ELRO HA68S User Manual

HA68
USER’S MANUAL
W W W . - N L . C O M
ENEN
MULTI-ZONE PROFESSIONAL ALARM SYSTEM
DECLARATION OF CONFORMITY
KONFORMITATSERKLARUNG
Company ROOS ELECTRONICS Address, City Broekakkerweg 15, 5126 BD PO Box 115, 5126 ZJGILZE Country The Netherlands
Declares that the product:
Description Alarm system Product number HA68, SA68P, SA68R, SA68M Trade mark ELRO
Is herewith confirmed to comply with the requirements set in the Council Directive on the Approximation of the Member States relating to:
Electro Magnetic Compatibility Directive (89/336/EEC) R&TTE Directive (1999/5/EEC) LVD Directive (73/23/EEC)
Assessment of compliance of the product with the requirements relating to EMC was based on the following standards: EN 301 489-1/-3:V1.4.1 (2002-08)
The requirements relating to Electrical Safety was based on the following standards: EN 600950-1:2001 The requirements relating RF was based on the following standard: EN 300 220-1 :V1.3.1 (2000-09) EN 300 220-3:V1.1.1 (2000-09)
DECLARATION DE CONFORMITE
Société ROOS ELECTRONICS Adresse/Ville Broekakkerweg 15, 5126 BD of Boite postale 115, 5126 ZJ GILZE Pays Pays-Bas
Déclarons que le produit : Description Systeme d'alarme Référence produit HA68, SA68P, SA68R, SA68M Marque de commercialisation ELRO
Est certifié conforme aux exigences définies dans la Directive du Conseil d'approximation des Etats Membres suivante :
Compatibilité Electro magnétique (89/336/EEC) Directive R&TTE (1999/5/EEC) Directive Basse Tension (73/23/EEC)
L'évaluation de conformité du produit par rapport aux exigences de Compatibilité Electro Magnétique a été effectuée sur la base des normes suivantes : EN 301 489-1/-3:V1.4.1
Les exigences Electriques surette ont été vérifiées par rapport a la norme suivante EN 60950-1 :2001 Les exigences radio ont été vérifiées par rapport à la norme suivante : EN 300 220-1 :V1.3.1 (2000-09) EN 300 220-3: V1.1.1 (2000-09)
Firma ROOS ELECTRONICS Adresse Broekakkerweg 15, 5126 BD of Postbox 115, 5126 ZJ GILZE Land Niederlande
Erklärung des Produktes:
Artikelbeschreibung Alarm system Artikel-Nr.: HA68, SA68P, SA68R, SA68M Markenname: ELRO
Hiermit bestätigen wir, um die Anforderungen aus den Richtlinien des Rates über die Annäherung der Mitgliedsstaaten zu befolgen, die Anerkennung folgender Richtlinien:
Elektromagnetische Verträglichkeit (EMC) (89/336/EEC) R&TTE-Anforderung (1999/5/EEC) Niederspannungsrichtlinie (LVD) (73/23.EEC
Die Bewertung des Produktes bezüglich der Anforderung bezüglich EMC basiert auf den folgenden Standards: EN 301 489-1/-3:V1.4.1
Die Anforderungen bezuglich Elektrisch Sicherheit basiert auf den folgenden Standards: EN 60950-1:2001 Die Anforderungen bezüglich RF basiert auf den folgenden Standards: EN 300 220-1 :V1.3.1 (2000-09) EN 300 220-3:V1.1.1 (2000-09)
Authorized representative: Mr. Ad Netten
Date: 06.09.2005
ENEN
KIT CONTENTS
The Alarm System should contain the following components.
- 1 x LCD Control Panel
- 2 x Wirefee PIR Detector
- 2 x Wirefree Magnetic Contact Detector
- 1 x Remote Control
Also included:
- Power Supply Adaptor
- Telephone Connection Lead
- Installation & Operating Manual
- Fixing pack
- 2 x 6V/1.2Ahr Sealed lead acid battery
- 4 x 3.6V/950 mAhr 1/2 AA size
- 1 x 3V CR2032 Lithium
6V/1.2 Ahr Sealed lead acid battery (for Control Panel)
3.6v 1/2AA Size Lithium battery (for PIR Detector and Magnetic Contact sets)
3V CR2032 Lithium cel (for Remote Control)
IMPORTANT
Please check all items as mentioned above are included in the package.
