Elsist MISSION 1000, MISSION 3000, MISSION 2000 Instruction Manual

Uninterruptible Power Systems
Mission 1K-2K-3K
Single Phase UP S
MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02 – 19 March 2015 2
Contents
1.Safety instruction ........................................................................................................................................ 3
1.1 Safety instruction ................................................................................................................................... 3
1.2 Symbols indication ................................................................................................................................ 3
2.Product Introduction ................................................................................................................................... 4
2.1 The appearance of the product ............................................................................................................. 4
2.2 The principle of the product ................................................................................................................... 5
2.3 Model ..................................................................................................................................................... 5
3.Installation .................................................................................................................................................... 6
3.1 Unpacking and inspection ..................................................................................................................... 6
3.2 Notes ..................................................................................................................................................... 6
3.3 UPS input connection ............................................................................................................................ 6
3.4 UPS output connection ......................................................................................................................... 6
3.5 Long backup external battery connection ............................................................................................. 7
4.Panel display,operation and running ........................................................................................................ 8
4.1 Faceplate display illumination ............................................................................................................... 8
4.2 Operation ............................................................................................................................................. 10
4.3 Parameter setting ................................................................................................................................ 11
4.4 Parameters inquiring ........................................................................................................................... 17
4.5 Run mode ............................................................................................................................................ 18
5.Maintenance ............................................................................................................................................... 20
5.1 Battery Maintenance ........................................................................................................................... 20
6.Troubleshooting and performance of product....................................................................................... 20
6.1 LED indication and warning table ....................................................................................................... 21
6.2 Troubleshooting ................................................................................................................................... 22
6.3 EMC standard/Safety standard ........................................................................................................... 23
6.4 Product Performance .......................................................................................................................... 23
6.5 Communication interface .................................................................................................................... 25
Manual instruction Thanks for purchasing our UPS, it is safe and reliable, so few maintenance is required. Read this manual carefully and completely. It includes instructions of safety installation and operation. They will help your UPS obtain the longest life and service. This manual accounts the internal working principle and the relative protection functions. This manual also contains information about the usage of the equipment. Please obey the instructions and all the warning stated in the manual or on the machine. Don’t operate the machine before fin ishing reading the safety and operation instructions.
Note: Because of the continuous improvements, our products may differ somewhat from the contents included in this manual. You can contact local office to get the information when necessary.
MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02 – 19 March 2015 3
1. SAFETY INSTRUCTION
This chapter mainly introduce the safety marks and notes of MISSION 1KVA-2KVA-3KVA series on-line UPS. Read this chapter carefully before operating on the equipment.
1.1 Safety instruction
There is dangerous voltage and high temperature inside the UPS. During the installation, operation and maintenance, please abide the local safety instructions and relative laws, otherwise it will result in personnel injury or equipment damage. Safety instructions in this manual act as a supplementary for the local safety instructions. Our company will not assume the liability that caused by disobey of safety instructions. Please note the following:
1. Don’t use the UPS when the actual load exceeds the rated load.
2. There are high-capacity batteries in the standard type UPS. You mustn’t open the enclosure or it will lead to electric shock. If it needs internal maintenance or battery replacement, please send it to the designated site.
3. Internal short-circuit of the UPS will cause electric shock or fire. So don’t place the containers equipped with liquid on the top of the UPS so as not to cause danger of electric shock and so on.
4. Don’t put the UPS in a place with high temperature or humidity as well as the corrosive gas, much dust.
5. Keep good air circulation between in-vent on front panel and out-vent on back panel.
6. Avoid direct sunlight or near heat-dispensed objects.
7. In case that the smoke appears on the UPS, please cut off the power as soon as possible and contact the dealer service site.
1.2 Symbols indication
The safety symbols cited in this manual are shown in table 1-1, which are used to inform readers of safety issues that should be obeyed when installation, operation and maintenance.
Safety Symbol
Indication
Attention
Static discharge sensitive
Electric shock
Table 1-1
There are three levers of safety grade: Dangerous, Warning and Attention. The remark is on the right side of the safety symbol, the detailed comments is behind, shown as following:
Dangerous: Indicate risk of serious injury or death or seriously damage the equipment
Warning: Indicate risk of serious injury or damage the equipment.
Attention: Indicate risk of injury or damage the equipment.
MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02 – 19 March 2015 4
2. PRODUCT INTRODUCTION
2.1 The appearance of the product
Fig. 1 Front Panel view Fig. 2 1KVA Rear Panel view
Fig. 3 2KVA Rear Panel view Fig. 4 3KVA Rear Panel view
MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02 – 19 March 2015 5
2.2 The principle of the product
Fig 5 UPS Principle Diagram
1. Input filter: Complete filtering the input AC utility power to provide the clean power for UPS.
2. AC/DC converter: Convert the filtered AC mains to DC and boost the DC for DC/AC inverter.
3. DC/DC booster: When the UPS works in battery mode, the circuit boosts the DC for DC/AC inverter.
4. DC/AC inverter: Convert the boosted DC to stable AC output.
5. Bypass: When overload or failure of inverting happen in the UPS, it transfers to bypass mode to supply power
to loads.
6. Charger: Standard unit provides 1A; long backup unit provides 7A.
7. Battery: Sealed Lead Acid Battery.
8. Output filter: Complete filtering the output of the UPS to provide the clean power for loads.
2.3 Model
UPS sort
MODEL NO
Remark
Standard unit
1KVA
Internal 1A charger, 2 PCS 7AH batteries
2KVA
Internal 1A charger, 4 PCS 7AH batteries
3KVA
Internal 1A charger, 6 PCS 7AH batteries
Long backup unit
1KVA
internal 6A charger, external 24V battery
2KVA
internal 6A charger, external 48V battery
3KVA
internal 6A charger, external 72V battery
The 12V/9AH battery which is sealed lead acid maintenance free can be chosen as internal battery of the standard unit. The 7A charger can be chosen as internal charger of the long backup unit. Two internal chargers can be used in long backup unit.
MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02 – 19 March 2015 6
3. INSTALLATION
3.1 Unpacking and inspection
1. Unpacking the box and check the UPS. If damaged or some parts missing, don’t start the machine and
inform your supplier.
2. Check the box content (please consult Box Content Table).
3. Check if the UPS is that you wanted to purchase. You can verify it on the label on the rear panel of the
UPS.
3.2 Notes
1. Please place the UPS in a clean, stable environment, avoid the vibration, dust, too humidity, flammable gas
and liquid, corrosive.
2. The ambient temperature around UPS should keep in a range of 0°C40°C. If UPS works above 40°C, it
is required that the rated value of the largest load decreases 12% while the temperature increases every 5°C . The highest temperature cannot be more than 50°C when UPS works.
3. UPS should be placed in a sufficiently ventilated place.
3.3 UPS input connection
Connect the UPS to the mains by input power cable which is equipped with the UPS.
Fig 6 Input Connection
3.4 UPS output connection
Fig 7 Output connection
MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02 – 19 March 2015 7
3.5 Long backup external battery connection
Fig 8 Battery connection
Warning:
Before installing battery, make sure that UPS and breaker are all turned off. Remove all your metallic
adornment such as finger ring, watch, and so on before connecting battery.
No anti-connection or short circuit between the battery anode and cathode forever. Red cable connect with
battery anode “+” and black cable connect with cathode “-”.
Please use the screwdriver with insulating handle. Do not lay the tools or metallic goods on the battery.
Notice:
When using the external battery, It is best to use external battery cable which matches with the equipment. When connecting load to UPS, first turn off load and then connect the power cable and finally turn on load
one-by-one.
Inductance loads such as motor, fluorescent lamp, photocopier are strictly prohibited connecting to UPS to
avoid damage.
Plug UPS on the special socket with over-current protection, the power socket that used should be
connected with ground wire.
UPS is likely to have output voltage no matter whether the power input cable is plugged in mains input
socket. If you wish UPS have no output, first break off the switch and then cancel the mains.
When connect laser printer, select the capacity of UPS according to the UPS start power because the startup
power is higher.
MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02 – 19 March 2015 8
4. PANEL DISPLAY, OPERATION AND RUNNING
The operation is simple, operators only need to read the manual and follow the operation instructions listed in this manual without any special training.
4.1 Faceplate display illumination
4.1.1 Keys function
Fig. 9 Front panel buttons instruction
ON key + Press and hold this key for more than half a second to turn on the UPS.
OFF key + Press and hold this key for more than half a second to turn off the UPS.
TEST/MUTE key + Press and hold the key for more than 1 second in Line mode or economical mode: UPS runs the self-test function. Press and hold the key for more than 1 second in battery mode: UPS runs the mute function.
INQUIRING key or Non-function setting mode: Press and hold the key for more than half a second (less than 2 seconds): Indicate the items of the LCD item section orderly. Press and hold this key for more than 2 seconds: Circularly and orderly display the items every 2 seconds, when press and hold the key for some time again, it will turn to output status.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Select the set option. FUNCTION SETTING key
Non-function setting mode: Press and hold the key for more than 2 seconds: Function setting interface. Function setting mode: Press and hold the key for more than half a second (less than 2 seconds): Affirm the set option. Press and hold the key for more than 2 seconds, exit from this function setting interface.