Elsner Suntracer KNX sl Installation And Adjustment Manual

Installation and Adjustment
EN
Suntracer KNX sl
Weather Station
Item number 70154
1 Contents
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Weather Station Suntracer KNX sl • from software version 1.00, ETS programme version 1.0
Status: 14.07.2016 • Errors excepted. Subject to technical changes.
1. Description ........................................................................................... 5
1.0.1. Deliverables ................................................................................................... 6
1.1. Technical specification ............................................................................................. 6
2. Installation and start-up ....................................................................... 7
2.1. Installation notes ...................................................................................................... 7
2.2. Installation location .................................................................................................. 8
2.3. Device design ......................................................................................................... 10
2.4. Installing the weather station ................................................................................ 10
2.4.1. Preparation for installation ........................................................................ 11
2.4.2. Fitting the lower part with mounting ........................................................ 11
2.4.3. Connection .................................................................................................. 13
2.4.4. Closing the installation ............................................................................... 14
2.5. Instructions for assembly and initial start-up ...................................................... 14
3. Addressing the equipment ................................................................. 15
4. Maintenance ....................................................................................... 15
5. Transfer protocol ............................................................................... 17
5.1. List of all communications objects ....................................................................... 17
6. Parameter setting .............................................................................. 57
6.0.1. Behaviour on power failure/power restoration ........................................ 57
6.0.2. Storage of threshold values ....................................................................... 57
6.0.3. Malfunction objects .................................................................................... 57
6.1. General settings ..................................................................................................... 57
6.1.1. GPS .............................................................................................................. 58
6.2. Location ................................................................................................................... 58
6.3. Rain .......................................................................................................................... 61
6.4. Temperature measurement value ........................................................................ 62
6.5. Temperature threshold values .............................................................................. 62
6.5.1. Temperature threshold value 1-4 .............................................................. 63
6.6. Frost alarm .............................................................................................................. 65
6.7. Brightness measurement value ............................................................................ 65
6.8. Brightness threshold values .................................................................................. 66
6.8.1. Brightness threshold value 1-4 .................................................................. 66
6.9. Twilight brightness threshold values ................................................................... 68
6.9.1. Twilight threshold value 1-4 ...................................................................... 68
6.10.Night ....................................................................................................................... 70
6.11.Sun position ........................................................................................................... 71
6.12.Wind measurement ............................................................................................... 71
6.13.Wind threshold values ........................................................................................... 72
6.13.1. Wind threshold value 1-4 ........................................................................... 73
6.14.Air pressure measurement ................................................................................... 75
6.15.Air pressure threshold values ............................................................................... 76
6.15.1. Air pressure threshold value 1-4 ............................................................... 76
6.16.Summer Compensation ........................................................................................ 78
6.17.Optimal usage of façade controller functions ..................................................... 79
2 Contents
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Weather Station Suntracer KNX sl • from software version 1.00, ETS programme version 1.0
Status: 14.07.2016 • Errors excepted. Subject to technical changes.
6.17.1. Classifying the façades for the control unit .............................................. 79
6.17.2. Orientation and inclination of the façade ................................................. 80
6.17.3. Shadow edge tracking and slat tracking ................................................... 81
6.17.4. Slat types and determination of width and spacing ................................ 82
6.17.5. Slat position for horizontal slats ................................................................ 83
6.17.6. Slat position for vertical slats .................................................................... 85
6.18.Simulation .............................................................................................................. 86
6.19.Status output .......................................................................................................... 87
6.20.Façade setting ........................................................................................................ 88
6.20.1. Façade safety ............................................................................................... 94
6.20.2. Façade automation ..................................................................................... 97
6.20.3. Computer ................................................................................................... 110
6.20.4. Computers 1-8 ........................................................................................... 110
6.21.Weekly timer ........................................................................................................ 113
6.21.1. Weekly timer period 1-24 ......................................................................... 114
6.22.Calendar timer ...................................................................................................... 115
6.22.1. Calendar clock Period 1-4 ......................................................................... 115
6.23.Logic ...................................................................................................................... 117
6.23.1. AND logic 1-8 and OR logic outputs 1-8 ................................................. 117
6.23.2. AND logic connection inputs ................................................................... 119
6.23.3. Connection inputs of the OR logic ........................................................... 122
3 Clarification of signs
This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to­date version of the manual is available.
Clarification of signs used in this manual
Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician.
Safety advice.
Safety advice for working on electrical connections, components, etc.
DANGER!
... indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided.
WARNING!
... indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided.
CAUTION!
... indicates a potentially hazardous situation which may lead to trivial or minor injuries if it is not avoided.
ATTENTION!
... indicates a situation which may lead to damage to property if it is not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.
4 Clarification of signs
5 Description
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
1. Description
The Weather Station Suntracer KNX sl for the KNX building bus system measures temperature, wind speed, brightness and air pressure. It recognises precipitation and receives the GPS signal for time and location. In addition, using location coordinates and the time, it calculates the exact position of the sun (azimuth and elevation).