SA68P
Wirefree PIR Detector
SA68M
Wirefree Magnetic Contact Detector
HA68 Control panel
SA68R
Remote Control
ENEN
-1--64-
INTRODUCTION AND OVERVIEW
MULTIPLE USERS
The system allows for up to 5 Users and a Master User to be configured. This allows the system Event Log to maintain a record of which users have armed and disarmed the system. Each user will have a different Password. In addition a 4 second voice recorder facility enables the users name to be recorded for use with the Latch-Key facility.
Only the Master User has access to the programming functions and is able to configure the system.
Note: Each Remote Control Units on the system will be recorded.
SYSTEM ARMING
The system has a full ‘Arm’ and two ‘Partial Arm’ modes. ARM will ‘Arm’ all zones while the ‘Partial Arm’ modes will only arm the zones that are enabled for the particular partial arm mode.
For example: The system could be configured such that during night time, ‘Partial Arm 1’ would arm only zones protecting the lower floor and outbuildings leaving the upper floor free for movement without triggering the alarm.
During the day while the property is occupied ‘Partial Arm 2’ would arm only the zones protecting the outbuildings. However, when the property is left un­occupied, the full ‘Arm’ mode will arm all zones to protect the entire property, (i.e. upper and lower floors and outbuildings).
ZONES
The system incorporates 32 wireless Alarm Zones for the connection of the system detectors that are used to independently monitor different areas of the property. In addition to standard intruder protection, each zone may also be configured to operate in one of four other modes:
- ‘Medical Help’ mode provides 24 hour monitoring of any panic switches incorporated into the system.
- ‘24-hour Intruder’ mode provides 24 hour intruder protection for areas/zones where continuous monitoring is required, (e.g. gun lockers).
- ‘Fire’ mode provides 24 hour monitoring of any Fire/Smoke detectors incorporated into the system.
- ‘Intruder’ mode allows a zone to be monitored while the system is armed. If a detector on a test zone is triggered an entry will be recorded in the Event Log and an alarm will occur.
‘Panic’ mode provides 24 hour monitoring of any emergency being occurred. Activation of any panic switch will immediately initiate a Full Alarm condition.
ENEN
-63--2-
BATTERIES
Before removing the battery cover on any device to replace the battery, ensure that the system is put into Test mode to avoid initiating an Alarm.
In addition there is the facility to connect 4 hard wired zones to the Control Panel, each of which is fully configurable with the same features as the wirefree zones (1-32).
The specifications for replacement batteries are as follows:
Note: Rechargeable batteries should NOT be fitted.
At the end of their useful life the batteries should be disposed of via a suitable Recycling Centre. Do not dispose of with your normal household waste. DO NOT BURN.
The Rechargeable batteries contain Sulphuric Acid – DO NOT ATTEMPT TO OPEN THE CASING.
ENTRY/EXIT DELAY
When the system is armed with the Exit-Delay enabled, no alarm signal from any detector on an active zone will be able to initiate an alarm until the Exit­Delay has expired. This enables the system to be armed from within the property and allows time for the user to exit the property without triggering an alarm. If the Exit-Delay is disabled then detectors on active zones will immediately be able to initiate an alarm as soon as the system begins to arm.
The system Exit-Delay may be configured for between 10 to 250 seconds or disabled completely.
If a detector on a zone with its Entry-Delay enabled is triggered, then an alarm condition will not occur until the Entry-Delay period has expired. This allows time for the user to re-enter the property and disarm the system before an alarm condition occurs. Generally only the zones on the main entry route to the property will be configured with an Entry-Delay. The remaining zones would be configured with their Entry-Delay disabled allowing them to immediately initiate an alarm a detector on the zone is triggered.
The Entry-Delay for each zone may be configured for between 10 to 250 seconds or disabled completely.
QUICK SET
The system may be fully armed in 5 seconds using the quick set facility, overriding the programmed exit-delay. This is useful for setting the system at night when the exit-delay warning beep will be silenced after just a few seconds.
ZONE LOCKOUT
If a detector on an active zone is triggered while the system is armed an alarm condition will occur. After the programmed alarm duration has expired the alarm will stop. If a single zone initiates an alarm condition more than three times then that zone will be ‘Locked Out’ and any further alarm signals from that zone will be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be disabled if required.
EVENT LOG
The Control Panel incorporates a memory capable of storing the last 50 system events. This enables the user to see which user has Armed/Disarmed the system and if and when any alarms occurred. The time, date and details of the event type will be recorded for each system event.
