Elsist NEMO 2.0 65, NEMO 2.0 80, NEMO 2.0 160, NEMO 2.0 200, NEMO 2.0 120 User Manual

...
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 1
Nemo2.0
65
80120160200300400
Single-phase Line Interactive series
Uninterruptible Power Supplies
USER MANUAL
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 2
1 – SAFETY INSTRUCTIONS
This section includes important information about Safety. Please, read it carefully before installing and operating the UPS.
When opening the box, if UPS is damaged or dented don’t connect it to electrical network. Please call
your reseller for product’s replacement
Check the electrical rating written on the label on the rear of UPS, for being sure that input voltage rating
is correctly set and in compliance with local Mains rating.
UPS must be connected to an accessible and near plug. UPS is designed for supplying equipment such as computer, monitor, cash register, telephone system or
similar. To supply any equipment different than above mentioned, please refer to your reseller or to call Naicon Service assistance for information
Before cleaning the UPS, disconnect it from the Mains. To clean external surface, please use only a dry
cloth. Don’t use any liquid cleanser, spray or chemical solvent, which may damage the electrical circuits of the device.
This UPS operates at dangerous voltages. Don’t open the device. The UPS doesn’t include circuits or
components accessible or repairable by the user. ONLY authorized personnel may access to the unit.
Connection to a plug without Ground connection may cause electrical shock, and is not in compliance
with Law regulation.
Don’t connect UPS input to its own output. Don’t connect a multiple plug system or an overvoltage suppression system to the UPS.In case of emergency, immediately push ON/OFF switch, disconnect the power cable from the wall plug
to correctly shutdown the UPS.
Don’t cover device’s air inlet, avoid direct exposure to direct sunlight or install it close to heating
sources, in order to avoid any overheating of the unit.
This equipment is intended to be used in interior. Avoid installing the UPS in locations where water or
excessive moisture are present.
Do not allow liquids or foreign bodies to penetrate the UPS. Do not place any drinks or any other liquid
container on top or near the unit.
Battery maintenance must be carried out by experienced personnel.  Replace the batteries with the same type.  The voltage of internal battery is set at 12/24Vcc, battery is sealed and contains acid. Do not open or
damage the battery. Released electrolyte is harmful to the skin and to the eyes. It can be toxic, too.
Handling batteries may result in electric shock and short circuit. Observe the following precautions when
working with batteries:
1) Don’t wear metallic objects
2) Use tools with isolated handles
3) Wear gloves and boots with rubber sole
4) Do not place tools or metal objects on the batteries
5) Disconnect the UPS before battery replacement.
Do not throw the batteries in the fire as they may explode. This UPS does not have to work either reversed or lying down.
Batteries are already connected.
Make sure that the sum of the leakage currents of the UPS and the loads connected to it does not
exceed 3.5 mA before connecting the equipment.
Be careful when disconnecting the equipment, there may be still residual voltages on the output sockets
due to the battery voltage. Battery cables must be disconnected if you need to access the UPS.
UPS is equipped with sealed lead-acid batteries. They are harmful if throw in the environment, so they
must be disposed of in compliance with the relevant Community directives. To dispose of the UPS, you must contact the appropriate authorized sites in your area, due to the electronic components and the plastic material of which the unit is made up.
WARNING
IN COMPLIANCE WITH THIS INSTRUCTIONS, ANY NON AUTHORIZED ASSISTANCE TO THE UPS
LEAD TO CANCELLATION OF THE WARRANTY,
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 3
2 – PRODUCT INTRODUCTION
Thanks for having purchased an ups of NEMO2.0 series. The ups is designed to give you maximum protection and is an easy to use device. This UPS is specially designed for PCs or similar equipment.
Thanks to its light weight and compact design, it fits perfectly into small working environments. NEMO2.0 series is equipped with the AVR function to stabilize the input voltage. It is also integrated with the DC start function (Cold start).
Main characteristics:
Full power protection.
Electrical noise suppression, voltage and overvoltage peak suppression, autonomy, are common requirements to many UPS types. This UPs provides a wider voltage range capability, in addition to the aforementioned characteristics. Within this wide voltage range, the load is supplied without any support from the battery. This feature not only protects your computer, but also improve and increases battery lifetime.
Cold start function (DC Start).
All NEMO2.0 models are equipped with cold start function, which means that even if the power supply is unplugged, the UPS can be activated simply by pushing the ON / OFF switch and will operated supplied by the battery.