All values can be used for the control of limit dependent switching outputs. States can be linked via AND logic gates and OR logic gates. Multi-function modules change input data as required by means of calculations, querying a condition, or converting the data point type. The integrated shade control system allows intelligent sun protection control of up to 8 façades.
The compact housing of the Suntracer KNX sl accommodates the sensors, evalua­tion circuits and bus-coupling electronics.
Functions:
Brightness measurement (current light strength)
GPS receiver, outputting the current time and location coordinates. The Weather Station Suntracer KNX sl also computes the position of the sun (azimuth and elevation)
Shade control for up to 8 façades with slat tracking and shadow edge tracking
Wind measurement: The wind strength is measured electronically and thus noiselessly and reliably, even during hail, snow and sub-zero temperatures. Even turbulent air and rising winds in the vicinity of the device are recorded
Precipitation detection: The sensor surface is heated, so that only drops and flakes are recognised as precipitation, but not mist or dew. When the rain or snow stops, the sensor is soon dry again and the precipitation warning ends
Temperature measurement
Frost protection for shading systems
Air pressure measurement
Weekly and calendar time switch: All time switching outputs can be used as communication objects. The weekly time switch has 24 periods. Each period can be configured either as an output or as an input. If the period is an output, then the switching time is set per parameter or per communication object. The calendar time switch has 4 periods. Two on/off switching operations, which are executed daily, can be set for each period
Switching outputs for all measured and computed values. Threshold values can be adjusted per parameter or via communication objects
8 AND and 8 OR logic gates, each with 4 inputs. All switching events as well as 16 logic inputs (in the form of communications objects) can be used as inputs for the logic gates. The output of each gate can be configured optionally as 1-bit or 2 x 8-bit
8 multi-function modules (computers) for changing the input data by calculations, by querying a condition or by converting the data point type
6 Description
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
Summer compensation for cooling systems. A characteristic curve matches the target temperature in the room to the external temperature and sets the minimum and maximum target temperature values.
Configuration is made using the KNX software ETS. The product file can be down­loaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser­vice” menu.
1.0.1. Deliverables
Weather station
Stainless steel installation band for pole installation
4×50 mm stainless steel roundhead screws and 6×30 mm dowels for wall mounting. Use fixing materials that are suitable for the base!
1.1. Technical specification
Housing Plastic
Colour White / Translucent
Assembly Surface mount
Protection category IP 44
Dimensions approx. 62 × 71 × 145 (W × H × D, mm)
Weight approx. 85 g
Ambient temperature Operation -30…+50°C, storage -30…+70°C
Auxiliary supply 12…40 V DC, 12…28 V AC. An appropriate power sup-
ply unit can be purchased from Elsner Elektronik.
Auxiliary current at 12V DC: max. 185 mA
at 24V DC: max. 90 mA at 24V AC: max. 82 mA
Bus current max. 10 mA
Data output KNX +/-
BCU type Integrated microcontroller
PEI type 0
Group addresses max. 2000
Assignments max. 2000
Communication objects 1387
Temperature sensor:
Measurement range -30°C … +50°C
Resolution 0.1°C
Accuracy ±0.5°C at -30°C … +25°C
±1.5°C at -30°C … +45°C
Wind sensor:
Measurement range 0 m/s … 35 m/s
Resolution 0.1 m/s
7 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
The product conforms with the provisions of EU directives.
2. Installation and start-up
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should only be performed by an electrician.
CAUTION! Live voltage!
There are unprotected live components inside the device.
National legal regulations are to be followed.
Ensure that all lines to be assembled are free of voltage and take precautions against accidental switching on.
Do not use the device if it is damaged.
Take the device or system out of service and secure it against unintentional use, if it can be assumed, that risk-free operation is no longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage. If it has been damaged in transport, inform the supplier immediately.
Accuracy ±15% of the measurement value when incoming flow
is 45°…315° (Frontal incoming flow corresponds to 180°)
Pressure sensor:
Measurement range 300 mbar … 1100 mbar
Resolution 0.1 mbar
Accuracy ±4 mbar
Brightness sensor:
Measurement range 0 lux … 150,000 lux
Resolution 1 lux at 0…255 lux
4 lux at 256…2,645 lux 163 lux at 2,646…128,256 lux 762 lux at 128,257…150,000 lux
Accuracy ±15% of the measurement value at 35 lux … 150,000
lux
8 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
The device may only be used as a fixed-site installation; that means only when assem­bled and after conclusion of all installation and operational start-up tasks and only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.
2.2. Installation location
Select an installation position on the building where the sensors can measure wind, rain and sunshine without hindrance. No structural elements should be mounted above the weather station, from which water could continue to drop on the precipita­tion sensor even after it has stopped raining or snowing. The weather station should not be shaded by structures or, for example, trees.
At least 60 cm of clearance must be left around the device. This facilitates correct wind speed measurement without eddies. At the same time, this prevents spray (raindrops hitting the device) or snow (snow penetration) from impairing the measurement. This also prevents birds from biting it.
Please ensure that the extended awning does not cast shade on the unit, and that it is protected from the wind.
Temperature measurements can also be distorted by external influences such as warming or cooling of the building structure on which the sensor is mounted (sunlight, heating or cold water pipes). Temperature variations from such sources of interference must be corrected in the ETS in order to ensure the specified accuracy of the sensor (temperature offset).
