elsner elektronik Sewi KNX AQS, Sewi KNX AQS/TH-D Installation And Adjustment

Page 1
EN
Sewi KNX AQS and Sewi KNX AQS/TH-D
Indoor Air Quality Sensors
Item numbers 70394 (AQS), 70397 (AQS/TH-D)
Installation and Adjustment
Page 2
Page 3
1 Contents
1. Description ........................................................................................... 5
1.0.1. Scope of delivery .......................................................................................... 6
1.1. Technical data ........................................................................................................... 6
1.1.1. Measuring accuracy ...................................................................................... 7
2. Installation and start-up ....................................................................... 7
2.1. Installation notes ...................................................................................................... 7
2.2. Installation location .................................................................................................. 8
2.3. Construction of the sensor ...................................................................................... 9
2.3.1. Housing from the outside ............................................................................ 9
2.3.2. Printed circuit boards / connections .......................................................... 10
2.4. Assembly ................................................................................................................ 10
2.5. Notes on mounting and commissioning .............................................................. 11
3. Addressing the equipment ................................................................. 12
4. Maintenance ....................................................................................... 12
5. Transfer protocol ............................................................................... 13
5.1. List of all communication objects ......................................................................... 13
6. Parameter setting .............................................................................. 28
6.1. Behaviour on power failure/ restoration of power .............................................. 28
6.2. General settings ..................................................................................................... 29
6.3. Temperature Measurement ................................................................................... 29
6.4. Temperature threshold values .............................................................................. 30
6.4.1. Threshold value 1, 2, 3, 4 ........................................................................... 30
6.5. Temperature PI control .......................................................................................... 32
6.5.1. Heating control level 1/2 ............................................................................. 37
6.5.2. Cooling control level 1/2 ............................................................................. 40
6.6. Summer Compensation ......................................................................................... 42
6.7. Humidity Measurement ......................................................................................... 43
6.8. Humidity threshold values .................................................................................... 44
6.8.1. Threshold value 1, 2, 3, 4 ........................................................................... 44
6.9. Humidity PI control ................................................................................................ 46
6.10.Dewpoint measurement ........................................................................................ 49
6.10.1. Cooling medium temp. monitoring ........................................................... 49
6.11.Absolute humidity ................................................................................................. 51
6.12.Comfort field .......................................................................................................... 52
6.13.Air Pressure Measurement ................................................................................... 53
6.14.Air pressure threshold values ............................................................................... 54
6.14.1. Air pressure threshold value 1-4 ............................................................... 54
6.15.CO2 Measurement ................................................................................................. 57
6.16.CO2 threshold values ............................................................................................ 57
6.16.1. Threshold value 1, 2, 3, 4 ........................................................................... 57
6.17.CO2 PI-control ........................................................................................................ 60
6.18.Variable comparator .............................................................................................. 62
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • from ETS programme version 1.1
Version: 10.09.2018 • Technical changes and errors excepted.
Page 4
2 Contents
6.18.1. Control variable comparator 1/2/3/4 .......................................................... 62
6.19.Computer ................................................................................................................ 63
6.19.1. Computer 1-8 ............................................................................................... 63
6.20.Logic ........................................................................................................................ 67
6.20.1. AND logic 1-8 and OR logic outputs 1-8 ................................................... 67
6.20.2. AND logic connection inputs ..................................................................... 69
6.20.3. Connection inputs of the OR logic ............................................................. 72
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • from ETS programme version 1.1
Version: 10.09.2018 • Technical changes and errors excepted.
Page 5
3 Clarification of signs
Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician.
This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to­date version of the manual is available.
Clarification of signs used in this manual
Safety advice.
Safety advice for working on electrical connections, components, etc.
DANGER!
WARNING!
CAUTION!
ATTENTION!
ETS In the ETS tables, the parameter default settings are marked by
... indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to trivial or minor injuries if it is not avoided.
... indicates a situation which may lead to damage to property if it is not avoided.
underlining.
Page 6
4 Clarification of signs
Page 7
5 Description

1. Description

The Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D for the KNX bus system measures the CO
Sewi KNX AQS/TH-D additionally measures the temperature, the air humidity and the air pressure and calculates the dew-point. The sensor can output a warning to the bus as soon as the comfort field, as per DIN 1946, is left.
Via the bus, the indoor sensors can receive external values and process it further with its own data to a total value (mixed value, e.g. room average).
All measurement values can be used for the control of limit-dependent switching out­puts. States can be linked via AND logic gates and OR logic gates. Multi-function mod­ules change input data as required by means of calculations, querying a condition, or converting the data point type. In addition, an integrated manipulated variable compar­ator can compare and output variables that were received via communication objects.
Integrated PI-controllers control ventilation (according to humidity or CO tion) and heating/cooling (according to temperature).
Functions:
Measuring the CO The share of internal measurement value and external value can be set as a percentage
Threshold values can be adjusted per parameter or via communication objects
PI controller for ventilation according to CO (one-stage) or Ventilate (one or two-stage)
8 AND and 8 OR logic gates, each with 4 inputs. All switching events as well as 16 logic inputs in the form of communications objects can be used as inputs for the logic gates. The output of each gate can be configured optionally as 1­bit or 2 x 8-bit
8 multi-function modules (computers) for changing the input data by calculations, by querying a condition or by converting the data point type
4 actuating variable comparators to output minimum, maximum or average values. 5 inputs each for values received via communication objects
Additional functions Sewi KNX AQS/TH-D:
Measuring the temperature and air humidity (relative, absolute), each with mixed value calculation. The share of internal measurement value and
external value can be set as a percentage
Bus message, whether the values for temperature and air humidity are within the comfort field (DIN 1946). Dew point calculation
Air pressure measurement. Output of the value as normal pressure and optionally as barometric pressure
PI-controller for heating (one or two-stage) and cooling (one or two-stage) according to temperature. Regulation according to separate setpoints or basic setpoint temperature
concentration in a room.
2
concentration of the air with mixed value calculation.
2
concentration: Ventilate/Air
2
concentra-
2
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 8
6 Description
PI controller for ventilation according to humidity: Ventilate/Air (one-stage) or Ventilate (one or two-stage)
Summer compensation for cooling systems. A characteristic curve matches the target temperature in the room to the external temperature and sets the minimum and maximum target temperature values
Configuration is made using the KNX software ETS. The product file can be down­loaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser­vice” menu.

1.0.1. Scope of delivery

•Sensor

1.1. Technical data

Housing Plastic Colour White (Cover glossy, skirting matt) Assembly Surface, wall or ceiling installation Protection category IP 30 Dimensions Ø approx. 105 mm, height approx. 32 mm Total weight approx. 50 g Ambient temperature Operation 0…+50°C, storage -30…+70°C Ambient humidity max. 85% RH, avoid condensation Operating voltage KNX bus voltage Bus current max. 20 mA Data output KNX +/- bus plug-in terminal BCU type Integrated microcontroller PEI type 0 Group addresses max. 2000 Assignments max. 2000 Communication objects Sewi KNX AQS/TH-D: 363
CO2 sensor:
Measurement range 0...2000 ppm Resolution 1 ppm Accuracy* ± 50 ppm ± 3% of the measured value Temperature sensor (only Sewi KNX AQS/TH-D): Measurement range 0°C…+50°C Resolution 0.1°C Accuracy* ±0.5°C at 0...+50°C Humidity sensor (only Sewi KNX AQS/TH-D): Measurement range 0% RH … 85% RH Resolution 0.1% RH
Sewi KNX AQS: 210
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 9
7 Installation and start-up
Accuracy ± 7,5% RH at 0…10% RH
Pressure sensor (only Sewi KNX AQS/TH-D): Measurement range 300 mbar … 1100 mbar Resolution 0.1 mbar Accuracy ±4 mbar
* Follow the instructions on Measuring accuracy.
The product conforms with the provisions of EU directives.
± 4,5% RH at 10…85% RH

1.1.1. Measuring accuracy

Deviations in measured values due to interfering sources (see chapter installation site) must be corrected in the ETS in order to achieve the specified accuracy of the sensor (offset).
During Temperature measurement, the self-heating of the device is taken into con­sideration by the electronics. The software compensates the self-heating by reducing the measured temperature by 1.0°C.

2. Installation and start-up

2.1. Installation notes

Installation, testing, operational start-up and troubleshooting should only be performed by an electrician.
CAUTION! Live voltage!
There are unprotected live components inside the device.
National legal regulations are to be followed.
Ensure that all lines to be assembled are free of voltage and take precautions against accidental switching on.
Do not use the device if it is damaged.
Take the device or system out of service and secure it against unintentional use, if it can be assumed, that risk-free operation is no longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage. If it has been damaged in transport, inform the supplier immediately.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 10
8 Installation and start-up
The device may only be used as a fixed-site installation; that means only when assem­bled and after conclusion of all installation and operational start-up tasks and only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.

2.2. Installation location

Install and use only in dry interior rooms! Avoid condensation.
The sensor is installed surface mounted on walls or ceilings.
When selecting an installation location, please ensure that the measurement results of
temperature, humidity and CO
ences. Possible sources of interference include:
Direct sunlight
Drafts from windows and doors
Draughts from ducts coming from other rooms or the outdoors
Warming or cooling of the building structure on which the sensor is mounted, e.g. due to sunlight, heating or cold water pipes
Connection lines and empty ducts which lead from warmer or colder areas to the sensor
Measurement variations from such sources of interference must be corrected in the ETS in order to ensure the specified accuracy of the sensor (offset).
are affected as little as possible by external influ-
2
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 11
9 Installation and start-up
Fig. 1 A Recess to open the hous-
ing. When closing the housing, the recess aligns to the marking on the skirt­ing
A

2.3. Construction of the sensor

2.3.1. Housing from the outside

Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 12
10 Installation and start-up
Fig. 2 1 a+b Long holes for mounting (hole distance 60 mm) 2 Sensors for temperature, humidity, pressure (only Sewi KNX AQS/TH-D) 3CO
2
-Sensor 4 Programming button 5 Programming LED 6KNX-terminal BUS +/­7 Cable bushing A Mark for aligning the cover
1a
A
1b
3 4
6
7
5
2
Fig. 3
Open the housing. To do this, carefully lift the cover from the skirting. Start at the recess (Fig. 2: A).

2.3.2. Printed circuit boards / connections

2.4. Assembly

Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 13
11 Installation and start-up
Fig. 4
Lead the bus cable through the cable busching in the skirting.
Fig. 5
Screw the skirting to the wall or the ceiling.
Hole distance 60 mm.
60 mm
Fig. 6
Connect the KNX bus to the KNX terminal.
Fig. 7
Close the housing by positioning the cover and snapping it into place. To do this, align the recess on the cover to the marking on the skirting (Fig. 1+2: A).

2.5. Notes on mounting and commissioning

Never expose the device to water (e.g. rain) or dust. This can damage the electronics. You must not exceed a relative humidity of 85%. Avoid condensation.
The air slots on the side must not be closed or covered.
After the bus voltage has been applied, the device will enter an initialisation phase last­ing a few seconds. During this phase no information can be received or sent via the bus.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 14
12 Addressing the equipment

3. Addressing the equipment

The equipment is delivered with the bus address 15.15.254. You can program a differ­ent address in the ETS by overwriting the address 15.15.254 or by teaching the device via the programming button.
The programming button is on the inside of the housing (Fig. 2: No. 3).

