Elpro Technologies 105U-G User Manual

Page 1
ELPRO Technologies Pty Ltd, 9/12 Billabong Street, Stafford Q 4053, Australia.
Tel: +61 7 33524533 Fax: +61 7 33524577 Email: sales@elprotech.com
Web: www.elprotech.com
User Manual
105U-G Wireless Gateway
Page 2
Important Notices
Thank you for your selection of the 105G module. We trust it will give you
many years of valuable service.
ATTENTION!
Incorrect termination of supply wires may
cause internal damage and will void warranty.
To ensure your 105G enjoys a long life,
double check ALL your connections with
the user’s manual
before turning the power on.
Page 3
105U-G Wireless Gateway User Manual
Page September 2004
Important Notice
ELPRO products are designed to be used in industrial environments, by experienced industrial engineering personnel with adequate knowledge of safety design considerations.
ELPRO radio products are used on unprotected licence-free radio bands with radio noise and interference. The products are designed to operate in the presence of noise and interference, however in an extreme case, radio noise and interference could cause product operation delays or operation failure. Like all industrial electronic products, ELPRO products can fail in a variety of modes due to misuse, age, or malfunction. We recommend that users and designers design systems using design techniques intended to prevent personal injury or damage during product operation, and provide failure tolerant systems to prevent personal injury or damage in the event of product failure. Designers must warn users of the equipment or systems if adequate protection against failure has not been included in the system design. Designers must include this Important Notice in operating procedures and system manuals.
These products should not be used in non-industrial applications, or life-support systems, without consulting ELPRO Technologies first.
1. For 105G modules, a radio licence is not required in most countries, provided the module is installed using the aerial and equipment configuration described in the 105U Installation Guide. Check with your local 105G distributor for further information on regulations.
2. For 105G modules, operation is authorised by the radio frequency regulatory authority in your country on a non-protection basis. Although all care is taken in the design of these units, there is no responsibility taken for sources of external interference. The 105U intelligent communications protocol aims to correct communication errors due to interference and to retransmit the required output conditions regularly. However some delay in the operation of outputs may occur during periods of interference. Systems should be designed to be tolerant of these delays.
3. To avoid the risk of electrocution, the aerial, aerial cable, serial cables and all terminals of the 105G module should be electrically protected. To provide maximum surge and lightning protection, the module should be connected to a suitable earth and the aerial, aerial cable, serial cables and the module should be installed as recommended in the Installation Guide.
4. To avoid accidents during maintenance or adjustment of remotely controlled equipment, all equipment should be first disconnected from the 105U module during these adjustments. Equipment should carry clear markings to indicate remote or automatic operation. E.g. "This equipment is remotely controlled and may start without warning. Isolate at the switchboard before attempting adjustments."
5. The 105G module is not suitable for use in explosive environments without additional protection.
Page 4
Contents
Limited Warranty, Disclaimer and Limitation of Remedies
ELPRO products are warranted to be free from manufacturing defects for a period of 2 years from the effective date of purchase. The effective date of purchase is decided solely by ELPRO Technologies.
This warranty does not extend to:
- failures caused by the operation of the equipment outside the particular product's specification, or
- use of the module not in accordance with this User Manual, or
- abuse, misuse, neglect or damage by external causes, or
- repairs, alterations, or modifications undertaken other than by an authorised Service Agent.
ELPRO’s liability under this warranty is limited to the replacement or repair of the product. This warranty is in lieu of and exclusive of all other warranties. This warranty does not indemnify the purchaser of products for any consequential claim for damages or loss of operations or profits and ELPRO is not liable for any consequential damages or loss of operations or profits resulting from the use of these products. ELPRO is not liable for damages, losses, costs, injury or harm incurred as a consequence of any representations, warranties or conditions made by ELPRO or its representatives or by any other party, except as expressed solely in this document.
How to Use This Manual
To receive the maximum benefit from your 105U-G product, please read the Introduction, Installation and Operation chapters of this manual thoroughly before using the 105U-G.
Chapter Four Configuration explains how to configure the modules using the Configuration Software available.
Chapter Six Troubleshooting will help if your system has problems. The foldout sheet 105U-G Installation Guide is an installation drawing appropriate for most
applications.
Page 5
105U-G Wireless Gateway User Manual
Page September 2004
CONTENTS
Chapter 1 INTRODUCTION ...............................................................................................9
1.1 105G OVERVIEW 9
1.1.1 Modbus / DF1 105G 10
1.1.2 Profibus 105G 10
1.1.3 Ethernet 105G 11
1.1.4 DeviceNet 105G 12
1.1.5 Modbus Plus 105G 12
1.2 T
HE 105G STRUCTURE 13
1.2.1 On-board I/O 14
1.2.2 I/O Expansion - 105S modules 14
1.3 T
HE WIRELESS NETWORK 14
1.3.1 105U to 105G Network 14
1.3.2 105G to 105G Network 15
1.3.3 “Data Concentrator” Networks 16
1.3.4 105G Repeaters 17
Chapter 2 OPERATION.....................................................................................................19
2.1 START-UP 19
2.2 O
PERATION 19
2.3 D
ATABASE 21
2.4 T
HE HOST - 105G LINK 23
2.4.1 Modbus / DF1 23
2.4.2 Profibus 23
2.4.3 Ethernet 24
2.5 R
ADIO SYSTEM DESIGN 24
2.5.1 Radio Signal Strength 24
2.5.2 Repeaters 25
2.6 R
ADIO COMMS FAILURE 25
2.6.1 Monitoring Communications Failure 26
2.7 S
ECURITY CONSIDERATIONS 26
Chapter 3 INSTALLATION .............................................................................................. 28
3.1 GENERAL 28
3.2 A
NTENNA INSTALLATION 28
3.2.1 Dipole antenna. 29
3.2.2 Yagi antenna. 30
3.3 P
OWER SUPPLY 31
3.3.1 AC Supply 32
3.3.2 DC Supply 32
3.3.3 Solar Supply 33
3.4 I
NPUT / OUTPUT 33
3.4.1 Digital Inputs / Outputs 33
3.5 S
ERIAL PORT 34
3.5.1 RS232 Serial Port 34
3.5.2 RS485 Serial Port 35
3.6 P
ROFIBUS PORT 37
3.7 E
THERNET PORT 38
3.8 M
ODBUS PLUS PORT 39
3.9 D
EVICENET PORT 40
Chapter 4 CONFIGURATION........................................................................................... 41
4.1 INTRODUCTION 41
4.2 C
ONFIGURATION PROGRAM 42
4.2.2 Security 46
Page 6
Contents
4.3 MAPPINGS 105G TO 105U I/O MODULES 48
4.3.1 Mappings from Inputs at Remote 105U I/O Modules 48
4.3.2 Mappings from 105G to Outputs at Remote 105U I/O Modules 50
4.3.3 Don’t Send if in Comm Fail 52
4.3.4 Startup Polls 53
4.3.5 Polls to Remote Modules 53
4.4 M
APPINGS FROM 105G TO OTHER 105G MODULES 53
4.4.1 Entering a Block Mapping 55
4.4.2 Host Device Trigger 56
4.4.4 Real-Time 57
4.4.5 Change-of-State 59
4.4.6 Mixing Normal Mappings and Block Mappings 59
4.4.7 Comms Fail for Block Mappings 59 “Repeater-only” Configuration 60
4.5 C
HANGE SENSITIVITY 60
4.6 S
ERIAL CONFIGURATION – MODBUS 62
4.6.1 MODBUS Slave 62
4.6.2 MODBUS Master 64
4.7 S
ERIAL CONFIGURATION - DF1 67
4.8 F
IELDBUS CONFIGURATION 71
4.9 F
IELDBUS CONFIGURATION - PROFIBUS SLAVE 76
4.10 F
IELDBUS CONFIGURATION - PROFIBUS MASTER 77
4.10.1 GSD File 77
4.10.2 Protocol and Supported Functions 78
4.10.3 Configuration 78
4.10.4 Message Interface 89 Error Codes 109 DPV1 Return Codes 110
4.11 F
IELDBUS CONFIGURATION - ETHERNET 111
4.11.1 Setting IP Address 111
4.11.3 EtherNet/IP 116
4.12 F
IELDBUS CONFIGURATION – DEVICENET 120
4.12.1 DeviceNet Introduction 120
4.12.2 DeviceNet Address Setting 120 EDS File 121
4.12.3 Protocol and Supported Functions 121
4.13 F
IELDBUS CONFIGURATION – MODBUS PLUS 121
4.13.1 Modbus Plus Introduction 121
4.13.2 Modbus Plus Addressing 122
4.13.3 Protocol & Supported Functions 122
4.13.4 Configuration 123
4.14 C
ONNECTING 105S SERIAL I/O 125
4.15 U
PLOADING AND DOWNLOADING 126
4.15.1 Loading from a 105G 126
Chapter 5 SPECIFICATIONS.......................................................................................... 128
Chapter 6 DIAGNOSTICS...............................................................................................130
6.1 DIAGNOSTICS CHART 130
6.2 D
IAGNOSTICS MENU 131
6.3 E
THERNET DIAGNOSTICS 138
6.4 F
IELDBUS INDICATING LEDS 140
Page 7
105U-G Wireless Gateway User Manual
Page September 2004
Chapter 7 WARRANTY .................................................................................................. 145
Appendix 1 STATUS REGISTERS.................................................................................... 146
Appendix 2 IT Functionality ...........................................................................................148
Page 8
105U-G Wireless Gateway User Manual
Page September 2004
Chapter 1 INTRODUCTION
1.1 105G Overview
The 105U-G Wireless Gateway products provide a wireless interface between various fieldbus protocols used in process and automation applications. The 105U-G includes an integral 900MHz license-free radio transceiver, and transfers transducer and control signals (I/O) using a highly secure and highly reliable radio protocol.
The 105U radio protocol is designed for very efficient radio band usage, with event reporting communications, automatic acknowledgment and error-correction, peer to peer addressing, multiple path routing, and frequency encoding and data encryption for system security.
Application types include:
The 105U-G interfaces between 105U wireless
I/O and various fieldbus protocols. Connect wireless I/O to PLC’s, DCS, SCADA or Internet.
Wireless extension of factory automation buses
such as Profibus.
Wireless interconnectivity between different
fieldbuses - Ethernet to Profibus to Modbus to DF1.
Combined networks of the above. The 105U-G has eight on-board discrete I/O. Each
I/O point can be configured individually as a contact input signal, or a discrete output signal. Input signals can sent via its fieldbus connection to a host device (PLC, DCS etc) or be transmitted by radio to other 105U units. The output signals can be driven by a host device, or linked to inputs on remote 105U units.
This document assumes the reader is familiar with the operation of the 105U I/O modules ­for further information, please refer to the User Manuals for these products.
Profibus Ethernet
Modbus DF1 Internet
105U I/O
105U I/O
Direct I/O
105U-G
Direct I/O
105U-G
Profibus
105U-G
Profibus
105U-G
Profibus
Ethernet
105U I/O
105U I/O
Direct I/O
105U-G
Direct I/O
Profibus
Modbus
105U-G
105U-G
105U-G
Modbus
105U-G
Ethernet
105U-G
Profibus
Page 9
Chapter One Introduction
The 105U-G is referred to as the 105G for the rest of this document, to clearly differentiate from normal 105U I/O modules.
Ordering information:
105U-G-MD1 Modbus Master & Slave / DF1 interface 105U-G-PR1 Profibus-DP Slave interface 105U-G-PR2 Profibus-DP Master interface 105U-G-ET1 Ethernet interface - Modbus TCP, Ethernet IP, FTP, HTML, Email 105U-G-DE1 DeviceNet Slave interface 105U-G-M+1 Modbus Plus Slave interface
1.1.1 Modbus / DF1 105G
The 105U-G-MD1 can be configured for Modbus master interface, Modbus slave, or DF1. Modbus is a Master-Slave protocol originally developed by Modicon (now part of the
Schneider group). It became a popular interconnect protocol with many equipment manufacturers. One Modbus master controls the Modbus network communications, which can comprise up to 250 Modbus slave devices. The Modbus master can read or write I/O values to/from Modbus slaves. The 105G can be configured as either Modbus Master or Modbus Slave. The variation of Modbus supported by the 105G is “Modbus RTU” (also known as “Modbus binary”).
DF1 is an Allen-Bradley protocol (Allen-Bradley is now part of the Rockwell Automation group). DF1 offers both full-duplex (point to point) and half-duplex (multidrop) operation. The 105G only supports the full-duplex operation - this is the default DF1 mode on most equipment. DF1 full-duplex is a “peer-to-peer” protocol. Either DF1 device can initiate commands to the other device, and both devices will respond to commands from the other device.
The 105U-G-MD1 has two serial connections - RS232 and RS485, on the bottom end plate of the module. The serial port provides both RS232 and RS485 hardware connections, however both connections are paralleled internally - both connections cannot be used at the same time. Either RS232 or RS485 can be used for Modbus communications, however only the RS232 port can be used for DF1. The serial port must be configured to suit the host device. Serial data rates between 1200 and 19200 baud may be selected, and character types with 7 or 8 data bits, even/odd/none parity, and 1 or 2 stop bits may be selected.
The Modbus/DF1 105G has 4300 general-purpose I/O registers. Each discrete, analog and pulse I/O point takes up one register.
1.1.2 Profibus 105G
The Profibus 105G provides Profibus-DP Slave functionality according to EN 50170. Profibus is a popular automation fieldbus that originated in Germany and is used extensively by Siemens and other automation suppliers.
The Profibus connection on the 105G is optically isolated RS485 using an on-board DC/DC converter. The Profibus port has automatic baudrate detection (9600 bit/s - 12 Mbit/s).
The Profibus Slave 105G (PR1) will connect to a Profibus LAN controlled by an external master device. The Profibus Master 105G (PR2) will control communications on a Profibus LAN, and can connect to up to 125 Profibus slave devices.
Page 10
105U-G Wireless Gateway User Manual
Page 11 © September 2004
The Profibus 105G I/O database has 4300 registers (each of 16 bit value), however the Profibus interface limits the amount of I/O that can be transferred via the Profibus port.
Slave unit (PR1). The PR1 slave unit only supports 416 x 8 bit bytes of I/O. Of the 416 bytes of I/O, there is a maximum 244 input bytes and maximum 244 output bytes - that is, if 244 input bytes are used then only 172 output bytes can be used (416 – 244). Each byte can represent 8 discrete inputs or outputs, or an 8-bit value, or two bytes can represent a 16­bit value. That is, analog or pulse I/O can be transferred as 8-bit registers (1 byte) or 16-bit registers (2 consecutive bytes).
An “output” is a value coming into the 105G via the fieldbus (that is, a value written to the 105G from the Profibus master). An input is a value going out from the 105G via the fieldbus (a value read by the Profibus master).
So a Profibus Slave 105G could handle up to 1952 (244 x 8) discrete inputs or 244 low resolution analog inputs or 122 (244 x ½) high resolution analog inputs, or some combination in between.
For example, a Profibus 105G can handle 400 discrete inputs, 240 discrete outputs, 90 analog inputs and 60 analog outputs (assume analogs are 16-bit). The number of input bytes is 230 (400/8 + 90*2). The number of output bytes is 150 (240/8 + 60*2). The total number of I/O bytes is 380. If the number of analog outputs was increased to 90, then the total output bytes would be 210 (240/8 + 90*2), and the total number of I/O bytes is 440 - this exceeds the capacity of the Profibus interface.
Master unit (PR2). The Profibus master interface supports 2048 input bytes and 2048 output bytes. Each byte can be 8 discrete inputs or outputs, but analog or pulse I/O take up 1 byte for low resolution values (8-bit) or 2 bytes for high resolution values (16-bit).
So a Profibus Master 105G can handle up to 4300 I/O total, but analog or pulse inputs are limited to 2048 x 8-bit values or 1024 x 16-bit values. The same limit applies to outputs.
For example, a Profibus Master 105G can handle 2000 discrete inputs and 500 analog inputs (assume analogs are 16-bit). The number of input bytes is 1250 (2000/8 + 500*2). The same unit could handle 4000 discrete outputs and 750 analog outputs. The number of output bytes is 2000 (4000/8 + 750*2). The total number of I/O is 3250 which is less than the total limit of 4300.
1.1.3 Ethernet 105G
The Ethernet 105G provides several different types of Ethernet functionality:
Modbus TCP. Modbus TCP uses Modbus as a base protocol within an Ethernet
communications structure. The 105G provides class 0, 1 and partially class 2 slave functionality.
EtherNet IP. EtherNet IP is the version of Ethernet used by Allen-Bradley devices. The
105G provides level 2 I/O server CIP (ControlNet and DeviceNet).
Internet functionality. The 105G has 1.4Mbyte of non-volatile “flash” memory for
embedded web “pages” (dynamic HTTP), on-board file system, user downloadable web
pages thru FTP server, and email functionality (SMTP). The Ethernet connection is a transformer isolated RJ45 connector, 10/100 Mbit/sec. The Ethernet 105G I/O database has 4300 registers (each of 16 bit value), however the
Ethernet interface only supports 2048 input bytes and maximum 2048 output bytes. Each
Page 11
Chapter One Introduction
byte can be 8 discrete inputs or outputs, but analog or pulse I/O take up 1 byte for low resolution values (8-bit) or 2 bytes for high resolution values (16-bit).
An “output” is a value coming into the 105G via the fieldbus. An input is a value going out from the 105G via the fieldbus.
So an Ethernet 105G can handle up to 4300 I/O total, but analog or pulse inputs are limited to 2048 x 8-bit values or 1024 x 16-bit values. The same limit applies to outputs.
For example, an Ethernet 105G can handle 2000 discrete inputs and 500 analog inputs (assume analogs are 16-bit). The number of input bytes is 1250 (2000/8 + 500*2). The same unit could handle 4000 discrete outputs and 750 analog outputs. The number of output bytes is 2000 (4000/8 + 750*2). The total number of I/O is 3250 which is less than the total limit of 4300.
1.1.4 DeviceNet 105G
The DeviceNet 105G provides DeviceNet 2.0 Slave functionality. DeviceNet is an automation fieldbus developed by Allen-Bradley (Rockwell Automation).
The DeviceNet connection on the 105G is optically isolated RS422 with selectable baudrate between 125 and 500 Kbit/sec.
The 105G I/O database has 4300 registers (each of 16 bit value), however the DeviceNet interface only supports 512 x 8 bit input bytes and 512 x 8 bit output bytes, and this limits the amount of I/O that can be transferred via the DeviceNet port.