Magnetic fields, transmitters and interference fields from electrical consumers (e.g. flu­orescent lamps, neon signs, switch mode power supplies etc.) can block or interfere with the reception of the GPS signal.
Fig. 1 There must be at least 60 cm clearance to oth­er elements (structures, construction parts, etc.) below, to the sides and in front of the de­vice.
60 cm
9 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
Fig. 2 The device must be attached to a vertical wall (or a pole).
wall or pole
90°
Fig. 3 The device must be mounted in the horizontal (transverse) direction.
Horizontal
Fig. 4 For installation in the northern hemisphere, the device must be aligned to face south.
For installation in the southern hemisphere, the device must be aligned to face north.
North
South
10 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
2.3. Device design
2.4. Installing the weather station
ATTENTION!
Even a few drops of water can damage the device electronics.
Do not open the device if water (e.g. rain) can get into it.
1
Fig. 5 1 GPS receiver in lid 2 Programming LED 3 Brightness measurement 4 Precipitation sensor in lid 5 Temperature measurement 6 Wind measurement 7 Programming key on the underside of the housing (recessed),see Addressing the
equipment, page 15
8 Air pressure sensor in housing
ATTENTION!
Sensitive wind sensor.
Remove the protective transport sticker after installation.
Do not touch the sensor on the wind measuring element (no. 6).
5
6
8
2
3
4
7
11 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
2.4.1. Preparation for installation
2.4.2. Fitting the lower part with mounting
Now, first of all, assemble the lower part of the housing with the integrated mounting for wall or pole installation.
Wall installation
Use fixing materials (dowels, screws) that are suitable for the base.
Fig. 6 Slacken both screws on the lid (top) and low­er part (bottom) with a Phillips screwdriver.
Fig. 7 Pull the lid and lower part completely apart. This also releases the plug-in connection be­tween the board in the lid and the socket in the lower part.
Fig. 8 The device is installed with two screws. Break off the two longitudinal holes in the lower part of the housing.
Longitudinal holes
12 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
Drilling plan
ATTENTION! The printout of the data sheet does not have original size! A separate, di­mensionally correct drilling plan is included ex works and this can be used as a tem­plate.
Fig. 9 a+b a) If the power lead is to be hidden when in-
stalled, it must emerge from the wall in the vicinity of the rear of the housing (marked area).
b) If the power lead is to be surface-mount-
ed, the cable guide is broken off. The lead is then fed into the device at the under­side of the housing.
Cable guide
Fig. 10 Feed the power lead through the rubber gas­ket.
Rubber gasket
13 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
Pole installation
The device is installed on the pole with the enclosed stainless steel mounting band.
2.4.3. Connection
The connector is in the lower part of the housing.
Fig. 11 Dimensions in mm. Variations are possible for technical reasons
A/B2× longitudinal holes 8 mm ×
5.5 mm
C Position of the cable outlet (rub-
ber gasket) in the housing
AB
C
Fig. 12 Feed the mounting band through the eyelets in the lower part of the housing.
Fig. 13 Break the cable guide off.
Feed the power lead through the rubber gas­ket.
Cable guide
Rubber gasket
14 Installation and start-up
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
2.4.4. Closing the installation
2.5. Instructions for assembly and initial start-up
Remove all transport protection stickers present after installation.
The wind measurement value and thus also all wind switching outputs cannot be out­put until 35 seconds after the power is turned on.
Fig. 14 Connect KNX data (+|-) and power supply (12…40V DC, 12…28V AC, 1|2) to the connector.
The terminal assignment of the power supply is polarity-independent.
-+12
-+12
KNX Voltage
Fig. 15 Push the lid on the lower part. This also makes the plug-in connection between the board in the lid and the socket in the lower part.
Fig. 16 Screw the lid (top) and lower part (bottom) to­gether.
15 Addressing the equipment
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
After the auxiliary voltage has been applied, the device will enter an initialisation phase lasting a few seconds. During this phase no information can be received or sent via the bus.
3. Addressing the equipment
The equipment is delivered ex works with the bus address 15.15.250. You program a different address in the ETS by overwriting the address 15.15.250 or teach the device using the programming button.
The programming button can be reached through the opening on the underside of the housing; it is recessed by approx. 15 mm. Use a thin object to reach the key, e. g. a
1.5 mm² wire.
4. Maintenance
WARNING! Risk of injury caused by components moved automatically!
The automatic control can start system components and place people in danger (e.g. moving windows/awnings if a rain/wind alarm has been triggered while cleaning).
Always isolate the device from the mains for servicing and cleaning.
1 2
Fig. 17 1 Programming button for teaching the device 2 Programming LED (under the semi-transparent lid)
16 Maintenance
Weather Station Suntracer KNX sl • Status: 14.07.2016 • Errors excepted. Subject to technical changes.
The device must regularly be checked for dirt twice a year and cleaned if necessary. In case of severe dirt, the sensor may not work properly anymore.
ATTENTION
The device can be damaged if water penetrates the housing.
Do not clean with high pressure cleaners or steam jets.
