • Yes
Analysis of the blocking object• At value 1: block | At value 0: release
Blocking object value before first call 0 • 1
Action when locking• Do not send message
Action upon release
(with 2 seconds release delay)
• At value 0: block | At value 1: release
• send 0
• send 1
[Dependent on the "Switching output
sends" setting]
The behaviour of the switching output on release is dependent on the value of the parameter "Switching output sends" (see "Switching output")
Switching output sends on changedo not send message •
Switching output sends on change to 1do not send message •
Switching output sends on change to 0do not send message •
Switching output sends on change and
periodically
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
Status object/s send/s
If switching output = 1 send 1
If switching output = 0 send 0
Send switching output status
40Parameter setting
Switching output sends on change to 1 and
periodically
Switching output sends on change to 0 and
periodically
If switching output = 1 send 1
If switching output = 0 send 0
6.7.Twilight brightness threshold values
Activate the twilight threshold values required (maximum four) The menus for the further setting of the threshold values are then displayed.
Threshold value 1No • Yes
Threshold value...No • Yes
Threshold value 4No • Yes
6.7.1.Twilight threshold value 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and programming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Maintain the
threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and
programming
Select whether the threshold value is to be specified per parameter or via a communication object.
Threshold value setpoint usingParameter • Communications object
When the threshold value per parameter is specified, then the value is set.
Threshold value in kLux1 … 1000; 10
When the threshold value per communication object is specified, the starting
value, object value limit and type of change to the threshold value are then set.
Start threshold value in Lux
valid until first call
Object value limit (min.) in Lux1 … 1000
Object value limit (max.) in Lux1 … 1000
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
1 … 1000; 10
41Parameter setting
Type of threshold changeAbsolute value • Increase/decrease
Increment in Lux
(upon increase/decrease change)
1000 • 2000 • 5000 • 10000 • 20000
With both of the methods for specifying the threshold values the hysteresis is set.
Hysteresis settingin % • absolute
Hysteresis in % of the threshold value
(for setting in %)
Hysteresis in Lux
(for absolute setting)
0 … 100; 50
0 … 1000; 5
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits.
When the following conditions apply, the
output is
(LV = Threshold value)
Delays can be set via objects
(in seconds)
Delay from 0 to 1 none • 1 s … 2 h
Delay from 1 to 0none • 1 s … 2 h
Switching output sends• on change
Cycle
(if sent periodically)
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
No • Yes
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
5 s ... 2 h
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
Use switching output blockNo • Yes
Analysis of the blocking object• At value 1: block | At value 0: release
Blocking object value before first call 0 • 1
Action when locking• do not send message
Action upon release
(with 2 seconds release delay)
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• At value 0: block | At value 1: release
• send 0
• send 1
[Dependent on the "Switching output
sends" setting]
42Parameter setting
The behaviour of the switching output on release is dependent on the value of the parameter "Switching output sends" (see "Switching output")
Switching output sends on changedo not send message •
Switching output sends on change to 1do not send message •
Switching output sends on change to 0do not send message •
Switching output sends on change and
periodically
Switching output sends on change to 1 and
periodically
Switching output sends on change to 0 and
periodically
status object/s send/s
if switching output = 1 send 1
if switching output = 0 send 0
send switching output status
if switching output = 1 send 1
if switching output = 0 send 0
6.8.Night
If necessary, activate the night recognition.
Use night recognitionNo • Yes
Set, in which cases delay times received are to be kept per object. The parameter is
only taken into consideration if the setting by object is activated further down. Please
note that the setting "After power restoration and programming" should not be used
for the initial start-up, as the factory settings are always used until the first call (setting
via objects is ignored).
Maintain the
delays received via communication objects • never
• after power supply restoration
• after power supply restoration and
programming
Specify below which brightness the device should recognise "night" and with which
hysteresis this is to be outputted.
Night is recognised below
Lux
Hysteresis in Lux0 ... 500; 5
1 ... 1000; 10
Set the delay for the switching and in which cases the switch output sends and which
value is output at night.
Delays can be set via objects
(in seconds)
Switching delay on night none • 1 s … 2 h
Switching delay on daynone • 1 s … 2 h
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
No • Yes
43Parameter setting
Switching output sends• on change
Send cycle
(if sent periodically)
Object value at night0 • 1
• on change to night
• on change to day
• on change and periodically
• on change to night and periodically
• on change to day and periodically
5 s ... 2 h
6.9.Wind measurement
If necessary, activate the wind malfunction object. Specify whether the measurement
should also be output in Beaufort.