Each byte can represent 8 discrete inputs or outputs, or an 8-bit value, or two bytes can represent a 16-bit value. That is, analog or pulse I/O can be transferred as 8-bit registers (1 byte) or 16-bit registers (2 consecutive bytes).
An “output” is a value coming into the 105G via the fieldbus (that is, a value written to the 105G from the DeviceNet master). An input is a value going out from the 105G via the fieldbus (a value read by the DeviceNet master).
So a DeviceNet 105G can normally handle up to 4096 (512 x 8) discrete inputs or 512 low resolution analog inputs or 256 (512 x ½) high resolution analog inputs, or some combination in between. It can also handle the same number of outputs, however the total I/O count cannot exceed the 105G database size of 4300.
1.1.5 Modbus Plus 105G
The Modbus Plus 105G provides Modbus Plus Slave functionality. The Modbus Plus connection on the 105G is optically isolated RS485 with standard baudrate of 1 Mbit/sec.
The 105G I/O database has 4300 registers (each of 16 bit value), however the Modbus Plus interface only supports 1024 input registers and maximum 1024 output registers. Each register can be 16 discrete inputs or outputs, or one analog or counter 16-bit value.
An “output” is a value coming into the 105G via the fieldbus. An input is a value going out from the 105G via the fieldbus.
So an Modbus Plus 105G can handle up to 4300 I/O total, but analog or pulse inputs are limited to 1024 x 16-bit values. The same limit applies to outputs.
The Modbus Plus interface allows global data base transactions with routing for up to six Modbus Plus networks.
Page 12
105U-G Wireless Gateway User Manual
Page 13 © September 2004
1.2 The 105G Structure
The 105G has three functional sections:
The Radio Interface consists of an I/O database (or "Process Image") that maintains the
latest values of all I/O in the wireless I/O system. The I/O database comprises 4300 x 16 bit I/O registers and 4300 x 16 bit status registers. There are also other registers in the database that can be used for system management - they are discussed later in this manual. NOTE – the terms ‘Radio Interface’ and ‘I/O database’ are used interchangeably throughout the manual.
The radio port allows the 105G to communicate with other 105G and/or 105U modules
using the 105U protocol (called “ELPRO 105U”). Messages from the 105U modules are received by the radio port and used to update the input values in the 105G Radio Interface. The radio port also creates the correct radio message to set outputs on the remote 105U modules.
The ELPRO 105U protocol is an extremely efficient protocol for radio communications.
Radio messages can be sent using exception reporting - that is, when there is a change of an input signal - or by read/write messages. Each message can comprise a single I/O value, or multiple I/O values (termed a “block” of I/O). There are also update messages, which are sent for integrity purposes. Messages include error checking, with the destination address sending a return acknowledgment. Up to five attempts are made to transmit the message if an acknowledgment is not received. The ELPRO 105U protocol is designed to provide reliable radio communications on an open license-free radio channel.
The Fieldbus port enables
communications between a host device, which could be a PLC, DCS, HMI, intelligent transducer, etc), and the 105G Radio Interface database. A “host device” may be one or several devices connected to the same fieldbus or network (for example, an Ethernet LAN) - in this manual, the LAN is considered as a “host device”.
The fieldbus port decodes messages from the host device and reads or writes I/O values to the database. The fieldbus port can also generate messages to the host device.
The 105G I/O database effectively isolates the fieldbus and the radio network. This provides a high level of system performance. The 105U radio protocol is very efficient and reliable for radio communications. It minimizes radio channel usage by "change-of-state" reporting, and allows the use of intermediate repeater addresses. It also allows peer-to-peer (105U to 105U, 105G to 105G) and peer-to-master (105U to 105G) communications. PLC protocols, by comparison, are designed to provide transfer of large I/O files by "wire" link. The 105G retains the advantage of both protocols in their respective communications media.
FIELDBUS
INTERFACE
FIELDBUS PROFIBUS
ETHERNET MODBUS DF1 DEVICENET MODBUS +
RADIO PORT
RADIO
INTERFACE
I/O
DATABASE
905U
RADIO
INTERFACE
105U-G
ON-BOARD I/O
EIGHT DISCRETE I/O SIG NALS
Page 13
Chapter One Introduction
1.2.1 On-board I/O
The 105G has eight on-board discrete I/O. Each I/O point can be used as either a discrete input (voltage free contact input) or discrete output (transistor output) - an I/O point cannot be used as both input and output. Each I/O point is linked to two separate I/O registers in the database - one for the “input” function and one for the “output” function.. If the output register is set “on” by the fieldbus or by a radio message from a remote module, then the 105G will automatically set the input register for the same I/O point to “off”. This means that the output register has priority over the input register - if there is a conflict, the input value is ignored.
The 105G also has three internal inputs linked to I/O registers:
Supply voltage status - if the normal supply fails, this status is set on.Low battery voltage. The 105G has an internal battery charger to trickle charge a back-up
battery. If the battery voltage is low, this status is set. Battery voltage - the actual value of the connected battery voltage.
1.2.2 I/O Expansion - 105S modules
The 105G provides eight on-board discrete I/O. Where additional I/O is required, 105S modules can be connected to the RS485 port of the 105G modules.
Note: 105S modules cannot be connected to the 105U-G-MD1 unit (as this unit uses the RS485 port for Modbus or DF1 communications), unless this unit is configured as “Repeater-only” and does not have a host device connected.
1.3 The Wireless Network
The 105G can communicate with up to 490 other addresses - this could be 490 other 105U modules, or in the case of 105K modules, it could be many thousands of modules (as many 105K modules can share the same address). 105G modules may take up more than one address under some circumstances.
Any 105G or 105U module can act as a radio repeater for other modules - that is, radio messages can be passed onto other modules. Up to five repeater addresses can be configured for messages transmitted to a 105G module.
Each module can have a unit address between 1 – 95, but the 105G also recognizes repeater addresses in conjunction with the unit address as the module “identifier”. Hence module #2 is recognized as different to #2 via #57 - #57 being a repeater.
1.3.1 105U to 105G Network
In the wireless I/O system, the 105G acts as a normal 105U module (this covers 105U I/O, 105S I/O, 105U-K and 105U-C modules).
105U modules transmit messages to the 105G address and the 105G acknowledges these messages like a normal 105U module. When a 105G transmits messages to change remote outputs, it will "re-try" if it does not receive an acknowledgment, like a normal 105U module.
Remote 105U modules can connect to 105S modules in the normal way. The 105G host can access I/O on 105S modules by using the intermediate 105U as a repeater.
Page 14
105U-G Wireless Gateway User Manual
Page 15 © September 2004
105U modules can transmit input messages directly to outputs on other
105U module, as well as the 105G. The same input can be transmitted to different addresses by entering two "mapping" configurations at the remote module.
Normal 105U Messages
I/O registers in a 105G can be configured (mapped) to outputs at remote 105U modules, or I/O registers in 105G modules. The 105G will transmit an I/O message when a “change-of-state” occurs for that I/O register . Registers have a configurable “sensitivity” value - this determines how much the register value has to change to trigger a change message. A change-of-state occurs when the register value has changed by more than the sensitivity value since the last transmission.
The 105G also transmits periodic update messages if there has been no change - if an I/O register is mapped to a remote output or another 105G, then that register can be configured with an update time.
105G modules can transmit to 105G modules as well as other 105G modules. There can be multiple 105G and 105C modules in a network - as well as 105U I/O. Because the 105U protocol is peer-to-peer, there are few constraints on communications between multiple 105U modules.
Poll Messages
A 105G can also generate poll messages to remote 105U modules. These poll messages act in the same way as a start-up poll - the remote module immediately responds with update messages for any I/O mappings configured to the 105G.
Poll messages can be triggered by:
time period, configurable 1 – 4096 sec (1.1 hour), or
real time clock, or
on demand by the host device, by writing to a “trigger register” in the 105G
1.3.2 105G to 105G Network
Different types of 105G modules can communicate - for example, a Modbus 105G can communicate with an Ethernet 105G. I/O registers in one 105G can be transmitted to I/O registers in another 105G. When the 105G is configured, “mappings” can be entered linking I/O registers to registers in another 105G.
105U-G
105U-3
105U-1
105S-2
505U-K
105U-G
105U-3
105U-1
PLC
105U-C
PLC
Page 15
Chapter One Introduction
As well as the normal “I/O change” messages and update messages, the 105G has “block read” and “block write” messages for use with other 105G modules. These messages will transmit multiple register values instead of only one as in the normal 105U message. The block read/write messages increase the efficiency of radio communications where a 105G “sees” a large number of changes in its database at the one time. For example, if a host writes a block of 100 signal values to a 105G, and 20 of these values have changed since the last write-operation. If the block is mapped to another 105G, then the 105G can transmit all 20 values in one radio message, instead of 20 messages.
Normal I/O messages can be repeated by any type of 105U I/O module, however block read/write messages can only be repeated by other 105G modules.
Block Read Message
A block read message is a request to another 105G to transmit the values of a consecutive block of registers. The destination 105G will respond with the values, which will be stored in a corresponding block of registers in the originating 105G. A block read message can be triggered by:
time period, configurable 1 – 4096 sec (1.1 hour), or
real time clock, or
on demand by the host device, by writing to a “trigger register” in the 105G.
Block Write Message
A block write message transmits a consecutive block of register values from one 105G to a destination 105G. It can be triggered by:
time period, configurable 1 – 4096 sec (1.1 hour), or
real time clock, or
on demand by the host device, by writing to a “trigger register” in the 105G, or
a change-of-state event occurring within the block of I/O registers.
If a block write message has been configured to be transmitted on change-of-state, a “time window” is configured. When a change-of-state occurs in one of the registers in the block, the time window will be activated. All changes during the time window will be grouped together and transmitted as one block write message. That is, the block write message will not be sent immediately the first change-of-state occurs (unless the time window is configured to zero), but will be sent at the end of the time window - any other registers in the block that change during the time window will be sent as part of the same message. The time window can be configured from 0 – 255 seconds.
1.3.3 “Data Concentrator” Networks
105G units can act as “data concentrator” units to collect I/O from a local network of 105U wireless I/O modules and pass the I/O on to another 105G as a block.
Page 16
105U-G Wireless Gateway User Manual
Page 17 © September 2004
This type of network reduces the amount of radio traffic and is suitable for systems with a large number of I/O modules. The system is divided into local sub-networks, each with a 105G unit. The 105U modules transmit their I/O vlaues to the 105G. The 105G then transfers these values to the “central” 105G using a block transfer which is very efficient compared to a lot of individual I/O transmissions.
The data concentrator network is different than using the 105G as a repeater. A repeater re­transmits each message in the same format. A data concentrator collects the I/O values as a block, and transmits the complete block in one transmission.
1.3.4 105G Repeaters
Any 105U module can repeat a normal radio message, however only 105G modules can repeat a block message. 105G units connected to a host device can also act as a repeater for other modules.
Where a 105G is being used without a host device as a repeater or data-concentrator, it can be configured as “Repeater-only”. This allows the RS232/485 port to be used for on-line diagnostics. If the unit is a 105U-G-MD1, the “Repeater-only” configuration also allows this module to connect to 105S serial I/O modules.
TO HOST DEVICE
NETWORK OF 105U I/O UNITS
105U-G
105U-G
NETWORK OF 105U I/O UNITS
105U-G
Page 17
105U-G Wireless Gateway User Manual
Page 19 © September 2004
Chapter 2 OPERATION
2.1 Start-up
The 105G operating software and the database configuration are stored in non-volatile memory, however the database I/O register values are lost on power failure (in the same way as a PLC).
On start-up, the 105G sends "start-up poll" messages to remote modules based on the source address of inputs configured in the database (the start-up messages can be disabled by configuration). The remote modules respond with update messages for their inputs, which sets initial values in the 105G I/O database registers. The 105G provides a delay of 5 seconds between each start-up poll, to allow the remote module to respond and to avoid overloading the radio channel.
If there are a lot of remote modules, then this start-up stage may take a significant time, and this should be allowed for in the system design. The 105G has an internal battery charger feature and the use of a back-up battery should be considered if this start-up delay presents a constraint to system reliability. Start-up polls may be disabled for individual remote modules in the database configuration.
For the host device, the 105G provides an "Active" signal on the RS232 port (DCD pin 1). Its purpose is to indicate to the host that the 105G is now processing output messages for the remote modules. When the 105G powers down (or should an internal fault occur), the "Active" signal resets (turn “off” or “0”). When the 105G starts-up, it holds the "Active" signal in a reset condition (“off” or “0”) for a time equal to the number of remote addresses (or modules) configured times 5 seconds plus any delay if remote addresses are offline. For example, if there are 20 remote addresses configured in the 105G database, then the “active” signal will be held in the reset state for 100 seconds (20 x 5). During this period, the 105G will not change any output values in its database. After this time, the 105G will set the "Active" signal (to “on” or “1”) - the host can then send messages to the 105G to update the output values in the database.
2.2 Operation
The 105G database can hold values for 4300 I/O signals plus the 8 on-board I/O. The database registers (also called I/O registers) can be accessed by both the radio port and the fieldbus port. The host device can change values in the database via the fieldbus, and the 105G can transmit radio messages out with the new values. Radio messages can be received with new values for database registers, and these new values can be written to the host device or read by the host device, via the fieldbus.
The 105G operation must be configured before the 105G will function. Configuration is achieved by creating a configuration file on a PC and downloading this file to the 105G. The 105G configuration may also be "uploaded" to a PC for viewing and modification. For more information, refer to the Configuration section of this document.
Each I/O register in the 105G database has a 16-bit value. It doesn’t matter if the remote I/O is digital (discrete), analog or pulse. The host protocol driver in the 105G will convert the 16 bit value into a value that the host will understand. For example, if the host device requests a
Page 18
Chapter One Introduction
binary/digital read command, the 105G will convert the 16 bit value into a binary (1 bit) value before it responds.
An example of normal operation - assume that a remote module has address 14 and the 105G is address 1. Module #14 is configured with a mapping DI1 I/O Reg 76 at #1. When DI1 turns "on", module #14 transmits a message. If the 105G can hear this message, it will transmit an acknowledgment back to module #14, and updates the value of I/O register 76 in the 105G database. The host device can read I/O register 76 via the data-bus, or the 105G may write the value of I/O register 76 to the host device.
I/O registers that receive values from other 105U or G modules via radio are configured with a “Communications fail time”. If the 105G does not receive a message for this I/O register within the comms-fail time, then the I/O register is given a “comms fail” status which the host device can read.
I/O registers that transmit out to other 105U or G modules are configured with an “update time” and a “sensitivity”. The 105G will transmit a message to the configured remote output whenever the I/O register value changes by the sensitivity amount – if it has not changed within the update time, the 105G will send a message anyway. The 105G will make five attempts to send a message - if it does not receive an acknowledgment from the remote module, then the I/O register is given a “comms fail” status which the host device can read.
Each I/O register has an associated “status” register, which includes information such as comms-fail status. As well as each I/O register having an individual comms-fail status, each remote module has an overall comms fail status. This status is “set” (on) whenever a comms­fail occurs for an individual I/O register, and is “reset” (off) whenever a message is received from the remote module. The 105G can be configured to not send any update messages to a remote module if it senses that the remote module is in “comms fail” - that is, if any I/O register associated with the remote module is in “comms fail”. It will start sending update messages again when the 105G receives a message from the remote module. The default configuration is that output updates ARE sent during comms fail conditions.
105U-G
105U-1
DIN1
#14
#1
Page 19
105U-G Wireless Gateway User Manual
Page 21 © September 2004
2.3 Database
The 105G database (Radio Interface) has 10 000 registers, each of 16 bit size. The structure of the database is:
Registers Purpose
0 - 4299 I/O registers 4300 - 4399 On-board I/O 4401 - 4499 Comms-fail status and radio strengths for remote modules 5000 - 9499 Status registers - 16 bit status for each I/O signal 9500 - 9999 Status registers for block read/write messages
The register numbers may be used by the Host Protocol Driver to access I/O values and I/O status information. Each configured I/O point has a 16 bit value (in registers 0000 - 4299), and a 16 bit status value. The status register is located at 5000 plus the I/O value register. For example, an I/O point in register number 2560 has a status value in register number 7560 (5000 + 2560).
Details of the status register are provided in Appendix A. The most important part of the status register is the 15th or most significant bit - this indicates comm-fail status for the I/O register. If the most significant bit is set, then the I/O register is in comms-fail.
The host device can read the status registers. For example, the communications status of an output configured at register number 3001 can be examined by reading register number 8001 (5000 + 3001). If the register value is greater than 32767, then the 15th bit is set, indicating that the output has a communications failure.
On-board I/O and Internal I/O
The 105G has eight discrete I/O points. These may be used as inputs or as outputs. Inputs are linked to registers 4300-4307. That is, if a contact connected to DIO1 is “on”, then register 4300 is given an “on” value. Outputs are controlled from registers 4320-4327; that is, if register 4327 is set to an “on” value, then output DIO8 is activated.
Whenever an output register is set “on”, the corresponding input register is automatically set “off”. For example, if register 4321 is set to “1”, the 105G will also set 4301 to “0”. This means that if both the input and output registers corresponding to the same I/O point are used in the configuration, then the output register has priority.
Outputs may be written to by either the host device or by a remote 105U via the radio port. Input values can be sent to the host device or to a remote module via the radio port.
The 105G also monitors its battery voltage and supply voltage. These are stored in registers 4310 and 4311 respectively, as 16 bit values, scaled so that a value of 16384 decimal (hex
4000) corresponds to 8 V, and a value of 49152 (hex C000) corresponds to 40V. A low battery alarm is available at register 4308. This becomes active when the battery
voltage falls below 11.3V, and clears when the battery voltage rises above 11.8V. Supply
Page 20
Chapter One Introduction
voltage is also monitored, and an alarm is available at register 4309. This becomes active if the supply voltage falls below 8.0V, and clears when the supply voltage rises above 9.0V.
I/O Register Description I/O Register Description
4300 Input value DIO 1 4320 Output value DIO 1 4301 Input value DIO 2 4321 Output value DIO 2 4302 Input value DIO 3 4322 Output value DIO 3 4303 Input value DIO 4 4323 Output value DIO 4 4304 Input value DIO 5 4324 Output value DIO 5 4305 Input value DIO 6 4325 Output value DIO 6 4306 Input value DIO 7 4326 Output value DIO 7 4307 Input value DIO 8 4327 Output value DIO 8 4308 Low battery voltage status 4309 Supply voltage fail status 4310 Battery voltage value 4311 Supply voltage value
Page 21
105U-G Wireless Gateway User Manual
Page 23 © September 2004
2.4 The Host - 105G Link
For the host device, the 105G "looks" like a single device (or a "virtual PLC"), containing the I/O for the complete wireless I/O system.