4. Maintenance

The air slots on the side must not get dirty or covered. As a rule, it is sufficient to wipe the device with a soft, dry cloth twice a year.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 15
13 Transfer protocol

5. Transfer protocol

Units:
Temperatures in degrees Celsius Air pressure in Pascal Air humidity in % Absolute air humidity in g/kg and/or g/m CO2 content in ppm Variables in %

5.1. List of all communication objects

Abbreviation flags:
C Communication R Read WWrite T Transfer UUpdate
No. Text Func-
1 Software version Output R-CT [217.1] DPT_Ver-
41 Temperature sensor: Malfunction Output R-CT [1.1] DPT_Switch 1 bit 42 Temperature sensor: External
measurement
43 Temperature sensor: Measured value Output R-CT [9.1] DPT_Val-
44 Temperature sensor: Total
measurement
45 Temperature sensor: Min./Max.
measurement query
46 Temperature sensor: Minimum
measurement
47 Temperature sensor: Maximum
measurement
48 Temperature sensor: Min./Max.
measurement reset
51 Temp. threshold value 1: Absolute
value 52 Temp. threshold value 1: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 53 Temp. threshold value 1: Switching
delay from 0 to 1 54 Temp. threshold value 1: Switching
delay from 1 to 0
3
tion
Input -WCT [9.1] DPT_Val-
Output R-CT [9.1] DPT_Val-
Input -WC- [1.017] DPT_Trig-
Output R-CT [9.1] DPT_Val-
Output R-CT [9.1] DPT_Val-
Input -WC- [1.017] DPT_Trig-
Input/ Output
Input -WC- [7.5] DPT_Time-
Input -WC- [7.5] DPT_Time-
Flags DPT Typ Size
sion
ue_Temp
ue_Temp
ue_Temp
ger
ue_Temp
ue_Temp
ger
RWCT [9.1] DPT_Val-
ue_Temp
PeriodSec
PeriodSec
2 bytes
2 bytes
2 bytes
2 bytes
1 bit
2 bytes
2 bytes
1 bit
2 bytes
2 bytes
2 bytes
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 16
14 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
55 Temp. threshold value 1: Switching
Output R-CT [1.1] DPT_Switch 1 bit
output 56 Temp. threshold value 1: Switching
Input -WC- [1.1] DPT_Switch 1 bit
output block 58 Temp. threshold value 2: Absolute
value
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
59 Temp. threshold value 2: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 60 Temp. threshold value 2: Switching
delay from 0 to 1 61 Temp. threshold value 2: Switching
delay from 1 to 0 62 Temp. threshold value 2: Switching
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
output 63 Temp. threshold value 2: Switching
Input -WC- [1.1] DPT_Switch 1 bit
output block 65 Temp. threshold value 3: Absolute
value
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
66 Temp. threshold value 3: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 67 Temp. threshold value 3: Switching
delay from 0 to 1 68 Temp. threshold value 3: Switching
delay from 1 to 0 69 Temp. threshold value 3: Switching
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
output 70 Temp. threshold value 3: Switching
Input -WC- [1.1] DPT_Switch 1 bit
output block 72 Temp. threshold value 4: Absolute
value
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
73 Temp. threshold value 4: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 74 Temp. threshold value 4: Switching
delay from 0 to 1 75 Temp. threshold value 4: Switching
delay from 1 to 0 76 Temp. threshold value 4: Switching
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
output 77 Temp. threshold value 4: Switching
Input -WC- [1.1] DPT_Switch 1 bit
output block 311 Humidity sensor: Malfunction Output R-CT [1.1] DPT_Switch 1 bit 314 Humidity sensor: External
measurement 315 Humidity sensor: Measured value Output R-CT [9.7] DPT_Val-
Input -WCT [9.7] DPT_Val-
ue_Humidity
2 bytes
2 bytes
ue_Humidity
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 17
15 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
316 Humidity sensor: Total measurement Output R-CT [9.7] DPT_Val-
2 bytes
ue_Humidity
317 Humidity sensor: Min./Max.
measurement query 318 Humidity sensor: Minimum
measurement 319 Humidity sensor: Maximum
measurement 320 Humidity sensor: Min./Max.
measurement reset 331 Humidity threshold value 1: Absolute
value
Input -WC- [1.017] DPT_Trig-
ger
Output R-CT [9.7] DPT_Val-
ue_Humidity
Output R-CT [9.7] DPT_Val-
ue_Humidity
Input -WC- [1.017] DPT_Trig-
ger
Input/ Output
RWCT [9.7] DPT_Val-
ue_Humidity
1 bit
2 bytes
2 bytes
1 bit
2 bytes
332 Humidity threshold value 1: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 333 Humidity threshold value 1: Delay
from 0 to 1 334 Humidity threshold value 1: Delay
from 1 to 0 335 Humidity threshold value 1:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 336 Humidity threshold value 1:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block 337 Humidity threshold value 2: Absolute
value
Input/ Output
RWCT [9.7] DPT_Val-
ue_Humidity
2 bytes
338 Humidity threshold value 2: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 339 Humidity threshold value 2:
Delay from 0 to 1 340 Humidity threshold value 2:
Delay from 1 to 0 341 Humidity threshold value 2:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 342 Humidity threshold value 2:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block 343 Humidity threshold value 3: Absolute
value
Input/ Output
RWCT [9.7] DPT_Val-
ue_Humidity
2 bytes
344 Humidity threshold value 3: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 345 Humidity threshold value 3:
Delay from 0 to 1 346 Humidity threshold value 3:
Delay from 1 to 0 347 Humidity threshold value 3:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 348 Humidity threshold value 3:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 18
16 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
349 Humidity threshold value 4:
Absolute value
Input/ Output
RWCT [9.7] DPT_Val-
ue_Humidity
2 bytes
350 Humidity threshold value 4: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 351 Humidity threshold value 4:
Delay from 0 to 1 352 Humidity threshold value 4:
Delay from 1 to 0 353 Humidity threshold value 4:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 354 Humidity threshold value 4:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block 381 Dewpoint: Measured value Output R-CT [9.1] DPT_Val-
2 bytes
ue_Temp
382 Coolant temp.: Threshold value Output R-CT [9.1] DPT_Val-
2 bytes
ue_Temp
383 Coolant temp.: Actual value Input RWCT [9.1] DPT_Val-
2 bytes
ue_Temp
384 Coolant temp.: Offset change
Input -WC- [1.1] DPT_Switch 1 bit
(1:+ | 0:-) 385 Coolant temp.: Current offset Output R-CT [9.1] DPT_Val-
2 bytes
ue_Temp
386 Coolant temp.: Switching delay from
0 to 1 387 Coolant temp.: Switching delay from
1 to 0
Input -WC- [7.5] DPT_Time-
PeriodSec
Input -WC- [7.5] DPT_Time-
PeriodSec
2 bytes
2 bytes
388 Coolant temp.: Switching output Output R-CT [1.1] DPT_Switch 1 bit 389 Coolant temp.: Switching output
Input -WC- [1.1] DPT_Switch 1 bit
block 391 Absolute humidity [g/kg] Output R-CT [14.5] DPT_Val-
4 bytes
ue_Amplitude
392 Absolute humidity [g/m²] Output R-CT [14.17] DPT_Val-
4 bytes
ue_Density
394 Ambient climate status:
Output R-CT [1.1] DPT_Switch 1 bit
1 = comfortable | 0 = uncomfortable 395 Ambient climate status: Text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 401 Air pressure sensor: Malfunction Output R-CT [1.1] DPT_Switch 1 bit 402 Air pressure sensor: Normal
measurement [Pa]
403 Air pressure sensor: Barometric
measurement [Pa]
404 Air pressure sensor: Min./Max.
measurement query
Output R-CT [14.58] DPT_Val-
ue_Pressure
Output R-CT [14.58] DPT_Val-
ue_Pressure
Input -WC- [1.017] DPT_Trig-
ger
4 bytes
4 bytes
1 bit
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 19
17 Transfer protocol
No. Text Func-
tion
405 Air pressure sensor: Min. normal
Output R-CT [14.58] DPT_Val-
measurement [Pa]
406 Air pressure sensor: Min. barometric
Output R-CT [14.58] DPT_Val-
measurement [Pa]
407 Air pressure sensor: Max. normal
Output R-CT [14.58] DPT_Val-
measurement [Pa]
408 Air pressure sensor: Max. barometric
Output R-CT [14.58] DPT_Val-
measurement [Pa]
409 Air pressure sensor: Min./Max.
Input -WC- [1.017] DPT_Trig-
measurement reset
410 Air pressure sensor: Pressure range
Output R-CT [16.0]
text
411 Air pressure threshold value 1:
Absolute value
412 Air pressure threshold value 1:
Input/ Output
Input -WC- [1.1] DPT_Switch 1 bit
(1:+ | 0:-)
413 Air pressure threshold value 1:
Input -WC- [7.5] DPT_Time-
Delay from 0 to 1
414 Air pressure threshold value 1:
Input -WC- [7.5] DPT_Time-
Delay from 1 to 0
415 Air pressure threshold value 1:
Output R-CT [1.1] DPT_Switch 1 bit
Switching output
416 Air pressure threshold value 1:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block
417 Air pressure threshold value 2:
Absolute value
418 Air pressure threshold value 2:
Input/ Output
Input -WC- [1.1] DPT_Switch 1 bit
(1:+ | 0:-)
419 Air pressure threshold value 2:
Input -WC- [7.5] DPT_Time-
Delay from 0 to 1
420 Air pressure threshold value 2:
Input -WC- [7.5] DPT_Time-
Delay from 1 to 0
421 Air pressure threshold value 2:
Output R-CT [1.1] DPT_Switch 1 bit
Switching output
422 Air pressure threshold value 2:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block
423 Air pressure threshold value 3:
Absolute value
424 Air pressure threshold value 3:
Input/ Output
Input -WC- [1.1] DPT_Switch 1 bit
(1:+ | 0:-)
425 Air pressure threshold value 3:
Input -WC- [7.5] DPT_Time-
Delay from 0 to 1
Flags DPT Typ Size
4 bytes
ue_Pressure
4 bytes
ue_Pressure
4 bytes
ue_Pressure
4 bytes
ue_Pressure
1 bit
ger
14
DPT_String_ASCII
RWCT [14.58] DPT_Val-
bytes
4 bytes
ue_Pressure
2 bytes
PeriodSec
2 bytes
PeriodSec
RWCT [14.58] DPT_Val-
4 bytes
ue_Pressure
2 bytes
PeriodSec
2 bytes
PeriodSec
RWCT [14.58] DPT_Val-
4 bytes
ue_Pressure
2 bytes
PeriodSec
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 20
18 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
426 Air pressure threshold value 3:
Delay from 1 to 0
427 Air pressure threshold value 3:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output
428 Air pressure threshold value 3:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block
429 Air pressure threshold value 4:
Absolute value
430 Air pressure threshold value 4:
Input/ Output
RWCT [14.58] DPT_Val-
ue_Pressure
4 bytes
Input -WC- [1.1] DPT_Switch 1 bit
(1:+ | 0:-)
431 Air pressure threshold value 4:
Delay from 0 to 1
432 Air pressure threshold value 4:
Delay from 1 to 0
433 Air pressure threshold value 4:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output
434 Air pressure threshold value 4:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block 441 CO2 Sensor: Malfunction Output R-CT [1.1] DPT_Switch 1 bit 442 CO2 Sensor: External measurement Input -WCT [9,008] DPT_Val-
2 bytes
ue_AirQuality
443 CO2 Sensor: Measured value Output R-CT [9,008] DPT_Val-
2 bytes
ue_AirQuality
444 CO2 Sensor: Total measurement Output R-CT [9,008] DPT_Val-
2 bytes
ue_AirQuality
445 CO2 Sensor: Max. measurement
query 446 CO2 Sensor: Maximum
measurement 447 CO2 Sensor: Max. reset
measurement 448 CO2 threshold value 1: Absolute
value
Input -WC- [1.017] DPT_Trig-
ger
Output R-CT [9,008] DPT_Val-
ue_AirQuality
Input -WC- [1.017] DPT_Trig-
ger
Input/ Output
RWCT [9,008] DPT_Val-
ue_AirQuality
1 bit
2 bytes
1 bit
2 bytes
449 CO2 threshold value 1: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 450 CO2 threshold value 1:
Delay from 0 to 1 451 CO2 threshold value 1:
Delay from 1 to 0 452 CO2 threshold value 1:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 453 CO2 threshold value 1:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 21
19 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
454 CO2 threshold value 2:
Absolute value
Input/ Output
RWCT [9,008] DPT_Val-
ue_AirQuality
2 bytes
455 CO2 threshold value 2: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 456 CO2 threshold value 2:
Delay from 0 to 1 457 CO2 threshold value 2:
Delay from 1 to 0 458 CO2 threshold value 2:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 459 CO2 threshold value 2:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block 460 CO2 threshold value 3:
Absolute value
Input/ Output
RWCT [9,008] DPT_Val-
ue_AirQuality
2 bytes
461 CO2 threshold value 3: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 462 CO2 threshold value 3:
Delay from 0 to 1 463 CO2 threshold value 3:
Delay from 1 to 0 464 CO2 threshold value 3:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 465 CO2 threshold value 3:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block 466 CO2 threshold value 4:
Absolute value
Input/ Output
RWCT [9,008] DPT_Val-
ue_AirQuality
2 bytes
467 CO2 threshold value 4: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit 468 CO2 threshold value 4:
Delay from 0 to 1 469 CO2 threshold value 4:
Delay from 1 to 0 470 CO2 threshold value 4:
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WC- [7.5] DPT_Time-
2 bytes
PeriodSec
Output R-CT [1.1] DPT_Switch 1 bit
Switching output 471 CO2 threshold value 4:
Input -WC- [1.1] DPT_Switch 1 bit
Switching output block 472 CO2 controller: Block (1: block) Input -WC- [1.2] DPT_Bool 1 bit 473 CO2 controller: Setpoint value Input/
Output
474 CO2 controller: Setpoint value
Input -WC- [1.2] DPT_Bool 1 bit
RWCT [9,008] DPT_Val-
ue_AirQuality
2 bytes
(1:+ | 0:-) 475 CO2 controller: Control variable
Output R-CT [5.1] DPT_Scaling 1 byte
ventilation 476 CO2 controller: Control variable
Output R-CT [5.1] DPT_Scaling 1 byte
ventilation level 2
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 22
20 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
477 CO2 controller: Ventilation status
Output R-CT [1.1] DPT_Switch 1 bit
(1:ON | 0:OFF) 478 CO2 controller: Status ventilation
Output R-CT [1.1] DPT_Switch 1 bit
level 2 (1:ON | 0:OFF) 481 Temp. controller: HVAC mode
(priority 1) 482 Temp. controller: HVAC mode
(priority 2) 483 Temp. controller: Mode frost/heat
Input -WC- [20.102] DPT_H-
1 byte
VACMode
Input RWCT [20.102] DPT_H-
1 byte
VACMode
Input RWCT [1.1] DPT_Switch 1 bit
protection activation 484 Temp. controller: Block (1 = Blocking) Input -WC- [1.1] DPT_Switch 1 bit 485 Temp. controller: Current setpoint Output R-CT [9.1] DPT_Val-
2 bytes
ue_Temp
486 Temp. controller: Switching
Input -WC- [1.1] DPT_Switch 1 bit
(0: Heating | 1: Cooling) 487 Temp. controller: Setpoint comfort
heating 488 Temp. controller: Setpoint comfort
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
Input -WC- [1.1] DPT_Switch 1 bit
heating (1:+ | 0: -) 489 Temp. controller: Setpoint comfort
cooling 490 Temp. controller: Setpoint comfort
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
Input -WC- [1.1] DPT_Switch 1 bit
cooling (1:+ | 0: -) 491 Temp. controller: Basic 16-bit
setpoint shift 492 Temp. controller: Setpoint standby
heating 493 Temp. controller: Setpoint standby
Input/ Output
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
2 bytes
Input -WC- [1.1] DPT_Switch 1 bit
heating (1:+ | 0: -) 494 Temp. controller: Setpoint standby
cooling 495 Temp. controller: Setpoint standby
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