Use malfunction objectNo • Yes
Measured value additionally
output in the Beaufort scale
Define the send pattern and, if necessary, activate the maximum value (this value is not
retained after a reset).
Send pattern• never
on change of
(if sent on change)
Send cycle
(if sent periodically)
Use maximum valueNo • Yes
No • Yes
• periodically
• on change
• on change and periodically
2% • 5% • 10% • 25% • 50%
5 s ... 2 h; 10 s
Beaufort scale
BeaufortMeaning
0Calm
1Light air
2Light breeze
3Gentle breeze
4Moderate breeze
5Fresh breeze
6Strong breeze
7High wind
8Gale
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
44Parameter setting
BeaufortMeaning
9Severe gale
10Storm
11Violent storm
12Hurricane
6.10.Wind threshold values
Activate the wind threshold values required (maximum four) The menus for the further
setting of the threshold values are then displayed.
Threshold value 1No • Yes
Threshold value...No • Yes
Threshold value 4No • Yes
6.10.1. Wind threshold value 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and programming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Maintain the
threshold values and delays received via
communication objects
.
• never
• after power supply restoration
• after power supply restoration and
programming
Select whether the threshold value is to be specified per parameter or via a communication object.
Threshold value setpoint usingParameter • Communications object
When the threshold value per parameter is specified, then the value is set.
Threshold value in 0.1 m/s1 … 350; 40
When the threshold value per communication object is specified, the starting
value, object value limit and type of change to the threshold value are then set.
Start threshold value in 0.1 m/s
valid until first call
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
1 … 350; 40
45Parameter setting
Object value limit (min.) in 0.1 m/s increments
Object value limit (max.) in 0.1 m/s increments
Type of threshold changeAbsolute value • Increase/decrease
Step size
(upon increase/decrease change)
1 … 350
1 … 350
0.1 m/s • 0.2 m/s • 0.5 m/s • 1.0 m/s • 2.0 m/s
• 5.0 m/s
With both of the methods for specifying the threshold values the hysteresis is set.
Hysteresis settingin % • absolute
Hysteresis in % (relative to threshold value)
(for setting in %)
Hysteresis in 0.1 m/s
(for absolute setting)
0 … 100; 50
0 … 350; 20
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits.
When the following conditions apply, the
output is
(LV = Threshold value)
Delays can be set via objects
(in seconds)
Delay from 0 to 1 none • 1 s … 2 h
Delay from 1 to 0none • 1 s … 2 h
Switching output sends• on change
Cycle
(if sent periodically)
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
No • Yes
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
5 s ... 2 h
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
Use switching output blockNo • Yes
Analysis of the blocking object• At value 1: block | At value 0: release
Blocking object value before first call 0 • 1
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• At value 0: block | At value 1: release
46Parameter setting
Action when locking• Do not send message
Action upon release
(with 2 seconds release delay)
• send 0
• send 1
[Dependent on the "Switching output
sends" setting]
The behaviour of the switching output on release is dependent on the value of the parameter "Switching output sends" (see "Switching output")
Switching output sends on changedo not send message •
Switching output sends on change to 1do not send message •
Switching output sends on change to 0do not send message •
Switching output sends on change and
periodically
Switching output sends on change to 1 and
periodically
Switching output sends on change to 0 and
periodically
Status object/s send/s
If switching output = 1 send 1
If switching output = 0 send 0
Send switching output status
If switching output = 1 send 1
If switching output = 0 send 0
6.11.Computer
Activate the multi-functional computer, with which the input data can be changed by
calculation, querying a condition or converting the data point type. The menus for the
further setting of the computer are then displayed.
Set, in which cases input values received are to be kept per object. Please note that the
setting "After power restoration and programming" should not be used for the initial
start-up, as the factory settings are always used until the first call (setting via objects is
ignored).
Maintain the
input values received via communication
objects
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• never
• after power supply restoration
• after power supply restoration and
programming
47Parameter setting
Select the function set the input mode and starting values for input 1 and input 2.