-3--62-
ENEN
CHIME
Chime is a low security facility for use when the system is Standby mode. If the Chime feature is ON, and a detector on a zone that has its Chime function enabled is triggered, the internal sounder will produce a low volume warning tone. A typical use of the Chime function would be to warn that a door or particular area has been accessed.
PIR DETECTORS
Under low battery conditions the LED behind the detector lens will flash when movement is detected to indicate that the battery needs to be replaced.
Under normal battery conditions the LED does not illuminate unless the PIR detector is in Walk Test mode.
VOICE DIALER
If the Voice Dialer is enabled and an alarm condition occurs, the system will call for help using your recorded alarm messages and up to six telephone numbers.
When an alarm condition occurs, the telephone voice dialer (if enabled) will call the first enabled number in the calling sequence and replay the recorded alarm messages for the configured ‘Play Time’. The recipient must acknowledge the message by pressing the button on their telephone keypad. If the call is unanswered or an acknowledgment is not received then the next active number in the dialing sequence will be called. The dialer will continue calling each number in turn until either all numbers in the sequence have been dialed the set number of times or the sequence is cancelled/acknowledged by the recipient.
DIGITAL DIALER
As an alternative to the Voice dialer the system may be configured to interface with a central monitoring station.
LATCH KEY
When the system is disarmed the Latch-Key facility, if enabled, will call the first latchkey phone number and replay the user message (recorded under user setup) for the set ‘Play Time’. The recipient must acknowledge the message by pressing the button on the telephone keypad. If the call is unanswered or an acknowledgment is not received then the second latchkey phone number will be called. The voice dialer will continue calling each number in turn until each number has been dialed the set number of times or the sequence is cancelled/acknowledged by the recipient.
For example, the latchkey facility is useful to inform parents that a child has returned from school and disarmed the system.
MAGNETIC CONTACT DETECTORS
Under low battery conditions, when the Detector is activated the transmit LED will be illuminated for approximately 1s as the door/window is opened.
Under normal battery conditions the LED will not illuminate as the Detector is operated, (unless the Detector is in Test Mode with the battery cover removed).
MAINTENANCE
Your Alarm System requires very little maintenance. However, a few simple tasks will ensure its continued reliability and operation.
CONTROL PANEL
The rechargeable batteries have a typical life of 3-4 years and need no maintenance during this period, provided they are kept charged. The batteries will be damaged if they are stored in a discharged state for long periods.
DETECTORS AND REMOTE CONTROL
The Detectors require very little maintenance. The batteries should be replaced once a year or when a low battery status is indicated.
IMPORTANT: Should you, for any reason, have to completely power-down the system (e.g. to move the system to a new premises) first put the system into Test mode before removing the Control Panel cover and disconnecting the power supply and backup batteries.
REMOTE SYSTEM CONTROL
It is possible to dial into the system via the connected telephone line to interrogate the system status and to have basic control over the system, (e.g. to Arm and Disarm the system). You may also activate the microphone on the control panel to Listen-In to what is happening in the protected property.
TAMPER PROTECTION
All system devices (except the Remote Control Units) incorporate Tamper protection features to protect against unauthorized attempts to interfere with the device. Any attempt to remove the battery covers from any device (except the Remote Control) or to remove the Solar Siren or Control Panel from the wall will initiate an alarm condition (unless the system is in Test or Programming modes), even if the system is Disarmed.
Remote Controls 1 x 3V CR2032 Lithium Cells
(or equivalent)
Magnetic Contact 1 x 3.6V 1/2 AA Size Lithium Cells Detectors (or equivalent)
PIR Detectors 1 x 3.6V 1/2 AA Size Lithium Cells
(or equivalent)
-61--4-
ENEN
Press to Listen-In via the Control Panel Microphone.
Press to stop Listen-In
Note: Listen-in will be automatically cancelled after 5 minutes if not cancelled manually.
Press to interrogate the system status. A message playing the latest status can be heard.
7
#
8
JAMMING DETECTION
In order to detect any attempts to illegally jam the radio channel used by your alarm system, a special jamming detection function is incorporated into the Control Panel and Solar Siren. If this feature is enabled, and the radio channel is jammed continuously for 30 seconds, when the system is armed, the Solar Siren will emit a pre-alarm series of rapid bleeps for 3 seconds. If the jamming continues for a further 10 seconds or more a full alarm condition will occur. In addition if the system is jammed for more than three periods of 10 seconds in a 5 minute interval, this will also generate a Full Alarm condition.
