Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • from ETS programme version 1.1
Version: 10.09.2018 • Technical changes and errors excepted.
3Clarification of signs
Installation, inspection, commissioning and troubleshooting of the device
must only be carried out by a competent electrician.
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-todate version of the manual is available.
Clarification of signs used in this manual
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER!
WARNING!
CAUTION!
ATTENTION!
ETSIn the ETS tables, the parameter default settings are marked by
... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
... indicates a situation which may lead to damage to property if it is
not avoided.
underlining.
4Clarification of signs
5Description
1.Description
The Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D for the KNX bus system
measures the CO
Sewi KNX AQS/TH-D additionally measures the temperature, the air humidity and
the air pressure and calculates the dew-point. The sensor can output a warning to the
bus as soon as the comfort field, as per DIN 1946, is left.
Via the bus, the indoor sensors can receive external values and process it further with
its own data to a total value (mixed value, e.g. room average).
All measurement values can be used for the control of limit-dependent switching outputs. States can be linked via AND logic gates and OR logic gates. Multi-function modules change input data as required by means of calculations, querying a condition, or
converting the data point type. In addition, an integrated manipulated variable comparator can compare and output variables that were received via communication objects.
Integrated PI-controllers control ventilation (according to humidity or CO
tion) and heating/cooling (according to temperature).
Functions:
•Measuring the CO
The share of internal measurement value and external value can be set as a
percentage
•Threshold values can be adjusted per parameter or via communication
objects
•PI controller for ventilation according to CO
(one-stage) or Ventilate (one or two-stage)
•8 AND and 8 OR logic gates, each with 4 inputs. All switching events as well
as 16 logic inputs in the form of communications objects can be used as inputs
for the logic gates. The output of each gate can be configured optionally as 1bit or 2 x 8-bit
•8 multi-function modules (computers) for changing the input data by
calculations, by querying a condition or by converting the data point type
•4 actuating variable comparators to output minimum, maximum or
average values. 5 inputs each for values received via communication objects
Additional functions Sewi KNX AQS/TH-D:
•Measuring the temperature and air humidity (relative, absolute), each with
mixed value calculation. The share of internal measurement value and
external value can be set as a percentage
•Bus message, whether the values for temperature and air humidity are within
the comfort field (DIN 1946). Dew point calculation
•Air pressure measurement. Output of the value as normal pressure and
optionally as barometric pressure
•PI-controller for heating (one or two-stage) and cooling (one or two-stage)
according to temperature. Regulation according to separate setpoints or basic
setpoint temperature
concentration in a room.
2
concentration of the air with mixed value calculation.
2
concentration: Ventilate/Air
2
concentra-
2
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
6Description
•PI controller for ventilation according to humidity: Ventilate/Air (one-stage)
or Ventilate (one or two-stage)
•Summer compensation for cooling systems. A characteristic curve matches
the target temperature in the room to the external temperature and sets the
minimum and maximum target temperature values
Configuration is made using the KNX software ETS. The product file can be downloaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Service” menu.
1.0.1. Scope of delivery
•Sensor
1.1.Technical data
HousingPlastic
ColourWhite (Cover glossy, skirting matt)
AssemblySurface, wall or ceiling installation
Protection categoryIP 30
DimensionsØ approx. 105 mm, height approx. 32 mm
Total weightapprox. 50 g
Ambient temperatureOperation 0…+50°C, storage -30…+70°C
Ambient humiditymax. 85% RH, avoid condensation
Operating voltageKNX bus voltage
Bus currentmax. 20 mA
Data outputKNX +/- bus plug-in terminal
BCU typeIntegrated microcontroller
PEI type0
Group addressesmax. 2000
Assignmentsmax. 2000
Communication objectsSewi KNX AQS/TH-D: 363
CO2 sensor:
Measurement range0...2000 ppm
Resolution1 ppm
Accuracy*± 50 ppm ± 3% of the measured value
Temperature sensor (only Sewi KNX AQS/TH-D):
Measurement range 0°C…+50°C
Resolution0.1°C
Accuracy*±0.5°C at 0...+50°C
Humidity sensor (only Sewi KNX AQS/TH-D):
Measurement range0% RH … 85% RH
Resolution0.1% RH
Sewi KNX AQS: 210
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The product conforms with the provisions of EU directives.
± 4,5% RH at 10…85% RH
1.1.1. Measuring accuracy
Deviations in measured values due to interfering sources (see chapter installation site)
must be corrected in the ETS in order to achieve the specified accuracy of the sensor
(offset).
During Temperature measurement, the self-heating of the device is taken into consideration by the electronics. The software compensates the self-heating by reducing
the measured temperature by 1.0°C.
2.Installation and start-up
2.1.Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
•National legal regulations are to be followed.
•Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
•Do not use the device if it is damaged.
•Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or
failure to follow the operating instructions voids any and all warranty and guarantee
claims.
After unpacking the device, check it immediately for possible mechanical damage. If it
has been damaged in transport, inform the supplier immediately.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
8Installation and start-up
The device may only be used as a fixed-site installation; that means only when assembled and after conclusion of all installation and operational start-up tasks and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2.Installation location
Install and use only in dry interior rooms! Avoid condensation.
The sensor is installed surface mounted on walls or ceilings.
