KNX Interface for WS1000 • from WS1000 software version 1.8, ETS programm version 3.0
Status: 15.04.2016 • Subject to technical changes. Errors excepted.
Page 3
2Clarification of signs
Installation, inspection, commissioning and troubleshooting of the device
must only be carried out by a competent electrician.
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-todate version of the manual is available.
Clarification of signs used in this manual
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER!
WARNING!
CAUTION!
ATTENTION!
ETSIn the ETS tables, the parameter default settings are marked by
... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
... indicates a situation which may lead to damage to property if it is
not avoided.
underlining.
Page 4
3Description
1.Description
The KNX Interface for WS1000 allows for communication between the WS1000
Color or WS1000 Style Control System and the KNX bus system. On the one hand, data
of the control unit can be sent to the KNX bus (e. g. weather data). On the other hand,
the WS1000 can control drives in the KNX system directly and use sensor data from
the KNX system.
Functions:
•Transmission of data from WS1000 Color/Style to the KNX bus: date/
time, position, weather data
•Control of actuators in the KNX bus system by the automatic functions of the
•Transmission of bus data to the WS1000 Color/Style: sensor data, push-
button commands
Configuration is made using the KNX software ETS. The product file can be downloaded from the Elsner Elektronik homepage on www.elsner-elektronik.de in the
“Service” menu.
1.1.Scope of delivery
•Interface
•KNX bus connector terminal
Interface and bus connector terminal are plugged on the board of the Control System
WS1000 Color/WS1000 Style.
1.2.Technical specifications
Mountingis plugged on the board of the Control WS1000
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
DANGER!
Risk to life from live voltage (mains voltage)!
There are unprotected live components within the device.
•VDE regulations and national regulations are to be followed.
•Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
•Do not use the device if it is damaged.
•Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or
failure to follow the operating instructions voids any and all warranty and guarantee
claims.
After unpacking the device, check it immediately for possible mechanical damage. If it
has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when assembled and after conclusion of all installation and operational start-up tasks and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2.Mounting and connection
Please take note of the chapters about installation of the control unit WS1000 in the
manual of WS1000 Color/Style.
1‘ Slot KNX terminal +/2‘/3‘Pins for connection of inter-
face
1KNX terminal plug +/2/3 Plug sockets
4Programming button for
setting up the device
5Programming LED
2.2.1. Fitting the interface to the board of WS1000
2.2.2. Connection
The KNX Interface for WS1000 is plugged on the connection board of the WS1000
Color or WS1000 Style. There are 2 blocks with 6 pins each for this purpose (no. 2’ and
3’). Place the interface on the pins and push it down.
Connect the KNX bus cable to the bus connector (red/black) and plug the connector to
the slot of the WS1000 board (no. 1’).
Before closing the housing of the control again, set up the bus connection with the programming button (no. 4). The KNX interface is displayed in the starting sequence of the
control (KNX interface found).
After the professional installation and commissioning, the basic settings have to be
made in the ETS and then in the control menu System > Installation.
After the programming in the ETS, the control must be reset (also when making
changes).
6.3.2. Service-Einstellungen, Reset
System > WS1000 einstellen > Service > Reset
Control System KNX WS1000 Color • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 8
7
2.4.KNX transmission protocol
Abbreviations
Flags:
C: Communication
R: Read
W: Write
T: Transfer
AU: Update
2.4.1. List of all communications objects
No. Name FunctionDPTFlags
0Software versionOutput217,001C R T
1DateInput / Output11,001C W T
2TimeInput / Output10,001C W T
3Date and time requestInput1,017C S
4Location BreitengradOutput14,007C R T
5Location LaengengradOutput14,007C R T
6Sun elevation AzimuthOutput14,007C R T
7Sun position ElevationOutput14,007C R T
8Sun elevation AzimuthOutput9.*C R T
9Sun position ElevationOutput9.*C R T
10Switching output night Output1,002C R T
11Switching output rainInput / Output1,002C R W T
12Outdoor temperature
measurement value
13Wind force measurement valueInput / Output9,005C R W T
14Wind force sensor 1 measurement
value
15Wind force sensor 2 measurement
value
16Wind force sensor 3 measurement
value
17Wind force sensor 4 measurement
value
18Wind direction 2 ByteInput9.*C W
19Winddirection 4 ByteInput14.007C W
20Brightness measurement valueInput / Output9,004C R W T
21Reserve
22WS1000 defectOutput1,002C R T
23Wind sensor defectOutput1,002C R T
Input / Output9,001C R W T
Input9.005C W