DATABASE
I/O
"VIRTUAL PLC"
DATA-BUS
“HOST DE VICE”
105U-G
2.4.1 Modbus / DF1
The user selects whether the 105U-G-MD1 should act as a Modbus Master or Modbus Slave or DF1 device.
The data type and baud rate of the serial communications must be configured at the 105G to match the host. Data types can be 7 or 8 bit, even/odd/no parity, with 1 or 2 stop bits. Data rates can be 300 - 19200 baud.
The full 105G database (4300 registers) can be accessed by the Host Device.
2.4.2 Profibus
The Profibus port has auto-detect of baud rate from 9600 bits/sec to 12Mbit/sec - no configuration is required.
The Profibus units have internal hardware comprising the Profibus Interface. The Profibus Interface handles all Profibus DP Network communications. The internal Radio Interface is separate to the Profibus Interface, and handles all radio communications. I/O in the Radio Interface is linked to I/O in the Profibus Interface in a flexible way via ESeries Configuration Software.
The Profibus Slave interface provides a total of 416 I/O bytes, with a maximum 244 input bytes and maximum 244 output bytes. A Profibus byte can contain 8 discrete (binary) values, or two bytes can be used for a 16-bit analogue or pulse register. So the Profibus interface is limited to 1952 discrete inputs or 122 analogue inputs or a combination. The same applies for outputs.
For example, a Profibus host wants to read 800 discrete inputs (100 bytes) and write 400 discrete outputs (50 bytes). This will take up 150 bytes of the Profibus Interface, leaving 266 left. The remaining bytes could be used for 133 analogue I/O - up to 72 analogue inputs (244 – 100 discrete input bytes) plus 61 analogue outputs - or vice-versa.
The Profibus Master interface provides a total of 2048 input bytes and 2048 output bytes. A byte can contain 8 discrete (binary) values, or two bytes can be used for a 16-bit analogue or pulse register. So the interface is limited to 4300 discrete inputs (the limit of the 105G database) or 1024 analogue inputs (the limit of the HMS interface) or a combination. The same applies for outputs.
Page 22
Chapter One Introduction
2.4.3 Ethernet
The Ethernet port automatically handles Ethernet communications at 10 or 100 Mbit/sec. An IP address is entered so that other Ethernet devices can recognize the 105G.
The Ethernet units have internal hardware comprising the Ethernet Interface. The Ethernet Interface handles all Ethernet Network communications. The internal Radio Interface is separate to the Ethernet Interface, and handles all radio communications. I/O in the Radio Interface is linked to I/O in the Ethernet Interface in a flexible way via ESeries Configuration Software.
The Ethernet Interface provides a total of 2048 input bytes and 2048 output bytes. An Ethernet byte can contain 8 discrete (binary) values, or two bytes can be used for a 16-bit analog or pulse register. So the Ethernet Interface is limited to 4300 discrete inputs (the limit of the 105G database) or 1024 analog inputs (the limit of the Ethernet interface) or a combination. The same applies for outputs.
For example, an Ethernet host wants to read 500 analog inputs (1000 bytes). The remaining input bytes (1548) could be used for 12,384 discrete inputs - but the 105G database is not this big. Provided there are no outputs required, there could be 3800 discrete inputs (4300 – 500 analogs). If there are outputs required, then the number of discrete inputs available will be further limited.
2.5 Radio System Design
Each wireless I/O system can have up to 95 unit addresses, although up to 255 105K module can share the same unit address (refer to 105K User Manual).
Each 105U module can have up to 31 x 105S modules connected to it. These modules are addressed 96 - 127. More than one 105S module can have the same address, provided they are not connected to the same 105U module - that is, #100 via #16 is identified as a different module to #100 via #65.
A constraint that needs to be considered is the capacity of the radio channel. If there is too much traffic on the radio channel, then the system quickly becomes unreliable. The recommended maximum average traffic density is 100 messages per minute provided all radio paths are reliable. If there are marginal radio paths, resulting in re-tries of transmitted messages, then the maximum traffic density is reduced considerably. Each block read/write messages should be counted as two messages because of the length of these messages.
A 105G can be used as a repeater module for messages between other modules.
2.5.1 Radio Signal Strength
The 105G records the radio signal strength of remote modules that communicate directly (that is, not via repeaters). There are 95 database registers (4401 – 4495) which store the radio strengths – corresponding to remote addresses #1 - #95. The radio strength (RSSI) is measured in dBm (relative to 1mW of RF power). The RSSI value is stored in the 8 least significant bits of each register - a value of –84 dBm would be stored as decimal 84.
These database registers will hold the strength of the last message received from the address. If a message is received from a remote module via a repeater, then the measurement is recorded in the address of the last repeater. For example, if a message is received from #24 directly, then the RSSI will be recorded in register 4424. If a message is received from #24 via #25, then the RSSI is recorded in register 4425. The 105G will not know what the radio
Page 23
105U-G Wireless Gateway User Manual
Page 25 © September 2004
strength of the message from #24 to #25 is. If #25 is another 105G, then it can record this RSSI and this register could be mapped to an I/O register in the first 105G.
The RSSI registers can be read by the host device, or mapped to I/O registers in other 105G modules.
The first half of the register (8 most significant bits) will be decimal 0 (hex 00) if the remote module has active communications. If a comms fail status to this address occurs, the most significant bit will be set. For example, if the last message received from #38 is –99dBm, then the 16 bit value of register 4438 will be decimal 99 or hex 0063. If the “comms fail” status for #38 is set, the 16 bit value of register 4438 will become decimal 32,867 (32768 +
99) or hex 8063.
2.5.2 Repeaters
Radio paths may be extended by using intermediate modules as repeaters. A repeater will receive and re-transmit the radio message. Up to five repeater addresses can be configured ­that is, a radio message can pass through five intermediate modules. For normal I/O messages, any 105U module (except 105U-K modules) can be used as a repeater, however for block read/write messages, only 105G modules can act as repeaters.
2.6 Radio Comms Failure
The 105G has an internal "communications failure" (comms fail) status for each I/O point in its database. There is also a comms fail status for each module with direct communications ­see 2.5.1 above.
For I/O registers which are mapped to a remote output or another 105G, the comms fail status is set if the 105G does not receive an acknowledgment for a message being sent to that remote output. The comms fail status resets when a successful transmission occurs.
For I/O registers which have been mapped , from a remote input or another 105G, a comms fail time period may be configured. If a radio message for this I/O register has not been received within this time, then this registers comms fail status is set. The comms fail status will reset when a message is received for this register. If the comms fail time is configured as zero, then the comms fail status will never be activated.
The communications failure status is bit 15 of the status register for each I/O point. If the host device reads a register as a digital or binary value, then the 105G returns bit 15 of the register (0 or 1) - this is the comms fail bit of a status register.
It is important to use the comms fail status in the overall system design, as any system can fail.
The 105G also provides an additional comms failure feature to stop the 105G transmitting output messages to an individual remote address if the 105G already knows that this remote address is in communication failure. This prevents the 105G from congesting the radio channel with a lot of unnecessary transmissions (and re-transmissions). This function is called "Don’t Send if In Comm Fail" and is configurable by the user for each individual remote address. The 105G retains a "remote address comms fail" status for the remote addresses configured for this function. If any output with this remote address goes into communications failure, then the remote address comms fail status is set ("on" or 1) - every time an input with this remote address receives a radio message, then the remote address comms fail status is reset ("off" or 0). While the remote address comms fail status is set, the 105G disables any output messages being sent to this remote address.
Page 24
Chapter One Introduction
When this feature is configured, all output transmissions are stopped if communications with a remote module fails for a short period. They will start again when an input message from this module is received. If the 105G determines that a output message should be sent to an output which is disabled because of this feature, then the output message will not be sent and the comms fail status of that output is set ("on" or 1).
If it is desired to use this function with a remote 105U module, but there are no inputs from this module being used, then it is easy to configure an unused input or an internal input (mains fail or low battery voltage etc). It is the comms fail status for the input, which is used, not the input itself.
2.6.1 Monitoring Communications Failure
The host device can monitor the communications status of an I/O point by reading the status register for this point as a binary/discrete register. Modbus, and many other protocols, will convert a 16 bit register value to a binary/discrete value by returning the most significant bit ­for the status register, this corresponds to the comms status bit.
For example, to monitor the comms status of I/O register 1045, perform a binary/discrete read on register 6045 (the status register for 1045). A value of “1” will be returned if this I/O point is in comms fail, and a “0” returned if the status is normal.
If it is desired to monitor the comms status of all I/O points, it is more efficient to only monitor the comms status of one I/O point at each remote module (if this point is in comms fail, then all points at the remote module will be in comms fail). If this point is an input, then the comms fail time for this input can be made short, to give an early warning of a comms problem (this means that the corresponding update time for the input at the 105U will need to be short). If the point is an output, then the update time for the output should be made short.
2.7 Security Considerations
There are three dimensions of security considerations:
1. Failure to operate when required - or “operational reliability”.
The features discussed above optimize operating reliability. Using an acknowledgment and re-try protocol ensures that the transmitting module is aware whether the transmitted message has been transmitted reliably. The “comms fail” alarms provide indication if the radio link has failed to operate.
2. Mal-operation, or operating when not requested.
This problem occurs when an output is “triggered” by the wrong radio device. The 105G modules use frequency encoding and a very secure addressing system to ensure this does not occur. An additional security level using data encryption can also be selected.
3. Malicious operation, or “hacking”
This is the problem most associated with security concerns - the ability for someone to access information from a radio system by “listening-in”, or to cause damage by transmitting radio messages to force outputs.
A security option can be selected during the module configuration to protect against this. The security option (if selected) adds data encryption to radio messages. Modules in the same system are automatically configured with the encryption key, such that only these
Page 25
105U-G Wireless Gateway User Manual
Page 27 © September 2004
modules can understand each other. “Foreign” modules will hear the messages, but cannot decrypt the messages. For more information, refer to section 4.2.2.
Page 26
Chapter One Introduction
Chapter 3 INSTALLATION
3.1 General
The 105G module is housed in a rugged aluminium case, suitable for DIN-rail mounting. Terminals will accept wires up to 2.5 sqmm in size.
All connections to the module must be low voltage (SELV). Normal 110-240V mains supply should not be connected to any terminal of the 105G module. Refer to Section 3.3 Power Supply.
Before installing a new system, it is preferable to bench test the complete system. Configuration problems are easier to recognise when the system units are adjacent. Following installation, the most common problem is poor communications caused by incorrectly installed aerials, or radio interference on the same channel, or the radio path being inadequate. If the radio path is a problem (i.e. path too long, or obstructions in the way), then higher performance aerials or a higher mounting point for the aerial may rectify the problem. Alternately, use an intermediate 105U Module as a repeater.
The foldout sheet 105U-G Installation Guide provides an installation drawing appropriate to most applications. Further information is detailed below.
Each 105G module should be effectively earthed/grounded via the “GND” terminal on the 105U module – this is to ensure that the surge protection circuits inside the module are effective.
3.2 Antenna Installation
The 105 module will operate reliably over large distances. The distance which may be reliably achieved will vary with each application – depending on the type and location of antennas, the degree of radio interference, and obstructions (such as hills or trees) to the radio path. Please refer to your distributor for the expected maximum distance to comply with local radio regulations. Where it is not possible to achieve reliable communications between two 105 modules, then a third 105 module may be used to receive the message and re-transmit it. This module is referred to as a repeater. This module may also have input/output (I/O) signals connected to it and form part of the I/O network – refer to Chapter 4 Configuration of this manual.
An antenna must be connected to each 105 module using the coaxial female connector which protrudes though one of the end plates.
To achieve the maximum transmission distance, the antennas should be raised above intermediate obstructions so the radio path is true “line of sight”. Because of the curvature of the earth, the antennas will need to be elevated at least 5 metres above ground for paths greater than 5 km (3 miles). For short distances, the modules will operate reliably with some obstruction of the radio path. Obstructions which are close to either antenna will have more of a blocking affect than obstructions in the middle of the radio path. For example, a group of trees around the antenna is a larger obstruction than a group of trees 100 metres from the antenna.
An antenna should be connected to the module via 50 ohm coaxial cable (eg RG58 or RG213) terminated with a male coaxial connector. The higher the antenna is mounted, the greater the
Page 27
105U-G Wireless Gateway User Manual
Page 29 © September 2004
transmission range will be, however as the length of coaxial cable increases so do cable losses. For use on unlicensed frequency channels, there are several types of antennas
suitable for use. It is important antenna are chosen carefully to avoid contravening the maximum power limit on the unlicensed channel - normally the net gain of the antenna/cable configuration should be no more than 2dB.
The net gain of an antenna/cable configuration is the gain of the antenna (in dBi) less the loss in the coaxial cable (in dB).
The gains and losses of typical antennas are
Antenna Gain (dB)
Dipole with integral 3m cable 0 Dipole without cable 2 5dBi Collinear(3dBd) 5 8dBi Collinear (6dBd) 8 3 element Yagi 5 6 element Yagi 10
Cable type Loss (dB per 10 m)
400-500MHz 869MHz
RG58 -3 -5 RG213 -1.5 -2.5 Cellfoil -1.5 -3 The net gain of the antenna/cable configuration is determined by adding the antenna gain and
the cable loss. For example, a 3 element Yagi with 15 metres of RG58 has a net gain of
0.5dB (5dB – 4.5dB) at 450MHz. Connections between the antenna and coaxial cable should be carefully taped to prevent
ingress of moisture. Moisture ingress in the coaxial cable is a common cause for problems with radio systems, as it greatly increases the radio losses. We recommend that the connection be taped, firstly with a layer of PVC Tape, then with a vulcanising tape such as “3M 23 tape”, and finally with another layer of PVC UV Stabilised insulating tape. The first layer of tape allows the joint to be easily inspected when trouble shooting as the vulcanising seal can be easily removed.
Where antennas are mounted on elevated masts, the masts should be effectively earthed to avoid lightning surges. The 220MHz and 400 – 500MHz radios are fitted with surge protection, however the 868MHz radio does not. For high lightning risk areas, additional surge suppression devices are recommended. If the antenna is not already shielded from lightning strike by an adjacent earthed structure, a lightning rod may be installed above the antenna to provide shielding.
3.2.1 Dipole antenna.
A unity gain dipole is the normal antenna for use on unlicensed channels. As it does not provide any gain, then the power transmitted from the antenna will be the same as the power out of the module, and hence will not exceed the permitted power of the unlicensed channel.
Page 28
Chapter 3 Installation
Dipole antennas should be mounted vertically, at least 1 metre away from a wall or mast for maximum performance.
3.2.2 Yagi antenna.
Yagi antennas are directional. That is, they have positive gain to the front of the antenna, but negative gain in other directions. This may be used to compensate for coaxial cable loss for installations with marginal radio path.
Yagi antennas should be installed with the central beam horizontal and must be pointed exactly in the direction of transmission to benefit from the gain of the antenna. Also note that Yagi antennas normally have a drain hole on the folded element - the drain hole should be located on the bottom of the installed antenna.
The Yagi antennas may be installed with the elements in a vertical plane (vertically polarised) or in a horizontal plane (horizontally polarised). For a two station installation, with both modules using Yagi antennas, horizontal polarisation is recommended. If there are more than two stations transmitting to a common station, then the Yagi antennas should have vertical polarisation, and the common (or “central” station should have a dipole or collinear (non-directional) antenna.
1m minimum
COLINEAR ANTENNA
MAST
EARTH STAKE IF GROUND CONDITIONS ARE POOR, INSTALL MORE THAN
INSTALL AERIAL ABOVE LOCAL OBSTRUCTIONS
ANT
905U
SURGE ARRESTOR (OPTIONAL)
COAXIAL CABLE
WEATHERPROOF CONNECTORS WITH “3M 23” TAPE
STRESS RELIEF LOOP
PROVIDE GOOD GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR
GND
for best performance
105U
Page 29
105U-G Wireless Gateway User Manual
Page 31 © September 2004
3.2.3 Collinear antenna.
A collinear antenna may be used in the same way as a 3 element Yagi to compensate for the losses in long lengths of coaxial cable. This type of antenna is generally used at a central site with more than one remote site or at a repeater site. The collinear antenna looks similar to the dipole, except that it is longer.
3.3 Power Supply
The 105G power supply is a switch-mode design which will accept either AC or DC supply. The module includes an integral battery charger for a backup battery.
The module accepts supply voltages in the following ranges :
12 – 24 volts AC RMS or 9 – 30 volts DC at the “supply” terminals, or
10.8 –15 volts DC at the “battery” terminals.
The power supply should be rated at 1.5 Amps.
105U
A
ntenna installed with drain holes down
Coax feed looped at connection
90
o
Page 30
Chapter 3 Installation
3.3.1 AC Supply
The AC supply is connected to the “SUP1” and “SUP2” terminals as shown below. The AC supply should be “floating” relative to earth.
3.3.2 DC Supply
For DC supplies, the positive lead is connected to “SUP1” and the negative to “GND”. The positive side of the supply must not be connected to earth. The DC supply may be a floating supply or negatively grounded.
The module may also be powered from an external 11 – 15 VDC battery supply without the need for a “normal” supply connected to “SUP1”. This external battery supply is connected to “BAT+” and “GND” terminals. The positive lead of the external supply should be protected by a 5A fuse.
Upon failure of the normal supply, the module may continue to operate for several hours from a backup battery. The battery charger is designed for sealed or vented lead acid batteries between 5 and 24 amphours - other types of batteries should not be used. Typically, a 5 Ahr battery will supply the 105G for 1 – 2 days, depending on the type of 105G.
On return of normal supply, the unit will recharge the battery. The maximum output of the battery charger is 0.7A when the supply voltage is greater than 12V, and 0.3A for less than 12V.
SUP1 SUP2 GND BAT+
12 – 24 VAC
Power Supply AC Out
- +
105U-G
Optional Battery
Fuse 5A
GND SUP1 SUP2 GND BAT+
9 – 30 VDC
Power Supply DC Out
- +
105U-G
Optional Battery
Fuse 5A
+
SUP1 SUP2 GND BAT+
- +
105U-G
BATTERY SUPPLY
11-15 VDC
Fuse 5A
Page 31
105U-G Wireless Gateway User Manual
Page 33 © September 2004
The 105G monitors the power supply and provides the following internal values, which can be mapped as I/O values:
Power failure (I/O Reg 4309) - if the supply voltage drops below 8V, this status value is
set on, and set off again when the voltage is more than 9V. For AC Supplies, this indicates low voltage at approximately 10 VAC, and the status is cleared when the supply voltage rises above approximately 12VAC
Low battery voltage (I/O Reg 4308) - this status value is set on if the battery voltage
drops to 11.3, and resets off when the battery voltage is more than 11.8V.