Autorestart.
Upon returning the Mains, the UPS will restart automatically.
Overload protection.
The internal microprocessor controls the load status in any operating conditions. In the event of overload or short circuit, your UPS will beep or will automatically turn off to avoid undesired damage to the load.
Modem connection and protection.
Two special connectors RJ45/RJ11, will protect your Modem or your LAN 10Base-T network from any noise generated by the phone line.
Power Management software.
NEMO2.0 series includes UPSilon software that enables communication between the UPS and a PC. By connecting the USB port of the UPS to a corresponding PC port, you can either check or do the following:
a) to control UPS and battery status. b) to save vital files during unattended shutdown. c) to plan Turn off and Turn on of the UPS for energy saving. d) to Log the UPS activities and status for checking them over the time.
All controls are performed and guaranteed by a high reliability microprocessor. “Green Power” function for energy saving. Light weight and compact dimensions.
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 4
3 - INSTALLATION AND OPERATION INSTRUCTIONS
WARNING: The unit is shipped from the factory with a fully charged internal battery, however, it could be
discharged during transportation, so it has to be recharged before use. To do this, connect the unit to an appropriate power outlet and let the battery recharge for at least 6 hours without any load connected.
Install the UPS according to the following items:
Install the UPS in an environment that is free of excessive dust, corrosive gas and conductive
contaminants and where there is adequate air circulation around the unit.
To place the UPS in ideal location that allow you to check visual alarms and sound indicators.
To place the UPS at least 20cm far from any monitor or screen in order to avoid interference.
Connect the power cord to an earthed power outlet. Connect your computer and its devices to the UPS output outlets. Don’t connect laser printers to UPS output.  To turn on the UPS press the start button located on the UPS front panel and wait for the test completion
until the beep ends and the blue display lights up. Your UPS is now working.
From now on your computer and its connected devices are protected by the UPS. Before turning off your UPS, make sure that your computer or any other electronic equipment has been
turned off completely.
To turn off the UPS, press the button on front panel, the blue display will turn off, then your UPS will be
switched off.
IMPORTANT: The total power consumption of the load must not exceed the maximum power rating of the
UPS, specified on UPS label.
4 – UPS TEST
If you want to simulate a network failure, then proceed by unplugging the UPS power cord from the mains socket. Don’t turn off the UPS. “Batt. Mode” signal will appear on the display and the buzzer will beep every 10 seconds (with fully charged battery). To resume normal operation with electrical network, simply reconnect the UPS power cord to the mains socket. After a certain delay (intentional delay in order to protect the load from surges that may occur when re-connecting the power cord or when the voltage is back after a power outage), the "Batt. Mode " icon will be off, the buzzer will stop beeping and the" AC Mode "icon will be displayed.
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 5
5 – LAYOUT AND DESCRIPTION
UPS FRONT VIEW
1
2
Rear view Nemo2.0 65-80
Rear view Nemo2.0 120
3 4 5 6 3 5 4
6
Rear view Nemo2.0 160
Rear view Nemo2.0 200-300
3
4
5 6 7 3 4
5
6 7 8
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 6
1. LCD Display
Please refer to Section 6
2. Power On/Off Switch
Push to switch On or switch Off the UPS.
3. Mains input
Nemo2.0 65-80-120-160-400 models are equipped with a power cord to plug directly into the outlet. Nemo2.0 200-300 is equipped with a male IEC plug. Insert the UPS power cord female plug into this socket and the other to the power outlet. A fuse in the housing protects against overload .
4. Output outlets
Connect your loads to these outlets to be protected by the UPS.
5. USB Communication ports
For remote communication. By installing the supplied software via the USB cable, you can manage the UPS and monitor its signals (Network status, UPS & Batteries, On/Off Scheduling, automatic File back-up after a network outage, etc.).
6. RJ45/RJ11 connection
These two modular sockets protect the ISDN connection to the Modem or LAN 10 Base-T from interference of power network.
7. Fuse
To protect input.
8. Fan
Rear view Nemo2.0 400
3
4
5
6
7
8
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 7
6 –LCD DISPLAY
1. Input Voltage
2. Output Voltage
3. Operation from Mains icon
4. Operation from Battery icon
5. Battery level
6. Low battery
7. Load level
8. Overload
9. Error icon
7 – VISUAL/AUDIBLE SIGNALS
Signals and Alarms on LCD display:
1. Mains ON - UPS OFF
Situation that occurs when the UPS is connected to the mains but is not switched on. The LCD shows information but is not backlit. In this situation, the batteries are in charging mode.