Input9.005C W
Input9.005C W
Input14.007C R W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 9
8
No. Name FunctionDPTFlags
24Temperature sensor defectOutput1,002C R T
25Weather station defectOutput1,002C R T
26BlockInput1,002C S
27Wind sensor 1 defectOutput1.002C R T
28Wind sensor 2 defectOutput1.002C R T
29Wind sensor 3 defectOutput1.002C R T
30Wind sensor 4 defectOutput1.002C R T
31Wind direction defectOutput1.002C R T
32Reserve
33Block 7_1: Long-timeInput / Output1,008C W T
34Block 7_1: Short-timeInput / Output1,01C W T
35Block 7_1: Actuation positionOutput5,001C T
36Block 7_1: Slat positionOutput5,001C T
37Block 7_1: Movement position
Input5,001C W T
feedback
38Block 7_1: Slat position feedbackInput5,001C W T
39Block 7_1: SafetyOutput 1,002C R T
33Block 7_1: SwitchingInput / Output1,001C W T
34Block 7_1: Switching feedbackOutput1,001C R T
34Block 7_1: DimmingOutput3,007C T
35Block 7_1: Dimmer value in %Input / Output5,001C W T
37Block 7_1: TemperatureInput9,001C W T
38Block 7_1: Air humidityInput9,007C W T
39Block 7_1: CO2Input9,008C W T
39Block 7_1: 2 byte floating pointInput9.*C W T
39Block 7_1: 4 byte floating pointInput14.*C W T
40Block 7_2: Long-timeInput / Output1,008C W T
41Block 7_2: Short-timeInput / Output1,01C W T
42Block 7_2: Actuation positionOutput5,001C T
43Block 7_2: Slat positionOutput5,001C T
44Block 7_2: Movement position
Input5,001C W T
feedback
45Block 7_2: Slat position feedbackInput5,001C W T
46Block 7_2: SafetyOutput 1,002C R T
40Block 7_2: SwitchingOutput1,001C W T
41Block 7_2: Switching feedbackInput1,001C R T
41Block 7_2: DimmingOutput3,007C T
42Block 7_2: Dimmer value in %Input / Output5,001C W T
44Block 7_2: TemperatureInput9,001C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 10
9
No. Name FunctionDPTFlags
45Block 7_2: Air humidityInput9,007C W T
46Block 7_2: CO2Input9,008C W T
46Block 7_2: 2 byte floating pointInput9.*C W T
46Block 7_2: 4 byte floating pointInput14.*C W T
47Block 7_3: Long-timeInput / Output1,008C W T
48Block 7_3: Short-timeInput / Output1,01C W T
49Block 7_3: Actuation positionOutput5,001C T
50Block 7_3: Slat positionOutput5,001C T
51Block 7_3: Movement position
Input5,001C W T
feedback
52Block 7_3: Slat position feedbackInput5,001C W T
53Block 7_3: SafetyOutput 1,002C R T
47Block 7_3: SwitchingOutput1,001C W T
48Block 7_3: Switching feedbackInput1,001C R T
48Block 7_3: DimmingOutput3,007C T
49Block 7_3: Dimmer value in %Input / Output5,001C W T
51Block 7_3: TemperatureInput9,001C W T
52Block 7_3: Air humidityInput9,007C W T
53Block 7_3: CO2Input9,008C W T
53Block 7_3: 2 byte floating pointInput9.*C W T
53Block 7_3: 4 byte floating pointInput14.*C W T
54Block 7_4: Long-timeInput / Output1,008C W T
55Block 7_4: Short-timeInput / Output1,01C W T
56Block 7_4: Actuation positionOutput5,001C T
57Block 7_4: Slat positionOutput5,001C T
58Block 7_4: Movement position
Input5,001C W T
feedback
59Block 7_4: Slat position feedbackInput5,001C W T
60Block 7_4: SafetyOutput 1,002C R T
54Block 7_4: SwitchingOutput1,001C W T
55Block 7_4: Switching feedbackInput1,001C R T
55Block 7_4: DimmingOutput3,007C T
56Block 7_4: Dimmer value in %Input / Output5,001C W T
58Block 7_4: TemperatureInput9,001C W T
59Block 7_4: Air humidityInput9,007C W T
60Block 7_4: CO2Input9,008C W T
60Block 7_4: 2 byte floating pointInput9.*C W T
60Block 7_4: 4 byte floating pointInput14.*C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 11
10
No. Name FunctionDPTFlags
61Block 7_5: Long-timeInput / Output1,008C W T
62Block 7_5: Short-timeInput / Output1,01C W T
63Block 7_5: Actuation positionOutput5,001C T
64Block 7_5: Slat positionOutput5,001C T
65Block 7_5: Movement position
Input5,001C W T
feedback
66Block 7_5: Slat position feedbackInput5,001C W T
67Block 7_5: SafetyOutput 1,002C R T
61Block 7_5: SwitchingOutput1,001C W T
62Block 7_5: Switching feedbackInput1,001C R T
62Block 7_5: DimmingOutput3,007C T
63Block 7_5: Dimmer value in %Input / Output5,001C W T
65Block 7_5: TemperatureInput9,001C W T
66Block 7_5: Air humidityInput9,007C W T
67Block 7_5: CO2Input9,008C W T
67Block 7_5: 2 byte floating pointInput9.*C W T
67Block 7_5: 4 byte floating pointInput14.*C W T
68Block 7_6: Long-timeInput / Output1,008C W T
69Block 7_6: Short-timeInput / Output1,01C W T
70Block 7_6: Actuation positionOutput5,001C T
71Block 7_6: Slat positionOutput5,001C T
72Block 7_6: Movement position
Input5,001C W T
feedback
73Block 7_6: Slat position feedbackInput5,001C W T
74Block 7_6: SafetyOutput 1,002C R T
68Block 7_6: SwitchingOutput1,001C W T
69Block 7_6: Switching feedbackInput1,001C R T
69Block 7_6: DimmingOutput3,007C T
70Block 7_6: Dimmer value in %Input / Output5,001C W T
72Block 7_6: TemperatureInput9,001C W T
73Block 7_6: Air humidityInput9,007C W T
74Block 7_6: CO2Input9,008C W T
74Block 7_6: 2 byte floating pointInput9.*C W T
74Block 7_6: 4 byte floating pointInput14.*C W T
75Block 7_7: Long-timeInput / Output1,008C W T
76Block 7_7: Short-timeInput / Output1,01C W T
77Block 7_7: Actuation positionOutput5,001C T
78Block 7_7: Slat positionOutput5,001C T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 12