Press to show the battery status.
Press to end the remote system control and hang up the Control Panel line.
BATTERY MONITORING
All system devices continuously monitor their battery condition. The Control Panel also monitors the battery condition of all PIR and Magnetic detectors. If the battery level of any device drops below acceptable levels then its low battery indication will be activated. In addition if any PIR or Magnetic Contact detector has a low battery status it will be recorded by the Control Panel and a message stored in the event log.
In the event of AC adaptor being disconnected from the Control Panel, the Control Panel by consuming the DC rechargeable battery can sustain 2 days of normal operation (under standby mode). However, the battery for that device should be replaced as soon as possible.
Note: Before removing the battery cover on any device to replace the battery ensure that the system is put into Test mode to avoid initiating a Full Alarm condition.
The low battery indication for each system component is as follows:
CONTROL PANEL
During a period of mains supply interruption the Control Panel will be powered by the rechargeable backup batteries. Under normal battery conditions the
Power LED on the panel will flash at 1s intervals. Under low battery conditions, if setting to the voice dialer mode, a pre-recorded message will be played once after one hour. If setting to the digital dialer mode, a radio signal will be emitted to the central monitoring station right away and send the signal again after 4 hours.
9
#
The jamming detection features in the Control Panel and Solar Siren operate independently.
The Jamming Detection circuit is designed to permanently scan for jamming signals. However, it is possible that it may detect other local radio interference operating legally or illegally on the same frequency. If it is planned to operate the jamming detection feature we recommend that the system is monitored for false jamming alarms for at least 2 weeks prior to leaving the Jamming Detection function permanently enabled.
BATTERY MONITORING
In addition to the battery monitor and low-battery indicators in each device, the Control Panel will also indicate a low battery status within any Passive Infra-Red or Magnetic Contact Detector on the system using the Event log.
REMOTE CONTROL
When the Remote Control is operated under low battery conditions the transmit LED will continue to flash after the button has been released.
Under normal battery conditions the LED will extinguish when the button is released.
ENEN
-5--60-
PLANNING AND EXTENDING YOUR WIREFREE ALARM SYSTEM
The following example below shows a typical property incorporating the sugges­ted positions for the Control Panel, PIR and Magnetic Detectors for optimum security. Use this as a guide for your installation in conjunction with the recom­mendations contained in this manual for planning your intruder alarm system.
REMOTE SYSTEM CONTROL
If the Remote System Control facility is enabled, the Control Panel will answer the call after the set number of rings and emit three beeps on the phone line to prompt for a User Password to be entered using the telephone keypad.
A valid User Password will be acknowledged with one long beep. An incorrect code will be acknowledged by two short beeps.
PIR-detector
Remote Control
LOUNGE
PIR-detector
LCD Control Panel
Back Door
KITCHEN
HALL
Ground Floor GARAGE
DINNING
ROOM
Magnetic Contact Detector
PIR­detector
Magnetic Contact Detector
SHED
PIR­detector
If the User Password is not entered within 30s or is entered incorrectly three times then the Control Panel will automatically hang-up the line.
By pressing the button on the telephone keypad within 30 seconds, the
#
Control Panel will automatically hang-up the line.
Use with an External Answer-Phone:
If the Remote System Control is to be used in conjunction with an external Answer-Phone then
The number of ‘one call ring’ for the Control Panel must be greater than that of the External Answer-Phone, otherwise the Control Panel will always pickup the call before the Answer-Phone.
To access the Remote System Control facility the Control Panel has a ‘double call dial-in’ feature to enable the Control Panel to pick-up the phone call before the external Answer-Phone cuts in. The ‘double call dial-in’ procedure is as follows:
1. Dial up the system and hang up after two rings.
2. Redial up the system within 28s as maximum (14s as minimum), the system will pickup the phone after 1 ring.
3. Enter the User Password as normal.
The following functions may be access via the remote. The system will acknowledge each signal with a single long beep.
Press to initiate ARM.
1
PIR-detector
Before attempting to install your Alarm System it is important to study your security requirements and plan your installation.
The alarm system may be extended to provide even greater protection by fitting additional PIR Detectors and Magnetic Contact Detectors as required.
Press to initiate Partial Arm 1.
Press to initiate Partial Arm 2.
Press to Disarm the system.
Press to turn the Siren OFF
2
3
4
5
. Press to turn the Siren ON.