Input -WC- [1.1] DPT_Switch 1 bit
cooling (1:+ | 0: -) 496 Temp. controller: Setpoint eco
heating 497 Temp. controller: Setpoint, eco
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
Input -WC- [1.1] DPT_Switch 1 bit
heating (1:+ | 0: -) 498 Temp. controller: Setpoint eco
cooling 499 Temp. controller: Setpoint, eco
Input/ Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
Input -WC- [1.1] DPT_Switch 1 bit
cooling (1:+ | 0: -) 500 Temp. controller: Control variable,
Output R-CT [5.1] DPT_Scaling 1 byte
heating (level 1)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 23
21 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
501 Temp. controller: Control variable,
Output R-CT [5.1] DPT_Scaling 1 byte
heating (level 2) 502 Temp. controller: Control variable,
Output R-CT [5.1] DPT_Scaling 1 byte
cooling (level 1) 503 Temp. controller: Control variable,
Output R-CT [5.1] DPT_Scaling 1 byte
cooling (level 2) 504 Temperature controller: Variable for
Output R-CT [5.1] DPT_Scaling 1 byte
4/6-way valve 505 Temp. controller: Status heating
Output R-CT [1.1] DPT_Switch 1 bit
level 1 (1:ON | 0:OFF) 506 Temp. controller: Status heating
Output R-CT [1.1] DPT_Switch 1 bit
level 2 (1:ON | 0:OFF) 507 Temp. controller: Status cooling
Output R-CT [1.1] DPT_Switch 1 bit
level 1 (1:ON | 0:OFF) 508 Temp. controller: Status cooling
Output R-CT [1.1] DPT_Switch 1 bit
level 2 (1:ON | 0:OFF) 509 Temp. controller: Comfort extension
status 510 Temp. controller: Comfort extension
time 515 European Summer Time: Outside
temperature 516 European Summer Time: Setpoint
value 517 European Summer Time: Block
Input/
RWCT [1.1] DPT_Switch 1 bit
Output Input RWCT [7.5] DPT_Time-
2 bytes
PeriodSec
Input -WCT [9.1] DPT_Val-
2 bytes
ue_Temp
Output R-CT [9.1] DPT_Val-
2 bytes
ue_Temp
Input -WC- [1.1] DPT_Switch 1 bit
(1 = Blocking) 521 Humidity controller: Block (1: block) Input -WC- [1.2] DPT_Bool 1 bit 522 Humidity controller: Setpoint value Input/
Output
523 Humidity controller: Setpoint
Input -WC- [1.2] DPT_Bool 1 bit
RWCT [9,007] DPT_Val-
ue_Humidity
2 bytes
value (1:+ | 0:-) 524 Humidity controller: Control variable
Output R-CT [5.1] DPT_Scaling 1 byte
dehumidification 525 Humidity controller: Control variable
Output R-CT [5.1] DPT_Scaling 1 byte
dehumidification level 2 526 Humidity controller: Control variable
Output R-CT [5.1] DPT_Scaling 1 byte
humidification 527 Humidity controller:
Output R-CT [1.1] DPT_Switch 1 bit Dehumidification status (1:ON | 0:OFF)
528 Humidity controller:
Output R-CT [1.1] DPT_Switch 1 bit Dehumidification 2 status (1:ON | 0:OFF)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 24
22 Transfer protocol
No. Text Func-
tion
529 Humidity controller: Humidification
Output R-CT [1.1] DPT_Switch 1 bit status (1:ON | 0:OFF)
1111 Control variable comparator 1:
Input -WC- [5.1] DPT_Scaling 1 byte Input 1
1112 Control variable comparator 1:
Input -WC- [5.1] DPT_Scaling 1 byte Input 2
1113 Control variable comparator 1:
Input -WC- [5.1] DPT_Scaling 1 byte Input 3
1114 Control variable comparator 1:
Input -WC- [5.1] DPT_Scaling 1 byte Input 4
1115 Control variable comparator 1:
Input -WC- [5.1] DPT_Scaling 1 byte Input 5
1116 Control variable comparator 1:
Output R-CT [5.1] DPT_Scaling 1 byte Output
1117 Control variable comparator 1:
Output -WC- [1.2] DPT_Bool 1 bit Block: block)
1118 Control variable comparator 2:
Input -WC- [5.1] DPT_Scaling 1 byte Input 1
1119 Control variable comparator 2:
Input -WC- [5.1] DPT_Scaling 1 byte Input 2
1120 Control variable comparator 2:
Input -WC- [5.1] DPT_Scaling 1 byte Input 3
1121 Control variable comparator 2:
Input -WC- [5.1] DPT_Scaling 1 byte Input 4
1122 Control variable comparator 2:
Input -WC- [5.1] DPT_Scaling 1 byte Input 5
1123 Control variable comparator 2:
Output R-CT [5.1] DPT_Scaling 1 byte Output
1124 Control variable comparator 2:
Output -WC- [1.2] DPT_Bool 1 bit Block (1: block)
1125 Control variable comparator 3:
Input -WC- [5.1] DPT_Scaling 1 byte Input 1
1126 Control variable comparator 3:
Input -WC- [5.1] DPT_Scaling 1 byte Input 2
1127 Control variable comparator 3:
Input -WC- [5.1] DPT_Scaling 1 byte Input 3
1128 Control variable comparator 3:
Input -WC- [5.1] DPT_Scaling 1 byte Input 4
1129 Control variable comparator 3:
Input -WC- [5.1] DPT_Scaling 1 byte Input 5
1130 Control variable comparator 3:
Output R-CT [5.1] DPT_Scaling 1 byte Output
Flags DPT Typ Size
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 25
23 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
1131 Control variable comparator 3:
Output -WC- [1.2] DPT_Bool 1 bit Block (1: block)
1132 Control variable comparator 4:
Input -WC- [5.1] DPT_Scaling 1 byte Input 1
1133 Control variable comparator 4:
Input -WC- [5.1] DPT_Scaling 1 byte Input 2
1134 Control variable comparator 4:
Input -WC- [5.1] DPT_Scaling 1 byte Input 3
1135 Control variable comparator 4:
Input -WC- [5.1] DPT_Scaling 1 byte Input 4
1136 Control variable comparator 4:
Input -WC- [5.1] DPT_Scaling 1 byte Input 5
1137 Control variable comparator 4:
Output R-CT [5.1] DPT_Scaling 1 byte Output
1138 Control variable comparator 4:
Output -WC- [1.2] DPT_Bool 1 bit Block (1: block)
1141 Computer 1: Input I1 Input RWCT Depending on
4 bytes
setting
1142 Computer 1: Input I2 Input RWCT Depending on
4 bytes
setting
1143 Computer 1: Input I3 Input RWCT Depending on
4 bytes
setting
1144 Computer 1: Output O1 Output R-CT Depending on
4 bytes
setting
1145 Computer 1: Output O2 Output R-CT Depending on
4 bytes
setting
1146 Computer 1: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1147 Computer 1: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1148 Computer 1: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit 1149 Computer 2: Input I1 Input RWCT Depending on
4 bytes
setting
1150 Computer 2: Input I2 Input RWCT Depending on
4 bytes
setting
1151 Computer 2: Input I3 Input RWCT Depending on
4 bytes
setting
1152 Computer 2: Output O1 Output R-CT Depending on
4 bytes
setting
1153 Computer 2: Output O2 Output R-CT Depending on
4 bytes
setting
1154 Computer 2: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1155 Computer 2: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 26
24 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
1156 Computer 2: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit 1157 Computer 3: Input I1 Input RWCT Depending on
4 bytes
setting
1158 Computer 3: Input I2 Input RWCT Depending on
4 bytes
setting
1159 Computer 3: Input I3 Input RWCT Depending on
4 bytes
setting
1160 Computer 3: Output O1 Output R-CT Depending on
4 bytes
setting
1161 Computer 3: Output O2 Output R-CT Depending on
4 bytes
setting
1162 Computer 3: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1163 Computer 3: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1164 Computer 3: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit 1165 Computer 4: Input I1 Input RWCT Depending on
4 bytes
setting
1166 Computer 4: Input I2 Input RWCT Depending on
4 bytes
setting
1167 Computer 4: Input I3 Input RWCT Depending on
4 bytes
setting
1168 Computer 4: Output O1 Output R-CT Depending on
4 bytes
setting
1169 Computer 4: Output O2 Output R-CT Depending on
4 bytes
setting
1170 Computer 4: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1171 Computer 4: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1172 Computer 4: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit 1173 Computer 5: Input I1 Input RWCT Depending on
4 bytes
setting
1174 Computer 5: Input I2 Input RWCT Depending on
4 bytes
setting
1175 Computer 5: Input I3 Input RWCT Depending on
4 bytes
setting
1176 Computer 5: Output O1 Output R-CT Depending on
4 bytes
setting
1177 Computer 5: Output O2 Output R-CT Depending on
4 bytes
setting
1178 Computer 5: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1179 Computer 5: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1180 Computer 5: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 27
25 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
1181 Computer 6: Input I1 Input RWCT Depending on
4 bytes
setting
1182 Computer 6: Input I2 Input RWCT Depending on
4 bytes
setting
1183 Computer 6: Input I3 Input RWCT Depending on
4 bytes
setting
1184 Computer 6: Output O1 Output R-CT Depending on
4 bytes
setting
1185 Computer 6: Output O2 Output R-CT Depending on
4 bytes
setting
1186 Computer 6: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1187 Computer 6: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1188 Computer 6: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit 1189 Computer 7: Input I1 Input RWCT Depending on
4 bytes
setting
1190 Computer 7: Input I2 Input RWCT Depending on
4 bytes
setting
1191 Computer 7: Input I3 Input RWCT Depending on
4 bytes
setting
1192 Computer 7: Output O1 Output R-CT Depending on
4 bytes
setting
1193 Computer 7: Output O2 Output R-CT Depending on
4 bytes
setting
1194 Computer 7: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1195 Computer 7: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1196 Computer 7: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit 1197 Computer 8: Input I1 Input RWCT Depending on
4 bytes
setting
1198 Computer 8: Input I2 Input RWCT Depending on
4 bytes
setting
1199 Computer 8: Input I3 Input RWCT Depending on
4 bytes
setting
1200 Computer 8: Output O1 Output R-CT Depending on
4 bytes
setting
1201 Computer 8: Output O2 Output R-CT Depending on
4 bytes
setting
1202 Computer 8: Condition text Output R-CT [16.0]
DPT_String_ASCII
14
bytes 1203 Computer 8: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1204 Computer 8: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit 1391 Logic input 1 Input -WC- [1.2] DPT_Bool 1 bit
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 28
26 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
1392 Logic input 2 Input -WC- [1.2] DPT_Bool 1 bit 1393 Logic input 3 Input -WC- [1.2] DPT_Bool 1 bit 1394 Logic input 4 Input -WC- [1.2] DPT_Bool 1 bit 1395 Logic input 5 Input -WC- [1.2] DPT_Bool 1 bit 1396 Logic input 6 Input -WC- [1.2] DPT_Bool 1 bit 1397 Logic input 7 Input -WC- [1.2] DPT_Bool 1 bit 1398 Logic input 8 Input -WC- [1.2] DPT_Bool 1 bit 1399 Logic input 9 Input -WC- [1.2] DPT_Bool 1 bit 1400 Logic input 10 Input -WC- [1.2] DPT_Bool 1 bit 1401 Logic input 11 Input -WC- [1.2] DPT_Bool 1 bit 1402 Logic input 12 Input -WC- [1.2] DPT_Bool 1 bit 1403 Logic input 13 Input -WC- [1.2] DPT_Bool 1 bit 1404 Logic input 14 Input -WC- [1.2] DPT_Bool 1 bit 1405 Logic input 15 Input -WC- [1.2] DPT_Bool 1 bit 1406 Logic input 16 Input -WC- [1.2] DPT_Bool 1 bit 1411 AND logic 1: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1412 AND logic 1: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount
1413 AND logic 1: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1414 AND logic 1: Block Input -WC- [1.1] DPT_Switch 1 bit 1415 AND logic 2: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1416 AND logic 2: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1417 AND logic 2: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1418 AND logic 2: Block Input -WC- [1.1] DPT_Switch 1 bit 1419 AND logic 3: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1420 AND logic 3: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1421 AND logic 3: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1422 AND logic 3: Block Input -WC- [1.1] DPT_Switch 1 bit 1423 AND logic 4: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1424 AND logic 4: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1425 AND logic 4: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1426 AND logic 4: Block Input -WC- [1.1] DPT_Switch 1 bit 1427 AND logic 5: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 29
27 Transfer protocol
No. Text Func-
Flags DPT Typ Size
tion
1428 AND logic 5: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1429 AND logic 5: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1430 AND logic 5: Block Input -WC- [1.1] DPT_Switch 1 bit 1431 AND logic 6: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1432 AND logic 6: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1433 AND logic 6: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1434 AND logic 6: Block Input -WC- [1.1] DPT_Switch 1 bit 1435 AND logic 7: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1436 AND logic 7: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1437 AND logic 7: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1438 AND logic 7: Block Input -WC- [1.1] DPT_Switch 1 bit 1439 AND logic 8: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1440 AND logic 8: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1441 AND logic 8: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1442 AND logic 8: Block Input -WC- [1.1] DPT_Switch 1 bit 1443 OR logic 1: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1444 OR logic 1: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1445 OR logic 1: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1446 OR logic 1: Block Input -WC- [1.1] DPT_Switch 1 bit 1447 OR logic 2: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1448 OR logic 2: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1449 OR logic 2: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1450 OR logic 2: Block Input -WC- [1.1] DPT_Switch 1 bit 1451 OR logic 3: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1452 OR logic 3: 8-bit output A Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1453 OR logic 3: 8-bit output B Output R-CT [5.010] DPT_-
1 byte
Value_1_Ucount 1454 OR logic 3: Block Input -WC- [1.1] DPT_Switch 1 bit 1455 OR logic 4: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 30
28 Parameter setting
No. Text Func-
tion
1456 OR logic 4: 8-bit output A Output R-CT [5.010] DPT_-
1457 OR logic 4: 8-bit output B Output R-CT [5.010] DPT_-
1458 OR logic 4: Block Input -WC- [1.1] DPT_Switch 1 bit 1459 OR logic 5: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1460 OR logic 5: 8-bit output A Output R-CT [5.010] DPT_-
1461 OR logic 5: 8-bit output B Output R-CT [5.010] DPT_-
1462 OR logic 5: Block Input -WC- [1.1] DPT_Switch 1 bit 1463 OR logic 6: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1464 OR logic 6: 8-bit output A Output R-CT [5.010] DPT_-
1465 OR logic 6: 8-bit output B Output R-CT [5.010] DPT_-
1466 OR logic 6: Block Input -WC- [1.1] DPT_Switch 1 bit 1467 OR logic 7: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1468 OR logic 7: 8-bit output A Output R-CT [5.010] DPT_-
1469 OR logic 7: 8-bit output B Output R-CT [5.010] DPT_-
1470 OR logic 7: Block Input -WC- [1.1] DPT_Switch 1 bit 1471 OR logic 8: 1-bit switching output Output R-CT [1.2] DPT_Bool 1 bit 1472 OR logic 8: 8-bit output A Output R-CT [5.010] DPT_-
1473 OR logic 8: 8-bit output B Output R-CT [5.010] DPT_-
1474 OR logic 8: Block Input -WC- [1.1] DPT_Switch 1 bit
Flags DPT Typ Size
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount
1 byte
Value_1_Ucount