2. Mains ON - UPS ON
Situation that occurs when the UPS is connected to the power supply and is switched on via the front panel button. After the end of the beep the LCD will turn on and the icon "3" will appear to indicate the operation of the power supply. The UPS is in normal mode, the load is protected and the batteries are being recharged.
3. Mains OFF - UPS ON (Network failure/ Battery Test)
Situation that occurs when the UPS is switched on and there is an outage (or want to simulate it to perform the Battery Test). The icon "4" lights up to indicate battery operation. The batteries are now feeding the load and are discharging. A beep indicates the remaining autonomy, the more the beep’s frequency is higher the less the autonomy time will be. When the battery reaches the end of discharge level, then "6" icon will also start blinking.
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 8
4. Mains OFF - UPS ON (DC Start)
Situation that occurs when the UPS is switched on via the button on the front panel. After a long and continuous beep, the display lights up as shown. The batteries are feeding the load and are discharging. A beep indicates the remaining autonomy, the more the beep’s frequency is higher the less the autonomy time will be. When the battery reaches the end of discharge level, then "6" icon will also start blinking.
5. Main ON - UPS ON (Overload)
Situation that occurs when a load higher than its capability is connected to the UPS working in normal mode. The icon "7" lights up until the load is above the limits, and the two "7-8" icons blink simultaneously with a continuous beep. After a few seconds, the UPS move to protection mode and switches off. The load is not supplied.
6. UPS error
Situation that occurs when the UPS detects a fault such as a short circuit or a very high overload at the output. The UPS switches off and the display shows the icon "9" as in the figure, moreover you will hear a continuous beep. To reset the beep, turn off the UPS with the On/Off button on the front panel.
8 – TROUBLESHOOTING
STATUS
CAUSE
SOLUTION
LCD display is Off
Discharged battery
Recharge the battery for at least 8hr
Battery failed
Replace the battery with the same
type of product
On/Off button is not switched On
Push ON/OFF button on front panel
Continuous beep when Mains is present
Overload on UPS
Verify that load doesn’t exceed the
rating of the UPS
Battery autonomy time in back-up mode is short
Overload on UPS
Partially remove the load
Battery voltage is very low
Recharge the battery for at least 8hr
Battery failure due to high
ambient temperatures or improper operation of the battery
Replace the battery with the same
type of product
Battery mode icon is On but Mains is present
Power cord is not connected
Check that power cord is correctly
plugged in.
Input fuse is blown
Check the fuse in its housing on the
rear of UPS and replace it if blown.
Battery is not recharged
Input fuse is blown
Check the fuse in its housing on the rear of UPS and replace it if blown.
NOTE: If there are other conditions not listed, then contact our service center.
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 9
9 – ACCESSORIES
Within the package are the following accessories, please check their presence.
MODEL
Input Power
Cord
Input power
cord
IEC320
Output
power cord
IEC320
Software
Manual
NEMO2.0 65
- 1 ●
NEMO2.0 80
● - ●
NEMO2.0 120
● - ●
NEMO2.0 160
● - ●
NEMO2.0 200
- 1 ●
NEMO2.0 300
- ● ●
NEMO2.0 400
● - ●
10 – TECHNICAL CHARACTERISTICS
MODEL NEMO2.0
65
80
120
160
200
300
400
INPUT
Input Voltage
220-230-240Vac
Input voltage range
162-290Vac
Frequency
50/60Hz (auto selection)
OUTPUT
Output Voltage
230Vac
Voltage tolerance
10%
Frequency
50/60Hz (following input frequency)
Power
650VA
800VA
1200VA
1600VA
2000VA
3000VA
4000VA
Active Power
330W
400W
600W
800W
1000W
1500W
2000W
Switching time
2-6 mS tpc
IEC outlet
2 2 4 2 2 2 2
Schuko outlet
- - - 2 2 2 2
NOISE FILTERING
Modem / T port (10BaseT/100baseT)
RJ11/RJ45 (network compatible)
BATTERY
Typ. Autonomy time
10 min
Battery capacity
1x4,5Ah
1x7Ah
1x9Ah
2x7Ah
2x9Ah
2x9Ah
4x9Ah
Type
Maintenance-free, sealed lead-acid
Recharging time
6-8 hr at 90% after a deep discharge
PROTECTION
Overvoltage/Undervoltage
Switch to Battery mode
Overload/Shortcircuit
Fuse and Electronic threshold (both on Mains modeand on Battery mode).