Battery voltage value (I/O Reg 4310) - 8 – 40VDC corresponds to hex 4000 – hex C000.
Supply voltage (I/O Reg 4311) - 8 – 40VDC corresponds to hex 4000 – hex C000.
3.3.3 Solar Supply
A 105G can be powered from a solar supply using an external regulator. If a 12V solar supply is used, the 12V battery can be connected to the battery supply connections of the 105G and the 105G will monitor for low battery status and also battery voltage. If a 24V solar supply is used, the 24V battery should be connected as a DC supply (SUP1 and GND) ­the supply voltage can be monitored however the “supply fail” voltage will activate too low to be used as a battery fail status.
3.4 Input / Output
The 105G has eight on-board discrete/digital I/O. These act as both discrete inputs and discrete outputs.
3.4.1 Digital Inputs / Outputs
All eight of the 105G DIO terminals may be used as discrete inputs. These inputs are suitable for voltage free contacts (such as mechanical switches) or NPN transistor devices (such as electronic proximity switches). PNP transistor devices are not suitable. Contact wetting current of approximately 5mA is provided to maintain reliable operation of driving relays.
Each digital input is connected between the appropriate “DIO” terminal and common “COM”. Each digital input circuit includes a LED indicator which is lit when the digital input is active, that is, when the input circuit is closed. Provided the resistance of the switching device is less than 200 ohms, the device will be able to activate the digital input.
+
_
DIO
DIO GND
105U-G
Voltage-free contact in
p
ut
Transistor in
p
ut
V+
V
-
Page 32
Chapter 3 Installation
All eight of the 105G DIO terminals may also be used as discrete outputs. The digital outputs are transistor switched DC signals, FET output to common rated at 30VDC 500 mA.
Digital outputs may be configured to individually turn off if no command message is received to that output for a certain period. This feature provides an intelligent watch dog for each output, so that a communications failure at a transmitting site causes the output to revert to a known state. See Chapter 4 Configuration for further details.
The output circuit is connected to the appropriate “DIO” terminal. Each digital output circuit includes a LED indicator which is lit when the digital output is active.
3.5 Serial Port
3.5.1 RS232 Serial Port
The serial port is a 9 pin DB9 female and provides for connection to a terminal or to a PC for configuration, field testing and for factory testing. It is also used by the Modbus/DF1 version for fieldbus connection.
This port is internally shared with the RS485 - ensure that the RS485 is disconnected before attempting to use the RS232 port. Communication is via standard RS232 signals. The 105G is configured as DCE equipment with the pinout detailed below.
DB9 Connector Pinout:
Pin Name Direction Function
1DCDOut
Used for "active" signal.
2 RD Out Serial Data Output 3 TD In Serial Data Input 4DTR In
Data Terminal Ready - may be used by Host Protocol Driver
5 SG Signal Ground 6 DSR Out Data Set Ready - always high when unit is powered on. 7 RTS In Request to Send - may be used by Host Protocol Driver 8 CTS Out Clear to send - may be used by Host Protocol Driver 9 RI Ring indicate - not connected
_
+
DC
Load
Max 30VDC
0.5A
DIO DIO
GND
105U-G
Page 33
105U-G Wireless Gateway User Manual
Page 35 © September 2004
Hardware handshaking using the CTS/RTS lines is provided, and are under the control of the Host Comms Driver. Example cable drawings for connection to a DTE host (a PC) or another DCE host are detailed below:
105U-G DB9
105U-G DB9
3.5.2 RS485 Serial Port
RS485 should not be used with the DF1 unit. The RS485 port provides for communication between the 105G unit and its host device using a multi-drop cable. Up to 32 devices may be connected in each multi-drop network. Note that the RS485 port is shared internally with the
RS232 port - make sure that the RS232 port is disconnected before using the RS485 port. RS485 is a balanced, differential standard but it is recommended that shielded, twisted pair
cable be used to interconnect modules to reduce potential RFI. An RS485 network should be wired as indicated in the diagram below and terminated at each end of the network with a 120-ohm resistor. On-board 120 ohm resistors are provided and may be engaged by operating the single DIP switch in the end plate next to the RS485 terminals. The DIP switch should be
105U-G
INTERNAL
EXTERNAL RESISTOR REQUIRED
TERMINATING RESISTOR SWITCH ON = TERMINATION OFF = NO TERM.
RESISTOR
Page 34
Chapter 3 Installation
in the “1” or “on” position to connect the resistor. If the module is not at one end of the RS485 cable, the switch should be off.
It is important to maintain the polarity of the two RS485 wires. On the 105G, terminal A (the terminal on the right) is positive and terminal B is negative.
Page 35
105U-G Wireless Gateway User Manual
Page 37 © September 2004
3.6 Profibus Port
The Profibus RS485 connector is a D9 connector in the top end-plate of the module (see below).
105U-G-PR1 (Profibus Slave) End Plate:
Note: If the “Use Rotary Switch Address” option in configuration software is selected, the two rotary switches are used to specify the Profibus Node Address in the range 0 – 99. In this case, the value on the left switch is multiplied by 10 and added to the value on the right switch to give the node address.
Where the 105G module is mounted at the end of the RS485 link, the RS485 link should be terminated by switching the termination switch “on” (down in the above diagram).
105U-G-PR2 (Profibus Master) End Plate:
For the Profibus Master 105G a second, unused, connector is also present.
ANTENNA CONNECTION (869MHz Only)
PROFIBUS D9
CONNECTOR
SELECTOR SWITCHES
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
RS485
TERMINATION
SWITCH
ANTENNA CONNECTION (869MHz Only)
PROFIBUS D9
CONNECTOR
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
UNUSED D9
CONNECTOR
Page 36
Chapter 3 Installation
The Profibus RS485 connection should be made to pins 3 and 8 of the Profibus D9 connector. The pinouts for this connector are:
Pin Description
1 Not connected 2 Not connected 3 +ve RS485 (Positive) 4 RTS (request to send) 5 GND - Isolated GND from RS485 side 6 +5V - Isolated 5V from RS485 side 7 Not connected 8
-ve RS485 (Negative)
9 Not connected
3.7 Ethernet Port
For 105U-G-ET1 modules only. The Ethernet connection uses a standard RJ45 connector on the top end-plate of the module.
The selector switches should all be “off” (in the diagram below, “off” is up).
ANTENNA CONNECTION (869MHz Only)
RJ45 ETHERNET
CONNECTION
SELECTOR
SWITCHES
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
Page 37
105U-G Wireless Gateway User Manual
Page 39 © September 2004
3.8 Modbus Plus Port
For 105U-G-M+1 modules only. Connection to the Modbus Plus Network is via the 9-pin D-SUB connector located at the
antenna end of the module. Pin-outs are outlined in the table below.
See section on configuration for description of selector switches.
Modbus Plus 9-pin D-SUB Connector:
Pin Name
1 Cable Shielding 2 MBP Line B 3 MBP Line A Housing PE
ANTENNA CONNECTION (869MHz Only)
D9 MODBUS
PLUS
SELECTOR SWITCHES
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
Page 38
Chapter 3 Installation
3.9 DeviceNet Port
For 105U-G-DE1 modules only. Connection to the DeviceNet Network is via the 5-pin plugable screw terminal connector
located at the antenna end of the module. Pin-outs are specified below.
5-pin plugable screw terminal fieldbus connector:
Pin Signal Description
1 V- Negative Supply Voltage 2 CAN_L CAN_L bus line 3 SHIELD Cable shield 4 CAN_H CAN_H bus line 5 V+ Positive supply voltage
DeviceNet uses termination resistors at each physical end of the bus. The termination resistor should be 121 ohm. This should be connected between CAN_H and CAN_L on the bus.
ANTENNA CONNECTION (869MHz Only)
DEVICENET
CONNECTION
SELECTOR
SWITCHES
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
Page 39
105U-G Wireless Gateway User Manual
Page 41 © September 2004
Chapter 4 CONFIGURATION
4.1 Introduction
A Windows program is provided to configure the 105U system. The configuration is done on a system basis - referred to as a “project” in the program. After the system configuration is entered, the configuration file can be loaded into each module via the RS232 port.
Each Project is configured with:
a system address, which is common to every module in the same system, and is used to
prevent "cross-talk" between modules in different systems. Separate networks with different system addresses may operate independently in the same area without affecting each other. The system address may be any number between 1 and 32 767. The actual value of the system address is not important, provided all modules in the same system have the same system address value. A system address of zero should not be used. The configuration program automatically offers a random number for the system address
- you can change this to any number in the valid range but we recommend that you use the random number.
a password for access protection. This is an optional feature. If selected, the project file
can only be opened by entering the correct password.
a security encryption key, used to encrypt and decrypt radio messages. This is an
optional feature. If selected, the configuration program will offer a random security key, or this can be over-written with your own key. A key is a string of any 8 ASCII characters.
Each module in the project is configured with a unit address. Each module must have a unique unit address within the one system. A valid unit address for a 105G is 1 to 95. A network may have up to 95 addresses communicating directly via radio (unit addresses 1 to
95). 105U I/O modules can have up to 31 modules communicating via RS485 (unit addresses 96 to 127).
The configuration program may allocate more than one unit address to a 105G if it is required because of the size of the system. If this is necessary, it will be done automatically by the configuration software.
Configuration consists of:
1. selecting the types of modules in the system and selecting address values
2. linking (called “mapping”) I/O registers to remote I/O
3. setting operating parameters such as change sensitivities and update times
4. selecting “block mappings” - only for block transfer of I/O registers between multiple
105G modules
5. selecting fieldbus addressing (all versions), and serial port configuration (Modbus and
DF1 only)
6. linking Radio Interface I/O registers to Fieldbus Interface I/O bytes (all modules except
for MD1)
Page 40
Chapter 3 Installation
All of these steps must be performed to configure the 105G module.
4.2 Configuration Program
The configuration software is available on a CD, and needs to be installed on your PC before you can use it. The CD contains a setup file called setup.exe. Select the configuration software window on the Product CD and an installation Wizard will guide you through the installation procedure. To upload and download configuration files to a module, you will need a RS-232 serial cable as shown below.
4.2.1 Program
Operation
Start the software by either clicking on the start bar and navigating to the Configuration menu or by running ESERIES.EXE in the directory selected in the setup stage.
The Initial screen will appear.
From the initial screen, , you can select an existing project, or start a new project. The name of the project will create a new folder which will eventually contain the configuration files for the modules in this system. Project folders are located under the folder \Projects\ - for example, if you create a project called “Fire Pumps”, then the files for this project will be found in the folder c:\……\Projects\Fire Pumps\.
105 End DB9 Male
1 2 3 4 5 6 7 8 9
Required
Optional
PC End
DB9 Female
1 2 3 4 5 6 7 8 9
Page 41
105U-G Wireless Gateway User Manual
Page 43 © September 2004
When you have selected the project, a screen will appear where you may enter the
system address. If you are editing an existing
project, the system address will already have been entered. Do not change the system address unless you are going to re-program all of the modules in the system.
Password. You have the option of entering a password to protect the configuration files against unauthorized changes. When you open a new project, you will be asked to enter a password - if you do not enter any text - that is, press “ESC” or “Enter”, then password protection is disabled. If you do enter a password, then you will need to enter this password to access the project. Without the password, you are unable access the project
The password can be between 6 and 256 characters. You can also change password at any time by over-typing the passowrd.
If you are starting a new project, you have the option of “Enabling Security”. This option enables encryption of the data sent over the radio. - please read Section 4.2.2 and the associated warnings before using this option.
To proceed with the configuration, double-click on the project name on the menu on the left side of the screen. “Units” will appear. You can now enter the types of units which will be used in the system. If you double-click on “Units”or select the “+” sign beside “Units”, then the modules that have already been created will be displayed.
Page 42
Chapter 3 Installation
Loading configuration from an existing module
To load the configuration from a module, connect the module to the PC via the RS232 cable, put the module into “Configuration Mode” by pressing the configuration button on the top end-plate, and click on “Load Unit”. This will allow you to view the module configuration, change it, or copy it for another module - refer to section
4.10 for full details.
Adding a new module to the system configuration
To add a new module to the system configuration, click on “Units” on the left-hand menu and then “Add Unit”. Select the type of module from the list. For 105G modules, you will be asked to select the bus protocol. This must match the 105U-G module type you have installed.
You have the option of selecting a unit address for the module, or allowing the program to select one automatically. If you choose to select the unit address the program will display the list of available addresses for you to select - valid addresses are 1 – 95.
The default name for a unit will include the unit address. For example, “105­G#10” is a 105U­G module with unit address 10. You can change the name of a unit
- for example, you could replace the default name with “Pump Station 14”.
Page 43
105U-G Wireless Gateway User Manual
Page 45 © September 2004
Deleting a Unit
A module can be deleted from the configuration by highlighting the unit and selecting “Delete Unit”.
Page 44
Chapter 3 Installation
4.2.2 Security
There are two security features available. You can enter a password to protect the configuration files, and you can enable security encryption of the radio transmissions.
The password can be between 6 and 256 characters. The password is case sensitive and any ASCII characters can be used. If you have entered a password, then this password will need to be entered whenever the configuration is changed. You are able to change the password from the “Utilities” menu. If unauthorised access to the files is a concern, we recommend that you change the password regularly or whenever there is a change of staff.
Data Encryption is an additional level of security. The security option uses a 64 bit security key to provide data encryption of the radio messages. All modules in the same system will be configured with the same security key used to encrypt and decrypt the messages. This feature is available for modules with firmware version 2.1 and higher. If you are adding modules to an old system which does not have the security encryption feature, then you cannot use security encryption on the new modules.
Note that the security key is different than the password.
To enable the security encryption, select the “Enable Security” box on the project display.
An 8-character random security key is automatically generated. If desired, a different security key may be entered and you will be prompted to enter the security code a second time to confirm. The security key can be any characters or numbers. Characters are case sensitive. The security key will never be displayed.
If you do not enable security, there will be no data encryption of the radio messages. This
is the default setting.
If a security key has been entered, this key is downloaded into each module as part of the
configuration download process. You can download another configuration at any time ­if the security key is different, or if there is no security key in the new configuration, the old key will be over-written.
You can change the security key in the configuration files simply by entering a new
security key in the security key window. You will be prompted to confirm the new security key. Note that if you change the security key, it will not match the security key previously loaded into existing modules.
If you want to change a configuration, we recommend that you change the archived
configuration, and then download the configuration onto the module. The archived configuration already has the valid security key.
If you lose the archived configuration, you can upload the configuration from a module,
but you cannot upload a security key. That is, you can upload the module configuration, view it, change it - but if you don’t know the original security key, the old key will be over-written when you download the new configuration. This module will no longer communicate with other modules in the system as the security key is different.
The security options provide security against a “hacker” in the following way:
A hacker cannot listen-in to radio messages without the security key to decrypt the radio
messages. Similarly, a hacker cannot force outputs by transmitting a radio message to a module without the security key.
A hacker cannot access the security key from an installed module or from the
configuration files.
Page 45
105U-G Wireless Gateway User Manual
Page 47 © September 2004
The archived configuration files cannot be changed, downloaded or uploaded without the
password.
Warning!! These security options provide a high level of security, but no data-security system can
provide “100% protection”. But it does make it very difficult for someone to interfere with the 105U system - difficult to the point where there would be many easier alternate ways to cause malicious damage.
The password must be kept in a secure place. Security procedures need to be adopted. If staff with access to the password leave your organisation, we recommend that the password be changed.
We recommend that you use a random 8-character string for the security key and that you do not record the key. It is not necessary to know what the security key is. The key will be recorded in the archived configuration files, and therefore the configuration files should be held in a secure place and backed up.
The security key does not prevent a hacker uploading a configuration from a module and downloading with a new security key. This module will no longer operate with other modules in the system. To prevent this, unauthorised access to modules must be prevented.
If you lose the configuration files, you can regenerate these by uploading the configuration from every module in the system into a new project with a new security key. After uploading each module, download the configuration with the new security key.
If you wish to change the security key, simply enter a new key in the configuration program, and download the new configuration to all modules in the system.
Note on Ethernet 105U-G. You are able to access the module configuration of an Ethernet 105G via the Ethernet port. To prevent this access, do not select “Enable Ethernet Debug” on the Ethernet configuration display - see section 4.8.
Page 46
Chapter 3 Installation
4.3 Mappings 105G to 105U I/O Modules
To transfer remote input signals to a 105G, or transfer a value to a remote output from a 105G, you set up “I/O mappings”. You enter mappings into the source unit, not the destination unit. That is, you configure a mapping at the “input” module. If you want to transfer an input signal at a 105U module to a 105G register, you enter a mapping at the 105U I/O module. If you want to transfer a 105G register to an output signal at a 105U module, you enter a mapping at the 105G module.
To configure mappings, double-click on the module in the left-hand menu - the menu will expand with selections for that module. Select “Mappings”.
Each mapping comprises only one I/O point. “Block Mappings” provide more advanced communications between 105G modules.
4.3.1 Mappings from Inputs at Remote 105U I/O Modules
Refer to the 105U I/O User Manual. When mapping inputs to a 105G, you will be asked to select an I/O Register. Select the “…”
box beside the “At I/O Register” heading - this will allow you to select the I/O register between 0 and 4299.
Page 47
105U-G Wireless Gateway User Manual
Page 49 © September 2004
Any I/O registers that have already been selected will have a colour shading. The update times, analogue sensitivities for these mappings can be set as per normal I/O
mappings. To map several inputs to consecutive I/O registers, use “Shift”-select or “Ctrl” - select to
highlight the inputs, and select the first I/O register in the range. The selected mappings will be entered with consecutive I/O registers.
For each “remote input” configured to a 105G, there is a comms-fail time parameter in the 105G. If the 105G does not receive a message destined to that I/O register within the “comms fail” time, then the “comms fail” status for that I/O register will be set - the most significant bit of the status register will be set to 1. The comms fail time should be more than the corresponding update time at the remote input.
Page 48
Chapter 3 Installation
To set the comms fail times, select the 105G, and select the “Comms Fail Time” option. Each remote input already mapped to the 105G will automatically be listed, including the remote module containing the mapping.
The default value for the comms-fail time is “disabled” or zero. To enter a time, select the I/O register from the list. The comms-fail time should be greater than the update time of the remote input.
4.3.2 Mappings from 105G to Outputs at Remote 105U I/O Modules
Mappings can be entered in the 105G to remote outputs. Select the “Mappings” option under the 105G. Select an I/O register and select the remote module and the output channel.