11
No. Name FunctionDPTFlags
79Block 7_7: Movement position
Input5,001C W T
feedback
80Block 7_7: Slat position feedbackInput5,001C W T
81Block 7_7: SafetyOutput 1,002C R T
75Block 7_7: SwitchingOutput1,001C W T
76Block 7_7: Switching feedbackInput1,001C R T
76Block 7_7: DimmingOutput3,007C T
77Block 7_7: Dimmer value in %Input / Output5,001C W T
79Block 7_7: TemperatureInput9,001C W T
80Block 7_7: Air humidityInput9,007C W T
81Block 7_7: CO2Input9,008C W T
81Block 7_7: 2 byte floating pointInput9.*C W T
81Block 7_7: 4 byte floating pointInput14.*C W T
82Block 7_8: Long-timeInput / Output1,008C W T
83Block 7_8: Short-timeInput / Output1,01C W T
84Block 7_8: Actuation positionOutput5,001C T
85Block 7_8: Slat positionOutput5,001C T
86Block 7_8: Movement position
Input5,001C W T
feedback
87Block 7_8: Slat position feedbackInput5,001C W T
88Block 7_8: SafetyOutput 1,002C R T
82Block 7_8: SwitchingOutput1,001C W T
83Block 7_8: Switching feedbackInput1,001C R T
83Block 7_8: DimmingOutput3,007C T
84Block 7_8: Dimmer value in %Input / Output5,001C W T
86Block 7_8: TemperatureInput9,001C W T
87Block 7_8: Air humidityInput9,007C W T
88Block 7_8: CO2Input9,008C W T
88Block 7_8: 2 byte floating pointInput9.*C W T
88Block 7_8: 4 byte floating pointInput14.*C W T
89Block 7_9: Long-timeInput / Output1,008C W T
90Block 7_9: Short-timeInput / Output1,01C W T
91Block 7_9: Actuation positionOutput5,001C T
92Block 7_9: Slat positionOutput5,001C T
93Block 7_9: Movement position
Input5,001C W T
feedback
94Block 7_9: Slat position feedbackInput5,001C W T
95Block 7_9: SafetyOutput 1,002C R T
89Block 7_9: SwitchingOutput1,001C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 13
12
No. Name FunctionDPTFlags
90Block 7_9: Switching feedbackInput1,001C R T
90Block 7_9: DimmingOutput3,007C T
91Block 7_9: Dimmer value in %Input / Output5,001C W T
93Block 7_9: TemperatureInput9,001C W T
94Block 7_9: Air humidityInput9,007C W T
95Block 7_9: CO2Input9,008C W T
95Block 7_9: 2 byte floating pointInput9.*C W T
95Block 7_9: 4 byte floating pointInput14.*C W T
96Block 7_10: Long-timeInput / Output1,008C W T
97Block 7_10: Short-timeInput / Output1,01C W T
98Block 7_10: Actuation positionOutput5,001C T
99Block 7_10: Slat positionOutput5,001C T
100Block 7_10: Movement position
Input5,001C W T
feedback
101Block 7_10: Slat position feedbackInput5,001C W T
102Block 7_10: SafetyOutput 1,002C R T
96Block 7_10: SwitchingOutput1,001C W T
97Block 7_10: Switching feedbackInput1,001C R T
97Block 7_10: DimmingOutput3,007C T
98Block 7_10: Dimmer value in %Input / Output5,001C W T
100Block 7_10: TemperatureInput9,001C W T
101Block 7_10: Air humidityInput9,007C W T
102Block 7_10: CO2Input9,008C W T
102Block 7_10: 2 byte floating pointInput9.*C W T
102Block 7_10: 4 byte floating pointInput14.*C W T
103Block 7_11: Long-timeInput / Output1,008C W T
104Block 7_11: Short-timeInput / Output1,01C W T
105Block 7_11: Actuation positionOutput5,001C T
106Block 7_11: Slat positionOutput5,001C T
107Block 7_11: Movement position
Input5,001C W T
feedback
108Block 7_11: Slat position feedbackInput5,001C W T
109Block 7_11: SafetyOutput 1,002C R T
103Block 7_11: SwitchingOutput1,001C W T
104Block 7_11: Switching feedbackInput1,001C R T
104Block 7_11: DimmingOutput3,007C T
105Block 7_11: Dimmer value in %Input / Output5,001C W T
107Block 7_11: TemperatureInput9,001C W T
108Block 7_11: Air humidityInput9,007C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 14
13
No. Name FunctionDPTFlags
109Block 7_11: CO2Input9,008C W T
109Block 7_11: 2 byte floating pointInput9.*C W T
109Block 7_11: 4 byte floating pointInput14.*C W T
110Block 7_12: Long-timeInput / Output1,008C W T
111Block 7_12: Short-timeInput / Output1,01C W T
112Block 7_12: Actuation positionOutput5,001C T
113Block 7_12: Slat positionOutput5,001C T
114Block 7_12: Movement position
Input5,001C W T
feedback
115Block 7_12: Slat position feedbackInput5,001C W T
116Block 7_12: SafetyOutput 1,002C R T
110Block 7_12: SwitchingOutput1,001C W T
111Block 7_12: Switching feedbackInput1,001C R T
111Block 7_12: DimmingOutput3,007C T
112Block 7_12: Dimmer value in %Input / Output5,001C W T
114Block 7_12: TemperatureInput9,001C W T
115Block 7_12: Air humidityInput9,007C W T
116Block 7_12: CO2Input9,008C W T
116Block 7_12: 2 byte floating pointInput9.*C W T
116Block 7_12: 4 byte floating pointInput14.*C W T
117Block 7_13: Long-timeInput / Output1,008C W T
118Block 7_13: Short-timeInput / Output1,01C W T
119Block 7_13: Actuation positionOutput5,001C T
120Block 7_13: Slat positionOutput5,001C T
121Block 7_13: Movement position
Input5,001C W T
feedback
122Block 7_13: Slat position feedbackInput5,001C W T
123Block 7_13: SafetyOutput 1,002C R T
117Block 7_13: SwitchingOutput1,001C W T
118Block 7_13: Switching feedbackInput1,001C R T
118Block 7_13: DimmingOutput3,007C T
119Block 7_13: Dimmer value in %Input / Output5,001C W T
121Block 7_13: TemperatureInput9,001C W T
122Block 7_13: Air humidityInput9,007C W T
123Block 7_13: CO2Input9,008C W T
123Block 7_13: 2 byte floating pointInput9.*C W T