17 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
5. Transfer protocol
Units:
Temperatures in degrees Celsius Brightness in Lux Wind in metres per second Air pressure in Pascal Azimuth and elevation in degrees
5.1. List of all communications objects
Abbreviation flags:
C Communication R Read WWrite T Transmit UUpdate
No. Text Function Flags DPT type Size
1 Software version Output R-CT [217.1] DPT_Version 2 bytes
21 Signal LED object 1s cycle Input -WC- [1.1] DPT_Switch 1 bit
22 Signal LED object 4s cycle Input -WC- [1.1] DPT_Switch 1 bit
24 GPS malfunction (0 : OK | 1: NOK) Output R-CT [1.2] DPT_Bool 1 bit
25 Date / time Output RWCT [19.1] DPT_DateTime 8 bytes
26 Date Output RWCT [11.1] DPT_Date 3 bytes
27 Time Output RWCT [10.1] DPT_TimeOfDay 3 bytes
28 Date and time query Input -WC- [1.017] DPT_Trigger 1 bit
30 Location: Northern latitude [°] Output R-CT [14.7] DPT_Value_An-
gleDeg
4 bytes
31 Location: Eastern longitude [°] Output R-CT [14.7] DPT_Value_An-
gleDeg
4 bytes
34 Rain: Switching output Output R-CT [1.1] DPT_Switch 1 bit
35 Rain: Switching output with fixed
delays
Output R-CT [1.1] DPT_Switch 1 bit
36 Rain: Switching delay to rain Input -WC- [7,005] DPT_TimePeri-
odSec
2 bytes
37 Rain: Switching delay to no rain Input -WC- [7,005] DPT_TimePeri-
odSec
2 bytes
41 Temperature sensor: Malfunction Output R-CT [1.1] DPT_Switch 1 bit
42 Temperature sensor: External meas-
urement
Input -WCT [9.1] DPT_Value_Temp 2 bytes
43 Temperature sensor: Measurement
value
Output R-CT [9.1] DPT_Value_Temp 2 bytes
44 Temperature sensor: Total measure-
ment
Output R-CT [9.1] DPT_Value_Temp 2 bytes
45 Temperature sensor: Min./Max. meas-
urement query
Input -WC- [1.017] DPT_Trigger 1 bit
18 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
46 Temperature sensor: Minimum meas-
urement
Output R-CT [9.1] DPT_Value_Temp 2 bytes
47 Temperature sensor: Maximum meas-
urement
Output R-CT [9.1] DPT_Value_Temp 2 bytes
48 Temperature sensor: Min./Max. meas-
urement reset
Input -WC- [1.017] DPT_Trigger 1 bit
51 Temp. threshold value 1: Absolute
value
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
52 Temp. threshold value 1: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
53 Temp. threshold value 1: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
54 Temp. threshold value 1: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
55 Temp. threshold value 1: Switching
output
Output R-CT [1.1] DPT_Switch 1 bit
56 Temp. threshold value 1: Switching
output block
Input -WC- [1.1] DPT_Switch 1 bit
58 Temp. threshold value 2: Absolute
value
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
59 Temp. threshold value 2: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
60 Temp. threshold value 2: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
61 Temp. threshold value 2: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
62 Temp. threshold value 2: Switching
output
Output R-CT [1.1] DPT_Switch 1 bit
63 Temp. threshold value 2: Switching
output block
Input -WC- [1.1] DPT_Switch 1 bit
65 Temp. threshold value 3: Absolute
value
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
66 Temp. threshold value 3: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
67 Temp. threshold value 3: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
68 Temp. threshold value 3: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
69 Temp. threshold value 3: Switching
output
Output R-CT [1.1] DPT_Switch 1 bit
70 Temp. threshold value 3: Switching
output block
Input -WC- [1.1] DPT_Switch 1 bit
72 Temp. threshold value 4: Absolute
value
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
73 Temp. threshold value 4: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
74 Temp. threshold value 4: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
75 Temp. threshold value 4: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
76 Temp. threshold value 4: Switching
output
Output R-CT [1.1] DPT_Switch 1 bit
No. Text Function Flags DPT type Size
19 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
77 Temp. threshold value 4: Switching
output block
Input -WC- [1.1] DPT_Switch 1 bit
81 Frost alarm Output R-CT [1.1] DPT_Switch 1 bit
95 Brightness sensor measurement Output R-CT [9.4] DPT_Value_Lux 2 bytes
96 Brightness sensor 2 measurement Output R-CT [9.4] DPT_Value_Lux 2 bytes
97 Brightness sensor 3 measurement Output R-CT [9.4] DPT_Value_Lux 2 bytes
98 Total brightness measurement Output R-CT [9.4] DPT_Value_Lux 2 bytes
101 Brightness sensor threshold value 1:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
102 Brightness sensor threshold value 1:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
103 Brightness sensor threshold value 1:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
104 Brightness sensor threshold value 1:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
105 Brightness sensor threshold value 1:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
106 Brightness sensor threshold value 1:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
108 Brightness sensor threshold value 2:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
109 Brightness sensor threshold value 2:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
110 Brightness sensor threshold value 2:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
111 Brightness sensor threshold value 2:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
112 Brightness sensor threshold value 2:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
113 Brightness sensor threshold value 2:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
115 Brightness sensor threshold value 3:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
116 Brightness sensor threshold value 3:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
117 Brightness sensor threshold value 3:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
118 Brightness sensor threshold value 3:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
119 Brightness sensor threshold value 3:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
120 Brightness sensor threshold value 3:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