6
ENEN
-59--6-
CHIME
The Chime facility can only be operated with the system in Disarm mode.
Press to toggle the Chime facility between ON and OFF.
REMOTE CONTROL UNIT
Note: If the Chime is ON and the system is then armed the Chime will remain
ON after the system is disarmed.
MUTE
The Mute facility can only be operated with the system in Disarm mode.
Press to toggle the Mute facility between ON and OFF.
Note: If the Mute is ON, no voice guidance will be made during operation. If the mute is OFF, voice guidance will be active. However, if ‘LINE STATUS’ LED illuminates while the mute is OFF, there is no voice guidance will be available.
LATCH KEY
Press to access the latch key function for quick programming.
EVENT-LOG
The Event Log will store the last 50 system Arm, disarm, alarm and detector Low Battery events. The Event Log will record the time, date and details for each event. If when the system is disarmed the “ALARM MEM’ LED is flashing and the panel beeps every 10s, this indicates that an alarm has occurred. To cancel the LED and stop the beeping you must access the event log or press to eliminate the flashing ‘ALARM MEM’ LED and the beeping as well. To access the Event Log, (with the system in Disarm): Press .
The Event-Log will automatically start scrolling through and displaying the event data starting with the most recent event. The data for each event is shown on two screens, each screen will be displayed for 5 seconds before moving on to the next screen and then the next event.
Use the and buttons to manually scroll through the event log to the
required position as necessary.
Press to return to Disarm.
TELEPHONE LINE DETECTION
When setting to the voice dialer and If ‘LINE STATUS’ LED is flashing, it implies bad telephone line connection or telephone network being out of order. Check the telephone line and re-test it.
When setting to the digital dialer and if ‘LINE STATUS’ LED is flashing, it implies two causes of failure. One is bad telephone line connection or telephone network being out of order. The other cause of failure is derived from the central monitoring station. Consult with the central monitoring station for help.
B C D
A
E
G
I
H
F
Front Back
A LED indicator F Key Chain Ring B Arm G Battery Cover C Partial Arm H Negative Polarity D Disarm I Positive Polarity E Panic Switch
The Remote Control Unit is used to Arm, Partial Arm and Disarm the system.
The Remote Control also incorporates a Panic switch. Activating the Panic switch will immediately initiate a Full Alarm condition whether the system is Armed or Disarmed, (unless the system is in Service, Test or Program mode).
The Remote Control adopts a CR2032 type Lithium cell which under normal conditions will have typical life in excess of 1 year. Under normal battery conditions the LED on the Remote control will only illuminate when a button is pressed. However, under low battery conditions this LED will flash every time the button is pressed. When this occurs the batteries should be replaced as soon as possible.
SETTING THE REMOTE CONTROL
1.Remove the rear cover by undoing the small screw on the rear of the Remote Control.
2.Insert the battery ensuring that the +v terminal faces upwards away from the PCB.
ENEN
-7--58-
3. Replace the rear cover and fixing screw.
4. In order to communicate with the Control Panel, the ID code of the Remote Control needs to be learned by the Control Panel. By pressing the button on the Remote Control will emit
Batterij
the ID code to the Control Panel instantly, subject to the Control Panel being set at the User Setup mode.
CONTROL PANEL
LOCATING THE CONTROL PANEL
When choosing a suitable location for the Control Panel, the following points should be considered.
Remote Control:
Press the ‘DISARM’ button, .
Control Panel:
User Password
If the system is disarmed and the ‘ALARM MEM’ LED is flashing with the panel beeping every few seconds, this indicates that an alarm condition has occurred. Use the Event Log to find out and make a note of where the alarm occurred to assist in tracing the cause of the alarm.
QUICK SET
To operate the quick set function and fully arm the system in 5s, overriding the programmed exit delay. Press:
1. The Control Panel should be located in a position out of sight of potential intruders and in a safe location, but easily accessible for system operation.
2. The Control Panel should be mounted on a sound flat surface to ensure that the rear tamper switch on the Control Panel is closed when the Panel is mounted. The Control Panel should be mounted at a convenient height of between 1.5 and 2m and in a position where it will be seen each day. Note: If small children are in the household, a further consideration should be given to keeping the units out of their reach.
3. It is recommended that the Control Panel should be positioned such that the Exit/Entry tone (emitted by the Control Panel) can be heard from outside the property.
4. The Control Panel should be mounted within a protected area so that any intruder cannot reach the Control Panel without opening a protected door or passing through an area protected by a PIR detector when the system is armed.