123Block 7_13: 4 byte floating pointInput14.*C W T
124Block 7_14: Long-timeInput / Output1,008C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 15
14
No. Name FunctionDPTFlags
125Block 7_14: Short-timeInput / Output1,01C W T
126Block 7_14: Actuation positionOutput5,001C T
127Block 7_14: Slat positionOutput5,001C T
128Block 7_14: Movement position
Input5,001C W T
feedback
129Block 7_14: Slat position feedbackInput5,001C W T
130Block 7_14: SafetyOutput 1,002C R T
124Block 7_14: SwitchingOutput1,001C W T
125Block 7_14: Switching feedbackInput1,001C R T
125Block 7_14: DimmingOutput3,007C T
126Block 7_14: Dimmer value in %Input / Output5,001C W T
128Block 7_14: TemperatureInput9,001C W T
129Block 7_14: Air humidityInput9,007C W T
130Block 7_14: CO2Input9,008C W T
130Block 7_14: 2 byte floating pointInput9.*C W T
130Block 7_14: 4 byte floating pointInput14.*C W T
131Block 7_15: Long-timeInput / Output1,008C W T
132Block 7_15: Short-timeInput / Output1,01C W T
133Block 7_15: Actuation positionOutput5,001C T
134Block 7_15: Slat positionOutput5,001C T
135Block 7_15: Movement position
Input5,001C W T
feedback
136Block 7_15: Slat position feedbackInput5,001C W T
137Block 7_15: SafetyOutput 1,002C R T
131Block 7_15: SwitchingOutput1,001C W T
132Block 7_15: Switching feedbackInput1,001C R T
132Block 7_15: DimmingOutput3,007C T
133Block 7_15: Dimmer value in %Input / Output5,001C W T
135Block 7_15: TemperatureInput9,001C W T
136Block 7_15: Air humidityInput9,007C W T
137Block 7_15: CO2Input9,008C W T
137Block 7_15: 2 byte floating pointInput9.*C W T
137Block 7_15: 4 byte floating pointInput14.*C W T
138Block 7_16: Long-timeInput / Output1,008C W T
139Block 7_16: Short-timeInput / Output1,01C W T
140Block 7_16: Actuation positionOutput5,001C T
141Block 7_16: Slat positionOutput5,001C T
142Block 7_16: Movement position
Input5,001C W T
feedback
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 16
15
No. Name FunctionDPTFlags
143Block 7_16: Slat position feedbackInput5,001C W T
144Block 7_16: SafetyOutput 1,002C R T
138Block 7_16: SwitchingOutput1,001C W T
139Block 7_16: Switching feedbackInput1,001C R T
139Block 7_16: DimmingOutput3,007C T
140Block 7_16: Dimmer value in %Input / Output5,001C W T
142Block 7_16: TemperatureInput9,001C W T
143Block 7_16: Air humidityInput9,007C W T
144Block 7_16: CO2Input9,008C W T
144Block 7_16: 2 byte floating pointInput9.*C W T
144Block 7_16: 4 byte floating pointInput14.*C W T
145Block 7_17: Long-timeInput / Output1,008C W T
146Block 7_17: Short-timeInput / Output1,01C W T
147Block 7_17: Actuation positionOutput5,001C T
148Block 7_17: Slat positionOutput5,001C T
149Block 7_17: Movement position
Input5,001C W T
feedback
150Block 7_17: Slat position feedbackInput5,001C W T
151Block 7_17: SafetyOutput 1,002C R T
145Block 7_17: SwitchingOutput1,001C W T
146Block 7_17: Switching feedbackInput1,001C R T
146Block 7_17: DimmingOutput3,007C T
147Block 7_17: Dimmer value in %Input / Output5,001C W T
149Block 7_17: TemperatureInput9,001C W T
150Block 7_17: Air humidityInput9,007C W T
151Block 7_17: CO2Input9,008C W T
151Block 7_17: 2 byte floating pointInput9.*C W T
151Block 7_17: 4 byte floating pointInput14.*C W T
152Block 7_18: Long-timeInput / Output1,008C W T
153Block 7_18: Short-timeInput / Output1,01C W T
154Block 7_18: Actuation positionOutput5,001C T
155Block 7_18: Slat positionOutput5,001C T
156Block 7_18: Movement position
Input5,001C W T
feedback
157Block 7_18: Slat position feedbackInput5,001C W T
158Block 7_18: SafetyOutput 1,002C R T
152Block 7_18: SwitchingOutput1,001C W T
153Block 7_18: Switching feedbackInput1,001C R T
153Block 7_18: DimmingOutput3,007C T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 17
16
No. Name FunctionDPTFlags
154Block 7_18: Dimmer value in %Input / Output5,001C W T
156Block 7_18: TemperatureInput9,001C W T
157Block 7_18: Air humidityInput9,007C W T
158Block 7_18: CO2Input9,008C W T
158Block 7_18: 2 byte floating pointInput9.*C W T
158Block 7_18: 4 byte floating pointInput14.*C W T
159Block 7_19: Long-timeInput / Output1,008C W T
160Block 7_19: Short-timeInput / Output1,01C W T
161Block 7_19: Actuation positionOutput5,001C T
162Block 7_19: Slat positionOutput5,001C T
163Block 7_19: Movement position
Input5,001C W T
feedback
164Block 7_19: Slat position feedbackInput5,001C W T
165Block 7_19: SafetyOutput 1,002C R T
159Block 7_19: SwitchingOutput1,001C W T
160Block 7_19: Switching feedbackInput1,001C R T
160Block 7_19: DimmingOutput3,007C T
161Block 7_19: Dimmer value in %Input / Output5,001C W T
163Block 7_19: TemperatureInput9,001C W T
164Block 7_19: Air humidityInput9,007C W T
165Block 7_19: CO2Input9,008C W T
165Block 7_19: 2 byte floating pointInput9.*C W T
165Block 7_19: 4 byte floating pointInput14.*C W T
166Block 7_20: Long-timeInput / Output1,008C W T
167Block 7_20: Short-timeInput / Output1,01C W T
168Block 7_20: Actuation positionOutput5,001C T
169Block 7_20: Slat positionOutput5,001C T
170Block 7_20: Movement position
Input5,001C W T
feedback
171Block 7_20: Slat position feedbackInput5,001C W T
172Block 7_20: SafetyOutput 1,002C R T