When selecting an installation location, please ensure that the measurement results of
temperature, humidity and CO
ences. Possible sources of interference include:
•Direct sunlight
•Drafts from windows and doors
•Draughts from ducts coming from other rooms or the outdoors
•Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
•Connection lines and empty ducts which lead from warmer or colder areas to
the sensor
Measurement variations from such sources of interference must be corrected in the
ETS in order to ensure the specified accuracy of the sensor (offset).
are affected as little as possible by external influ-
2
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
9Installation and start-up
Fig. 1
A Recess to open the hous-
ing. When closing the
housing, the recess aligns
to the marking on the skirting
A
2.3.Construction of the sensor
2.3.1. Housing from the outside
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
10Installation and start-up
Fig. 2
1 a+b Long holes for mounting (hole distance 60 mm)
2 Sensors for temperature, humidity, pressure (only Sewi KNX AQS/TH-D)
3CO
2
-Sensor
4Programming button
5Programming LED
6KNX-terminal BUS +/7Cable bushing
A Mark for aligning the cover
1a
A
1b
3
4
6
7
5
2
Fig. 3
Open the housing. To do this, carefully lift the
cover from the skirting. Start at the recess
(Fig. 2: A).
2.3.2. Printed circuit boards / connections
2.4.Assembly
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
11Installation and start-up
Fig. 4
Lead the bus cable through the cable
busching in the skirting.
Fig. 5
Screw the skirting to the wall or the ceiling.
Hole distance 60 mm.
60 mm
Fig. 6
Connect the KNX bus to the KNX terminal.
Fig. 7
Close the housing by positioning the cover
and snapping it into place. To do this, align
the recess on the cover to the marking on the
skirting (Fig. 1+2: A).
2.5.Notes on mounting and commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electronics.
You must not exceed a relative humidity of 85%. Avoid condensation.
The air slots on the side must not be closed or covered.
After the bus voltage has been applied, the device will enter an initialisation phase lasting a few seconds. During this phase no information can be received or sent via the
bus.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
12Addressing the equipment
3.Addressing the equipment
The equipment is delivered with the bus address 15.15.254. You can program a different address in the ETS by overwriting the address 15.15.254 or by teaching the device
via the programming button.
The programming button is on the inside of the housing (Fig. 2: No. 3).
4.Maintenance
The air slots on the side must not get dirty or covered. As a rule, it is sufficient to wipe
the device with a soft, dry cloth twice a year.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
13Transfer protocol
5.Transfer protocol
Units:
Temperatures in degrees Celsius
Air pressure in Pascal
Air humidity in %
Absolute air humidity in g/kg and/or g/m
CO2 content in ppm
Variables in %
5.1.List of all communication objects
Abbreviation flags:
C Communication
R Read
WWrite
T Transfer
UUpdate
No. TextFunc-
1Software versionOutputR-CT[217.1] DPT_Ver-
41Temperature sensor: MalfunctionOutputR-CT[1.1] DPT_Switch 1 bit
42Temperature sensor: External
measurement
43Temperature sensor: Measured value OutputR-CT[9.1] DPT_Val-
44Temperature sensor: Total
measurement
45Temperature sensor: Min./Max.
measurement query
46Temperature sensor: Minimum
measurement
47Temperature sensor: Maximum
measurement
48Temperature sensor: Min./Max.
measurement reset
51Temp. threshold value 1: Absolute
value
52Temp. threshold value 1: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch 1 bit
53Temp. threshold value 1: Switching
delay from 0 to 1
54Temp. threshold value 1: Switching
delay from 1 to 0
3
tion
Input-WCT [9.1] DPT_Val-
OutputR-CT[9.1] DPT_Val-
Input-WC-[1.017] DPT_Trig-
OutputR-CT[9.1] DPT_Val-
OutputR-CT[9.1] DPT_Val-
Input-WC-[1.017] DPT_Trig-
Input/
Output
Input-WC-[7.5] DPT_Time-
Input-WC-[7.5] DPT_Time-
Flags DPT TypSize
sion
ue_Temp
ue_Temp
ue_Temp
ger
ue_Temp
ue_Temp
ger
RWCT [9.1] DPT_Val-
ue_Temp
PeriodSec
PeriodSec
2 bytes
2 bytes
2 bytes
2 bytes
1 bit
2 bytes
2 bytes
1 bit
2 bytes
2 bytes
2 bytes
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
14Transfer protocol
No. TextFunc-
Flags DPT TypSize
tion
55Temp. threshold value 1: Switching
OutputR-CT[1.1] DPT_Switch 1 bit
output
56Temp. threshold value 1: Switching
Input-WC-[1.1] DPT_Switch 1 bit
output block
58Temp. threshold value 2: Absolute
value
Input/
Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
59Temp. threshold value 2: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch 1 bit
60Temp. threshold value 2: Switching
delay from 0 to 1
61Temp. threshold value 2: Switching
delay from 1 to 0
62Temp. threshold value 2: Switching
Input-WC-[7.5] DPT_Time-
2 bytes
PeriodSec
Input-WC-[7.5] DPT_Time-
2 bytes
PeriodSec
OutputR-CT[1.1] DPT_Switch 1 bit
output
63Temp. threshold value 2: Switching
Input-WC-[1.1] DPT_Switch 1 bit
output block
65Temp. threshold value 3: Absolute
value
Input/
Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
66Temp. threshold value 3: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch 1 bit
67Temp. threshold value 3: Switching
delay from 0 to 1
68Temp. threshold value 3: Switching
delay from 1 to 0
69Temp. threshold value 3: Switching
Input-WC-[7.5] DPT_Time-
2 bytes
PeriodSec
Input-WC-[7.5] DPT_Time-
2 bytes
PeriodSec
OutputR-CT[1.1] DPT_Switch 1 bit
output
70Temp. threshold value 3: Switching
Input-WC-[1.1] DPT_Switch 1 bit
output block
72Temp. threshold value 4: Absolute
value
Input/
Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
73Temp. threshold value 4: (1:+ | 0:-)Input-WC-[1.1] DPT_Switch 1 bit
74Temp. threshold value 4: Switching
delay from 0 to 1
75Temp. threshold value 4: Switching
delay from 1 to 0
76Temp. threshold value 4: Switching