MECHANICAL CHARACTERISTICS
Dimensions (WxDxH) mm
101x298x142
149x353x
162
158x380x198
145x436x
213
Weight (Kg)
3,9
4,4
4,7
8,4
10
10,5
23
ENVIROMENT
Ambient
Temperature 0-40°C ,Humidity 0-90% without condensation, altitude max. 3000 mt.
Audible noise
< 40dbA (measured at 1mt.) both on “Mains mode” and on Battery mode”.
STANDARD
IEC/EN62040-1 IEC/EN62040-2 IEC/EN62040-3 IEC/EN60950-1
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 10
11 – WARRANTY
Dear Customer, Thank you for purchasing a NAICON product. We hope that you be satisfied. If the product fails in warranty period, please contact your dealer or call +39 02 950031 or go to www.naicon.com/elsist. Before contacting your dealer or authorized service network, we recommend that you read the operating and maintenance manual carefully.
With this warranty, NAICON warrants the product to be defective in materials or workmanship for 2 years, as of the original delivery date. If there are material or manufacturing defects during the warranty period, ELSIST affiliates, Authorized Service Centers or authorized resellers located in the EEC will repair or (at ELSIST discretion) replace the defective product or components under the terms and conditions below, without any charge for labor or spare parts costs. ELSIST reserves the right (in its sole discretion) to replace the components of defective products or low cost products with assembled parts or new or refurbished products. Conditions.
1. This warranty will only be valid if the defective product is returned together with the sales invoice. ELSIST reserves the right to refuse warranty service in the absence of such documents or if the information contained therein is incomplete or illegible.
2. This warranty does not cover the costs and / or any damages and / or defects resulting from any modifications or adjustments made to the product, without prior written permission from ELSIST, in order to adapt the product to local technical or safety standards in countries other than those for which the product was originally designed and manufactured.
3. This warranty will be void if the model or serial number indicated on the product has been modified, deleted, removed or otherwise illegible.
4. Are excluded by the warranty:
Periodic maintenance and repair or replacement of parts subject to normal wear and tear.  Any modification or modification to the product, without prior written permission from ELSIST to enhance performance than
those described in the User and Maintenance Manual
• All costs of technical staff support and any transport from the customer's adress to Assistance Center and vice versa as
well as all the risks involved.
Damages due to:
a. Improper use, including but not limited to: (a) the use of the product for any purpose other than the intended use or
failure to observe the ELSIST instructions for correct use and maintenance of the product, (b) installation or use of the
product not complying with the Technical or Safety standards in the country in which it is used. b. Repairs by unauthorized personnel or by the Customer himself. c. Accidental events, lightning, floods, fires, incorrect ventilation or other causes not attributable to ELSIST. d. Defects of the equipment or equipment to which the product was connected.
5. This warranty does not affect the buyer's rights established by applicable national laws nor the Customer's rights to the reseller arising out of the sales contract.
Unless authorized by the manufacturer, reproduction of any part of this manual is prohibited. Our equipment, built with the utmost care and with selected components, is controlled by ELSIST Quality Services. However, if you notice any anomalies, please inform us by calling 02-950031 specifying serial number and model of the devide, which are printed on the identification plate at the rear side of the UPS. ELSIST Assistance Service is also available to collect requests, comments, suggestions, if any.
In case of failure: Contact our Customer Service Center at +39 02 95 0031, and verify the UPS malfunction.
If the products returned to NAICON were OPERATING or if they were delivered without our permission or for out-of-warranty products, they will be returned to the customer by charging a cost that will depend on the country where will be shipped.
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
Rev. 02 27 Gennaio 2017 11
TABLE OF CONTENTS
1. SAFETY INSTRUCTIONS pag. 2
2. PRODUCT INTRODUCTION pag. 3
3. INSTALLATION AND OPERATION INSTRUCTIONS pag. 4
4. UPS TEST pag. 4
5. LAYOUT AND DESCRIPTION pag. 5
6. LCD DISPLAY pag. 7
7. VISIBLE/AUDIBLE SIGNALS pag. 7
8. TROUBLESHOOTING pag. 8
9. ACCESSORIES pag. 9
10. TECHNICAL CHARACTERISTICS pag. 9
11. WARRANTY pag. 10