166Block 7_20: SwitchingOutput1,001C W T
167Block 7_20: Switching feedbackInput1,001C R T
167Block 7_20: DimmingOutput3,007C T
168Block 7_20: Dimmer value in %Input / Output5,001C W T
170Block 7_20: TemperatureInput9,001C W T
No.Name FunctionDPTFlags
171Block 7_20: Air humidityInput9,007C W T
172Block 7_20: CO2Input9,008C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 18
17
No. Name FunctionDPTFlags
172Block 7_20: 2 byte floating pointInput9.*C W T
172Block 7_20: 4 byte floating pointInput14.*C W T
173Block 7_21: Long-timeInput / Output1,008C W T
174Block 7_21: Short-timeInput / Output1,01C W T
175Block 7_21: Actuation positionOutput5,001C T
176Block 7_21: Slat positionOutput5,001C T
177Block 7_21: Movement position
Input5,001C W T
feedback
178Block 7_21: Slat position feedbackInput5,001C W T
179Block 7_21: SafetyOutput 1,002C R T
173Block 7_21: SwitchingOutput1,001C W T
174Block 7_21: Switching feedbackInput1,001C R T
174Block 7_21: DimmingOutput3,007C T
175Block 7_21: Dimmer value in %Input / Output5,001C W T
177Block 7_21: TemperatureInput9,001C W T
178Block 7_21: Air humidityInput9,007C W T
179Block 7_21: CO2Input9,008C W T
179Block 7_21: 2 byte floating pointInput9.*C W T
179Block 7_21: 4 byte floating pointInput14.*C W T
180Block 7_22: Long-timeInput / Output1,008C W T
181Block 7_22: Short-timeInput / Output1,01C W T
182Block 7_22: Actuation positionOutput5,001C T
183Block 7_22: Slat positionOutput5,001C T
184Block 7_22: Movement position
Input5,001C W T
feedback
185Block 7_22: Slat position feedbackInput5,001C W T
186Block 7_22: SafetyOutput 1,002C R T
180Block 7_22: SwitchingOutput1,001C W T
181Block 7_22: Switching feedbackInput1,001C R T
181Block 7_22: DimmingOutput3,007C T
182Block 7_22: Dimmer value in %Input / Output5,001C W T
184Block 7_22: TemperatureInput9,001C W T
185Block 7_22: Air humidityInput9,007C W T
186Block 7_22: CO2Input9,008C W T
186Block 7_22: 2 byte floating pointInput9.*C W T
186Block 7_22: 4 byte floating pointInput14.*C W T
187Block 3_1: SwitchingOutput1,001C W T
188Block 3_1: Switching feedbackInput1,001C R T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 19
18
No. Name FunctionDPTFlags
188Block 3_1: DimmingOutput3,007C T
189Block 3_1: Dimmer value in %Input / Output5,001C W T
187Block 3_1: TemperatureInput9,001C W T
188Block 3_1: Air humidityInput9,007C W T
189Block 3_1: CO2Input9,008C W T
189Block 3_1: 2 byte floating pointInput9.*C W T
189Block 3_1: 4 byte floating pointInput14.*C W T
190Block 3_2: SwitchingOutput1,001C W T
191Block 3_2: Switching feedbackInput1,001C R T
191Block 3_2: DimmingOutput3,007C T
192Block 3_2: Dimmer value in %Input / Output5,001C W T
190Block 3_2: TemperatureInput9,001C W T
191Block 3_2: Air humidityInput9,007C W T
192Block 3_2: CO2Input9,008C W T
192Block 3_2: 2 byte floating pointInput9.*C W T
192Block 3_2: 4 byte floating pointInput14.*C W T
193Block 3_3: SwitchingOutput1,001C W T
194Block 3_3: Switching feedbackInput1,001C R T
194Block 3_3: DimmingOutput3,007C T
195Block 3_3: Dimmer value in %Input / Output5,001C W T
193Block 3_3: TemperatureInput9,001C W T
194Block 3_3: Air humidityInput9,007C W T
195Block 3_3: CO2Input9,008C W T
195Block 3_3: 2 byte floating pointInput9.*C W T
195Block 3_3: 4 byte floating pointInput14.*C W T
196Block 3_4: SwitchingOutput1,001C W T
197Block 3_4: Switching feedbackInput1,001C R T
197Block 3_4: DimmingOutput3,007C T
198Block 3_4: Dimmer value in %Input / Output5,001C W T
196Block 3_4: TemperatureInput9,001C W T
197Block 3_4: Air humidityInput9,007C W T
198Block 3_4: CO2Input9,008C W T
198Block 3_4: 2 byte floating pointInput9.*C W T
198Block 3_4: 4 byte floating pointInput14.*C W T
199Block 3_5: SwitchingOutput1,001C W T
200Block 3_5: Switching feedbackInput1,001C R T
200Block 3_5: DimmingOutput3,007C T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 20
19
No. Name FunctionDPTFlags
201Block 3_5: Dimmer value in %Input / Output5,001C W T
199Block 3_5: TemperatureInput9,001C W T
200Block 3_5: Air humidityInput9,007C W T
201Block 3_5: CO2Input9,008C W T
201Block 3_5: 2 byte floating pointInput9.*C W T
201Block 3_5: 4 byte floating pointInput14.*C W T
202Block 3_6: SwitchingOutput1,001C W T
203Block 3_6: Switching feedbackInput1,001C R T
203Block 3_6: DimmingOutput3,007C T
204Block 3_6: Dimmer value in %Input / Output5,001C W T
202Block 3_6: TemperatureInput9,001C W T
203Block 3_6: Air humidityInput9,007C W T
204Block 3_6: CO2Input9,008C W T
204Block 3_6: 2 byte floating pointInput9.*C W T
204Block 3_6: 4 byte floating pointInput14.*C W T
205Block 3_7: SwitchingOutput1,001C W T
206Block 3_7: Switching feedbackInput1,001C R T
206Block 3_7: DimmingOutput3,007C T
207Block 3_7: Dimmer value in %Input / Output5,001C W T
205Block 3_7: TemperatureInput9,001C W T
206Block 3_7: Air humidityInput9,007C W T
207Block 3_7: CO2Input9,008C W T
207Block 3_7: 2 byte floating pointInput9.*C W T
207Block 3_7: 4 byte floating pointInput14.*C W T
208Block 3_8: SwitchingOutput1,001C W T
209Block 3_8: Switching feedbackInput1,001C R T
209Block 3_8: DimmingOutput3,007C T