6. Parameter setting

6.1. Behaviour on power failure/ restoration of power

Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters with the delays established in the "General settings" parameter block.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 31
29 Parameter setting

6.2. General settings

Set basic characteristics for the data transfer.
Send delay after power-up and programming for: Measured values 5 s • ... • 2 h Threshold values and switching outputs 5 s • ... • 2 h Controller objects 5 s • ... • 2 h Comparator and computer objects 5 s • ... • 2 h Logic objects 5 s • ... • 2 h Maximum telegram rate • 1 message per second
• ...
• 5 messages per second
• ...
• 20 messages per second
The following temperature settings are only available for the Sewi KNX AQS/TH-D model.

6.3. Temperature Measurement

Select, whether a malfunction object is to be sent if the sensor is faulty.
Use malfunction object No • Yes
Use Offsets to adjust the readings to be sent.
Offset in 0.1°C -50…50; 0
The unit can calculate a mixed value from its own reading and an external value. Set the mixed value calculation if desired. If an external portion is used, all of the following settings (threshold values, etc.) are related to the overall reading.
Use external measured value No • Yes Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% Sending pattern for internal and total mea-
sured value
At and above change of
(if sent on change)
Send cycle
(if sent periodically)
• never
• periodically
• on change
• on change and periodically
0.1°C • 0.2°C • 0.5°C • ... • 5.0°C
5 s • 10 s • ... • 2 h
The minimum and maximum readings can be saved and sent to the bus. Use the "Reset temperature min/max. value" objects to reset the values to the current readings. The values are not retained after a reset.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 32
30 Parameter setting
Use minimum and maximum value No • Yes

6.4. Temperature threshold values

Activate the required temperature threshold values. The menus for setting the th­reshold values are displayed.
Use threshold value 1/2/3/4 Yes • No

6.4.1. Threshold value 1, 2, 3, 4

Threshold value
Set, in which cases threshold values and delay times received via object are to be retained. The parameter is only taken into consideration if the setting via object is ac­tivated below. Please note that the setting "After power supply restoration and pro­gramming" should not be used for the initial start-up, as the factory settings are always used until the first communication (setting via objects is ignored).
Maintain the threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and programming
Set the threshold value directly in the application program using parameters, or define them via the bus using a communication object.
Threshold value setting via parameter:
Set the threshold values and hysteresis directly.
Threshold value setting via Parameter • Communication objects Threshold value in 0.1°C -300 … 800; 200
Threshold value setting via a communication object:
Define, how the threshold value is to be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined, which will be valid until the first communication with a new threshold value. For units which have already been taken into service, the last communicated threshold value can be used. Basically, a temperature range is given, in which the threshold value can be changed (object value limit).
A set threshold value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 33
31 Parameter setting
Threshold value setting via Parameter • Communication objects Start threshold value in 0.1°C
valid until first communication Object value limit (min) in 0.1°C -300…800 Object value limit (max) in 0.1°C -300…800 Type of threshold value change Absolute value • Increase/decrease Increment
(upon increase/decrease change)
-300 … 800; 200
0.1°C • ... • 5°C
Set the hysteresis independent of the type of threshold value specification.
Hysteresis setting in % • absolute Hysteresis in 0.1° 0...1100; 50 Hysteresis in % of the threshold value 0 … 50; 20
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under­cut. The output switching delay can be set using objects or directly as a parameter.
When the following conditions apply, the output is (TV = Threshold value)
Delays can be set via objects (in seconds)
Switching delay from 0 to 1
(If delay can be set via objects: valid until 1st communication)
Switching delay from 1 to 0
(If delay can be set via objects: valid until 1st communication)
Switching output sends • on change
Cycle
(only if sending periodically is selected)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 No • Yes
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s • 10 s • 30 s… • 2 h
Block
The switching output can be blocked using an object.
Use switching output block No • Yes
If the block is activated, define specifications here for the behaviour of the output when blocked.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 34
32 Parameter setting
Analysis of the blocking object • At value 1: block | At value 0: release
Blocking object value before 1st communication
Behaviour of the switching output On block • Do not send message
On release (with 2 seconds release delay)
• At value 0: block | At value 1: release 0 • 1
• send 0
• send 1 [Dependent on the "Switching output
sends" setting]
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
Switching output sends on change • Do not send message
Switching output sends on change to 1 • Do not send message
Switching output sends on change to 0 • Do not send message
Switching output sends on change and periodically
Switching output sends on change to 1 and periodically
Switching output sends on change to 0 and periodically
• Send switching output status
• if switching output = 1 send 1
• if switching output = 0 send 0 Send switching output status
if switching output = 1 send 1
if switching output = 0 send 0