122 Brightness sensor threshold value 4:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
123 Brightness sensor threshold value 4:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
No. Text Function Flags DPT type Size
20 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
124 Brightness sensor threshold value 4:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
125 Brightness sensor threshold value 4:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
126 Brightness sensor threshold value 4:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
127 Brightness sensor threshold value 4:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
129 Brightness sensor 2 threshold value 1:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
130 Brightness sensor 2 threshold value 1:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
131 Brightness sensor 2 threshold value 1:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
132 Brightness sensor 2 threshold value 1:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
133 Brightness sensor 2 threshold value 1:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
134 Brightness sensor 2 threshold value 1:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
136 Brightness sensor 2 threshold value 2:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
137 Brightness sensor 2 threshold value 2:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
138 Brightness sensor 2 threshold value 2:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
139 Brightness sensor 2 threshold value 2:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
140 Brightness sensor 2 threshold value 2:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
141 Brightness sensor 2 threshold value 2:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
143 Brightness sensor 2 threshold value 3:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
144 Brightness sensor 2 threshold value 3:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
145 Brightness sensor 2 threshold value 3:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
146 Brightness sensor 2 threshold value 3:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
147 Brightness sensor 2 threshold value 3:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
148 Brightness sensor 2 threshold value 3:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
150 Brightness sensor 2 threshold value 4:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
151 Brightness sensor 2 threshold value 4:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
No. Text Function Flags DPT type Size
21 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
152 Brightness sensor 2 threshold value 4:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
153 Brightness sensor 2 threshold value 4:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
154 Brightness sensor 2 threshold value 4:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
155 Brightness sensor 2 threshold value 4:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
157 Brightness sensor 3 threshold value 1:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
158 Brightness sensor 3 threshold value 1:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
159 Brightness sensor 3 threshold value 1:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
160 Brightness sensor 3 threshold value 1:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
161 Brightness sensor 3 threshold value 1:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
162 Brightness sensor 3 threshold value 1:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
164 Brightness sensor 3 threshold value 2:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
165 Brightness sensor 3 threshold value 2:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
166 Brightness sensor 3 threshold value 2:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
167 Brightness sensor 3 threshold value 2:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
168 Brightness sensor 3 threshold value 2:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
169 Brightness sensor 3 threshold value 2:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
171 Brightness sensor 3 threshold value 3:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
172 Brightness sensor 3 threshold value 3:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
173 Brightness sensor 3 threshold value 3:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
174 Brightness sensor 3 threshold value 3:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
175 Brightness sensor 3 threshold value 3:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
176 Brightness sensor 3 threshold value 3:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
178 Brightness sensor 3 threshold value 4:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
179 Brightness sensor 3 threshold value 4:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
No. Text Function Flags DPT type Size
22 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
180 Brightness sensor 3 threshold value 4:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
181 Brightness sensor 3 threshold value 4:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
182 Brightness sensor 3 threshold value 4:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
183 Brightness sensor 3 threshold value 4:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
185 Total brightness threshold value 1:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
186 Total brightness threshold value 1:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
187 Total brightness threshold value 1:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
188 Total brightness threshold value 1:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
189 Total brightness threshold value 1:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
190 Total brightness threshold value 1:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
192 Total brightness threshold value 2:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
193 Total brightness threshold value 2:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