To map several consecutive I/O registers to several outputs, select the first I/O register in the range and use “Shift”-select or “Ctrl” - select to highlight the multiple outputs. The selected mappings will be entered with consecutive I/O registers.
Page 49
105U-G Wireless Gateway User Manual
Page 51 © September 2004
Change Sensitivities
Radio messages to remote modules can be change messages (when the value of the I/O register changes) or update messages (when the update time has elapsed). If a change message is sent, the update period restarts.
You can configure the amount of change required to trigger a change message - this is called the change sensitivity. Sensitivities are configured for blocks of I/O registers - that is, each I/O register does not have a unique sensitivity. You can configure up to 50 sensitivity values
- that is, there can be 50 blocks of registers with different sensitivities. For more information on this, refer to section 4.5.
Page 50
Chapter 3 Installation
Update Times
To change the update times of output mappings, select the Update Times option. Any I/O registers that have already been mapped to remote outputs will automatically be listed. The default update time is 10 minutes.
Changing Multiple Settings
You can change the Comms Fail Times or Update Times of several I/O points simultaneously by using the <Shift> Select feature. For example, if you want to change all times to 1 minute, you could change each individually, or you could “block” all entries using the “Shift” Select feature and select “Edit”. You only need to enter the change once to change all of the inputs selected. This feature is also available with the other configurable parameters.
4.3.3 Don’t Send if in Comm Fail
You can configure a special “Don’t Send if in Comms Fail” mapping. If this is configured for a particular remote module, the 105G will not transmit output messages to this remote address, if there is a communications failure status on any input or output configured for the same remote address. Output messages will re-start when a message is received from the remote module. The use of this option can prevent the radio channel becoming congested if there are many outputs at that module.
Page 51
105U-G Wireless Gateway User Manual
Page 53 © September 2004
To configure this special mapping, select the “New Don’t Send in Comms Fail Mapping” box. You will be asked to select which remote module this function applies to. You can enter more than one of these mappings if there are more than one modules.
4.3.4 Startup Polls
You can enter start up polls for remote modules by using the “New Poll Mapping” box. This function is the same as for the 105U I/O modules. A start-up poll is a special message sent when the 105G starts up. When the remote module receives a start-up poll, it will immediately respond with update messages for all its inputs that are mapped to the 105G. This allows the 105G to have correct values on start-up.
4.3.5 Polls to Remote Modules
It is possible for a 105G to send a poll to a remote module at other times apart from start-up. A poll can be sent under the following events:
based on a configurable time period
based on real time clock
on-demand by the host device.
For information on this configuration, refer to the next section on “Block Mappings”.
4.4 Mappings from 105G to other 105G Modules
Individual links between 105G modules can be configured under the “Mappings” selection as described in the previous section. For example, if you want to transfer I/O Reg 144 in 105G#2 to I/O Reg 286 in 105G#3, you can enter the following mapping:
Whenever I/O Reg 144 changed by the sensitivity amount, 105G#2 would send a message to 105G#3 to write the value in I/O Reg 286. The problem arises if there are a lot of these mappings. Each radio message only relates to one register-register link. If you want to map 1000 registers from one 105G to another, then this could generate a lot of radio messages.
To get around this problem, it is possible to configure “block mappings”. With a block mapping, multiple registers (a “block of registers”) can be transferred together in the one radio message. This improves the efficiency of the radio communications.
Page 52
Chapter 3 Installation
Read/Write Mappings
The mappings can be “read” or “write” mappings. A Read mapping is a request sent to another 105G to return a block of values. A Write mapping is a message sending a block of values to another 105G. A Read mapping from 105G#2 to 105G#3 could be the same as a Write mapping from 105G#3 to 105G#2 (that is, in the reverse direction) - except the Read mapping is initiated from #2 and the Write mapping is initiated from #3.
Word/Bit Mappings
Read and Write mappings are also selected as Word or Bit mappings - that is, you can select a Read Word mapping or a Read Bit mapping and you can select a Write Word mapping or a Write Bit mapping. “Word” refers to a complete 16-bit register value; “Bit” refers to the value of the most significant bit of a register - this bit is the “binary value” or “digital value” of the register.
If you use a Word block mapping of 50 registers, you are transferring a block of 50 x 16-bit values. If you use a Bit block mapping of 50 registers, you are only transferring the digital value of each register - that is 50 x 1 bit values. This is a lot more efficient for a radio message, but Bit mappings are only suitable for discrete or digital I/O. A Bit mapping will convert the 16-bit register to a single bit, transfer it and store the bit value in the most significant bit of the destination register.
Note: The maximum block size for each block mapping is 64 registers.
REMOTE
105G
BLOCK OF I/O
REGISTERS
ACKNOWLEDGMENT
BLOCK WRITE
MESSAGE
BLOCK OF I/O
REGISTERS
READ REQUEST
BLOCK READ
MESSAGE
LOCAL
105G
Page 53
105U-G Wireless Gateway User Manual
Page 55 © September 2004
4.4.1 Entering a Block Mapping
Select the “source” 105G on the left hand menu - select “Block Mappings” and then “New Block Mapping” from the right-hand display. The Block Mapping Configuration display will appear.
Select the “Command Type” from the pop-down window in the centre of the display. The red arrow will confirm the direction of the block transfer. Now select the destination module
- only the 105G modules already configured will be shown. If you need to use repeaters in the radio link, enter the repeater addresses, starting with the repeater closest to the source module.
Under “Source Gateway”, enter the I/O Register and I/O Count. The I/O Register is the first register in the block and the I/O Count is the number of registers - in the above example, the block of registers will be 110 – 124 (15 registers starting at I/O Reg 110).
If you are entering a Write mapping, then the values in this block will be sent to another 105G. If it is a Read mapping, then values from another 105G will be sent to this block.
Under “Destination Gateway”, enter the I/O Register - this is the first register in the block. You do not need to enter the block size as this will always be the same as the block size in the source 105G. In the above example, the destination block will be I/O registers 32 – 46 (15 registers starting at register 32). So, in the above example, a block of 15 x 16-bit values will be written from I/O Reg 110 – 124 in 105G#1 to I/O Reg 32 – 46 in 105G#2.
Each mapping entered is allocated a status register - the register number appears on the right hand of the Block Mapping display. These registers store relevant status information about the block mapping - the structure of these Block Mapping status registers is shown in Appendix 1.
Page 54
Chapter 3 Installation
In the above example, the status register for the block mapping has been automatically assigned to register 9500.
The rest of the mapping configuration involves the mapping trigger - or what initiates the mapping message.
Mapping “Triggers”
A block mapping can be “triggered” or initiated by several different methods.
By the host device writing to a “trigger register” in the source 105G - the block mapping
message is sent each time the host device writes to the trigger register.
By configuring a time period - the 105G will send the block mapping message if this
time period has elapsed since the last message has been sent.
By configuring a real-time clock - the 105G will send the block mapping message at the
configured times.
By a change-of-state within the I/O block. This can only occur for Write mappings. If a
value in the block changes by more than the sensitivity amount, then the block message will be sent. You can enter a delay period such that the message is sent after the delay period.
Combinations of the above triggers can occur - for example, the block mapping message will be sent if a change-of-state occurs, AND at the configured real-time, AND when the host device writes to the trigger register.
4.4.2 Host Device Trigger
Each block mapping that is configured is allocated a status register in the range 9500 – 9999 (i.e. one status register for a maximum of 500 possible block mappings). The status register for a given block mapping is shown on the right hand side of the Block Mapping display (under the heading “Status Lcn”). Bit 13 of the associated status register is the “Force bit” - if Bit 13 is turned “on”, then the associated mapping is forced, or triggered. Depending on the module version, a particular algorithm may apply to the setting of the force bit. This algorithm and details of the block status registers are given in Appendix 1.
Page 55
105U-G Wireless Gateway User Manual
Page 57 © September 2004
4.4.3 Time Period
On the Block Mapping display, there are two configuration windows - “Period” and “Offset” - these determine the time period trigger and real-time trigger.
For a time-period trigger, select “Continuous” in the “Period” pop-down window. Under “Offset” enter the time-period in seconds. In the above example, the mapping will be sent
every 300 seconds or 5 minutes. Note that the time period is after the last transmission - if the block mapping message is
triggered by the host device, or by a change-of-state, then the timer is reset and the time period starts again.
The “Offset” value can be set from 0 – 4095 seconds (68 minutes). If you do not want the message to be sent on a time period, set the “Offset” value to zero.
If you want the block mapping to be sent only on time period (and not on change as well), select the “Disable” box in the bottom left hand corner - this disables change messages for this block mapping.
4.4.4 Real-Time
The block mapping message can be sent at a real-time by setting the “Period” value. In this example, “period” is set to 6 minutes - the message will be sent every 6 minutes starting at the beginning of each hour. That is, the message will be sent at XX:00, XX:06, XX:12, XX:18, XX:24 …. XX:54 - where XX represents any hour of the day.
If “Period” was set to 1 minute, then the message would be sent every minute, on the minute. The “Offset” value provides an offset to the specified time. In this example, if the “Offset”
was set to 10 seconds, then the messages will be sent 10 seconds later - at XX:00:10, XX:06:10, XX:12:10 etc.
Page 56
Chapter 3 Installation
The reason for the offset is to stagger messages with the same time setting. For example, if you configure 5 block mappings all to be sent at 10 minutes, then the 105G will try to send these messages at the same time - some of the messages will have to wait until the earlier messages have been sent. If you are sending Read messages as well as Write messages, then the return messages could clash with outgoing messages.
To avoid this, you can delay some messages using the Offset feature. For example, if you have 5 mappings to be sent at 10 minutes, then the first could have zero offset, the second 3 sec offset, the third 6 sec offset etc.
If you do not wish to have a real-time trigger, set “Period” to continuous. If you want the block mapping to be sent only on real-time (and not on change as well),
select the “Disable” box in the bottom left hand corner - this disables change messages for this block mapping.
Setting the Clock
The clock within the 105G can be set by the host device, and read by the host device. The 105G provides four clock registers for days/hours/minutes/seconds - the registers are 4330 –
4333. On power-up, these registers are set to zero. Reg 4333 increments each second, Reg 4332 increments each minute, Reg 4331 each hour and Reg 4330 each day.
Item Clock Location Set Location
Days 4330 4340 Hours 4331 4341 Minutes 4332 4342 Seconds 4333 4343
The clock registers are used by the 105G for the real-time-clock trigger. The host device can read these registers. The host device can also set the 105G clock at any time by writing to the appropriate Set register. The Set registers are : 4340 – 4343. The procedure for setting the real time clock via these registers depends on the module firmware version (to find out what firmware version the module contains, simply display the diagnostics menu – see section on diagnostics). The set registers can also be set via radio using appropriate I/O or block mappings.
Firmware versions up to 1.50:
Registers 4340 – 4343 are normally zero. When a value is written into one of these registers, the 105G copies the value into the corresponding clock register, and then sets the Set register back to zero. For example, if the host device writes a value of 7 into Reg 4341, the 105G will write 7 into 4331 and set 4341 back to zero.
Firmware version 1.50 and later:
Registers 4340 – 4343 will only be transferred to the corresponding clock registers when their value changes from 0. For example to write a value of 7 to the hours register, first write the value 0 to the Set hours register 4341, then write the value 7 to the same register. (i.e. by always first writing the value 0 to the Set register this ensures that the change-of-state from 0 will be detected). Values must be held (i.e. not change) for approx 200msec to be detected.
Page 57
105U-G Wireless Gateway User Manual
Page 59 © September 2004
4.4.5 Change-of-State
If a value in the block changes by more than the sensitivity amount, then the block message will be sent (this can only occur for Write mappings). The sensitivity values are set under the “Sensitivity” option as per section 4.5.
A delay time can be entered to reduce the number of change triggers in active systems. For example, if 20 seconds is selected in the “Delay” window, then the change message will be sent 20 seconds after the change-of-state occurs - if other changes occur during the 20 second period, all of these changes are sent in the one message.
The delay time can be set from 0 – 254 seconds. If you do not wish change messages to occur, select the “Disable” box.
4.4.6 Mixing Normal Mappings and Block Mappings
Block mappings can include I/O Registers already used with normal I/O mappings. For example, a remote 105U I/O module could map a remote input to I/O Reg 743. At the
105G, the host device could read I/O Reg 743, and you could also configure a block mapping including this register to another 105G. You could write a block I/O Reg 700 – 800 to another 105G.
4.4.7 Comms Fail for Block Mappings
Each block mapping has an associated mapping number. Up to 500 block mappings may be entered. A status register is maintained for each block mapping. The most significant bit of this register contains the comm fail status.
If a block mapping does not receive an acknowledgement from the remote module, then the comms fail status is set - this can be monitored by the host device.
Page 58
Chapter 3 Installation
4.4.8 “Repeater-only” Configuration
Any 105G module can act as a repeater unit. However a 105G may need to be installed as a repeater only (that is, there is no host device connected). In this case, the base 105G, the 105U-G-MD1 unit would normally be used as this is the lowest cost of the 105G modules.
A repeater can be configured as a “Repeater­only” unit. The advantages are:
the serial port will then provide on-line diagnostics (instead of off-line diagnostics), or105S serial I/O modules can be connected to the serial port - normally 105S modules
cannot be used with MD1 units.
4.5 Change Sensitivity
“Change” messages for both individual I/O mappings and block mappings use a sensitivity value to trigger the message. Sensitivities are configured for blocks of I/O registers - that is, each I/O register does not have a unique sensitivity. You can configure up to 50 sensitivity values - that is, there can be 50 blocks of registers with different sensitivities.
In the above example, three sensitivity blocks have been configured:
1. I/O registers 0 – 49 have a sensitivity of 1000 (or 1.5% of the 16 bit range)
2. I/O registers 100 – 499 have a sensitivity of 250 (or 0.4% of the 16 bit range)
3. I/O registers 1000 – 2999 have a sensitivity of 100 (or 0.15% of the 16 bit range) All of the registers between 0 and 49 have a sensitivity value of 1000. If register 34 has
changed value by more than 1000 since the last transmission for that register, then a change trigger will occur for register 34. Sensitivity values are in decimal and can vary between 1 and 65535 (16-bit).
Up to 50 blocks of sensitivities can be configured. If a register is included in more than one block, then the first sensitivity value configured will be accepted and later values ignored.
Page 59
105U-G Wireless Gateway User Manual
Page 61 © September 2004
Registers which are not included in any block use the “default” sensitivity which is also user­configurable. In the above example, the default sensitivity is 1 and is the sensitivity for all I/O registers not included in the three blocks.
Important Note. Sensitivity values need to be selected carefully for analogue or counting registers as small values can result in a large number of change messages, which can overload the radio channel. A sensitivity value of 1 in 65535 is a change of 0.0015%. If the host device writes an analogue value to a 105G every 100msec, it will change by at least 1 bit each time. A small sensitivity value will cause a change message to be sent every 100msec. If there are many analogue values in the same situation, then there would be many change messages every 100msec. Sensitivity values for analogue I/O should be set to be greater than the normal process noise of the signal. For example, if a flow signal has a normal process oscillation of 2.5%, then the sensitivity should be set to 3% (or a value of 2000) to avoid change transmissions from the process oscillations.
Page 60
Chapter 3 Installation
4.6 Serial Configuration – MODBUS
The 105U-G-MD1 module provides interface for Modbus Slave, Modbus Master and Allen­Bradley DF1. This Modbus interface uses the Modbus RTU protocol - also known as the Modbus Binary protocol. This manual assumes that the reader has a good understanding of the Modbus or DF1 protocol.
4.6.1 MODBUS Slave
If you use the 105G Modbus Slave interface, then the host device will be a Modbus Master device. The only configuration required for the Modbus slave interface is selecting the Modbus address and serial port parameters. This is done in the “Serial Settings” screen. A valid Modbus slave address is 1 to 255.
Each I/O register (and status register) in the 105G can act as one of the following types of Modbus registers
00001-09999 = Output Coils (digital/single bit) 10001-19999 = Input Bits (digital/single bit) 30001-39999 = Input Registers (analog/16 bit) 40001-49999 = Output Registers (analog/16 bit)
For example:
If the Modbus Master sends the 105G a “read” command for Modbus input 10457, then
the 105G will respond with the value in I/O register 457.
If the Modbus Master sends the 105G a “write” command for Modbus output 02650, then
the 105G will write the value to I/O register 2650.
If the Modbus Master sends the 105G a “read” command for Modbus input 30142, then
the 105G will respond with the value in I/O register 142.
If the Modbus Master sends the 105G a “write” command for Modbus output 40105, then
the 105G will write the value to I/O register 105.
The 105G I/O register values are 16 bit (hexadecimal values ‘0000’ to ‘FFFF’, or decimal 0 to
65535), regardless of whether the register represents a discrete, analog or count point. The value of a discrete (digital) I/O point is stored in the 105G database as a hexadecimal '0000'
(“off”) or hex 'FFFF' (“on”). However the 105G will respond with either a ‘0’ (“off”) or ‘1’ (“on”) to a digital read command from the Modbus master - these are commands 01 and 02. Similarly, the 105G will accept ‘0’ or ‘1’ from the Modbus master in a digital write command and store ‘0000’ or ‘FFFF’ in the database location - these commands are 05 and 15.
Page 61
105U-G Wireless Gateway User Manual
Page 63 © September 2004
The modbus function codes that the 105G will respond to are shown in the table below.
Supported Modbus Function Codes: Function Code
Meaning
01 Read the state of multiple digital output points 02 Read the state of multiple digital input points
03 Read the value of multiple output registers 04 Read the value of multiple input registers 05 Set a single digital output ON or OFF 06 Set the value of a single output register 07 Read Exception Status - compatibility - returns zero 08
Loopback test Supported codes 0 return query data 10 clear diagnostic counters 11 bus message count 12 CRC error count 14 slave message count
15 Set multiple digital output points ON or OFF 16 Set multiple output registers
Analog I/O are 16 bit register values. A value of decimal 8192 (hex 2000) represents 0mA. A value of 49152 (hex C000) represents 20mA. Each 1 mA has a value of 2048 (hex 0800) - a change of 4096 (hex 1000) is equivalent to a change of 2mA. A 4-20mA signal will vary between 16384 (hex 4000) and 49152 (hex C000). A 0-20mA signal will vary between 8192 (hex 2000) and 49152 (hex C000).
Pulse counts are stored as a 16-bit register. When the register rolls over, from ‘FFFF’ (hex), the next value will be ‘0001’. The register will only have a value of ‘0000’ when the remote module starts up, and the previous count is lost. This value will indicate that the counter has reset.
