1. Description

The Temperature Sensor KNX T-AP measures temperature in indoor and outdoor areas. The sensor can receive an external measured value via the bus and process it with the own data to an overall temperature (mixed value).
The KNX T-AP provides four switching outputs with adjustable threshold values as well as additional AND and OR logic gates. The sensor has got a PI controller for hea­ting and cooling.
Functions:
Measurement of temperature
Mixed value from own measured value and external value (proportions can be set in percentage)
PI controller for heating (one or two step) and cooling (one or two step)
4 switching outputs with adjustable threshold values (Threshold values can be set by parameter or via communication objects)
4 AND and 4 OR logic gates with each 4 inputs. Every switching incident as well as 8 logic inputs (in the form of communication objects) may be used as inputs for the logic gates. The output of each gate may optionally be configured as 1 bit or 2 x 8 bits
Configuration is made using the KNX software ETS. The programme file (format VD), the data sheet and the manual can be downloaded from the Elsner Elektronik home­page on www.elsner-elektronik.de in the “Service” menu.

1.1. Technical specifications

Housing Plastic material, sensor sleeve metal
Colour Grey
Mounting On-wall
Protection category IP 65
Dimensions approx. 65 × 93 × 38 (W × H × D, mm)
Weight approx. 70 g
Ambient temperature Operation -30…+85°C, Storage -55…+125°C
Operating voltage KNX bus voltage
Bus current max. 5.5 mA, max. 15 mA when programming LED is
Data output KNX +/- bus terminal plug
BCU type Own micro controller
PEI type 0
Group addresses max. 184
Allocations max. 184
Communication objects 80