194 Total brightness threshold value 2:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
195 Total brightness threshold value 2:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
196 Total brightness threshold value 2:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
197 Total brightness threshold value 2:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
199 Total brightness threshold value 3:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
200 Total brightness threshold value 3:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
201 Total brightness threshold value 3:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
202 Total brightness threshold value 3:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
203 Total brightness threshold value 3:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
204 Total brightness threshold value 3:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
206 Total brightness threshold value 4:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
207 Total brightness threshold value 4:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
No. Text Function Flags DPT type Size
23 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
208 Total brightness threshold value 4:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
209 Total brightness threshold value 4:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
210 Total brightness threshold value 4:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
211 Total brightness threshold value 4:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
213 Twilight brightness threshold value 1:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
214 Twilight brightness threshold value 1:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
215 Twilight brightness threshold 1: delay
from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
216 Twilight brightness threshold 1: delay
from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
217 Twilight brightness threshold value 1:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
218 Twilight brightness threshold value 1:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
220 Twilight brightness threshold value 2:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
221 Twilight brightness threshold value 2:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
222 Twilight brightness threshold 2: delay
from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
223 Twilight brightness threshold 2: delay
from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
224 Twilight brightness threshold value 2:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
225 Twilight brightness threshold value 2:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
227 Twilight brightness threshold value 3:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
228 Twilight brightness threshold value 3:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
229 Twilight brightness threshold 3: delay
from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
230 Twilight brightness threshold 3: delay
from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
231 Twilight brightness threshold value 3:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
232 Twilight brightness threshold value 3:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
234 Twilight brightness threshold value 4:
Absolute value
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
235 Twilight brightness threshold value 4:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
No. Text Function Flags DPT type Size
24 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
236 Twilight brightness threshold 4: delay
from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
237 Twilight brightness threshold 4: delay
from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
238 Twilight brightness threshold value 4:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
239 Twilight brightness threshold value 4:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
251 Night: Switching output Output R-CT [1.1] DPT_Switch 1 bit
252 Night: Switching delay on night Input -WC- [7,005] DPT_TimePeri-
odSec
2 bytes
253 Night: Switching delay on day Input -WC- [7,005] DPT_TimePeri-
odSec
2 bytes
261 Sun position: Azimuth Output R-CT [14.7] DPT_Value_An-
gleDeg
4 bytes
262 Sun position: Elevation Output R-CT [14.7] DPT_Value_An-
gleDeg
4 bytes
263 Sun position: Azimuth Output R-CT [9] 9.xxx 2 bytes
264 Sun position: Elevation Output R-CT [9] 9.xxx 2 bytes
271 Wind sensor: Malfunction Output R-CT [1.1] DPT_Switch 1 bit
272 Wind sensor: Measurement [m/s] Output R-CT [9.5] DPT_Value_Wsp 2 bytes
273 Wind sensor: Measurement [Beaufort] Output R-CT [20.014] DPT_Beau-
fort_Wind_Force_S­cale
1 byte
274 Wind sensor: Max. query measure-
ment
Input -WC- [1.017] DPT_Trigger 1 bit
275 Wind sensor: Maximum measurement
[m/s]
Output R-CT [9.5] DPT_Value_Wsp 2 bytes
276 Wind sensor: Maximum measurement
[Beaufort]
Output R-CT [20.014] DPT_Beau-
fort_Wind_Force_S­cale
1 byte
277 Wind sensor: Max. reset measurement Input -WC- [1.017] DPT_Trigger 1 bit
281 Wind threshold value 1: Absolute value Input/
Output
RWCT [9.5] DPT_Value_Wsp 2 bytes
282 Wind threshold value 1: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
283 Wind threshold value 1: Delay from
0to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
284 Wind threshold value 1: Delay from
1to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
285 Wind threshold value 1: Switching out-
put
Output R-CT [1.1] DPT_Switch 1 bit
286 Wind threshold value 1: Switching out-
put block
Input -WC- [1.1] DPT_Switch 1 bit
287 Wind threshold value 2: Absolute value Input/
Output
RWCT [9.5] DPT_Value_Wsp 2 bytes
288 Wind threshold value 2: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
289 Wind threshold value 2: Delay from
0to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
No. Text Function Flags DPT type Size
25 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
290 Wind threshold value 2: Delay from
1to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
291 Wind threshold value 2: Switching