210Block 3_8: Dimmer value in %Input / Output5,001C W T
208Block 3_8: TemperatureInput9,001C W T
209Block 3_8: Air humidityInput9,007C W T
210Block 3_8: CO2Input9,008C W T
210Block 3_8: 2 byte floating pointInput9.*C W T
210Block 3_8: 4 byte floating pointInput14.*C W T
211Block 3_9: SwitchingOutput1,001C W T
212Block 3_9: Switching feedbackInput1,001C R T
212Block 3_9: DimmingOutput3,007C T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 21
20
No. Name FunctionDPTFlags
213Block 3_9: Dimmer value in %Input / Output5,001C W T
211Block 3_9: TemperatureInput9,001C W T
212Block 3_9: Air humidityInput9,007C W T
213Block 3_9: CO2Input9,008C W T
213Block 3_9: 2 byte floating pointInput9.*C W T
213Block 3_9: 4 byte floating pointInput14.*C W T
214Block 3_10: SwitchingOutput1,001C W T
215Block 3_10: Switching feedbackInput1,001C R T
215Block 3_10: DimmingOutput3,007C T
216Block 3_10: Dimmer value in %Input / Output5,001C W T
214Block 3_10: TemperatureInput9,001C W T
215Block 3_10: Air humidityInput9,007C W T
216Block 3_10: CO2Input9,008C W T
216Block 3_10: 2 byte floating pointInput9.*C W T
216Block 3_10: 4 byte floating pointInput14.*C W T
217Block 2_1: SwitchingOutput1,001C W T
218Block 2_1: Switching feedbackInput1,001C R T
217Block 2_1: TemperatureInput9,001C W T
218Block 2_1: Air humidityInput9,007C W T
218Block 2_1: 2 byte floating pointInput9.*C W T
218Block 2_1: 4 byte floating pointInput14.*C W T
219Block 2_2: SwitchingOutput1,001C W T
220Block 2_2: Switching feedbackInput1,001C R T
219Block 2_2: TemperatureInput9,001C W T
220Block 2_2: Air humidityInput9,007C W T
220Block 2_2: 2 byte floating pointInput9.*C W T
220Block 2_2: 4 byte floating pointInput14.*C W T
221Block 2_3: SwitchingOutput1,001C W T
222Block 2_3: Switching feedbackInput1,001C R T
221Block 2_3: TemperatureInput9,001C W T
222Block 2_3: Air humidityInput9,007C W T
222Block 2_3: 2 byte floating pointInput9.*C W T
222Block 2_3: 4 byte floating pointInput14.*C W T
223Block 2_4: SwitchingOutput1,001C W T
224Block 2_4: Switching feedbackInput1,001C R T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 22
21
No. Name FunctionDPTFlags
223Block 2_4: TemperatureInput9,001C W T
224Block 2_4: Air humidityInput9,007C W T
224Block 2_4: 2 byte floating pointInput9.*C W T
224Block 2_4: 4 byte floating pointInput14.*C W T
225Block 2_5: SwitchingOutput1,001C W T
226Block 2_5: Switching feedbackInput1,001C R T
225Block 2_5: TemperatureInput9,001C W T
226Block 2_5: Air humidityInput9,007C W T
226Block 2_5: 2 byte floating pointInput9.*C W T
226Block 2_5: 4 byte floating pointInput14.*C W T
227Block 2_6: SwitchingOutput1,001C W T
228Block 2_6: Switching feedbackInput1,001C R T
227Block 2_6: TemperatureInput9,001C W T
228Block 2_6: Air humidityInput9,007C W T
228Block 2_6: 2 byte floating pointInput9.*C W T
228Block 2_6: 4 byte floating pointInput14.*C W T
229Block 2_7: SwitchingOutput1,001C W T
230Block 2_7: Switching feedbackInput1,001C R T
229Block 2_7: TemperatureInput9,001C W T
230Block 2_7: Air humidityInput9,007C W T
230Block 2_7: 2 byte floating pointInput9.*C W T
230Block 2_7: 4 byte floating pointInput14.*C W T
231Block 2_8: SwitchingOutput1,001C W T
232Block 2_8: Switching feedbackInput1,001C R T
231Block 2_8: TemperatureInput9,001C W T
232Block 2_8: Air humidityInput9,007C W T
232Block 2_8: 2 byte floating pointInput9.*C W T
232Block 2_8: 4 byte floating pointInput14.*C W T
233Block 2_9: SwitchingOutput1,001C W T
234Block 2_9: Switching feedbackInput1,001C R T
233Block 2_9: TemperatureInput9,001C W T
234Block 2_9: Air humidityInput9,007C W T
234Block 2_9: 2 byte floating pointInput9.*C W T
234Block 2_9: 4 byte floating pointInput14.*C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 23
22
No. Name FunctionDPTFlags
235Block 2_10: SwitchingOutput1,001C W T
236Block 2_10: Switching feedbackInput1,001C R T
235Block 2_10: TemperatureInput9,001C W T
236Block 2_10: Air humidityInput9,007C W T
236Block 2_10: 2 byte floating pointInput9.*C W T
236Block 2_10: 4 byte floating pointInput14.*C W T
237Block 1_1: TemperatureInput9,001C W T
237Block 1_1: 2 byte floating pointInput9.*C W T
237Block 1_1: 4 byte floating pointInput14.*C W T
238Block 1_2: TemperatureInput9,001C W T
238Block 1_2: 2 byte floating pointInput9.*C W T
238Block 1_2: 4 byte floating pointInput14.*C W T
239Block 1_3: TemperatureInput9,001C W T
239Block 1_3: 2 byte floating pointInput9.*C W T
239Block 1_3: 4 byte floating pointInput14.*C W T
240Block 1_4: TemperatureInput9,001C W T
240Block 1_4: 2 byte floating pointInput9.*C W T
240Block 1_4: 4 byte floating pointInput14.*C W T
241Block 1_5: TemperatureInput9,001C W T
241Block 1_5: 2 byte floating pointInput9.*C W T
241Block 1_5: 4 byte floating pointInput14.*C W T
242Block 1_6: TemperatureInput9,001C W T
242Block 1_6: 2 byte floating pointInput9.*C W T
242Block 1_6: 4 byte floating pointInput14.*C W T
243Block 1_7: TemperatureInput9,001C W T
243Block 1_7: 2 byte floating pointInput9.*C W T
243Block 1_7: 4 byte floating pointInput14.*C W T
244Block 1_8: TemperatureInput9,001C W T
244Block 1_8: 2 byte floating pointInput9.*C W T