6.5. Temperature PI control

Activate the control if you want to use it.
Use control No • Yes
General control
Set, in which cases setpoint values and extension time received via object are to be retained. The parameter is only taken into consideration if the setting via object is activated below. Please note that the setting "After power supply restoration and pro­gramming" should not be used for the initial start-up, as the factory settings are always used until the 1st communication (setting via objects is ignored).
Maintain the Target values and extension time received
via communication objects
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• never
• after power supply restoration
• after power supply restoration and programming
Page 35
33 Parameter setting
For an adequate regulation of the ambient temperature, comfort, standby, eco and building protection modes may be used.
Comfort when present, Standby during short absences, Eco as a night-time mode and Frost/heat protection (building protection) e. g. with the window open.
The settings for the temperature control include the setpoint temperatures for the in­dividual modes. Objects are used to determine which mode is to be selected. A change of mode may be triggered manually or automatically (e.g. by a timer, window contact).
The mode may be switched with two 8 bit objects of different priority. Objects „... HVAC mode (Prio 2)“ for switching in everyday operation and „... HVAC mode (Prio 1)“ for central switching with higher priority. The objects are coded as follows: 0 = Auto 1 = Comfort 2 = Standby 3 = Eco 4 = Building Protection
Alternatively, you can use three objects, with one object switching between eco and standby mode and the two others activating comfort mode and frost/heat protection mode respectively. The comfort object blocks the eco/standby object, and the frost/ heat protection object has the highest priority. Objects „... Mode (1: Eco, 0: Standby)“, „... comfort activation mode" and „... frost/heat protection activation mode"
Switch mode via • two 8 Bit objects (HVAC Modes)
• three 1 bit objects
Select the mode to be activated after reset (e.g. power failure, reset of the line via the bus) (Default). Then configure a temperature control block via the blocking object.
Mode after reset • Comfort
Behaviour of the blocking object with value • 1 = Block | 0 = release
Value of the blocking object after reset 0 • 1
• Standby
• Eco
• Building protection
• 0 = block | 1 = release
Specify when the current control variables of the controller are to be sent to the bus. Periodic sending is safer, in case a message does not reach a recipient. You may also set up periodical monitoring by the actuator with this setting.
Send control variable • on change
from change (in % absolute) 1...10; 2
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• on change and periodically
Page 36
34 Parameter setting
Cycle (if sent periodically)
5 s • ... • 5 min • … • 2 h
The status object reports the current status of the control variables (0% = OFF, >0% = ON) and may for example be used for visualisation, or to switch off the heating pump as soon as the heating is switched off.
Send status objects • on change
Cycle (if sent periodically)
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s • ... • 5 min • … • 2 h
Then define the type of control. Heating and/or cooling may be controlled in two le­vels.
Type of control • Single level heating
• Dual-level heating
• Single-level cooling
• Dual-level cooling
• Single-level heating + single-level cooling
• Dual-level heating + single-level cooling
• Dual-level heating + dual-level cooling
General setpoint values
You may enter separate setpoint values for each mode or use the comfort setpoint as a basic value. If you are using the control for both heating and cooling, you may also select the set- ting "separately with switching object". Systems used for cooling in summer and for heating in winter can thus be switched from one to the other. If you are using the basic value, only the deviation from the comfort setpoint value is listed for the other modes (e.g, 2°C less for standby mode).
Setting the setpoint values • with separate setpoint values with
Behaviour of the switching object at value
(with switching object)
Value of the switching object after reset
(with switching object)
Switching object
• with separate setpoint values without Switching object
• with comfort setpoint as a basis with Switching object
• with comfort setpoint as a basis without Switching object
• 0 = Heating | 1 = Cooling
• 1 = Heating | 0 = Cooling 0 • 1
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 37
35 Parameter setting
The increment for the setpoint changes is predefined. Whether the change only re­mains temporarily active (not saved) or is also retained after power supply restoration (and programming), is specified in the first section of "General control". This also ap­plies to a comfort extension.
Increment for setpoint changes (in 0.1 °C)
1… 50; 10
The control may be reset to comfort mode from eco mode, which is used as night mo­de, via the comfort extension. This allows the user to maintain the comfort setpoint value for a longer time, e.g. when having guests. The duration of this comfort extensi­on period is set. After the comfort extension period expires, the system returns to eco mode.
Comfort extension time in seconds (can only be activated from eco mode)
1…36000; 3600
Comfort Setpoint
Comfort mode is usually used for daytime mode when people are present. A starting value is defined for the comfort setpoint as well as a temperature range in which the setpoint value may be modified.
Starting heating/cooling setpoint (in 0.1 °C) valid until 1st communication
(not upon saving the setpoint value after programming)
If setpoint values are entered separately:
Min. object value heating/cooling (in 0.1 °C)
Max. object value heating/cooling (in 0.1 °C)
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is set.
Minimum base setpoint (in 0.1°C) -300…800; 160 Maximum base setpoint (in 0.1°C) -300…800; 280 Reduction by up to (in 0.1°C) 0…200; 50 Increase by up to (in 0.1°C) 0…200; 50
-300…800; 210
-300…800; 160
-300…800; 280
If the comfort setpoint is used as the basis without a switching object, a dead zone is specified for the control mode "heating and cooling" to avoid direct switching from he­ating to cooling.
Dead zone between heating and cooling
(only if both heating AND cooling are used)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
1…100; 50
Page 38
36 Parameter setting
Standby setpoint
Standby mode is usually used for daytime mode when people are absent.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint value may be changed.
Starting heating/cooling setpoint (in 0.1 °C) valid until 1st communication
Min. object value heating/cooling (in 0.1 °C)
Max. object value heating/cooling (in 0.1 °C)
-300…800; 210
-300…800; 160
-300…800; 280
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is set.
Reduce heating setpoint (in 0.1°C)
(for heating)
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 30
0…200; 30
Eco setpoint
Eco mode is usually used for night mode.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint value may be changed.
Starting heating/cooling setpoint (in 0.1 °C) valid until 1st communication
Min. object value heating/cooling (in 0.1 °C)
Max. object value heating/cooling (in 0.1 °C)
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is set.
Reduce heating setpoint (in 0.1°C)
(for heating)
Increase cooling setpoint (in 0.1°C)
(for cooling)
-300…800; 210
-300…800; 160
-300…800; 280
0…200; 50
0…200; 60
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 39
37 Parameter setting
Setpoint values for frost/heat protection (building protection)
The building protection mode is for example used as long as windows are opened for ventilation. Setpoints for frost protection (heating) and heat protection (cooling) are determined which may not be modified from outside (no access via operating devices etc.). The building protection mode may be activated with delay, which allows you to leave the building before the controls switch to frost/heat protection mode.
Setpoint frost protection (in 0.1°C) -300…800; 70 Activation delay less than • 5 s • ... • 5 min • … • 2 h Setpoint heat protection (in 0.1°C) -300…800; 350 Activation delay less than • 5 s • ... • 5 min • … • 2 h
General control variables
This setting appears for the control types "Heating and Cooling" only. Here, you can decide whether to use a common control variable for heating and cooling. If the 2nd level has a common control variable, you also determine the control mode of the 2nd level here.
For heating and cooling • separate control variables are used
Use control variable for 4/6-way valve
(only for common control variables in level 1)
Control type
(for level 2 only)
Control variable of the 2nd Level is on
(only for level 2 with 2 point controlling)
• common control variables are used for Level 1
• common control variables are used for Level 2
• common control variable are used for Level 1+2
No • Yes
• 2-point-control
• PI control
• 1 bit object
• 8 bit object
When using the control variable for a 4/6 way valve, the following applies: 0%...100% heating = 66%...100% control variable OFF = 50% control variable 0%...100% cooling = 33%...0% control variable

6.5.1. Heating control level 1/2

If a heating control mode is configured, one or two setting sections for the heating le­vels are displayed.
In the 1st level, heating is controlled by a PI control, which allows to either enter control parameters or select predetermined applications.
In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI or a 2-point-control.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 40
38 Parameter setting
In level 2, the setpoint difference between the two levels must also be specified, i.e. be­low which setpoint deviation the second level is added.
Setpoint difference between 1st and 2nd level (in 0.1°C)
(for level 2)
Control type
(for level 2, no common control variables)
Control variable is a
(for level 2 with 2-point controlling, no common control variables)
0...100; 40
• 2-point-control
• PI control
• 1 bit object
• 8 bit object
PI control with control parameters:
This setting allows individual input of the parameters for PI control.
Control type PI control Setting of the controller by Controller parameter
• specified applications
Specify the deviation from the setpoint value at which the maximum control variable value is reached, i.e. the point at which maximum heating power is activated. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate to the heating system at this point (observe ma­nufacturer's instructions).
Maximum control variable is reached at setpoint/actual difference of (in °C)
Reset time (in min.) 1...255; 30
0...5
Now specify what should be sent when the control is blocked. Set a value greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating. On release, the control variable follows the rule again.
When blocked, the control variable shall • not be sent
Value (in %) (if a value is sent)
• send a specific value
0...100
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.
PI control with predetermined application:
This setting provides fixed parameters for frequent applications.
Control type PI control Setting of the controller by • Controller parameter
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
specified applications
Page 41
39 Parameter setting
Application • Warm water heating
Maximum control variable is reached at setpoint/actual difference of (in °C)
Reset time (in min.) Warm water heating: 150
• Floor heating
• Convection unit
• Electric heating Warm water heating: 5
Floor heating: 5 Convection unit: 4 Electric heating: 4
Floor heating: 240 Convection unit: 90 Electric heating: 100
Now specify what should be sent when the control is blocked. Set a value greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating. On release, the control variable follows the rule again.
When blocked, the control variable shall • not be sent
Value (in %) (if a value is sent)
• send a specific value
0...100
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.
2-point-control (only level 2):
2-point-control is used for systems which are only set to ON or OFF.
Control type
(is determined at a higher level for com­mon control variables)
2-point-control
Enter the hysteresis that prevents frequent on/off switching of temperatures in the th­reshold range.
Hysteresis (in 0.1°C) 0...100; 20
If separate control variables are used, select whether the control variable of the 2nd le­vel is a 1 bit object (on/off) or an 8 bit object (on with percentage/off).
Control variable is a • 1 bit object
Value (in %) (for 8 bit object)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• 8 bit object
0...100
Page 42
40 Parameter setting
Now specify what should be sent when the control is blocked. Set a value greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating. On release, the control va­riable follows the rule again.
When blocked, the control variable shall • not be sent
Value (in %) only if a value is sent
• send a specific value
0...100

6.5.2. Cooling control level 1/2

If a cooling control mode is configured, one or two setting sections for the cooling le­vels are displayed.
In the 1st level, cooling is controlled by a PI control in which either control parameters can be entered or predetermined applications can be selected.
In the 2nd level (therefore only for 2-level cooling), cooling is controlled via a PI or a 2­point-control. In level 2, the setpoint deviation between the two levels must also be specified, i.e. abo­ve which setpoint value deviation the second level is added.
Setpoint difference between 1st and 2nd level (in 0.1°C)
(for level 2)
Control type
(for level 2, no common control variables)
Control variable is a
(for level 2 with 2-point controlling, no common control variables)
0...100; 40
• 2-point-control
• PI control
• 1 bit object
• 8 bit object
PI control with control parameters:
This setting allows individual input of the parameters for PI control.
Control type PI control Setting of the controller by Controller parameter
• specified applications
Specify the deviation from the setpoint value which reaches maximum variable value, i.e. the point at which maximum cooling power is activated. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate to the cooling system at this point (observe manufacturer's instructions).
Maximum control variable is reached at setpoint/actual difference of (in °C)
Reset time (in min.) 1...255; 30
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
0...5
Page 43
41 Parameter setting
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
When blocked, the control variable shall • not be sent
Value (in %) (if a value is sent)
• send a specific value
0...100
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.
PI control with predetermined application:
This setting provides fixed parameters for a cooling ceiling
Control type PI control Setting of the controller by • Controller parameter
Application • Cooling ceiling Maximum control variable is reached
at setpoint/actual difference of (in °C) Reset time (in min.) Cooling ceiling: 30
specified applications
Cooling ceiling: 5
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
When blocked, the control variable shall • not be sent
Value (in %) (if a value is sent)
• send a specific value
0...100
2-point-control (only level 2):
2-point-control is used for systems which are only set to ON or OFF.
Control type
is determined at a higher level for common variables
2-point-control
Enter the hysteresis that prevents frequent on/off switching of temperatures in the th­reshold range.
Hysteresis (in 0.1°C) 0...100; 20
If separate control variables are used, select whether the control variable of the 2nd le­vel is a 1 bit object (on/off) or an 8 bit object (on with percentage/off).
Control variable is a • 1 bit object
Value (in %) (for 8 bit object)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• 8 bit object
0...100
Page 44
42 Parameter setting
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
When blocked, the control variable shall • not be sent
Value (in %) (if a value is sent)
• send a specific value
0...100
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.

6.6. Summer Compensation

With the summer compensation the target value for the room temperature can auto­matically be adapted by cooling at higher outdoor temperatures. The objective is to prevent a too great a difference between indoor and outdoor temperature in order to keep the energy consumption low.
Activate the summer compensation.
Use summer compensation No • Yes
Using the points 1 and 2, define the outdoor temperature range in which the target value for the indoor temperature is to be adapted linearly. Then, specify which indoor temperature target values are to be valid below point1 and above point 2.
Standard values according to DIN EN 60529
Point 1: External temperature = 20°, Target value = 20°C. Point 2: External temperature = 32°, Target value = 26°C.
Characteristic curve description: External temperature point 1 (in 0.1°C
increments) Outdoor temperature point 2 (in 0.1°C
increments) below point 1
the target value is (in 0.1°C) above point 2
the target value is (in 0.1°C)
0 ... 500 ; 200
0 ... 500 ; 320
0 ... 500 ; 200
0 ... 500 ; 260
Set the send pattern for the summer compensation.
Send pattern • periodically
on change of
(if sent on change)
Send cycle
(if sent periodically)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• on change
• on change and periodically
0.1°C • 0.2°C • 0.5°C • 1°C • 2°C • 5°C
5 s ... 2 h; 1 min
Page 45
43 Parameter setting
If necessary, activate the block for the summer compensation and set what a 1 or 0 at the block input means and what happens in the event of a block.
Use block No • Yes Analysis of the blocking object • At value 1: block | At value 0: release
Blocking object value before first call 0 • 1 Action when locking • do not send
Value (in increments of 0.1°C)
(if a value is sent during blocking)
• At value 0: block | At value 1: release
• Send value 0 ... 500; 200
The following humidity settings are only available for the Sewi KNX AQS/TH-D model.