output
Output R-CT [1.1] DPT_Switch 1 bit
292 Wind threshold value 2: Switching
output block
Input -WC- [1.1] DPT_Switch 1 bit
293 Wind threshold value 3: Absolute value Input/
Output
RWCT [9.5] DPT_Value_Wsp 2 bytes
294 Wind threshold value 3: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
295 Wind threshold value 3: Delay from
0to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
296 Wind threshold value 3: Delay from
1to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
297 Wind threshold value 3: Switching out-
put
Output R-CT [1.1] DPT_Switch 1 bit
298 Wind threshold value 3: Switching out-
put block
Input -WC- [1.1] DPT_Switch 1 bit
299 Wind threshold value 4: Absolute value Input/
Output
RWCT [9.5] DPT_Value_Wsp 2 bytes
300 Wind threshold value 4: (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
301 Wind threshold value 4: Delay from
0to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
302 Wind threshold value 4: Delay from
1to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
303 Wind threshold value 4: Switching
output
Output R-CT [1.1] DPT_Switch 1 bit
304 Wind threshold value 4: Switching
output block
Input -WC- [1.1] DPT_Switch 1 bit
401 Sensor air pressure: Malfunction Output R-CT [1.1] DPT_Switch 1 bit
402 Sensor air pressure: Normal measure-
ment [Pa]
Output R-CT [14.58] DPT_Value_-
Pressure
4 bytes
403 Sensor air pressure: Barometric meas-
urement [Pa]
Output R-CT [14.58] DPT_Value_-
Pressure
4 bytes
404 Sensor air pressure: Min./Max. meas-
urement query
Input -WC- [1.017] DPT_Trigger 1 bit
405 Sensor air pressure: Min. normal
measurement [Pa]
Output R-CT [14.58] DPT_Value_-
Pressure
4 bytes
406 Sensor air pressure: Min. barometric
measurement [Pa]
Output R-CT [14.58] DPT_Value_-
Pressure
4 bytes
407 Sensor air pressure: Max. normal
measurement [Pa]
Output R-CT [14.58] DPT_Value_-
Pressure
4 bytes
408 Sensor air pressure: Max. barometric
measurement [Pa]
Output R-CT [14.58] DPT_Value_-
Pressure
4 bytes
409 Sensor air pressure: Min./Max. meas-
urement reset
Input -WC- [1.017] DPT_Trigger 1 bit
410 Sensor air pressure: Pressure range
text
Output R-CT [16.0] DPT_String_AS-
CII
14 bytes
411 Air pressure threshold value 1:
Absolute value
Input/ Output
RWCT [14.58] DPT_Value_-
Pressure
4 bytes
No. Text Function Flags DPT type Size
26 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
412 Air pressure threshold value 1:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
413 Air pressure threshold value 1:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
414 Air pressure threshold value 1:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
415 Air pressure threshold value 1:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
416 Air pressure threshold value 1:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
417 Air pressure threshold value 2:
Absolute value
Input/ Output
RWCT [14.58] DPT_Value_-
Pressure
4 bytes
418 Air pressure threshold value 2:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
419 Air pressure threshold value 2:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
420 Air pressure threshold value 2:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
421 Air pressure threshold value 2:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
422 Air pressure threshold value 2:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
423 Air pressure threshold value 3:
Absolute value
Input/ Output
RWCT [14.58] DPT_Value_-
Pressure
4 bytes
424 Air pressure threshold value 3:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
425 Air pressure threshold value 3:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
426 Air pressure threshold value 3:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
427 Air pressure threshold value 3:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
428 Air pressure threshold value 3:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
429 Air pressure threshold value 4:
Absolute value
Input/ Output
RWCT [14.58] DPT_Value_-
Pressure
4 bytes
430 Air pressure threshold value 4:
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
431 Air pressure threshold value 4:
Delay from 0 to 1
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
432 Air pressure threshold value 4:
Delay from 1 to 0
Input -WC- [7.5] DPT_TimePeriod-
Sec
2 bytes
433 Air pressure threshold value 4:
Switching output
Output R-CT [1.1] DPT_Switch 1 bit
434 Air pressure threshold value 4:
Switching output block
Input -WC- [1.1] DPT_Switch 1 bit
515 Summer Compensation: Outdoor tem-
perature
Input -WCT [9.1] DPT_Value_Temp 2 bytes
516 Summer Compensation: Target value Output R-CT [9.1] DPT_Value_Temp 2 bytes
No. Text Function Flags DPT type Size
27 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
517 Summer Compensation: Block
(1 = Blocking)
Input -WC- [1.1] DPT_Switch 1 bit
539 Façade Wind measurement 1 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
540 Façade Wind measurement 2 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
541 Façade Wind measurement 3 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
542 Façade Wind measurement 4 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
543 Façade Wind measurement 5 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
544 Façade Wind measurement 6 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
545 Façade Wind measurement 7 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
546 Façade Wind measurement 8 in m/s Input -WCT [9.5] DPT_Value_Wsp 2 bytes
547 Façade Wind automation blocking
duration in min.
Input/ Output
RWCT [7.006] DPT_TimePeri-
odMin
2 bytes
548 Façade Wind automation blocking
duration in min. (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
549 Façade Rain (1: Rain | 0: no rain) Input -WCT [1.1] DPT_Switch 1 bit
550 Façade Rain automation Delay in min-
utes
Input/ Output
RWCT [7.006] DPT_TimePeri-
odMin
2 bytes
551 Façade Rain automation Delay in min-
utes (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
552 Façade Brightness in Lux Input -WCT [9.4] DPT_Value_Lux 2 bytes
553 Façade Twilight threshold value in
kLux
Input/ Output
RWCT [9.4] DPT_Value_Lux 2 bytes