244Block 1_8: 4 byte floating pointInput14.*C W T
245Block 1_9: TemperatureInput9,001C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 24
23
No. Name FunctionDPTFlags
245Block 1_9: 2 byte floating pointInput9.*C W T
245Block 1_9: 4 byte floating pointInput14.*C W T
246Block 1_10: TemperatureInput9,001C W T
246Block 1_10: 2 byte floating pointInput9.*C W T
246Block 1_10: 4 byte floating pointInput14.*C W T
247Block 1_11: TemperatureInput9,001C W T
247Block 1_11: 2 byte floating pointInput9.*C W T
247Block 1_11: 4 byte floating pointInput14.*C W T
248Block 1_12: TemperatureInput9,001C W T
248Block 1_12: 2 byte floating pointInput9.*C W T
248Block 1_12: 4 byte floating pointInput14.*C W T
249Block 1_13: TemperatureInput9,001C W T
249Block 1_13: 2 byte floating pointInput9.*C W T
249Block 1_13: 4 byte floating pointInput14.*C W T
250Block 1_14: TemperatureInput9,001C W T
250Block 1_14: 2 byte floating pointInput9.*C W T
250Block 1_14: 4 byte floating pointInput14.*C W T
251Block 1_15: TemperatureInput9,001C W T
251Block 1_15: 2 byte floating pointInput9.*C W T
251Block 1_15: 4 byte floating pointInput14.*C W T
252Block 1_16: TemperatureInput9,001C W T
252Block 1_16: 2 byte floating pointInput9.*C W T
252Block 1_16: 4 byte floating pointInput14.*C W T
253Block 1_17: TemperatureInput9,001C W T
253Block 1_17: 2 byte floating pointInput9.*C W T
253Block 1_17: 4 byte floating pointInput14.*C W T
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 25
24
2.5.Parameter setting
Malfunctions and error messages
Malfunction/Defect of the KNX interface:
•In the display unit of the KNX Interface, the message "KNX interface defect"
is displayed instead of the weather animation.
•No communication with the bus takes place.
•If it is configured in the ETS that the weather data needs to be received from
the bus, a wind or rain alarm is triggered to the controller.
Malfunction/Defect of the controller KNX Interface (KNX interface does not
receive any message from the controller for 30 seconds):
•A fault warning is transmitted to the bus.
Malfunction/Defect of a KNX sensor or actuator that has already been
configured (no data reception):
•In the manual menu of the KNX Interface, the message "No measured values
received" or "Position unknown" or "Defect" is displayed for the bus subscriber.
2.5.1. General settings
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 26
25
Transmission delays after power-up and
programming for:
Weather data5 s • 10 s • 30 s • 1 min • … • 2 h
Functional blocks5 s • 10 s • 30 s • 1 min • … • 2 h
Maximum message rate10 • 20 messages per second
Weather data• do not use
Malfunction objectdo not use • use
Locking object for all outputsdo not use • use
Blocking before 1st communication
(only if the locking object is used for all
outputs)
• send to bus
• receive from bus
not active • active
2.5.2. Wind sensors
In this menu you can set the evaluation of additional wind sensors by the control. A
wind sensor connected directly to the control can transmit data to the bus, a wind
sensor in the bus system can transmit data to the control. The reception of data from
the bus can be monitored. In this case, wind alarm will be triggered if data has not been
received correctly.
Wind speed:
Monitoring time for wind sensors 1...45 s • 10 s • 30 s • 1 min • … • 2 h
Wind sensor 1/2/3/4• do nor use
If the wind sensor is connected directly to the control an transmits on the bus:
Sending behaviour• transmit periodically
on change of
(only if transmitting on change)
Transmit cycle
(only if transmitting periodically)
Use malfunction object verwendenNo • Yes
Wind direction:
• transmits on bus
• receives from bus (without monitoring)
• receives from bus (with monitoring)
• transmit on change
• transmit on change and periodically
0.5 m/s • 1.0 m/s • 2.0 m/s • 5.0 m/s
5 secs • 10 secs • 30 secs • 1 min • … • 2 h
Note: The function „Wind direction: transmits on bus“ is not possible with P03i-GPS
weather station, as wind direction is not detected.
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 27
26
Wind direction• do nor use
on change of
(only if transmitting on change)
Transmit cycle
(only if transmitting periodically)
Use malfunction object verwendenNo • Yes
[• transmits on bus]
• receives from bus (without monitoring)
• receives from bus (with monitoring)
0.5 m/s • 1.0 m/s • 2.0 m/s • 5.0 m/s
5 secs • 10 secs • 30 secs • 1 min • … • 2 h
If the wind direction sensor is connected directly to the control and transmits on the
bus:
Sending behaviour• transmit periodically
on change of
(only if transmitting on change)
Transmit cycle
(only if transmitting periodically)
Use malfunction object verwendenNo • Yes
• transmit on change
• transmit on change and periodically
0.5 m/s • 1.0 m/s • 2.0 m/s • 5.0 m/s
5 secs • 10 secs • 30 secs • 1 min • … • 2 h
If the reception of the wind direction from the bus is monitored:
Monitoring time
of wind direction sensor
5 secs • 10 secs • 30 secs • 1 min • … • 2 h
2.5.3. Weather data
The menu point appears only if weather data needs to be transmitted on the bus or
received from it.