Function (I = Input)• Prerequisite: E1 = E2
• Prerequisite: E1 > E2
• Prerequisite: E1 >= E2
• Prerequisite: E1 < E2
• Prerequisite: E1 <= E2
• Prerequisite: E1 - E2 >= E3
• Prerequisite: E2 - E1 >= E3
• Prerequisite: E1 - E2 amount >= E3
• Calculation: E1 + E2
• Calculation: E1 - E2
• Calculation: E2 - E1
• Calculation: E1 - E2 Amount
• Calculation: Output 1 = E1 × X + Y |
Output 2 = E2 × X + Y |
• Transformation: General
Tolerance for comparison
0 ... 4,294,967,295
(in the case of prerequisite E1 = E2)
Input type[Selection options depending on the func-
tion]
• 1 bit
• 1 byte (0...255)
• 1 byte (0%...100%)
• 1 byte (0°...360°)
• 2 byte counter without math. symbol
• 2 byte counter with math. symbol
• 2 byte floating point
• 4 byte counter without math. symbol
• 4 byte counter with math. symbol
• 4 byte floating point
Starting value E1 / E2 / E3[Input range depending on the type of
input]
Prerequisites
When querying the prerequisites set the output type and output values at different statuses:
Output type• 1 bit
• 1 byte (0...255)
• 1 byte (0%...100%)
• 1 byte (0°...360°)
• 2 byte counter without math. symbol
• 2 byte counter with math. symbol
• 2 byte floating point
• 4 byte counter without math. symbol
• 4 byte counter with math. symbol
• 4 byte floating point
Output value (if applicable output value A1 / A2)
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
48Parameter setting
if the condition is met0 [Input range depending on the type of
output]
if the condition is not met0 [Input range depending on the type of
output]
if the monitoring time period
is exceeded
0 [Input range depending on the type of
output]
if blocked0 [Input range depending on the type of
output]
Set the output send pattern.
Output sends• on change
• on change and after reset
• on change and periodically
• when receiving an input object
• when receiving an input object
and periodically
Type of change
(is only sent if "on change" is selected)
• on each change
• on change to condition met
• on change to condition not met
Send cycle
5 s ... 2 h; 10 s
(if sent periodically)
Set the text to be displayed for conditions met / not met.
Text if the condition is met[Free text max. 14 chars.]
Text if the condition is not met[Free text max. 14 chars.]
If applicable set the send delays.
Send delay in the event of change
none • 1 s • ... • 2 h
to the condition is met
Send delay in the event of change
none • 1 s • ... • 2 h
to the condition is not met
Calculations and transformation
For calculations and transformations set the output values to the various conditions:
Output value (if applicable A1 / A2)
if the monitoring time period
is exceeded
0 [Input range depending on the type of
output]
if blocked0 [Input range depending on the type of
output]
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
49Parameter setting
Set the output send pattern.
Output sends• on change
on change of
(only if calculations are
transmitted for changes)
Send cycle
(if sent periodically)
• on change and after reset
• on change and periodically
• when receiving an input object
• when receiving an input object
and periodically
1 ... [Input range depending on the type of
input]
5 s ... 2 h; 10 s
For Calculations of the form output 1 = E1 × X + Y | output 2 = E2 × X +Y define
the variables X and Y. The variables can have a positive or negative sign, 9 digits before
and 9 digits after the decimal point.
Formula for output A1: A1 = E1 × X + Y
X1.00 [free input]
Y0.00 [free input]
Formula for output A2: A2 = E2 × X + Y
X1.00 [free input]
Y0.00 [free input]
Further settings for all formulas
If necessary, activate the input monitoring. Set which inputs are to be monitored, at
which intervals the inputs are to be monitored and what value the "monitoring status"
should have, if the monitoring period is exceeded without feedback.
Use input monitoringNo • Yes
Monitoring of• E1
Monitoring period5 s • ... • 2 h; 1 min
Value of the object "monitoring status"
if period is exceeded
• E2
• E3
• E1 and E2
• E1 and E3
• E2 and E3
• E1 and E2 and E3
[depending on the function]
0 • 1
If necessary, activate the computer block and set what a 1 or 0 at the block entry means
and what happens in the event of a block.
Use blockNo • Yes
Analysis of the blocking object• At value 1: block | At value 0: release
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• At value 0: block | At value 1: release
50Parameter setting
Value before first call 0 • 1
Output pattern
On block
On release• as send pattern [see above]
• do not send anything
• send value
• send current value immediately
6.12.Weekly timer
In the weekly timer in the device 24 periods can be defined. These periods are, for example, used for the internal automatic function timed opening and timed closure.
The respective period objects can be configured as inputs or outputs, i.e. send to the
bus (timer internal, use internal and for other bus members) or be switched from there
(timer function via an external device). If several devices are used in the system, the
timer settings may be done on one device that sends the period objects as output. The
other devices take over the timer-command (input), whereby a better synchronisation
is achieved.
Activate the required periods for the weekly timer. The menus for the further setting of
the computer are then loaded.
Use period 1No • Yes
Use period ... No • Yes
Use period 24No • Yes
6.12.1. Weekly timer period 1-24
Set whether the period can be set (period object is the output and is sent to the bus) or
if the period is received externally via the bus (period object is the input).