Modbus Errors
Four Modbus error messages are reported to the Modbus Master. An error response is indicated by the address of the return message being 128 plus the original slave address.
Page 62
Chapter 3 Installation
Supported Exception Codes: Exceptio n Code
Name Description
01 Illegal function The module does not support the function code in the query 02 Illegal data address The data address received in the query is outside the
initialized memory area 03 Illegal data value The data in the request is illegal 06 Busy Unable to process message
4.6.2 MODBUS Master
If you use the 105G as a Modbus Master, then the host device(s) will be Modbus Slave device(s). If the RS485 port is used, then multiple Modbus Slave devices can be connected to
the 105G. The 105G Modbus Master will generate Modbus read and write commands to the Modbus Slave devices.
First read the above section on Modbus Slave operation, for an understanding of how the 105G handles Modbus registers, and the types of Modbus commands the 105G Master can generate.
The Modbus Master commands are configured in the “Serial Mapping” screen. The serial port is configured in the same way as described in the above section on Modbus Slave.
To enter a Modbus command, select “New Serial Mapping”. The following example is a digital write command which writes 105G I/O registers 20 – 25 (6 registers) to Modbus outputs 00012 – 00017, at Modbus Slave address 1.
The entry under “I/O Register” is the first I/O register in the 105G to be transferred - the “I/O count” is the number of registers to be transferred. If the selected Modbus slave does not respond to the command, then the 105G will write a ‘FFFF’ value to one of its own registers, configured under “CF Register” - in this case it is register 4800.
The “Command Type” selected is a write command (you can select read or write) - which means that the values are sent from the 105G to the Modbus Slave. The type of write command is a “Digital” write, meaning that the register values will be written as digital/binary values”.
Page 63
105U-G Wireless Gateway User Manual
Page 65 © September 2004
If the Modbus Slave device does not respond to the Modbus command, the 105G will try another 3 times (“Max Retries” = 3). The Modbus command will be sent to the Modbus Slave every 100msec. The address of the Modbus Slave is 1 (permissible addresses are 1 –
255). Because a digital write command has been selected, the destination register type will be digital outputs, with Modbus tag “0xxxxx”. The first destination Modbus location is 12 (or 00012) - as there are 6 registers transferred, the destination locations will be 00012 –
00017. The second example is a register read command to the same Modbus Slave (address 1). The
command requests the Modbus Slave to return the values of 10 registers which will be stored in I/O registers 463 - 473 in the 105G. As the command is a “register read” command, the target Modbus locations will be of the type 3xxxx. The starting location is 30001. So the values of locations 30001 – 30010 in Modbus Slave 1 will be transferred to I/O registers 463 – 473 in the 105G.
The CF Register (“comms fail” register) acts as a digital alarm – the value of the register will normally be 0, and will be set to FFFF (hex) if the slave device does not positively respond to the serial command within Max Retries attempts. In the examples, the same CF Register (4327 – i.e. DOT8) has been used for both serial mappings, such that the local digital output will be activated if the slave fails to respond to either serial command. Alternately, any other internal register could have been chosen and mapped via radio if desired.
Page 64
Chapter 3 Installation
To complete the Fieldbus Configuration, enter any other Modbus commands that may be required to transfer I/O points between the 105G and the Modbus Slave devices.
Digital I/O
The value of a digital I/O point is stored in the 105G database as a hexadecimal '0000' (“off”) or hex 'FFFF' (“on”). However the 105G will generate either a ‘0’ (“off”) or ‘1’ (“on”) to a digital output point (Coil) when sending commands to a Modbus slave - these are commands 05 and
15. Similarly, the 105G will accept ‘0’ or ‘1’ from the Modbus slave in response to a digital read command and store ‘0000’ or ‘FFFF’ in the database location - these commands are 01 and
02.
Analog I/O
Analog I/O from the remote 105U modules are 16 bit register value. A value of 8192 (hex
2000) represents 0mA. A value of 49152 (hex C000) represents 20mA. Each mA has value of 2048 (hex 0800) - a change of 4096 (hex 1000) is equivalent to a change of 2mA. A 4-20mA signal will vary between 16384 (hex 4000) and 49152 (hex C000). A 0-20mA signal will vary between 8192 (hex 2000) and 49152 (hex C000).
Pulse I/O
Pulse counts from the remote 105U modules are shown as a 16-bit register. When the register rolls over, from ‘FFFF’ (hex), the next value will be ‘0001’. The register will only have a value of ‘0000’ when the remote module starts up, and the previous count is lost. This value will indicate that the counter has reset.
Modbus Retry Delay
The 105G Modbus Master configuration includes a feature to limit the frequency at which slave devices are polled for data. The 105G will poll each Modbus slave in order. If there is no delay
Page 65
105U-G Wireless Gateway User Manual
Page 67 © September 2004
time entered, the 105G will poll as quickly as it is able to. If there is a delay time entered, then this delay time will occur between each poll message.
When updated values are received from the 105U radio network, the current polling sequence is interrupted, and the new values are written immediately to the appropriate slaves.
Re-tries on the Serial Port
When communicating with Modbus slaves, the 105G may be configured to re-try (or re-send) a message zero or more times if no response is received from a slave. If all retries are used up, that slave is flagged as being in communication failure. Further attempts to communicate with the slave will have zero re-tries. When a successful response is received from the Modbus slave, the communication failure flag is reset and the configured number of re-tries will be used. This means that an off-line slave device will not unduly slow down the communications network.
Comms Fail
A “Comms Fail” image location in the 105G database. This image location should be in the range 4500 to 4999. If a response is not received from the Modbus slave after all re-tries have been sent, the 105G will set this Comms Fail image location to hex(FFFF). When the 105G sends the next poll for this I/O Command, it will not send any re-tries if a response is not received to the first message. When a response is eventually received, the 105G will reset the value in Comms Fail image location to 0, and the normal re-try sequence will operate.
Different I/O Commands can use different Comms Fail image locations, however we recommend that you use the same image location for all I/O Commands to the same Modbus slave address.
4.7 Serial Configuration - DF1
The 105G DF1 Driver allows the 105G to communicate with Allen-Bradley devices supporting the DF1 protocol. Supported commands allow communication with 500 CPU devices (SLC and Micrologix) and with PLC2 series devices. DF1 offers both full-duplex (point to point) and half-duplex (multidrop) operation. The 105G only supports the full­duplex operation - this is the default DF1 mode on most equipment. DF1 full-duplex is a “peer-to-peer” protocol. Either DF1 device can initiate commands to the other device, and both devices will respond to commands from the other device. The 105G can act as both a command initiator and a command responder.
An Application Note and configuration files are available describing how to configure an Allen-Bradley PLC to communicate with a DF1 105G. This is available from the Elpro web­site www.elprotech.com
The 105G will initiate the following command types to a command responder, according to the configuration. The 105G will automatically generate the correct command type depending on the configuration you enter. The 105G will also respond to these command types if they are sent from a command initiator.
Page 66
Chapter 3 Installation
Command Description Code Function
Code
Comment
Protected Write 0x00
NONE
PLC2 series and SLC / Micrologix
Unprotected Read 0x01
NONE
PLC2 series and SLC / Micrologix
Diagnostic Status 0x06
0x00
Diagnostic Commands
Echo message 0x06 0x00
Unprotected Write 0x08
NONE
PLC2 series and SLC500 / Micrologix
Typed logical Read 0x0F 0xA2 Type SLC500 and Micrologix
Read Bits
0x0F
0xA2 0x85 Reads MSB of each 105G I/O register and
writes the bits to the destination register, starting at the LSB of the register. Min transfer is 16 bits.
Read Integers
0x0F
0xA2 0x89 Return signed 16 bit value
Read Long Ints
0x0F
0xA2 0x91 Unsigned 16 bit register per long-word
Typed logical Write 0x0F 0xAA Type SLC500 and Micrologix
Write Bits
0x0F
0xAA 0x85 Writes bits from the source register, starting
at the LSB, to the MSB of a block of 105G I/O registers. Min. transfer is 16 bits.
Write Integers
0x0F
0xAA 0x89 Writes a signed 16 bit value
Write LongIntegers
0x0F
0xAA 0x91 Low 16 bits of long-word placed in register.
Upper 16 bits ignored.
The SLC and Micrologic PLC’s read/write two types of registers. An “Integer” has a signed 16 bit value (-32768 to 32767). A “Long Integer” has a 32 bit value. The 105G registers contain an unsigned 16 bit value (0 to 65535). We recommend that you use Long Integer read/write commands - the upper 16 bits of the 32 bit value will be ignored. Refer to more information in the Analogue I/O and Pulse I/O sections below. The PLC2 uses unsigned 16 bit registers in the same format as the 105G.
The 105G DF1 driver will update remote outputs whenever a data value changes by more than the I/O register sensitivity. If the response from a data request contains a changed data value, the new value will be transmitted to the remote 105U on the radio network. Similarly, if the 105G receives a command to change a data value, the new value will be transmitted to the remote 105U module.
The DF1 commands are configured in the “Serial Mapping” screen. The serial port should be configured in the same way as the host device. If the 105G acts only as a command responder, no further configuration is required.
If the 105G acts as a command initiator, you can enter a “Request Delay” between commands sent to the host. To enter a DF1 command, select “New Serial Mapping”. The following example is a file write command which writes 105G I/O registers 80 – 104 (25 registers) to DF1 files I3.1 to I27.1 at DF1 address 2
.
Page 67
105U-G Wireless Gateway User Manual
Page 69 © September 2004
The entry under “I/O Register” is the first I/O register in the 105G to be transferred - the “I/O count” is the number of registers to be transferred.
The “Command Type” selected is a file write command (you can select read or write) ­which means that the values are sent from the 105G to the host device. The type of write command is a “Integer” write, meaning that the register values will be written as register values.
The DF1 address of the host device (or “Slave”) is 2.
Discrete I/O
The value of a digital I/O point is stored in the 105G database as a hexadecimal '0000' (“off”) or hex 'FFFF' (“on”). However the 105G will generate either a ‘0’ (“off”) or ‘1’ (“on”) to a binary
Page 68
Chapter 3 Installation
file when initiating a “Typed Logical Write” command or responding to a “Typed Logical Read” command. Similarly, the 105G will accept ‘0’ or ‘1’ from responding device to a “Typed Logical Read” command or from an initiating device generating a “Typed Logical Write” command and store ‘0000’ or ‘FFFF’ in the database location. The file type for a binary file (bit file) is 0x85.
In the PLC (that is, the D F1 ho st de vice), discrete values (“bits”) are stored in 16 bit registers ­each register stores 16 bit values (or 16 discrete values). You can only transfer these values in groups of 16. That is, a read or write command will transfer a minimum of 16 bits to/from the 105G. If more than 16 are transferred, then they will be transferred in multiples of 16. You cannot transfer an individual bit - you must transfer the 16 bits in that PLC register, which will be transferred to/from 16 consecutive I/O registers in the 105G.
Note: The PLC reads or writes digital bits starting at the LSB of each register. In the 105G, only one bit is written to each I/O register, and this is the MSB.
Analogue I/O
Analogue I/O from the remote 105U modules are 16 bit register value. A value of 8192 (hex
2000) represents 0mA. A value of 49152 (hex C000) represents 20mA. Each mA has value of 2048 (hex 0800) - a change of 4096 (hex 1000) is equivalent to a change of 2mA. A 4-20mA signal will vary between 16384 (hex 4000) and 49152 (hex C000). A 0-20mA signal will vary between 8192 (hex 2000) and 49152 (hex C000).
Note: If analogue values are read to and written from an integer file in an SLC or Micrologix CPU, integer files contain 16 bit signed values. These represent values in the range -32768 to
32767. The data values from the 105U modules are treated as 16 bit unsigned values. To convert the data from an analogue input, move the data from the integer file to a long file (MOV command) then mask out the high 16 bits (MVM with mask value FFFF). This will result in a long integer value in the range 0 to 65535.
Alternatively, use a long integer file type to transfer the analogue value as a long integer in the range 0-65535.
Pulse I/O
Pulse counts from the remote 105U modules are shown as a 16-bit register. When the register rolls over, from ‘FFFF’ (hex), the next value will be ‘0001’. The register will only have a value of ‘0000’ when the remote module starts up, and the previous count is lost. This value will indicate that the counter has reset.
Note: The values from the 105G module are 16 bit unsigned values. When they are copied to the Integer file in the PLC, they will be treated as 16 bit signed values. These values may be converted to the original (unsigned) values using the MOV and MVM instructions described in the previous section (Analogue I/O). Again, using a Long Integer type will avoid this problem.
500 CPU (SLC and MicroLogix) file types and addressing
The 105G provides a linear address space of 10,000 data words. This is compatible with PLC2 addresses, but does not match the addressing used by the 500CPU modules (SLC and Micrologic). These address data by file number and file offset. To address an I/O register, L, in the 105G, use DF1 file number L / 100, with the remainder value (L % 100) as the DF1 file offset. For example, to read I/O register 2643 in the 105G, read from file number 26, offset 43.
Page 69
105U-G Wireless Gateway User Manual
Page 71 © September 2004
4.8 Fieldbus Configuration
All 105G modules (except MD1) have separate internal hardware comprising the Fieldbus Interface, consisting of a separate microprocessor and appropriate hardware for the network connection. This Fieldbus Interface handles all fieldbus communications, and transfers I/O in the Fieldbus Interface Registers to/from the fieldbus. Conversely, the 105G Radio Interface handles all radio communications, and transfers I/O in the Radio Interface Registers to/from the radio network. For I/O transfer between the radio network and the fieldbus network, I/O Registers in the Radio Interface must be linked with registers in the Fieldbus Interface using configuration software.
Depending on the fieldbus protocol, the size of the Fieldbus Interface may be limited (for example, the Profibus Slave interface supports only 416 bytes I/O). The Radio Interface supports 10,000 registers, of which 4300 are general-purpose I/O registers. Each Radio Interface register is 16-bit, even for discrete (or “digital”) input or output values. The Fieldbus Interface comprises a block of 8-bit bytes (referred to as “locations”). Digital I/O can be packed - each fieldbus location can hold 8 digital inputs or outputs. Analog or pulse values can be stored as a low resolution 8-bit value (a single fieldbus location) or as a high resolution 16-bit value (two consecutive fieldbus locations).
To optimize I/O usage, the 105G provides a flexible method of data transfer between the Radio Interface and the Fieldbus Interface. The user configures links between the Radio Interface and Fieldbus Interface via Fieldbus Mappings in the ESeries Configuration
Software. The diagram shows in more detail the relationship between the Radio Interface and Fieldbus Interface.
4.8.1 Fieldbus Mappings
The Fieldbus Interface is divided into two distinct areas. The IN Area contains input data that is made available to the host device. The OUT Area contains output data from the host device. This is in contrast to the Radio Interface, in which each 16-bit register can be used as input or output. Also note the size of the Fieldbus Interface is variable, depending on the type of fieldbus.
ESeries Configuration Software provides user configurable Fieldbus Mappings to link the required Fieldbus I/O to the Radio Interface. Write mappings write I/O values from the Radio Interface to the Fieldbus IN Area. Read mappings read I/O values from the Fieldbus OUT Area to the Radio Interface.
WRITE
RADIO
INTERFACE
I/O
DATABASE
I/O REGISTERS FIELDBUS
LOCATIONS
READ
FIELDBUS
INTERFACE
RADIO
DRIVER
DATA BUS
ANTENNA
Page 70
Chapter 3 Installation
If you want to send a value from the 105G to the host device, use a Fieldbus Write Mapping. The input data from the Radio Interface (i.e. input data that has either come in from the radio or from local I/O) will be transferred to the IN Area via the fieldbus write mapping. The host device can then read this input data from the IN Area.
If you want to send a value from the host device to the 105G, use a Fieldbus Read Mapping. The host device can write output data to the OUT Area. The output data from the OUT Area will then be transferred to the Radio Interface via the fieldbus read mapping. The radio driver can then either send this output over the radio or to a local I/O.
Several different configurable transfer modes are also available for fieldbus mappings to ensure the I/O is formatted according to the requirements of the particular fieldbus protocol or host device. The six possible types of Fieldbus Mapping are outlined in the table below.
4.8.2 Transfer Mode
Radio Interface registers are all 16-bit general-purpose input or output registers. That is, analog inputs or outputs are stored as a 16-bit value. Digital inputs or outputs occupy a whole 16-bit register and are stored as either 0000(hex) or FFFF(hex) for compatibility with the ELPRO Radio Protocol. However, the Fieldbus Interface may contain (depending on the protocol) significantly less registers than the Radio Interface (see diagram above). Also, certain protocols may require a different I/O structure than that used by the Radio Interface registers. Consequently, depending on the fieldbus mapping transfer mode (see above table), Radio Interface registers may or may not be compressed.
105G Module
IN Area
OUT Area
Radio Interface
Write from I/O Reg
Read to I/O Reg
Fieldbus Interface
Write from Host
Read from Host
Fieldbus
Profibus 244 Bytes Modbus/TCP 2048 Bytes Ethernet/IP allows 6 input
connections; each connection Max 512 bytes
Modbus Plus 2048 bytes DeviceNet 512 bytes
Profibus 244 Bytes
Modbus/TCP 2048 Bytes
Ethernet/IP allows 6 output connections; each connection Max 512 bytes
Modbus Plus 2048 bytes DeviceNet 512 bytes
10,000 x 16-bit
I/O Registers
Page 71
105U-G Wireless Gateway User Manual
Page 73 © September 2004
Fieldbus Mapping Types
Transfer Mode Read Mapping Write Mapping Single Bit
The 105G reads a block of consecutive bits from Fieldbus OUT Area and stores each bit in consecutive I/O Registers, as hex FFFF or 0000.
The 105G takes the MSB (most significant bit) of a block of consecutive I/O Registers, converting the 16 bit I/O register values into 0 or 1, and writes to consecutive bits of Fieldbus IN Area.
Byte (8-bit)
The 105G reads consecutive bytes (8-bit values) from Fieldbus OUT Area and stores each byte in the most significant 8-bits of a consecutive I/O register.
The 105G takes the most significant 8-bits of consecutive I/O registers and writes them to consecutive bytes (8-bit values) of the Fieldbus IN area.
Word (16-bit)
The 105G reads consecutive words (2x8-bit values) form Fieldbus OUT Area and stores each word in a consecutive I/O Register.
The 105G takes consecutive I/O registers and writes them to consecutive words (2x8-bit values) of Fieldbus IN Area.
“Word” transfer mode offers no compression, but rather a direct transfer of 16-bit registers between Radio Interface and Fieldbus Interface. This mode would suit the transfer of registers containing pulse counts or analog values with no loss of resolution.