6.7. Humidity Measurement

Select, whether a malfunction object is to be sent if the sensor is faulty.
Use malfunction object No • Yes
Use Offsets to adjust the readings to be sent.
Offset in 0.1% RH -50…50; 0
The unit can calculate a mixed value from its own reading and an external value. Set the mixed value calculation if desired. If an external portion is used, all of the following settings (threshold values, etc.) are related to the overall reading.
Use external measured value No • Yes Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% Sending pattern for internal and total mea-
sured value
At and above change of
(if sent on change)
Send cycle
(if sent periodically)
• never
• periodically
• on change
• on change and periodically
0.1% RH • 0.2% RH • 0.5% RH • 1.0% RH • ...
• 20.0% RH 5 s • 10 s • ... • 2 h
The minimum and maximum readings can be saved and sent to the bus. Use the "Reset humidity min/max. value" objects to reset the values to the current readings. The values are not retained after a reset.
Use minimum and maximum value No • Yes
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 46
44 Parameter setting

6.8. Humidity threshold values

Activate the required air humidity threshold values. The menus for setting the th­reshold values are displayed.
Use threshold value 1/2/3/4 Yes • No

6.8.1. Threshold value 1, 2, 3, 4

Threshold value
Set, in which cases threshold values and delay times received via objects are to be retained. The parameter is only taken into consideration if the setting via object is ac­tivated below. Please note that the setting "After power supply restoration and pro­gramming" should not be used for the initial start-up, as the factory settings are always used until the first communication (setting via objects is ignored).
Maintain the threshold values and delays received via
communication objects
Set the threshold value directly in the application program using parameters, or define them via the bus using a communication object.
• never
• after power supply restoration
• after power supply restoration and programming
Threshold value setting using parameter:
Set the threshold values and hysteresis directly.
Threshold value setting using Parameter • Communication objects Threshold value in 0.1% RH 1 … 1000; 650
Threshold value setting using a communication object:
Define, how the threshold value is to be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined, which will be valid until the first communication with a new threshold value. For units which have already been taken into service, the last communicated threshold value can be used. Basically, a humidity range is specified in which the threshold value can be changed (object value limit).
A set threshold value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 47
45 Parameter setting
Threshold value setting using Parameter • Communication objects Starting threshold value in 0.1% RH
valid until first communication Object value limit (min.) in 0.1%RH 1…1000 Object value limit (max.) in 0.1%RH 1…1000 Type of threshold value change Absolute value • Increase/decrease Increment
(upon increase/decrease change)
1 … 1000; 650
0.1% RH • ... • 2.0% RH • ... • 20.0% RH
Set the hysteresis independent of the type of threshold value specification.
Hysteresis setting in % • absolute Hysteresis in 0.1% RH 0...1000; 100 Hysteresis in %
(relative to the threshold value)
0 … 50; 20
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under­cut. The output switching delay can be set using objects or directly as a parameter.
When the following conditions apply, the output is (TV = Threshold value)
Delays can be set via objects (in seconds)
Switching delay from 0 to 1
(If delay can be set via objects: valid until 1st communication)
Switching delay from 1 to 0
(If delay can be set via objects: valid until 1st communication)
Switching output sends • on change
Cycle
(is only sent if periodically is selected)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 No • Yes
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s • 10 s • 30 s… • 2 h
Block
The switching output can be blocked using an object.
Use switching output block No • Yes
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 48
46 Parameter setting
If the block is activated, define specifications here for the behaviour of the output when blocked.
Analysis of the blocking object • At value 1: block | At value 0: release
Blocking object value before first communi­cation
Behaviour of the switching output On block • Do not send message
On release (with 2 seconds release delay)
• At value 0: block | At value 1: release 0 • 1
• send 0
• send 1 [Dependent on the "Switching output
sends" setting]
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
Switching output sends on change • Do not send message
Switching output sends on change to 1 • Do not send message
Switching output sends on change to 0 • Do not send message
Switching output sends on change and periodically
Switching output sends on change to 1 and periodically
Switching output sends on change to 0 and periodically
• Send switching output status
• if switching output = 1 send 1
• if switching output = 0 send 0 Send switching output status
if switching output = 1 send 1
if switching output = 0 send 0

6.9. Humidity PI control

If you activate humidity control, you can use the following settings to define control ty­pe, setpoint values, and humidification and dehumidification.
Use humidity control No • Yes
General control
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D can be used to control one- or
two-level dehumidification or combined humidification/dehumidification.
Type of control • One-level dehumidification
Configure a block for the humidity control using the blocking object.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• Two-level dehumidification
• Humidification and dehumidification
Page 49
47 Parameter setting
Behaviour of the blocking object with value • 1 = Block | 0 = release
Blocking object value before first communication
• 0 = block | 1 = release 0 • 1
Specify when the current control variables are to be sent to the bus. Periodic sending is safer, in case a message does not reach a recipient. You may also set up periodic monitoring using an actuator with this setting.
Send control variable • on change
Send cycle (is only sent if "periodically" is selected)
• on change and periodically 5 s • ... • 5 min • … • 2 h
The status object shows the current status of the output variable (0 = OFF, >0 = ON) and can for example be used for visualisation.
Send status object(s) • on change
Send cycle (is only sent if "periodically" is selected)
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s • ... • 5 min • … • 2 h
Controller setpoint
Set, in which cases setpoint values received via object are to be retained. Please note that the setting "After power supply restoration and programming" should not be used for the initial start-up, as the factory settings are always used until the first communi­cation (setting via objects is ignored).
Maintain the setpoint value received via communication
object
• never
• after power supply restoration
• after power supply restoration and programming
During initial commissioning, a setpoint value must be defined which is valid until the first communication of a new setpoint value. For units which have already been ta­ken into service, the last communicated setpoint value can be used. Basically, an air humidity range is specified in which the setpoint value can be changed (object value limit).
Enter, how the setpoint value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 50
48 Parameter setting
A set setpoint value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Start setpoint in % valid until first communication
(not upon saving the setpoint value after programming)
Object value limit (min.) in % 0…100; 30 Object value limit (max.) in % 0…100; 70 Type of setpoint value change Absolute value • Increase/decrease Increment
(upon increase/decrease change)
0 … 100; 50
1% • 2% • 3% • 5% • 10%
In "Humidification and dehumidification" control mode, a dead zone is specified so that a direct changeover switching between humidification and dehumidification can be avoided.
Dead zone between humidification and dehumidification in %
(only if both humidification and dehumidifi­cation are used)
0…50; 10
Humidification starts, when the relative air humidity is lower or equal to the setpoint value - dead zone value.
Dehumidification and/or humidification
Depending on the control mode, settings sections for humidification and dehumidifi­cation appear (level 1/2).
For dual-level dehumidification, the setpoint value difference between the two levels must be defined, i.e. the setpoint value which, when exceeded, triggers the switch to the 2nd level.
Target value difference between level 1 and 2 in %
(for level 2 only)
0...50; 10
Determine the deviation from the setpoint value at which the maximum variable value is reached, i.e. the point at which maximum output is used. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 51
49 Parameter setting
urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate for the humidification/dehumidification system at this point (note manufacturer instructions).
Maximum control variable is reached at target/actual difference of %
Reset time in minutes 1...255; 3
1...50; 5
Now specify, what should be sent when the control is blocked. On release, the control variable follows the rule again.
When blocked, the control variable shall • not be sent
Value in % (if a value is sent)
• send a specific value
0...100

6.10. Dewpoint measurement

The Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D calculates the dewpoint temperature and can output the value to the bus.
Sending pattern • never
At and above change of
(if sent on change)
Send cycle
(if sent periodically)
• periodically
• on change
• on change and periodically
0.1°C • 0.2°C • 0.5°C • 1.0°C • 2.0°C • 5.0°C
5 s • 10 s • 30 s • 1 min • … • 2 h
Activate the monitoring of the coolant temperature if required. The menus for setting the monitoring are displayed.
Use monitoring of the coolant temperature No • Yes

6.10.1. Cooling medium temp. monitoring

A threshold value can be set for the temperature of the coolant, which is based on the current dewpoint temperature (offset/deviation). The switching output of the coolant temperature monitoring system can provide a warning prior to any build-up of conden­sation in the system, and/or activate appropriate countermeasures.
Threshold value
Threshold value = dewpoint temperature + offset
Set, in which cases offset received via object is to be retained. Please note that the set­ting "After power supply restoration and programming" should not be used for the in-
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 52
50 Parameter setting
itial start-up, as the factory settings are always used until the first communication (set­ting via objects is ignored).
Maintain the offset received via communication object • never
.
• after power supply restoration
• after power supply restoration and programming
During initial commissioning, an offset must be defined which is valid until the first communication of a new offset. For units which have already been taken into service, the last communicated offset can be used.
A set offset will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Start offset in °C valid until first communication
Increment for offset change 0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C •
Hysteresis setting in % • absolute Hysteresis of the threshold value in %
(for setting in %)
Threshold value hysteresis in 0.1°C increments
(at absolute setting)
Threshold value sends • never
At and above change of
(if sent on change)
Send cycle
(if sent periodically)
0...200; 30
2°C • 3°C • 4°C • 5°C
0 ... 50; 20
0 ... 1000; 50
• periodically
• on change
• on change and periodically
0.1°C • 0.2°C • 0.5°C • 1.0°C • 2.0°C • 5.0°C
5 s • 10 s • 30 s • 1 min • … • 2 h
Switching output
The output switching delay can be set using objects or directly as a parameter.
When the following conditions apply, the output is (TV = Threshold value)
Delays can be set via objects (in seconds)
Switching delay from 0 to 1
for setting via objects: valid until 1st communication
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 No • Yes
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Page 53
51 Parameter setting
Switching delay from 1 to 0
for setting via objects: valid until 1st communication
Switching output sends • on change
Send cycle
(is only sent if periodically is selected)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s • 10 s • 30 s… • 2 h
Blocking
The switching output can be blocked using an object. Define specifications here for the behaviour of the output when blocked.
Use switching output block No • Yes Analysis of the blocking object • At value 1: block | At value 0: release
Blocking object value before first communi­cation
Behaviour of the switching output On block • Do not send message
On release (with 2 seconds release delay)
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
Switching output sends on change • Do not send message
Switching output sends on change to 1 • Do not send message
Switching output sends on change to 0 • Do not send message
Switching output sends on change and periodically
Switching output sends on change to 1 and periodically
Switching output sends on change to 0 and periodically
• At value 0: block | At value 1: release 0 • 1
• send 0
• send 1 [Dependent on the "Switching output
sends" setting]
• Send switching output status
• if switching output = 1 send 1
• if switching output = 0 send 0 Send switching output status
if switching output = 1 send 1
if switching output = 0 send 0

6.11. Absolute humidity

The absolute air humidity value is detected by the Sewi KNX AQS and Sewi KNX AQS/TH-D and can be output to the bus.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 54
52 Parameter setting
Use absolute humidity No • Yes
Sending pattern • never
At and above change of
(if sent on change)
Send cycle
(if sent periodically)
• periodically
• on change
• on change and periodically
0.1 g • 0.2 g • 0.5 g • 1.0 g • 2.0 g • 5.0 g
5 s • 10 s • 30 s… • 2 h

6.12. Comfort field

The Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D can send a message to the bus if the limits of the comfort field are exceeded. In this way, it is for example possible to monitor compliance with DIN 1946 (standard values) or even to define your own comfort field.
Use comfort field No • Yes
Specify the sending pattern, a Text for comfortable and uncomfortable and the Ob- ject value.
Sending pattern • never
Text for comfortable [Free text max. 14 chars.] Text for uncomfortable [Free text max. 14 chars.] Object value is at • comfortable = 1 | uncomfortable = 0
Send cycle
(if sent periodically)
• periodically
• on change
• on change and periodically
• comfortable = 0 | uncomfortable = 1 5 s • 10 s • 30 s… • 2 h
Define the comfort field by specifying the minimum and maximum values for tempe­rature and humidity. The specified standard values comply with DIN 1946
Maximum temperature in °C (Standard 26°C)
Minimum temperature in °C (Standard 20°C)
Maximum relative humidity in % (Standard 65%)
Minimum relative humidity in % (Standard 30%)
Maximum absolute humidity in 0.1 g/kg (Standard 115 g/kg)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
25 ... 40; 26
10 ... 21; 20
52 ... 90; 65
10 ... 43; 30
50 ... 200; 115
Page 55
53 Parameter setting
Temperature hysteresis: 1°C Relative humidity hysteresis: 2% RH Absolute humidity hysteresis: 2 g/kg
The following air pressure settings are only available for the Sewi KNX AQS/TH-D model.