Period• can be set
(period object is output)
• can be switched (time period object
is output)
Period can be set (time period object is output)
Set whether the switching times are set per object and in which cases the switching
times received are to be retained. Please note that the setting "After power restoration
and programming" should not be used for the initial start-up, as the factory settings are
always used until the first call (setting via objects is ignored).
Use objects for switching timesNo • Yes
The threshold values and delays received by the communication object
Switching data should• not be retained
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• be retained after power restoration
• be retained after power restoration and
programming
51Parameter setting
Set the switching on and off times and the days of the week for this period. If, for example, 15:35 is set as the switch-off time, the output switches off on the change from
15:35 to 15:36.
Switch on time (hours)0 … 23
Switch on time (minutes)0 … 59
Switch-off time (hours)0 … 23
Switch-off time (minutes)0 … 59
Period switches to
Monday ... SundayNo • Yes
Set the send pattern for the week clock switch output and the value of the output.
Switching output sends• never
Send cycle
(if sent periodically)
8-bit output value if
Period active
8-bit output value if
Period not active
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodically
5 s ... 2 h; 10 s
0 ... 255
0 ... 255
Period that can be switched externally (time period is the input)
The time switches are taken over from an external timer switch. Set at which value the
period is to be active and define the object value before the first communication.
Period is active• at object value = 1
Object value prior to initial communication 0 • 1
• at object value = 0
6.13.Calendar timer
In the calendar timer in the device, four periods with two switching sequences can be
defined.
Activate the required periods for the calendar timer. The menus for the further setting
of the computer are then loaded.
Use period 1No • Yes
Use period ...No • Yes
Use period 4No • Yes
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
52Parameter setting
6.13.1. Calendar clock Period 1-4
Set whether the switching date and the switching time are set per object and in which
cases the switching dates and times received are to be retained. Please note that the
setting "After power restoration and programming" should not be used for the initial
start-up, as the factory settings are always used until the first call (setting via objects
is ignored).
Use objects for switching timesNo • Yes
Maintain the
switching data and times received via com-
munication objects
.
Define the period
From:
MonthJanuary … December
Day1 … 29 / 1 … 30 / 1 … 31 (according to
Up to and including:
MonthJanuary … December
Day1 … 29 / 1 … 30 / 1 … 31 (according to
• never
• after power restoration
• after power restoration and
programming
month)
month)
Sequence 1 / 2
Define the switching times.
Switch on time (hours)0 … 23
Switch on time (minutes)0 … 59
Switch-off time (hours)0 … 23
Switch-off time (minutes)0 … 59
Switching output sends• never
Send cycle
(if sent periodically)
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodically
5 s ... 2 h; 10 s
53Parameter setting
Set the send pattern for the switch sequence and the value of the 8-bit output.
Switching output sends• never
Send cycle
(if sent periodically)
8-bit output value if
Period active
8-bit output value if
Period not active
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodically
5 s ... 2 h; 10 s
0 ... 255
0 ... 255
6.14.Logic
The device has 16 logic inputs, eight AND and eight OR logic gates.
Activate the logic inputs and assign object values up to first call.
Use logic inputsYes • No
Object value prior to first call for:
- Logic input 10 • 1
- Logic input ...0 • 1
- Logic input 160 • 1
Activate the required logic outputs.
AND logic
AND logic 1not active • active
AND logic ...not active • active
AND logic 8not active • active
OR logic
OR logic 1not active • active
OR logic ...not active • active
OR logic 8not active • active
6.14.1. AND logic 1-8 and OR logic outputs 1-8
The same setting options are available for AND and OR logic.
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
54Parameter setting
Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out
put should send if logic = 1 and = 0.
1. / 2. / 3. / 4. Input• do not use
- Logic inputs 1...16
- Logic inputs 1...16 inverted
• all switching events that the device
provides (see AND logic connection inputs, Seite 55
and Verknüpfungseingänge der ODER Logik, Seite 100)
Output type• a 1-Bit-object
• two 8-bit objects
If the output type is a 1-bit object, set the output values for the various conditions.
Output value
1 • 0
if logic = 1
Output value
1 • 0
if logic = 0
Output value
1 • 0
If block is active
Output value if
1 • 0
monitoring period is exceeded
If the output type is two 8-bit objects, set the type of object and the output values
for the various conditions.