“Byte” transfer mode operates on only the most significant BYTE (the first 8 bits) of Radio Interface registers, but allows these bytes to be consecutively packed in the Fieldbus Interface. This mode would suit the transfer of analog values in low-resolution, in cases where I/O space is at a premium. Byte Address Mode is recommended when using byte transfer mode (see Address Mode section below).
Bit transfer mode operates on only the most significant BIT of Radio Interface registers, but allows these bits to be consecutively packed in the Fieldbus Interface. This mode would suit the transfer of digital I/O in cases where it is not desirable (or possible) to use a whole 16-bit register just to store a 0 or 1 value.
4.8.3 Address Mode
Configuration software allows the Fieldbus Interface IN and OUT areas to be addressed as an array of 8-bit bytes (Byte Address Mode) or an array of 16-bit words (Word Address Mode). The address mode may be required to change depending on the transfer mode, the protocol, or the particular host device. The Address Mode option is included so that the configuration software can be setup to use the same I/O addressing method used by the host device. The actual structure of I/O in this database can only be physically altered via the transfer mode.
The Fieldbus Interface IN and OUT areas are simply a block of I/O memory, exchanged according to the configured protocol. For example, with a Profibus slave that supports 244 bytes of inputs, the fieldbus interface IN area could be addressed either as byte locations 1 to 244 or as word locations 1 to 122. Note that in either case, the underlying database structure is unchanged, the difference is limited to the Fieldbus IN/OUT Area address that is displayed by configuration software.
Certain protocols have an inherent or preferred byte or word structure – for example, Modbus is a protocol that usually operates on 16-bit (word) registers. Consequently,
Page 72
Chapter 3 Installation
configuration software will default to the most common address mode for that protocol. Configuration software may also apply an offset and/or scaling to the IN/OUT Area addressing to suit the particular protocol. For example Modbus/TCP areas start from location 1, but other fieldbuses may start at location 0.
Note:
The Fieldbus Interface IN and OUT Area both number from 0 - that is, there is an input
0 as well as an output 0 (an offset may apply for some protocols).
All IN/OUT Area locations accessed by the fieldbus must be part of a fieldbus mapping
in the 105G - that is, if a host device is writing to bytes 0 – 100 in the OUT Area, there must be at least one fieldbus read mapping that uses these locations - if not, the Fieldbus Interface will generate an error response message.
Fieldbus mappings to/from the IN/OUT areas should always start at location 0 if possible
(or the lowest available unused location). Configuration Software will always automatically choose the next lowest available location – it is strongly recommended that this topology be used so as not to place unnecessary processing overhead on the module.
4.8.4 Fieldbus Mapping Configuration
The example below shows the Fieldbus Mapping configuration screen when adding new or editing existing Fieldbus Mappings. Starting from the left of the screen, the I/O Register selection specifies the starting I/O Register from the Radio Interface (press the “…” button to make a selection graphically). The I/O Count parameter specifies how many consecutive I/O Registers are to be transferred or linked. Command Type and Transfer Mode specify the type of Fieldbus Mapping (see Fieldbus Mappings table above). Finally, I/O Location specifies the IN or OUT Area location in the Fieldbus Interface (see earlier diagram).
Page 73
105U-G Wireless Gateway User Manual
Page 75 © September 2004
Three Fieldbus Mappings are illustrated in the example below. Note that “Word Address Mode” is selected, meaning that the Fieldbus Interface IN and OUT Areas will be treated as word-addressed arrays by configuration software. The parameters for each fieldbus mapping
were setup using the mapping configuration screen as described above.
The first Fieldbus Mapping is a “Write WORD” mapping, writing I/O Registers 10 – 15 from the Radio Interface to word-locations 1 – 5 in the Fieldbus IN Area. Because the transfer mode is “word” complete 16-bit registers are transferred.
The second mapping is a “Read BIT” mapping, reading 12 bits from Fieldbus OUT Area word-location 1(word address mode is selected) to I/O Registers 30 – 41. Remember that for such a BIT transfer, that each individual bit in the Fieldbus Interface is transferred to an entire 16-bit I/O Register. Note also that there is a word-location 1 for both the Fieldbus OUT and IN areas.
The third mapping is another “Read BIT” mapping, reading 8 bits from Fieldbus OUT Area word-location 1 to I/O Registers 4320 – 4327 (i.e. local DOT 1 – 8). Note here that we are again reading from Fieldbus OUT Area word-location 1 (as with the previous mapping). However, since each word-location contains 16-bits and the last mapping used only 12 of those, we have been able to follow on from the previous mapping (see below).
The Fieldbus Register Selection screen below was shown when selecting the Fieldbus OUT Area location for the third mapping in the above example. This screen shows the currently used portion of the Fieldbus OUT Area, and allows the user to graphically select the location for the current mapping. NOTE – by default configuration software will always choose the next available Fieldbus Interface register for fieldbus mappings. Allowing configuration software to automatically make the selection is strongly recommended wherever possible.
Clicking on the required location in the top panel will alter the currently selected word­location. Further, clicking individual bits in the “Bit Usage” panel at the bottom of the screen, allows the current BIT mapping to be specified at the bit-level of the currently selected word.
The lighter blue areas indicate the extent of already existing fieldbus mappings. It can be seen that bits 0 – 11 of word location 1 have already been used (by the second mapping in the
Page 74
Chapter 3 Installation
example). The dark blue area in the register selection screen above shows the extent and
location of the current fieldbus mapping graphically. The status panel at the bottom of the window always displays the extent of the current selection, which can be seen to be word 1, bit 12 to word 2, bit 3.
A status location (4500) may be used to give the host device status information about the Fieldbus Interface. This register will be value 0x0000 if the Fieldbus Interface is “on-line” and communicating with the fieldbus, or value 0xFFFF if it is “off-line”. If you wish to use a status register, select the “Enable Status Location” box. This register could be mapped to a remote module or local output as an alarm.
4.9 Fieldbus Configuration - Profibus Slave
The Profibus 105U-G-PR1 acts as a Profibus DP Slave - the host device is a Profibus Master. If you use the 105U-G with a PLC, the PLC configuration tool will require a GSD file so it can recognize the Profibus interface in the 105U-G. This file loads into the PLC configuration software (for example, Siemens STEP 7). The file is available on the same CD as the configuration software or from the Elpro web page www.elprotech.com.
Configuration of the Profibus Fieldbus Interface comprises allocating a Profibus Slave address to the 105G, and configuring links between the Radio Interface and the Fieldbus Interface (i.e. Fieldbus Mappings).
The Profibus address can be set in the “Fieldbus Config” screen or via the rotary switch on the end-plate of the module- valid slave addresses are 1 – 126. If the “Enable Rotary Switch” box is not selected, then the address entered in the program will be used and the rotary switch value ignored. If the “Enable Rotary Switch” box is selected, then the address
Page 75
105U-G Wireless Gateway User Manual
Page 77 © September 2004
entered in the configuration program will be ignored and the rotary switch read on start-up of the 105G.
The Profibus interface has 416 bytes, of which 244 can be used as input bytes, or 244 can be used as output bytes.
Note: For bit transfers, the bit offset is counted from the least significant bit (LSB) of the byte (with bit 0 being the LSB) - if you transfer 3 bits with a bit offset of 5, then you will transfer bits 5-7 of the byte. This is different than the Ethernet unit which counts the offset from the most significant bit - refer next section.
An application note for configuring a Siemens S7 PLC to communicate with a Profibus 105G can be downloaded from the Elpro web-site www.elprotech.com
4.10 Fieldbus Configuration - Profibus Master
The 105U-G-PR2 implements a complete Profibus-DPV0/DPV1 master. The hardware is optimized for high throughput and can be used in mono or multi master networks up to 12 Mbit/s. Up to 125 slaves with a total max of 2048 byte input and 2048 byte output data can be connected.
4.10.1 GSD File
Each device in a Profibus network is associated with a GSD file, containing all necessary information about the device. In general, the profibus slave device manufacturer supplies the relevant GSD files. ESeries Configuration Software uses these files during network configuration.
Page 76
Chapter 3 Installation
4.10.2 Protocol and Supported Functions
The 105U-G-PR2 implements a complete Profibus-DPV0/DPV1 master and includes the following features:
Up to 125 slaves can be connected
Up to 2048 bytes input &output data
Up to 12 Mbit/s on Profibus
RS-485 optically isolated Profibus interface with on-board DC/DC converter
Configuration via ESeries Configuration Software
Acyclic Communication (DPV1)
Alarm Handling (DPV1)
4.10.3 Configuration
Profibus network configuration is performed via the ESeries Configuration Utility. The 105G Profibus Master provides up to 2048 bytes of inputs and 2048 bytes of outputs in the fieldbus interface for I/O on the profibus network. I/O in the fieldbus interface must be linked with I/O in the radio interface via appropriate fieldbus mappings (see 4.8 Fieldbus Configuration above) for I/O transfer with the radio network.
Configuration of the profibus network is through the Profibus Network Config tab in ESeries Configuration Software. Through this section, the entire (local) profibus network including I/O data transfer with profibus slaves is configured. Before a profibus slave is configured on the network, its corresponding GSD file must be installed. To install a GSD file choose File|Install GSD File. Once the GSD file(s) have been installed, the devices corresponding to those GSD files will appear as devices on the Profibus DP treeview on the left side of the network configuration screen.
Page 77
105U-G Wireless Gateway User Manual
Page 79 © September 2004
The profibus network configuration screen is divided into three main areas (see above). The left hand Profibus DP Treeview displays all the available slaves, i.e. those whose
corresponding GSD files have been installed. The right hand top section Busview displays graphically the devices that are currently configured on the profibus network – individual devices can be selected here and their I/O configuration and other properties viewed/altered. The right hand bottom section Listview shows the I/O configuration of a particular slave when a slave device is selected in the busview, or the netowrk configuration (i.e. what slaves are configured and their corresponding addresses) when the profibus master node is selected in the busview.
Adding a Slave to the Network
To add a profibus slave to the network, locate the required slave and simply drag the slave icon onto the visible bus cable on the busview, or right click the required slave and choose add to network. To add a slave with a specific profibus node address to the network, locate the required slave and drag the icon to the network listview (ensure that the master node is selected in the busview so that the network list is displayed in the listview rather than the slave I/O configuration list). The above example shows a slave device being added to the network at node address 7.
Slave Address
To change the node address of a slave already configured on the network, locate the slave in the network listview and drag it to the position in the list corresponding to the desired address. Alternately, the slave address can be modified from the module properties page (see below).
Page 78
Chapter 3 Installation
Module Properties (Slave)
To display the properties of a given slave, right click the required slave in the busview and choose properties (or double click the icon in the busview). Under the general tab, various details (including GSD file details) relating to the selected slave device are displayed. Several configurable options are also available (see below).
Profibus Address
The actual profibus address of the selected slave is shown in the address selection box. Only available addresses are listed and can be selected as new address.
Watchdog
According to the profibus specification, a slave device may be configured with a watchdog function such that the master must poll the slave within a defined interval. If this feature is enabled and the master fails, the slaves watchdog timer will timeout and the slave will reset itself.
Group Assignment
If the slave supports sync/freeze functionality, it can be assigned to the masters sync/freeze groups by clicking on the checkboxes. The sync/freeze assignment of the groups is also displayed (these can be changed via the master properties dialog).
Parameter Assignment
A slaves user-specific parameters can be changed via the parameter assignment page. User­specific parameters for a slave device are defined in the corresponding GSD file for the device, the definition of which are device-specific and should be found in the documentation for the device.
Parameters can be altered via combo boxes or via direct input of hexadecimal values. The hexadecimal values for the user_prm_data are displayed at the bottom of the screen and can be edited directly (consult the device specific documentation for the meaning of these values).
Adding I/O to a Slave
The possible I/O combinations for a given slave may be fixed or configurable (i.e. modular) depending on the GSD file for the device. When the I/O configuration is fixed, the fixed I/O are always defined whenever the device is added to the network. However, for modular devices, the I/O configuration must be assigned manually.
Page 79
105U-G Wireless Gateway User Manual
Page 81 © September 2004
The GSD file for a modular slave will define a maximum number of I/O slots – each of which may be configured with an I/O module. The available I/O module’s for a particular slave can be viewed by expanding the slave node in the Profibus DP Treeview. To add an I/O module to a slave, first ensure the required slave is selected in the busview, then drag the required I/O module into a spare slot of the slave listview.
When an I/O module is added to a slave, configuration software will automatically assign that I/O to the next available space in the fieldbus interface. The input and output addresses that are assigned here will correspond to the locations that must be transferred via fieldbus mappings in order to make the I/O available to the radio network. The input and/or output address assigned by software for a given I/O module can be altered by double clicking on that I/O module entry in the slave listview (see above).
The start address in the fieldbus interface for the inputs or outputs can be altered in the corresponding Start field as shown above. Since the 105G provides for up to 2048 bytes of inputs and 2048 bytes of outputs, the possible range for inputs or outputs is 0 – 2047.
I/O modules may also have associated user parameter data defined by the corresponding GSD file. The meaning of these parameters (if applicable) is specific to the slave implementation, and may be altered via the Parameter Assignment tab of the Module Properties form.
Configuration software also provides an additional I/O module to all slaves that is not defined in the GSD files, which is the Universal Module. The universal module allows the input/output length, unit, and consistency to be assigned custom values as required – however not all slave implementations will support this feature (consult the specific slave documentation for details).
The Length parameter defines the length of the input or output module in either bytes or words (according to the corresponding Unit parameter). The data consistency over the
Page 80
Chapter 3 Installation
profibus network may be applied to the selected unit (i.e. byte or word) or to the total length of the input or output selection.
Depending on the particular slave, Manufacturer Specific Data may also apply to an I/O module. This data is a string of hexadecimal bytes, the meanings of which (if applicable) are device specific and should be detailed in the documentation for the particular device.
Master Properties
The profibus master 105G has some configurable properties that affect the entire profibus network. These properties can be accessed by double clicking the master icon in the network busview, or right-clicking the icon and choosing properties.
Profibus Tab
The Address parameter specifies the actual profibus address of the profibus master (default =
0). Only available addresses are listed and can be selected as new address. The serial baud rate for the entire profibus network is selected – this is the baud rate that will be used by the master and therefore must also be supported by all slave devices on the network. Most slaves will support auto baud rate detect, but it should be ensured that any slave on the network supports the configured baud rate.
The Profile parameter controls the assignment of Bus Parameters for the profibus network. In the single master (default) profile, the bus parameters are calculated automatically by configuration software and are optimised for speed – no other masters may be connected to the network. The User Defined profile allows the bus parameters to be manually configured for special network configurations and should only be used if the user is familiar with the individual profibus parameters (see Bus Parameters Tab below).
Page 81
105U-G Wireless Gateway User Manual
Page 83 © September 2004
The storage format determines if word values are stored in big endian (Motorola – most
significant byte has lowest address) or little endian (Intel – Least significant byte has lowest
address) format.
Group Properties Tab
A DP master can send the SYNC and/or FREEZE control commands simultaneously to a group of slaves for synchronization purposes. Therefore the slaves must be assigned to Sync/Freeze - groups. Up to 8 groups may be configured as SYNC and/or FREEZE groups. Any slaves that are configured to belong to a particular group (via that slaves module
properties|group assignment configuration) may be synchronized using the Message Interface instruction SET_SLAVE_MODE (see section on the Message Interface below).
Bus Parameters Tab
The bus parameters can be adjusted only when the selected profile is user defined (see Profibus Tab above). These parameters should only be changed if the user is familiar with the
individual profibus parameters according to the profibus specification.
Adjustable bus parameters: Tslot
The slot time determines the maximum length of time the sender has to wait to receive a response from the partner.
Max. Tsdr + 15 <= Tslot <= 16.383 t_bit
Max Tsdr
The maximum station delay responder determines the maximum length of time required by the responding node to respond
35 + 2*Tset + Tqui <= Max. Tsdr <= 1.023 t_bit
Page 82
Chapter 3 Installation
Min Tsdr
The minimum station delay responder determines the minimum length of time permitted for the responding node to respond.
11 t_bit <= Min. Tsdr <=Max. Tsdr - 1
Tset
The setup time determines the length of time elapsing in the node between a data frame being received and a response occuring
1 t_bit <= Tset <= 494 t_bit
Tqui
The quiet time is the time a modulator needs after recognizing a send frame to switch from send to receive.
0 t_bit <= Tqui <= MIN(31 t_bit, Min. Tsdr - 1)
Gap Factor
The Gap Factor determines how many token rounds occur before a new active node (master) can be added to the token ring.
1 <= Gap Factor <= 100
Page 83
105U-G Wireless Gateway User Manual
Page 85 © September 2004
Retry Limit
The Retry Limits determines the number of attemps (repeated message frames) allowed to access a node.
1 <= Retry Limit <= 15
HSA
All active nodes (masters) scan the network continuously up to the HSA (highest station address). HSA must be set at minimum to the highest profibus address (master or slave) connected to the network.
0 <= HSA <= 126
Delta_Ttr
This value can be set for multi master networks with the selected profile Multi Master. Delta Ttr is added to the calculated Ttr to increase the Ttr for using multiple masters in a network.
256 t_bit <= Ttr <= 16.776.960 t_bit
Non-adjustable bus parameters Ttr
The target rotation time determines the maximum available time for a token pass. During this time all active nodes (masters) obtain the token one time to send data. ESeries Config Software calculates an optimized Ttr depending on the values of other bus parameters. If an individual bus parameter is changed, pressing the Recalculate-button recalculates the Ttr including Delta_Ttr.
Watchdog
The watchdog determines the watchdog time transferred to slaves if the watchdog is enabled.
Tid2
The idle time 2 determines the maximum length required before a transmitting node can send the next message after sending a message frame that is not acknowledged.
Tid2 = Max. Tsdr Tid1
The idle time 1 determines the minimum length required before a transmitting node can send the next message after sending a message frame that is not acknowledged.
Tid1 = 35 + 2*Tset + Tqui Trdy
The ready time determines the minimum time for a transmitting node to receive a response message frame.
Trdy = Min. Tsdr
Page 84
Chapter 3 Installation
Configuration Example:
The Following example describes a simple configuration of a 105G connected to a simple Profibus Slave I/O device. Described is the configuration of the local 105G Profibus master only, for more detailed configuration examples, an application note can be downloaded from
www.elprotech.com.