6.13. Air Pressure Measurement

If necessary, activate the air pressure malfunction object. Specify at which height abo­ve sea level the device is installed and whether the reading is to be additionally output as barometric pressure (see below information on air pressure).
Use malfunction object No • Yes Height above sea level -1000...10000; 200 Additionally output measured value
as barometric pressure
Define the transmission pattern and, if necessary, activate the minimum and ma- ximum value (these values are not retained after a reset).
Sending pattern for measured value • never
at and above change of
(if sent on change)
Send cycle
(if sent periodically)
Use minimum and maximum value No • Yes
No • Yes
• periodically
• on change
• on change and periodically 10 Pa • 20 Pa • 50 Pa • 100 Pa • 200 Pa •
500 Pa 5 s ... 2 h; 1 min
Dependent on the air pressure measured, a Text object can be sent. Specify the sen­ding pattern and enter the text.
Sending pattern for text object • never
Text for normal pressure range < 98,000 Pa
(e.g. weather is stormy) 98,000...100,000 Pa
(e.g. weather is rainy) 100,000...102,000 Pa
(e.g. weather is changeable)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• periodically
• on change
• on change and periodically
stormy
rainy
changeable
Page 56
54 Parameter setting
102,000...104,000 Pa (e.g. weather is sunny)
< 104,000 Pa (e.g. weather is very dry)
Send cycle
(if sent periodically)
sunny
very dry
5 s ... 2 h; 1 min
Information on air pressure
The unit for air pressure is Pascal (Pa). 1 Pa = 0.01 hPa = 0.01 mbar
The air pressure is specified as "normal air pressure" or as "barometric pressure". The normal air pressure is the pressure compensated for height and temperature. The barometric air pressure is the pressure measured directly by the sensor (without com­pensation).
Air pressure (in Pa)
up to 98,000 Pa very low stormy
98,000 ... 100,000 Pa low rainy
100,000 ... 102,000 Pa normal changeable
102,000 ... 104,000 Pa high sunny
104,000 Pa: very high very dry
Meaning Weather tendency

6.14. Air pressure threshold values

Activate the required air pressure threshold value. The menus for setting the threshold values are displayed.
Threshold value 1/2/3/4 No • Yes

6.14.1. Air pressure threshold value 1-4

Threshold value
Set, in which cases threshold values and delay times received are to be kept per object. The parameter is only taken into consideration if the specification/ setting by object is activated further down. Please note that the setting "After power restoration and pro-
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 57
55 Parameter setting
gramming" should not be used for the initial start-up, as the factory settings are always used until the first call (setting via objects is ignored). Select the type of measured value for the calculation of the threshold value (see Infor- mation on air pressure)
Maintain the threshold values and delays received via
communication object
• never
• after power supply restoration
• after power supply restoration and programming
Type of measurement for threshold value calculation
• Normal air pressure
• Barometric pressure
Select whether the threshold value is to be specified per parameter or via a communi­cation object.
Threshold value setpoint using Parameter • Communications object
When the threshold value per parameter is specified, then the value is set.
Threshold value in 10 Pa 3000 … 11000; 10200
When the threshold value per communication object is specified, the starting value, object value limit and type of change to the threshold value are then set.
Start threshold value in 10 Pa valid until first call
Object value limit (min.) in 10 Pa 3000 … 11000 Object value limit (max.) in 10 Pa 3000 … 11000 Type of threshold change Absolute value • Increase/decrease Step size
(upon increase/decrease change)
3000 … 11000; 10200
10 Pa • 20 Pa • 50 Pa • 100 Pa • 200 Pa • 500 Pa
With both of the methods for specifying the threshold values the hysteresis is set.
Hysteresis setting in % • absolute Hysteresis in % (relative to threshold value)
(for setting in %)
Hysteresis in 10 Pa
(for absolute setting)
0 … 50; 20
0 … 11000; 100
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut. Set the delay for the switching and in which cases the switch output transmits.
When the following conditions apply, the output is (LV = Threshold value)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
Page 58
56 Parameter setting
Delays can be set via objects (in seconds)
Delay from 0 to 1 none • 1 s … 2 h Delay from 1 to 0 none • 1 s … 2 h Switching output sends • on change
Cycle
(if sent periodically)
No • Yes
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s ... 2 h
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry means and what happens in the event of a block.
Use switching output block No • Yes Analysis of the blocking object • At value 1: block | At value 0: release
Blocking object value before first call 0 • 1 Action when locking • Do not send message
Action upon release (with 2 seconds release delay)
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
Switching output sends on change do not send message •
Switching output sends on change to 1 do not send message •
Switching output sends on change to 0 do not send message •
Switching output sends on change and periodically
Switching output sends on change to 1 and periodically
Switching output sends on change to 0 and periodically
• At value 0: block | At value 1: release
• send 0
• send 1 [Dependent on the "Switching output
sends" setting]
Status object/s send/s
If switching output = 1 send 1
If switching output = 0 send 0 Send switching output status
If switching output = 1 send 1
If switching output = 0 send 0
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 59
57 Parameter setting

6.15. CO2 Measurement

Select, whether a malfunction object is to be sent if the sensor is faulty.
Use malfunction object No • Yes
Use Offsets to adjust the readings to be sent.
Offset in ppm -100…100; 0
The unit can calculate a mixed value from its own reading and an external value. Set the mixed value calculation if desired. If an external portion is used, all of the following settings (threshold values, etc.) are related to the overall reading.
Use external measured value No • Yes Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% Sending pattern for internal and total mea-
sured value
At and above change of (relative to the last measured value)
(if sent on change)
Send cycle
(if sent periodically)
The maximum reading can be saved and sent to the bus. Using the "Reset CO2 ma­ximum value" objects, the value can be reset to the current reading. The value is not retained after a reset.
Use maximum value No • Yes
• never
• periodically
• on change
• on change and periodically 2% • 5% • ... • 50%
5 s • 10 s • ... • 2 h

6.16. CO2 threshold values

Activate the required CO2 threshold value. The menus for setting the threshold values are displayed.
Use threshold value 1/2/3/4 Yes • No
300 ppm ... 1000 ppm: fresh air 1000 ppm ... 2000 ppm: used air
1000 ppm = 0.1 %

6.16.1. Threshold value 1, 2, 3, 4

Threshold value
Set, in which cases threshold values and delay times received via object are to be retained. The parameter is only taken into consideration if the setting via object is ac­tivated below. Please note that the setting "After power supply restoration and pro-
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 60
58 Parameter setting
gramming" should not be used for the initial start-up, as the factory settings are always used until the first communication (setting via objects is ignored).
Maintain the threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and programming
Set the threshold value directly in the application program using parameters, or define them via the bus using a communication object.
Threshold value setting using parameters:
Set the threshold values and hysteresis directly.
Threshold value setting using Parameter • Communication objects Threshold value in ppm 0 … 2000; 1200
Threshold value setting using a communication object:
Define, how the threshold value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined, which will be valid until the first communication of a new threshold value. For units which have already been taken into service, the last communicated threshold value can be used. Basically, a range is specified in which the threshold value can be changed (object value limit).
A set threshold value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Threshold value setting using Parameter • Communication objects Start threshold value in 0.1°C
valid until first communication Limitation of object value (min) in ppm 10…2000 Limitation of object value (max) in ppm 1…2000; 1000 Type of threshold value change Absolute value • Increase/decrease Increment in ppm
(upon increase/decrease change)
-300 … 800; 200
1 • 2 • 5 • 10 • 20 • ... • 200
Set the hysteresis independent of the type of threshold value specification.
Hysteresis setting in % • absolute Hysteresis in ppm 0...2000; 500 Hysteresis in % of the threshold value 0 … 50; 20
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 61
59 Parameter setting
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under­cut. The output switching delay can be set using objects or directly as a parameter.
When the following conditions apply, the output is (TV = Threshold value)
Delays can be set via objects (in seconds)
Switching delay from 0 to 1
(If delay can be set via objects: valid until first communication)
Switching delay from 1 to 0
(If delay can be set via objects: valid until first communication)
Switching output sends • on change
Cycle
(is only sent if periodically is selected)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 No • Yes
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s • 10 s • 30 s… • 2 h
Block
The switching output can be blocked using an object.
Use switching output block No • Yes
If the block is activated, define specifications here for the behaviour of the output when blocked.
Analysis of the blocking object • At value 1: block | At value 0: release
Blocking object value before first communi­cation
Behaviour of the switching output On block • Do not send message
On release (with 2 seconds release delay)
• At value 0: block | At value 1: release 0 • 1
• send 0
• send 1 [Dependent on the "Switching output
sends" setting]
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
Switching output sends on change • Do not send message
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• Send switching output status
Page 62
60 Parameter setting
Switching output sends on change to 1 • Do not send message
Switching output sends on change to 0 • Do not send message
Switching output sends on change and periodically
Switching output sends on change to 1 and periodically
Switching output sends on change to 0 and periodically
• if switching output = 1 send 1
• if switching output = 0 send 0 Send switching output status
if switching output = 1 send 1
if switching output = 0 send 0

6.17. CO2 PI-control

If you activate air quality control, you can use the following settings to define control type, setpoint values, and ventilation.
Use control Yes • No
General control
The Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D can be used to control one or two-stage ventilation.
Type of control • One-stage ventilation
Configure a block for the ventilation control using the blocking object.
Behaviour of the blocking object with value • 1 = Block | 0 = release
Blocking object value before first communication
• Two-stage ventilation
• 0 = block | 1 = release 0 • 1
Specify when the current control variables are to be sent to the bus. Periodic sending is safer, in case a message does not reach a recipient. You may also set up periodic monitoring using an actuator with this setting.
Send control variable • on change
at and above change of (in ppm) 1...20; 2 Cycle
(if sent periodically)
• on change and periodically
5 s • ... • 5 min • … • 2 h
The status object shows the current status of the output variable (0 = OFF, >0 = ON) and can for example be used for visualisation.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 63
61 Parameter setting
Send status object(s) • on change
Cycle (if sent periodically)
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically 5 s • 10 s • … • 2 h
Controller setpoint
The setpoint values can be set directly in the application program using parameters, or be defined via the bus using a communication object.
Setpoint value setting using parameters:
Set the setpoint value directly.
Specified setpoint using Parameter • Communication objects Target value in ppm 400…5000; 800
Setpoint value setting via communication object:
Enter, how the setpoint value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
During initial commissioning, a setpoint value must be defined which is valid until the first communication of a new setpoint value. For units which have already been taken into service, the last communicated setpoint value can be used. Basically, an air humi­dity range is given in which the setpoint value can be changed (object value limit).
A set setpoint value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Threshold value setting using Parameter • Communication objects The last communicated value should be
retained
Start setpoint value in ppm valid until first communication
(not upon saving the setpoint value after programming)
Object value limit (min) in 0.1°C 400…2000; 400 Object value limit (max) in 0.1°C 400…2000; 1500 Type of threshold value change Absolute value • Increase/decrease Increment in ppm
(upon increase/decrease change)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• never
• after power supply restoration
• after power supply restoration and programming
400… 2000; 800
1 • 2 • 5 • ... • 20 • ... • 100 • 200
Page 64
62 Parameter setting
Ventilation control
Depending on the control mode, one and/or two setting sections for the ventilation sta­ges are displayed.
For two-stage ventilation, the setpoint value difference between the two stages must be defined, i.e. the setpoint value which, when exceeded, triggers the switch to the 2nd level.
Target value difference between 1st and 2nd level in ppm
(for level 2 only)
Determine the deviation from the setpoint value at which the maximum variable value is reached, i.e. the point at which maximum output is used. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate to the ventilation system at this point (follow the manufacturer's instructions).
Maximum control variable is reached at setpoint value/actual difference of (in ppm)
Reset time in minutes 1...255; 30
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
When blocked, the control variable shall • not send anything
Value in % (if a value is sent)
100...2000; 400
100...2000
• send a value
0...100

6.18. Variable comparator

The integrated variable comparators can output maximum, minimum and average values.
Use comparator 1/2/3/4 No • Yes

6.18.1. Control variable comparator 1/2/3/4

Determine what the control variable comparator should output, and activate the input objects to be used. Transmission patterns and blocks can also be set.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 65
63 Parameter setting
Output delivers • Maximum value
Use input 1 / 2 / 3 / 4 / 5 No • Yes Output sends • on change of output
Send cycle
(if sent periodically)
At and above change of
(if sent on change)
Analysis of the blocking object • at value 1: block | at value 0: release
Blocking object value before 1st communication
Behaviour of the switching output On block • do not send message
Sent value in % 0 ... 100 output sends on release
(with 2 seconds release delay)
• Minimum value
• Average value
• on change of output and periodically
• when receiving an input object
• when receiving an input object and periodically
5 s • 10 s • 30 s • ... • 5 min • … • 2 h
1% • 2% • 5% • 10% • 20% • 25% • 50%
• at value 0: block | at value 1: release 0 • 1
• Send value
• the current value
• the current value after receipt of an object