Object type• Value (0…255)
• Percent (0…100%)
• Angle (0…360°)
• Scene call-up (0…127)
Output value object A
0 … 255 / 100% / 360° / 127; 1
if logic = 1
Output value object B
0 … 255 / 100% / 360° / 127; 1
if logic = 1
Output value object A
0 … 255 / 100% / 360° / 127; 0
if logic = 0
Output value object B
0 … 255 / 100% / 360° / 127; 0
if logic = 0
Output value object A
0 … 255 / 100% / 360° / 127; 0
if block is active
Output value object B
0 … 255 / 100% / 360° / 127; 0
if block is active
Output value object A if
0 … 255 / 100% / 360° / 127; 0
monitoring period is exceeded
Output value object B if
0 … 255 / 100% / 360° / 127; 0
monitoring period is exceeded
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
55Parameter setting
Set the output send pattern.
Send pattern• on change of logic
Send cycle
(if sent periodically)
• on change of logic to 1
• on change of logic to 0
• on change of logic and periodically
• on change of logic to 1 and periodically
• on change of logic to 0 and periodically
• on change of logic+object receipt
• on change of logic+object receipt
and periodically
5 s • 10 s • ... • 2 h
Block
If necessary, activate the block for the logic output and set what a 1 or 0 at the block
input means and what happens in the event of a block.
Use blockNo • Yes
Analysis of the blocking object• At value 1: block | At value 0: release
Blocking object value before first call 0 • 1
Output pattern
On block
On release
(with 2 seconds release delay)
• At value 0: block | At value 1: release
• Do not send message
• Transmit block value [see above,
Output value if blocking active]
[send value for current logic status]
Monitoring
If necessary, activate the input monitoring. Set which inputs are to be monitored, at
which intervals the inputs are to be monitored and what value the "monitoring status"
should have, if the monitoring period is exceeded without a feedback being given.
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
58Parameter setting
Weekly timer period 5 active
Weekly timer period 5 inactive
Weekly timer period 6 active
Weekly timer period 6 inactive
Weekly timer period 7 active
Weekly timer period 7 inactive
Weekly timer period 8 active
Weekly timer period 8 inactive
Weekly timer period 9 active
Weekly timer period 9 inactive
Weekly timer period 10 active
Weekly timer period 10 inactive
Weekly timer period 11 active
Weekly timer period 11 inactive
Weekly timer period 12 active
Weekly timer period 12 inactive
Weekly timer period 13 active
Weekly timer period 13 inactive
Weekly timer period 14 active
Weekly timer period 14 inactive
Weekly timer period 15 active
Weekly timer period 15 inactive
Weekly timer period 16 active
Weekly timer period 16 inactive
Weekly timer period 17 active
Weekly timer period 17 inactive
Weekly timer period 18 active
Weekly timer period 18 inactive
Weekly timer period 19 active
Weekly timer period 19 inactive
Weekly timer period 20 active
Weekly timer period 20 inactive
Weekly timer period 21 active
Weekly timer period 21 inactive
Weekly timer period 22 active
Weekly timer period 22 inactive
Weekly timer period 23 active
Weekly timer period 23 inactive
Weekly timer period 24 active
Weekly timer period 24 inactive
Calendar timer period 1 sequence 1 active
Calendar timer period 1 sequence 1 inactive
Calendar timer period 1 sequence 2 active
Calendar timer period 1 sequence 2 inactive
Calendar timer period 2 sequence 1 active
Calendar timer period 2 sequence 1 inactive
Calendar timer period 2 sequence 2 active
Calendar timer period 2 sequence 2 inactive
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
59Parameter setting
Calendar timer period 3 sequence 1 active
Calendar timer period 3 sequence 1 inactive
Calendar timer period 3 sequence 2 active
Calendar timer period 3 sequence 2 inactive
Calendar timer period 4 sequence 1 active
Calendar timer period 4 sequence 1 inactive
Calendar timer period 4 sequence 2 active
Calendar timer period 4 sequence 2 inactive
6.14.3. Connection inputs of the OR logic
The OR logic connection inputs correspond to those of the AND logic. In addition, the
following inputs are available for the OR logic:
AND logic output 1
AND logic output 1 inverted
AND logic output 2
AND logic output 2 inverted
AND logic output 3
AND logic output 3 inverted
AND logic output 4
AND logic output 4 inverted
AND logic output 5
AND logic output 5 inverted
AND logic output 6
AND logic output 6 inverted
AND logic output 7
AND logic output 7 inverted
AND logic output 8
AND logic output 8 inverted
Weather Station Suntracer KNX sl basic • Version: 11.03.2016 • Technical changes and errors excepted.
Elsner Elektronik GmbH Control and Automation Technology
Sohlengrund 16
75395 Ostelsheim Phone +49(0) 7033 /30 945-0 info@elsner-elektronik.de
Germany Fax +49(0) 70 33/ 30 945-20 www.elsner-elektronik.de
Technical support: +49 (0) 70 33 / 30 945-250
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.