The example will transfer 8 x digital points from the radio network to the slave device. A single 16-bit analog value will be transferred from the profibus slave to the radio network. Several configuration steps via ESeries Configuration Software are required:
Profibus Network Configuration
Fieldbus Configuration (Fieldbus Mappings)
Radio Configuration (I/O or Block Mappings)
1) Profibus Network Configuration
Once the GSD file for the profibus slave has been installed, the slave device can be added to the profibus network (see Configuration section above). For this example, the slave is a modular device, therefore we add the necessary I/O modules to the slave. The example requires 8 x digital points to be transferred to the slave - hence we add the ‘1 Byte Out’ module - and 1 x analog point (16-bit) to be transferred from the slave – hence we add the ‘2 Byte In’ module (see below).
When these modules are added, configuration software automatically picks the next free fieldbus interface registers (shown in the Input Address and Output Address columns), which may later be altered by double-clicking on the relevant I/O module. In this example, the automatically chosen locations are Fieldbus IN locations 0..1, and Fieldbus OUT location 0.
Page 85
105U-G Wireless Gateway User Manual
Page 87 © September 2004
2) Fieldbus Configuration.
The next configuration step is to transfer the I/O in the Fieldbus Interace to the Radio Interface so that the profibus I/O is available to the radio network. The 8 x digital output to
be sent to the profibus slave are transferred using a fieldbus write mapping. Since the 8 x digital outputs are all contained in a ‘1 Byte Out’ module, we use ‘Single Bit Mode’ for the fieldbus write mapping. The configured mapping (see below) transfers the 8 x I/O Registers
100..107 in the radio interface to single bits in Fieldbus Location 0 of the fieldbus interface (corresponding to the Output Address of the corresponding ‘1 Byte Out’ module).
The 1 x analog input to be read from the slave must now be transferred to the radio interface. Here we use a fieldbus read mapping using a ‘Word Mode’ (16-bit) transfer from Fieldbus Locations 0..1 to I/O Register 200.
Page 86
Chapter 3 Installation
3) Radio Configuration
To complete the configuration, the I/O that has now been transferred to the radio interface must be mapped over the radio network. The analog input from the slave is mapped to an analog output at a remote 105U-1, the 8 x digital output at the profibus slave will be activated in this example via appropriate mapping from 8 x digital input at a remote 105U-4 (see below).
Page 87
105U-G Wireless Gateway User Manual
Page 89 © September 2004
4.10.4 Message Interface
In addition to cyclic data exchange with slave devices, the 105G Profibus Master also supports a number of acyclcic services that may be triggered via a special Message Interface. The message interface is by default disabled, but will become enabled by also enabling a “Status Location” via the fieldbus configuration tab in configuration software.
The message interface is used to instruct the 105G to perform a specific task, to request data, to indicate certain events (alarms), or to respond to requests. The message interface can be controlled via a host or other smart device by constructing the appropriate message in the Message Interface Area of the 105G I/O Registers (radio interface). Since the message interface is part of the radio interface, it may be controlled either remotely via appropriate block mappings (i.e. remote 105G), or locally via a device on the profibus network (i.e. configuration tool, PLC, or other smart device).
The supported messages are listed in the table below.
Message Description
SET_SLAVE_MODE Send control command to slave(s) (Sync/Freeze) GET_SLAVE_DIAG Get diagnostic information from a slave GET_SLAVE_CONFIG Get slave configuration SET_SLAVE_ADDRESS Set node address of a slave (If supported by slave) MSAC1_READ acyclic read (class 1) MSAC1_WRITE acyclic write (class 1) GET_LIVE_LIST Get information from all nodes on the network MSAC1_PROFIDRIVE_V3_PARAM_
WRITE
PROFIdrive v.3 acyclic parameter access
MSAL1_ALARM_IND Alarm indication from DPV1 slave MSAL1_ALARM_CON Confirmation to FB_MSAL1_ALARM_IND
Page 88
Chapter 3 Installation
The message interface supports the following types of communication:
Command - Response A message is sent by the message initiator, and the message recipient is required to
respond. The message initiator can be either the 105G or host device.
Indication
A message is sent by the message initiator, and no response is required. The message initiator can be either the 105G or host device.
Message Structure
A message consists of a message header and message data (see table below). The header consists of a series of 16-bit registers that specifies the type of message and the length of the message data. The message data may be up to 128 x 16bit registers in length and contain data that is specific to the particular message.
Offset: Register:
0 Message ID 1 Message Information 2 Command Number 3 Data Size 4 Extended Word 1 5 Extended Word 2 6 Extended Word 3 7 Extended Word 4 8 Extended Word 5
9 Extended Word 6 10 Extended Word 7 11 Extended Word 8 12 Message Data
:::
(up to
139 256 Bytes)
Message ID
The Message ID register contains a 16-bit integer identifier for the command. When a response is sent back to the message initiator, the same message ID is used in that message. Message ID’s can be selected arbitrarily, but successive messages must contain different ID’s so as to trigger the execution of the message (i.e. a message will only be executed upon the ID value changing).
Header
Data
Page 89
105U-G Wireless Gateway User Manual
Page 91 © September 2004
Message Information
This register contains information about whether the message is a command or a response,
and may also indicate an error (see below).
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Err C/R(reserved) Error Code Message Type
For example, a command message will always contain the value 4002h in this register. A response message will contain 0002h, and may contain error information as detailed in the table below.
Bit/Field Description Contents
Err This bit indicates if the received message
contains any errors
0: Message OK 1: Error
C/R This bit indicates if the message is a
command or a response
0: Response Message 1: Command Message
Error Code
If the Err bit is set this field contains additional error information
0h: Invalid Message ID 1h: Invalid Message Type 2h: Invalid Command 3h: Invalid Data Size 4h-6h: Message header malformed 8h: Invalid Response 9h: Flash Config Error Fh: Invalid Other (All other values are reserved)
Message Type
This field specifies the message type 2h: This field must always equal 2.
Command Number
This register contains a 16 bit command identifier, which contains the identifier corresponding to the exact message command to be executed.
Data Size
This register specifies the size of the Message Data in bytes. The maximum Message Data size is 256 bytes.
Extended Words 1 ... 8
These registers are specific for each command. Consult the specification for each command for further information.
Page 90
Chapter 3 Installation
Message Interface Addressing
Command messages and response messages are allocated fixed locations in the radio interface (I/O Registers). Also, spontaneously generated alarm messages are allocated unique fixed locations in the radio interface. The memory allocation of these messages in the radio interface is outlined in the table below.
I/O Register Purpose
4550 - 4689 Message IN Area (i.e. Messages to send to Profibus Interface) 4700 - 4839 Message OUT Area (i.e. Messages from Profibus Interface) 4850 - 4899 Spontaneous Message OUT Area (i.e. Alarm Messages from Profibus)
4900 – 4949 Spontaneous Alarm ACK IN Area (i.e. ACK to above)
For example, a message could be sent to the Profibus Interface by constructing the required message in the “Message IN Area”, either via radio using appropriate block mapping(s) or locally via a host device or configuration tool. This message is activated upon change-of-state of the Message ID field (see “Message Structure” above). The profibus interface may generate a response to this message in the “Message OUT Area”, which may then also be transmitted via radio using appropriate block mappings or locally via the host device.
Page 91
105U-G Wireless Gateway User Manual
Page 93 © September 2004
Set Slave Mode
SET_SLAVE_MODE: Command Number = 0003h.
In addition to station related user data transfer, which is executed automatically, the master can send control commands to a single slave, a group of slaves or all slaves simultaneously. These control commands are transmitted as multicast commands. This permits use of sync and freeze modes for event controlled synchronisation of the slaves.
The slaves begin sync mode when they receive a sync command from their assigned master. The outputs of all addressed slaves are then frozen in their current state. During subsequent user data transmissions, the output data are stored at the slaves, but the output states remain unchanged. The stored output data are not sent to the outputs until the next sync command is received. Sync mode is concluded with the unsync command.
Similarly, a freeze control command causes the addressed slaves to assume freeze mode. In this operating mode, the states of the inputs are frozen until the master sends the next freeze command. Freeze mode is concluded with the unfreeze command.
Note : Not all slaves supports this feature. Consult the documentation for the actual slave for further information.
Command and response layout:
Command Response
Message ID
(ID) (ID)
Message Information
4002h 0002h
Command Number
0003h 0003h
Data Size
0000h 0000h
Extended Word 1
Slave
Address
Group Select Slave Address Group Select
Extended Word 2
Control
Command
- Control Command
-
Extended Word 3
- -
Extended Word 4
- -
Extended Word 5
- -
Extended Word 6
- -
Extended Word 7
- Extended Fault Info
Extended Word 8
- Fault Information
Slave Address
Range 1-125; 127 If the request applies for only one slave, that Slave Address must be entered in the range
1-125. If a slave group is to be addressed, Slave Address should be 127 (Multicast address).
Group Select
Range 01h -FFh (Bit coded) This parameter decides which group should be addressed, see below.
Page 92
Chapter 3 Installation
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
Group 8 Group 7 Group 6 Group 5 Group 4 Group 3 Group 2 Group 1
Example: To address Group 1, 2 and 4, the Group Select value should be 0Dh. If an individual slave should be addressed the correct group selection must also be made, since the slave will ignore the message if it does not belong to the requested group(s).
The group(s) a slave belongs to is determined during network configuration with ESeries Configuration Software, and is downloaded during initialisation to each slave via the Profibus telegram Set_Prm.
Control Command
This parameter specifies the command to send.
Bit Explanation
0 (LSB) Reserved (set to zero) 1 Reserved (set to zero) 2 Unfreeze input data 3 Freeze input data 4 Unsynchronize output data 5 Synchronize output data 6 Reserved (set to zero) 7 (MSB) Reserved (set to zero)
Fault Information &Extended Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the response, information about the fault can be found here.
‘Fault Information’ contents ‘Extended Fault Information’ contents
0001h Address out of range ­0002h Group number 0 not permitted -
000Ah Incorrect operation mode 5001h Invalid Freeze group (Group is not initiated to be Freeze group) 5002h Invalid Sync group (Group is not initiated to be a Sync group) 5003h Incorrect Control Command
000Ah
Failed to send Global Control request
5004h No Sync-/ or Freeze groups enabled in master configuration.
00FFh Module not initialised -
Page 93
105U-G Wireless Gateway User Manual
Page 95 © September 2004
Get Slave Diagnostics
GET_SLAVE_DIAG: Command Number = 0004h This command reads diagnostic data from a specified slave. Note: The response data size depends on the actual slave implementation. Range 6 -244.
Command and response layout:
Command Response
Message ID
(ID) (ID)
Message Information
4002h 0002h
Command Number
0004h 0004h
Data Size
0000h (Size of data)
Extended Word 1
Slave
Address
Type of
request
Slave Address
Type of request
Extended Word 2
- -
Extended Word 3
- -
Extended Word 4
- -
Extended Word 5
- -
Extended Word 6
- -
Extended Word 7
- Extended Fault Info
Extended Word 8
- Fault Information
Response data word 1
Station Status1Station Status
2
Response data word 2
Station Status
3
Master
Address
Response data word 3
Ident Number
Response data word 4
:::
Response data word n
Extended Diagnostic Data
Slave Address
Range 1-125, specifies the slave to read diagnostics from.
Type of request
0x00: Internal slave diagnostic request. The diagnostic information stored in the master is returned. Can only be requested for slaves configured by the master.
0x01: External slave diagnostic request. A diagnostic request is sent on the network to the specified slave. Can be requested for all slaves on the network.
Station Status [1 ...3 ]
Consult EN50170 Vol.2 for further information.
Page 94
Chapter 3 Installation
Master Address
Address of the master that parameterized the slave
Ident Number
Unique ID assigned by the Profibus User Organization
Extended Diagnostic Data
Slave user specific diagnostic data. Consult the documentation for the actual slave for further information.
Fault Information &Extended Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the response, information about the fault can be found here.
‘Fault Information’ contents ‘Extended Fault Information’ contents
0001h Address out of range -
0018h
DPMC_M_START has not yet occurred (DPMC_ERR_M_NOT_ALLOWED)
000Ah
Failed to read Diagnostic Data from slave
002Bh
Buffer provided by the user is not sufficient. (DPMC_ERR_M_BLOCK_LEN_INVALID)
00FFh Module not initialised -
Page 95
105U-G Wireless Gateway User Manual
Page 97 © September 2004
Set Slave Address
SET_SLAVE_ADDRESS: Command Number = 0006h This command makes it possible to set the node address of a specified slave, provided that
the slave supports this feature. Note: The message data size depends on the actual slave implementation; range 0 -240 bytes.
Command and response layout:
Command Response
Message ID
(ID) (ID)
Message Information
4002h 0002h
Command Number
0006h 0006h
Data Size
(Size of data) (Size of data)
Extended Word 1
Current
Slave Add
New Slave
Add
Current Slave
Add
New Slave
Add
Extended Word 2
Slave Ident Number Slave Ident Number
Extended Word 3
No_add_Chg -
No_add_
Chg
-
Extended Word 4
- -
Extended Word 5
- Err Code1 Err Code2
Extended Word 6
- Err Code3 Err Code4
Extended Word 7
- Return Code
Extended Word 8
- Fault Information
Message data byte 1
Slave Data 1 Slave Data 1
:::
::: :::
Message data byte n
Slave Data n Slave Data n
Current Slave Address
Range 1-125, specifies the current address of the slave
New Slave Address
Range 1-125, specifies the new address of the slave
Slave Ident Number
Ident number for the slave, whose address should be altered
No_add_Chg
This parameter specifies whether it is allowed to change the slave address again at a later stage. If this is not allowed, then it is only possible to change the address with this function after initial reset. After the initial reset the slave takes the default address 126.
00h: Change of address is still possible at a later stage 01h-FFh: Change of address only possible after the initial address (dflt address = 126)
Page 96
Chapter 3 Installation
Error Code [1 ...4 ]
If ‘Return Code ’ equals 8030h (‘Negative indication from lower layer ’), status values according to the DP-specification are available in ‘Error Code 1 ’. Error Codes 2 ...3 are reserved.
(See "Return Codes" and "Error Codes" in section 4.10.5 below.)
Return Code
See "Return Codes" in section 4.10.5 “DP Error Codes ”.
Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the response, information about the fault can be found here.
0001h: Current slave address out of range. 0002h: New slave address out of range. 000Ah: Failed to execute request.(See ‘Return Code ’ for additional fault information)) 000Bh: Remote station failure.(See ‘Return Code ’ for additional fault information) 00FFh: Module not initialised.
Slave Data
With this parameter it is possible to deliver user specific data. The data is stored in the slave if possible (i.e. EEPROM, FLASH etc.)
Page 97
105U-G Wireless Gateway User Manual
Page 99 © September 2004
Get Live List
GET_LIVE_LIST: Command Number = 0018h This command returns 127 bytes of information about the nodes on the network. Every byte
stands for one bus subscriber, and the position of the byte in the response data assigns the address
Command and response layout:
Command Response
Message ID
(ID) (ID)
Message Information
4002h 0002h
Command Number
0018h 0018h
Data Size
0000h 007Fh
Extended Word 1
- -
Extended Word 2
- -
Extended Word 3
- -
Extended Word 4
- -
Extended Word 5
- -
Extended Word 6
- -
Extended Word 7
- Return Code
Extended Word 8
- Fault Information
Response data byte 1
Station Type 0
Response data byte 2
Station Type 1
:::
:::
Response data byte 127
Station Type 126
Station Type [0 ...126]
00h: Slave Station 01h: Master Station not yet ready for Token ring (station only physically at the bus) 02h: Master Station ready to enter Token ring (there is not yet any Token
transmission) 03h: Master Station in Token ring (Token transmission through the station) 04h: Station does not exist
Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the response, information about the fault can be found here.
000Ah: Failed to build Live List 00FFh: Module not initialised
Page 98
Chapter 3 Installation
DPV1 Acyclic Read
MSAC1_READ: Command Number = 0020h This command initiates a DPV1 Class 1 acyclic read request. Consult EN50170 (DPV1) for
more information.
Command and response layout:
Command Response
Message ID
(ID) (ID)
Message Information
4002h 0002h
Command Number
0020h 0020h
Data Size
0000h (Size of data)
Extended Word 1
Slave Add Slot No. Slave Add Slot No.
Extended Word 2
Index Length Index Length
Extended Word 3
- -
Extended Word 4
- -
Extended Word 5
- - Error Decode
Extended Word 6
- Err Code1 Err Code2
Extended Word 7
- Return Code
Extended Word 8
- Fault Information
Response data byte 1
Data 1
Response data byte 2
Data 2
:::
:::
Response data byte n
Data n
Slave Address
Station address of the slave responder
Slot Number &Slot Index
Used in the slave to address the desired data block.
Length
This parameter specifies the number of bytes of the data block that has to be read. If the server data block length is less than requested, the length of the response will be the actual length of the data block. If the server data block is greater or equal, then the response will contain the same amount of data.
The slave may answer with an error response if the data access is not allowed.
Data [1 ...n]
Returned data
Return Code
See "Return Codes" in section “DP Error Codes ” below.
Page 99
105U-G Wireless Gateway User Manual
Page 101 © September 2004
Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the response,
information about the fault can be found here. 0001h: Address out of range 000Ah: Failed to execute MSAC1_Alarm_Ack request 000Bh: Remote station failure 0010h: Remote Station DPV1 Failure (see ‘Error Decode’ below). 00FFh: Module not initialised
Error Decode, Error Code 1 & Error Code 2
If ‘Fault Information ’ contains error code 0010h, more information according to the DPV1 specification can be found here.
Page 100
Chapter 3 Installation
DPV1 Acyclic Write
MSAC1_WRITE: Command Number = 0021h This command initiates a DPV1 Class 1 acyclic write request. Consult EN50170 (DPV1) for
more information.
Command and response layout:
Command Response
Message ID
(ID) (ID)
Message Information
4002h 0002h
Command Number
0021h 0021h
Data Size
(Size of data) (Size of data)
Extended Word 1
Slave Add Slot No. Slave Add Slot No.
Extended Word 2
Index Length Index Length
Extended Word 3
- -
Extended Word 4
- -
Extended Word 5
- - Error Decode
Extended Word 6
- Err Code1 Err Code2
Extended Word 7
- Return Code
Extended Word 8
- Fault Information
Message data byte 1
Data 1 Data 1
:::
::: :::
Message data byte n
Data n Data n
Slave Address
Station address of the slave responder
Slot Number & Slot Index
Used in the slave to address the desired data block.
Length
This parameter specifies the number of bytes that has to be written. If the destination data block size is less than requested, the response will contain an error message. If the data block length is greater than or equal to the requested length, the response contains the number of bytes that has been written. The slave may answer with an error response if the data access is not allowed.
Data [ 1 ...n ]
Data that should be written.