554 Façade Twilight threshold value in Lux
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
555 Façade Outside temperature (°C) Input -WCT [9.1] DPT_Value_Temp 2 bytes
556 Façade Heat protection threshold value
in °C
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
557 Façade Frost alarm threshold value in
°C (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
558 Façade Frost alarm start temperature
in °C
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
559 Façade Frost alarm start temperature
in °C (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
560 Façade Frost alarm start delay in hours Input/
Output
RWCT [7.006] DPT_TimePeri-
odHrs
2 bytes
561 Façade Frost alarm start temperature
in hours (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
562 Façade Frost alarm stop temperature
in °C
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
563 Façade Frost alarm stop temperature
in °C (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
564 Façade Frost alarm stop delay in hours Input/
Output
RWCT [7.006] DPT_TimePeri-
odHrs
2 bytes
565 Façade Frost alarm stop delay in hours
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
566 Façade Pyranometer in W/m² Input -WCT [9.022]DPT_Pow-
erDensity
2 bytes
No. Text Function Flags DPT type Size
28 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
567 Façade Pyranometer in W/m² Input -WCT [14.5] DPT_Value_Am-
plitude
4 bytes
568 Façade X channel status output
(1: activate)
Input RWC- [1.1] DPT_Switch 1 bit
569 Façade X channel name Output R-CT [16.0] DPT_String_AS-
CII
14 bytes
570 Façade X channel (1:+ | 0:-) Input -WC- [1.1] DPT_Switch 1 bit
571 Façade X channel state text Output R-CT [16.0] DPT_String_AS-
CII
14 bytes
572 Façade X channel status bit text Output R-CT [16.0] DPT_String_AS-
CII
14 bytes
573 Façade X channel status bit state Output R-CT [1.1] DPT_Switch 1 bit
574 Façade X channel delay Output R-CT [7,005] DPT_TimePeri-
odSec
2 bytes
575 Façade X channel status bit selection
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
576 Façade Wind simulation in m/s Input RWC- [9.5] DPT_Value_Wsp 2 bytes
577 Façade Wind extension blocking simu-
lation (1: active)
Input RWC- [1.1] DPT_Switch 1 bit
578 Façade Wind alarm simulation
(1: active)
Input RWC- [1.1] DPT_Switch 1 bit
579 Façade Rain simulation (1: active) Input RWC- [1.1] DPT_Switch 1 bit
580 Façade External temperature in °C sim-
ulation
Input RWC- [9.1] DPT_Value_Temp 2 bytes
581 Façade Internal temperature in °C sim-
ulation
Input RWC- [9.1] DPT_Value_Temp 2 bytes
582 Façade Brightness in Lux simulation Input RWC- [9.4] DPT_Value_Lux 2 bytes
583 Façade Sun intensity simulation in
watts/m²
Input RWC- [9.022]DPT_Pow-
erDensity
2 bytes
584 Façade Date simulation Input RWC- [11.1] DPT_Date 3 bytes
585 Façade Time simulation Input RWC- [10.1] DPT_TimeOfDay 3 bytes
586 Façade Sun direction simulation in °,
with date & time
Output R-CT [14.7] DPT_Value_An-
gleDeg
4 bytes
587 Façade Sun height simulation in °, with
date & time
Output R-CT [14.7] DPT_Value_An-
gleDeg
4 bytes
588 Façade Sun direction simulation in ° Input RWC- [14.7] DPT_Value_An-
gleDeg
4 bytes
589 Façade Sun height simulation in ° Input RWC- [14.7] DPT_Value_An-
gleDeg
4 bytes
590 Façade Reset simulation (1: reset) Input -WC- [1.015]DPT_Reset 1 bit
591 Façade Sun angle mode simulation
(1: On | 0: Off)
Input RWC- [1.1] DPT_Switch 1 bit
592 Façade 1 simulation (1: On | 0: Off) Input RWC- [1.1] DPT_Switch 1 bit
593 Façade 1 block Input RWC- [1.1] DPT_Switch 1 bit
594 Façade 1 safety (1: On | 0: Off) Output R-CT [1.1] DPT_Switch 1 bit
595 Façade 1 wind extension block (1: On |
0: Off)
Input -WC- [1.1] DPT_Switch 1 bit
No. Text Function Flags DPT type Size
29 Transfer protocol
Weather Station Suntracer KNX sl • Version: 14.07.2016 • Technical changes and errors excepted.
596 Façade 1 wind extension block thresh-
old value in m/s
Input RWCT [9.5] DPT_Value_Wsp 2 bytes
597 Façade 1 wind extension block thresh-
old value (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
598 Façade 1 wind extension block status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
599 Façade 1 wind alarm (1: On | 0: Off) Input -WC- [1.1] DPT_Switch 1 bit
600 Façade 1 wind alarm threshold value in
m/s
Input RWCT [9.5] DPT_Value_Wsp 2 bytes
601 Façade 1 wind alarm threshold value
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
602 Façade 1 wind alarm status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
603 Façade 1 frost alarm status
(1: On | 0: Off)
Output RWCT [1.1] DPT_Switch 1 bit
604 Façade 1 rain automation release/block Input RWC- [1.1] DPT_Switch 1 bit
605 Façade 1 rain alarm status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
606 Façade 1 timed opening release/block Input RWC- [1.1] DPT_Switch 1 bit
607 Façade 1 timed opening status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
608 Façade 1 external temperature Block-
ing release/block
Input RWC- [1.1] DPT_Switch 1 bit
609 Façade 1 external temperature Block
in °C
Input/ Output
RWCT [9.1] DPT_Value_Temp 2 bytes
610 Façade 1 external temperature Block
in °C (1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
611 Façade 1 external temperature Block
status (1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
612 Façade 1 timed closure release/block Input RWC- [1.1] DPT_Switch 1 bit
613 Façade 1 timed closure status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
614 Façade 1 night closure release/block Input RWC- [1.1] DPT_Switch 1 bit
615 Façade 1 night closure status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
616 Façade 1 heating protection release/
block
Input RWC- [1.1] DPT_Switch 1 bit
617 Façade 1 heating protection status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
618 Façade 1 pyranometer release/block Input RWC- [1.1] DPT_Switch 1 bit
619 Façade 1 pyranometer in W/m² Input/
Output
RWCT [9.022]DPT_Pow-
erDensity
2 bytes
620 Façade 1 pyranometer in W/m²
(1:+ | 0:-)
Input -WC- [1.1] DPT_Switch 1 bit
621 Façade 1 pyranometer status
(1: On | 0: Off)
Output R-CT [1.1] DPT_Switch 1 bit
622 Façade 1 internal temperature in °C Input -WCT [9.1] DPT_Value_Temp 2 bytes