5. The Control Panel must be located within reach of a mains socket.
6. If the telephone based functionality is to be used then the Control Panel will
need connecting to a convenient telephone point.
Note: It is recommended that the telephone connection lead is not extended beyond 5m before connecting to a telephone master or secondary outlet.
7. Do not locate the Control Unit closer than 1m to any large metallic object,
(e.g. mirrors, radiators, etc) as this may affect the radio range of the Control Panel.
User Password
PANIC ALARM
A full Alarm condition can be immediately initiated at any time (whether the system is Armed or Disarmed) in the event of threat or danger by activating a Panic switch on either the Remote Control or the Control Panel.
Remote Control:
Slide the Panic switch upwards.
Control Panel:
Press and hold the button for approximately 3 seconds. The alarm will continue either for the alarm duration when the system will automatically reset or until the system is disarmed.
TAMPER
If the battery cover of any device is removed or if the Siren or Control Panel are removed from the wall then a Full Alarm condition will be initiated even if the system is Disarmed. The alarm condition will continue either for the alarm duration when the system will automatically reset or until the system is Disarmed. The ‘ALARM MEM’ LED on the Control Panel will flash and the panel will beep every few seconds to indicate an alarm has occurred.
Note: The Tamper protection facility on the Siren operates independently. If the Tamper on the Siren is activated this will not be indicated at the Control Panel.
ENEN
-57--8-
ARM
The system can be set in ARM mode using either the Remote Control or the Control Panel as follows:
Remote Control:
Press the ‘ARM’ button,
MOUNTING THE CONTROL PANEL
1. Undo the two captive fixing screws on top of the panel and open the cover. The cover is hinged along the bottom edge.
2. Unclip and remove the two back-up batteries on either side of the panel.
Control Panel:
Press the Arm button followed by the User Password and then the Enter button:
User Password
By pressing , the programmed exit delay will be overrided to 5 seconds.
PART-ARM 1
The system can be set in PARTIAL Arm 1 mode using either the Remote Control or the Control Panel as follows:
Remote Control:
Press the ‘PARTIAL ARM’ button, .
Control Panel:
User Password
By pressing , the programmed exit delay will be overrided to 5 seconds.
PARTIAL ARM 2
The system can be set in Partial Arm 2 mode using either the Remote Control or the Control Panel as follows:
Remote Control:
Press the ‘PARTIAL ARM’ button twice, , .
Control Panel:
User Password
By pressing , the programmed exit delay will be overrided to 5 seconds.
3. Hold the Control Panel in position on the wall and mark the positions of the four fixing holes. Remove the Panel and drill four 5mm holes and fit the 25mm Wall Plugs.
IMPORTANT: Do not drill the fixing holes with the Control Panel in position; as the resulting dust and vibration may damage the Control Panel’s internal components and invalidate the guarantee.
4. Fit two 18mm No.4 screws into the top holes until almost fully home and hang the Control Panel over these screws using the two keyhole slots in the top corners of the panel casing.
5. Route the cable from the Power Supply Unit up behind and on the right hand side of the Control Panel and connect the plug to the DC power socket in the panel. Ensuring that the cable is not trapped between the panel and the wall.
6. Fix the Panel to the wall using two 18mm No. 4 screws in the lower two fixing holes in the panel and tighten the upper fixing screws until they just grip the casing. Do not over tighten the fixing screws as this could damage or distort the casing.
7. Ensure that the ‘Reset’ and the ‘Hard-Wired Siren tamper detect’ jumper links are set in the OFF position.
8. Connect battery leads to both back-up batteries and refit batteries.
Battery 1 (left): Red lead to +ve battery terminal
Blue lead to –ve battery terminal
Battery 2 (right): Blue lead to +ve battery terminal
Black lead to –ve battery terminal
IMPORTANT: Take care when connecting battery leads to the batteries as connecting incorrectly could damage the batteries or the Control Panel.
Note: The Power LED may flash to indicate that the unit is being operated from the back-up batteries and that mains supply is not present.
DISARM
The system can be Disarmed using either the Remote Control or the Control Panel as follows:
9. If fitted, remove the plastic film covering the LCD display and on the display window on the cover.
10. Close the lid of the Control Panel and tighten the captive fixing screws.
11. Plug in and switch ON the Power Supply Unit, (the Power LED should
illuminate).
-9--56-
ENEN
Loading...
+ 23 hidden pages