Weather data is transmitted on the bus
In "General Settings", the option selected is:
Weather datasend to bus
Date and time• do not transmit
Transmit cycle
(only if "periodically" is selected)
Location coordinates• do not transmit
On change of
(only if "on change" is selected)
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 29
28
Brightness measurement value• do not transmit
On change of
(only if "on change" is selected)
Transmit cycle
(only if "periodically" is selected)
• transmit periodically
• transmit on change
• transmit on change and periodically
2% • 5% • 10% • 25% • 50%
5 s • 10 s • 30 s • 1 min • … • 2 h
Weather data is received from the bus
In "General Settings", the option selected is:
Weather datareceive from bus
Set the monitoring of the wind and rain objects:
Use monitoring of wind and rain objectsNo • Yes
Monitoring period for wind object5 s • 10 s • 30 s • 1 min • … • 2 h
Monitoring period for rain object5 s • 10 s • 30 s • 1 min • … • 2 h
If the KNX Interface does not receive any wind measured value or the precipitation
status, a wind alarm or rain alarm is triggered to the controller. Drives with appropriate
automatic settings for wind or rain protection then move to the safe position.
No date / time (KNX Interface is not receiving any time information from the bus
after start-up/reset):
•In the display unit of the KNX Interface, the message "Please set the time" is
displayed instead of the weather animation.
No weather data (KNX Interface is not receiving any weather data from the bus
after start-up/reset):
•In the display unit of the KNX Interface, the message "No link to the weather
station" is displayed instead of the weather animation.
•There is no automatic control active and the wind and rain alarms are
cautiously active, i.e. drives with the appropriate settings for wind and rain
protection move to the safe position.
•The normal automatic mode of operation is restored only if all the weather data
has been received (brightness value, wind value, precipitation status and value
of outdoor temperature).
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 30
2.5.4. Functional blocks
29
Sending behaviour of safety objects• on change
Transmit cycle
(only if "periodically" is selected)
Use blocks with 7 objectsNo • Yes
Use blocks with 3 objectsNo • Yes
Use blocks with 2 objectsNo • Yes
Use blocks with 1 objectNo • Yes
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
5 s • 10 s • 30 s • 1 min • … • 2 h
Blocks with 7 objects
The menu point appears only if the option that blocks with 7 objects should be used
has been selected with "Functional blocks".
The data for awnings, blinds, shutters, windows and Elsner electronic ceiling fans
WL305/610 is transmitted with the help of these 22 blocks. The blocks are also suitable
for light, dimmers, buttons, 3-way combination sensors (temperature, humidity and
CO2), thermal hygrometer, temperature sensors and floating point values.
In "Functional Blocks", the option selected is:
Use blocks with 7 objectsYes
Block 7_1
… Block 7_22
• Do not use
• Output: Blind
• Output: Awning
• Output: Shutters
• Output: Windows
• Output: Sliding window
• Output: Step window
• Output: Light switchable
• Output: Light dimmable
• Input: Up/down key
• Input: On/Off key
• Input: Temperature
• Input: Temperature, humidity
• Input: Temperature, humidity, CO2
• Input: 2 byte floating point
• Input: 4 byte floating point
• Fan WL305/610
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 31
30
Bus communication of wireless ventilation units
If wireless ventilation units are switched to level 1 of air extraction, the flap is open but
the blower stands still. Air extraction level = 12.5% is transmit on the bus.
The menu point appears only if the option that blocks with 3 objects should be used
has been selected with "Functional blocks".
The data for dimmers and 3-way combination sensors (temperature, humidity and
CO2) is transmitted with the help of these 10 blocks. The blocks are also suitable for
light, buttons, thermal hygrometer, temperature sensors and floating point values.
In "Functional Blocks", the option selected is:
Use blocks with 3 objectsYes
Block 3_1
… Block 3_10
• Do not use
• Output: Light switchable
• Output: Light dimmable
• Input: Up/down key
• Input: On/Off key
• Input: Temperature
• Input: Temperature, humidity
• Input: Temperature, humidity, CO2
• Input: 2 byte floating point
• Input: 4 byte floating point
Blocks with 2 objects
The menu point appears only if the option that blocks with 2 objects should be used
has been selected with "Functional blocks".
The data for light, buttons and the thermal hygrometer is transmitted with the help of
these 10 blocks. The blocks are also suitable for temperature sensors and floating point
values.
In "Functional Blocks", the option selected is:
Use blocks with 2 objectsYes
Block 2_1
… Block 2_10
• Do not use
• Output: Light switchable
• Input: Up/down key
• Input: On/Off key
• Input: Temperature
• Input: Temperature, humidity
• Input: 2 byte floating point
• Input: 4 byte floating point
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 32
31
Blocks with 1 object
The menu point appears only if the option that blocks with 1 object should be used has
been selected with "Functional blocks".
The data for temperature sensors and floating point values is transmitted with the help
of these 17 blocks.
In "Functional Blocks", the option selected is:
Use blocks with 1 objectYes
Block 1_1
… Block 1_17
• Do not use
• Input: Temperature
• Input: 2 byte floating point
• Input: 4 byte floating point
KNX Interface for WS1000 • Status: 15.04.2016 • Errors excepted. Subject to technical changes.
Page 33
Elsner Elektronik GmbH Control and Automation Technology
Sohlengrund 16
75395 Ostelsheim Phone +49(0) 7033 /30 945-0 info@elsner-elektronik.de
Germany Fax +49(0) 70 33/ 30 945-20 www.elsner-elektronik.de
Technical support: +49 (0) 70 33 / 30 945-250
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.