6.19. Computer

Activate the multi-functional computer, with which the input data can be changed by calculation, querying a condition or converting the data point type. The menus for the further setting of the computer are then displayed.
Computer 1/2/3/4/5/6/7/8 No • Yes

6.19.1. Computer 1-8

Set, in which cases input values received are to be kept per object. Please note that the setting "After power restoration and programming" should not be used for the initial start-up, as the factory settings are always used until the first call (setting via objects is ignored).
Maintain the input values received via communication
objects
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• never
• after power supply restoration
• after power supply restoration and programming
Page 66
64 Parameter setting
Select the function set the input mode and starting values for input 1 and input 2.
Function (I = Input) • Prerequisite: E1 = E2
• Prerequisite: E1 > E2
• Prerequisite: E1 >= E2
• Prerequisite: E1 < E2
• Prerequisite: E1 <= E2
• Prerequisite: E1 - E2 >= E3
• Prerequisite: E2 - E1 >= E3
• Prerequisite: E1 - E2 amount >= E3
• Calculation: E1 + E2
• Calculation: E1 - E2
• Calculation: E2 - E1
• Calculation: E1 - E2 Amount
• Calculation: Output 1 = E1 × X + Y | Output 2 = E2 × X + Y |
• Transformation: General
Tolerance for comparison
0 ... 4,294,967,295
(in the case of prerequisite E1 = E2)
Input type [Selection options depending on the func-
tion]
• 1 bit
• 1 byte (0...255)
• 1 byte (0%...100%)
• 1 byte (0°...360°)
• 2 byte counter without math. symbol
• 2 byte counter with math. symbol
• 2 byte floating point
• 4 byte counter without math. symbol
• 4 byte counter with math. symbol
• 4 byte floating point
Starting value E1 / E2 / E3 [Input range depending on the type of
input]
Prerequisites
When querying the prerequisites set the output type and output values at different sta­tuses:
Output type • 1 bit
• 1 byte (0...255)
• 1 byte (0%...100%)
• 1 byte (0°...360°)
• 2 byte counter without math. symbol
• 2 byte counter with math. symbol
• 2 byte floating point
• 4 byte counter without math. symbol
• 4 byte counter with math. symbol
• 4 byte floating point
Output value (if applicable output value A1 / A2)
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 67
65 Parameter setting
if the condition is met 0 [Input range depending on the type of
output]
if the condition is not met 0 [Input range depending on the type of
output]
if the monitoring time period is exceeded
0 [Input range depending on the type of output]
if blocked 0 [Input range depending on the type of
output]
Set the output send pattern.
Output sends • on change
• on change and after reset
• on change and periodically
• when receiving an input object
• when receiving an input object and periodically
Type of change
(is only sent if "on change" is selected)
• on each change
• on change to condition met
• on change to condition not met
Send cycle
5 s ... 2 h; 10 s
(if sent periodically)
Set the text to be displayed for conditions met / not met.
Text if the condition is met [Free text max. 14 chars.] Text if the condition is not met [Free text max. 14 chars.]
If applicable set the send delays.
Send delay in the event of change
none • 1 s • ... • 2 h
to the condition is met Send delay in the event of change
none • 1 s • ... • 2 h
to the condition is not met
Calculations and transformation
For calculations and transformations set the output values to the various conditions:
Output value (if applicable A1 / A2) if the monitoring time period
is exceeded
0 [Input range depending on the type of output]
if blocked 0 [Input range depending on the type of
output]
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 68
66 Parameter setting
Set the output send pattern.
Output sends • on change
on change of (only if calculations are
transmitted for changes)
Send cycle
(if sent periodically)
• on change and after reset
• on change and periodically
• when receiving an input object
• when receiving an input object and periodically
1 ... [Input range depending on the type of input]
5 s ... 2 h; 10 s
For Calculations of the form output 1 = E1 × X + Y | output 2 = E2 × X +Y define the variables X and Y. The variables can have a positive or negative sign, 9 digits before and 9 digits after the decimal point.
Formula for output A1: A1 = E1 × X + Y X1.00 [free input] Y0.00 [free input] Formula for output A2: A2 = E2 × X + Y X1.00 [free input] Y0.00 [free input]
Further settings for all formulas
If necessary, activate the input monitoring. Set which inputs are to be monitored, at which intervals the inputs are to be monitored and what value the "monitoring status" should have, if the monitoring period is exceeded without feedback.
Use input monitoring No • Yes Monitoring of • E1
Monitoring period 5 s • ... • 2 h; 1 min Value of the object "monitoring status"
if period is exceeded
• E2
• E3
• E1 and E2
• E1 and E3
• E2 and E3
• E1 and E2 and E3 [depending on the function]
0 • 1
If necessary, activate the computer block and set what a 1 or 0 at the block entry means and what happens in the event of a block.
Use block No • Yes Analysis of the blocking object • At value 1: block | At value 0: release
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• At value 0: block | At value 1: release
Page 69
67 Parameter setting
Value before first call 0 • 1 Output pattern
On block On release • as send pattern [see above]
• do not send anything
• send value
• send current value immediately

6.20. Logic

The device has 16 logic inputs, eight AND and eight OR logic gates.
Activate the logic inputs and assign object values up to first call.
Use logic inputs Yes • No Object value prior to first call for:
- Logic input 1 0 • 1
- Logic input ... 0 • 1
- Logic input 16 0 • 1
Activate the required logic outputs.
AND logic
AND logic 1 not active • active AND logic ... not active • active AND logic 8 not active • active
OR logic
OR logic 1 not active • active OR logic ... not active • active OR logic 8 not active • active

6.20.1. AND logic 1-8 and OR logic outputs 1-8

The same setting options are available for AND and OR logic.
Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out put should send if logic = 1 and = 0.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 70
68 Parameter setting
1. / 2. / 3. / 4. Input • do not use
- Logic inputs 1...16
- Logic inputs 1...16 inverted
• all switching events that the device provides (see Connection inputs of the AND/OR logic)
Output type • a 1-Bit-object
• two 8-bit objects
If the output type is a 1-bit object, set the output values for the various conditions.
Output value
1 • 0
if logic = 1 Output value
1 • 0
if logic = 0 Output value
1 • 0
If block is active Output value if
1 • 0
monitoring period is exceeded
If the output type is two 8-bit objects, set the type of object and the output values for the various conditions.
Object type • Value (0…255)
• Percent (0…100%)
• Angle (0…360°)
• Scene call-up (0…127)
Output value object A
0 … 255 / 100% / 360° / 127; 1
if logic = 1 Output value object B
0 … 255 / 100% / 360° / 127; 1
if logic = 1 Output value object A
0 … 255 / 100% / 360° / 127; 0
if logic = 0 Output value object B
0 … 255 / 100% / 360° / 127; 0
if logic = 0 Output value object A
0 … 255 / 100% / 360° / 127; 0
if block is active Output value object B
0 … 255 / 100% / 360° / 127; 0
if block is active Output value object A if
0 … 255 / 100% / 360° / 127; 0
monitoring period is exceeded Output value object B if
0 … 255 / 100% / 360° / 127; 0
monitoring period is exceeded
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 71
69 Parameter setting
Set the output send pattern.
Send pattern • on change of logic
Send cycle
(if sent periodically)
• on change of logic to 1
• on change of logic to 0
• on change of logic and periodically
• on change of logic to 1 and periodically
• on change of logic to 0 and periodically
• on change of logic+object receipt
• on change of logic+object receipt and periodically
5 s • 10 s • ... • 2 h
Block
If necessary, activate the block for the logic output and set what a 1 or 0 at the block input means and what happens in the event of a block.
Use block No • Yes Analysis of the blocking object • At value 1: block | At value 0: release
Blocking object value before first call 0 • 1 Output pattern
On block
On release (with 2 seconds release delay)
• At value 0: block | At value 1: release
• Do not send message
• Transmit block value [see above, Output value if blocking active]
[send value for current logic status]
Monitoring
If necessary, activate the input monitoring. Set which inputs are to be monitored, at which intervals the inputs are to be monitored and what value the "monitoring status" should have, if the monitoring period is exceeded without a feedback being given.
Use input monitoring No • Yes Input monitoring • 1 • 2 • 3 • 4
Monitoring period 5 s • ... • 2 h; 1 min Output behaviour on exceeding the moni-
toring time
• 1 + 2 • 1 + 3 • 1 + 4 • 2 + 3 • 2 + 4 • 3 + 4
• 1 + 2 + 3 • 1 + 2 + 4 • 1 + 3 + 4 • 2 + 3 + 4
• 1 + 2 + 3 + 4
• Do not send message
• Send value exceeding [= value of the parameter "monitoring period"]

6.20.2.AND logic connection inputs

Do not use
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 72
Logic input 1 Logic input 1 inverted Logic input 2 Logic input 2 inverted Logic input 3 Logic input 3 inverted Logic input 4 Logic input 4 inverted Logic input 5 Logic input 5 inverted Logic input 6 Logic input 6 inverted Logic input 7 Logic input 7 inverted Logic input 8 Logic input 8 inverted Logic input 9 Logic input 9 inverted Logic input 10 Logic input 10 inverted Logic input 11 Logic input 11 inverted Logic input 12 Logic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input 15 inverted Logic input 16 Logic input 16 inverted Temperature sensor malfunction ON Temperature sensor malfunction OFF Humidity sensor malfunction ON Humidity sensor malfunction OFF Pressure sensor malfunction ON Pressure sensor malfunction OFF CO2 sensor malfunction ON CO2 sensor malfunction OFF Switching output 1 Temperature Switching output 1 Temperature inverted Switching output 2 Temperature Switching output 2 Temperature inverted Switching output 3 Temperature Switching output 3 Temperature inverted Switching output 4 Temperature Switching output 4 Temperature inverted
70 Parameter setting
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 73
71 Parameter setting
Switching output 1 Humidity Switching output 1 Humidity inverted Switching output 2 Humidity Switching output 2 Humidity inverted Switching output 3 Humidity Switching output 3 Humidity inverted Switching output 4 Humidity Switching output 4 Humidity inverted Switching output coolant temperature Switching output coolant temperature inverted Ambient climate is comfortable Ambient climate is uncomfortable Switching output 1 Pressure Switching output 1 Pressure inverted Switching output 2 Pressure Switching output 2 Pressure inverted Switching output 3 Pressure Switching output 3 Pressure inverted Switching output 4 Pressure Switching output 4 Pressure inverted Switching output 1 CO2 Switching output 1 CO2 inverted Switching output 2 CO2 Switching output 2 CO2 inverted Switching output 3 CO2 Switching output 3 CO2 inverted Switching output 4 CO2 Switching output 4 CO2 inverted Comfort temperature controller active Comfort temperature controller inactive Standby temperature controller active Standby temperature controller inactive Eco temperature controller active Eco temperature controller inactive Frost protection temperature controller active Frost protection temperature controller inactive Heating 1 temperature controller active Heating 1 temperature controller inactive Heating 2 temperature controller active Heating 2 temperature controller inactive Cooling 1 temperature controller active Cooling 1 temperature controller inactive Cooling 2 temperature controller active Cooling 2 temperature controller inactive Humidity controller dehumidification 1 active Humidity controller dehumidification 1 inactive Humidity controller dehumidification 2 active Humidity controller dehumidification 2 inactive
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 74
72 Parameter setting
Humidity controller humidification active Humidity controller humidification 1 inactive CO2 controller ventilation 1 active CO2 controller ventilation 1 inactive CO2 controller ventilation 2 active CO2 controller ventilation 2 inactive

6.20.3. Connection inputs of the OR logic

The OR logic connection inputs correspond to those of the AND logic. In addition, the following inputs are available for the OR logic:
Switching output AND logic 1 Switching output AND logic 1 inverted Switching output AND logic 2 Switching output AND logic 2 inverted Switching output AND logic 3 Switching output AND logic 3 inverted Switching output AND logic 4 Switching output AND logic 4 inverted Switching output AND logic 5 Switching output AND logic 5 inverted Switching output AND logic 6 Switching output AND logic 6 inverted Switching output AND logic 7 Switching output AND logic 7 inverted Switching output AND logic 8 Switching output AND logic 8 inverted