Elotech R4000 Description And Operating Manual

Page 1
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 1 / 36
R4000
Temperature Controller with 4 or 8 zones Heating/Cooling
Depth: 122mm Format: 96mm x 96mm
DESCRIPTION AND OPERATING MANUAL
ELOTECH Industrieelektronik GmbH
Verbindungsstraße 27 D - 40723 HILDEN FON +49 2103 / 255 97 0 FAX +49 2103 / 255 97 29 www.elotech.de Email: info@elotech.de
Page 2
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 2 / 36
Contents
Contents ....................................................................................................................................... 2
1 General Information ................................................................................................................ 3
2 Installation Instructions ........................................................................................................... 3
3 Type Code .............................................................................................................................. 4
4 Connection Diagram ............................................................................................................... 5
4.1 Connection Diagram: Power supply, Logic Inputs and Heater Current ................................ 5
4.2 Connection Diagram: Monitoring Relay ............................................................................. 6
4.3 Connection Diagram: Sensor Inputs ................................................................................. 6
4.4 Connection Diagram: Logic Outputs ................................................................................. 6
4.5 Connection Diagram: Relay Outputs ................................................................................. 7
4.6 Connection Diagram: Fieldbus Interfaces ......................................................................... 7
4.7 Connection Diagram: LAN and USB .................................................................................. 7
5 Display and Keyboard ............................................................................................................. 8
5.1 Window-Overview ........................................................................................................... 8
5.2 Display screens (Windows) .............................................................................................. 9
5.2.1 Window: Actual Process Values ................................................................................ 9
5.2.2 Window: Main ........................................................................................................10
5.2.3 Window: Zone synopsis ..........................................................................................11
5.2.4 Window: Monitoring display ....................................................................................12
5.3 Adjusting windows .........................................................................................................13
5.3.1 Window: Entering number value .............................................................................13
5.3.2 Window: Selection with tiles ....................................................................................14
5.3.3 Window: Selection List view ....................................................................................14
5.3.4 Window: Saving to multiple zones ...........................................................................15
5.3.5 Window: Setting text ..............................................................................................15
5.4 More display screens (more Windows) ............................................................................16
5.4.1 Window: Process ....................................................................................................16
5.4.2 Window: Graph ......................................................................................................16
5.4.3 Window: Log (Logbook) ..........................................................................................17
5.4.4 Window: Program (Program controller graph) ..........................................................17
5.4.5 Window: Program controller Selection/Setting ..........................................................18
Course of program control: .................................................................................18
5.4.6 Window: Parameter ................................................................................................19
5.4.7 Zone – Parameter list .............................................................................................19
Menu: Heating Control Parameter ........................................................................21
Menu: Cooling Control Parameter ........................................................................22
Ramps: Ramp rising / Ramp falling ......................................................................23
Menu: Softstart ..................................................................................................23
Menu: Alarm values ............................................................................................24
Menu: Sensor settings .........................................................................................25
5.4.8 Window: Tools .......................................................................................................25
Configuration Monitoring 1+2 ..............................................................................26
Configuration -Alarm 1+2 ................................................................................27
Configuration Current alarm (option) ...................................................................28
5.4.9 Wizard ...................................................................................................................29
5.4.10 Window: System ....................................................................................................29
Settings .............................................................................................................30
Field bus / USB / LAN ..........................................................................................31
About / Firmware update ................................................................................33
Sensor ...............................................................................................................33
Configuration Output relay ..................................................................................34
Configuration Output digital ................................................................................34
6 Error Messages ......................................................................................................................34
7 Technical Data .......................................................................................................................35
Page 3
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 3 / 36
1 General Information
Symbols used:
www.elotech.de
Messages shown by the
controller are written in this font.
MRS / MRE
M
easuring
R
ange
S
tart /
M
easuring
R
ange
End
<§>
Symbolizes the value of the factory adjustment of the respective pa-
rameters.
2 Installation Instructions
Make sure the device is used for the intended purpose only. R4000 controllers are designed for installation in control panels.
Protect the device against impermissible humidity and contamination. The permitted ambient temperature range may not be exceeded.
Electrical connections must be made according to valid regulations and by properly qualified personnel.
If using thermocouple sensors, compensation lines have to be connected directly to the con­troller terminals. Sensors may be connected only in compliance with the programmed range.
Sensor cables and signal lines (e.g. logic or linear voltage outputs) must be laid separately from control lines and mains voltage supply cables (power cables). In order to maintain CE-Compliance screened detectors - and signal lines have to be used. It is not permitted to connect the grounds of the sensor-inputs and logic-outputs with each other.
Separate installation of controller and inductive loads is recommended. Interference from contactor coils must be suppressed by connecting adapted RC-combina­tions parallel to the coils. Control circuits (e.g. for contactors) should not be connected to the mains power supply ter­minals of the controller.
The configuration parameters (Window: System) are generally to be selected first.
Disclaimer of Liability
The contents of this document is checked for the conformity with the hardware and software described. Nevertheless, we are unable to preclude the possibility of deviations so that we are unable to assume warranty for full compliance. However, the information given in the publication is reviewed regularly. Necessary amendments are incorporated in the following editions. We would be pleased to receive any improvement proposals which you may have. The information contained herein is subject to change without notice.
Electronic scrap and components are subject to special treatment and must be disposed of by authorised companies.
Page 4
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 4 / 36
3 Type Code
R4000 - y - 000aa- dd- - 5
24 VDC5
No00 RS 232-C +
RS 485 + 0/20mA TTY
03
CAN07 Profibus-DP09
No0
Power Supply:
Fieldbus Interface:
Heater Current Monitoring:
Yes
(Logic outputs only)
5
4-zones04
Zones:
8-zones08
Page 5
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 5 / 36
4 Connection Diagram
Ground connection
Ground connection (flat plug 6,3mm) must be connected to an earth rail via a thick cable (>=4qmm) in the shortest possible way (<20cm)!
4.1 Connection Diagram:
Power supply, Logic Inputs and Heater Current
Function of the logic inputs:
In_1: 0 = Setpoint 1 active for all zones. 1 = Setpoint2 active for all zones.
In_2: 0 = Parameter “Authorisation” is adjustable. 1 = Parameter “Authorisation” is not adjustable.
In_3: no function
In_4: no function
Page 6
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 6 / 36
4.2 Connection Diagram: Monitoring Relay
4.3 Connection Diagram: Sensor Inputs
It is not permitted to connect the grounds of the sensor-inputs and logic-outputs with each other!
RTD: The parameter “Sensor Settings / Sensor” has to be set accordingly to the connection diagram (2-wire/3-wire)
4.4 Connection Diagram: Logic Outputs
The power supply for the logic outputs has to be wired ex­ternally: +24V have to be applied to the terminals B3 and G3.
B3 is connected internally to E3 and G3 is connected to K3. So the terminals E3 and K3 can be used to loop the +24V.
Page 7
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 7 / 36
4.5 Connection Diagram: Relay Outputs
4.6 Connection Diagram: Fieldbus Interfaces
Type 03 / 07 : Serial Interface / CAN
The serial fieldbus module (Type: 03) contains the three interfaces RS232, RS485 und TTY. By choosing the connection and setting the parameter ”HW-config“ the desired bus is selected.
Typ 09: Profibus
The 5V-Supply is designed for the supply of the termination resistors. Further loads are not allowed.
4.7 Connection Diagram: LAN and USB
USB: Save process data, configuration data and alarm data on an USB-Stick. Write back configuration data from USB-Stick to the controller. Make a Firmwareupdate. (Please use FAT formatted USB flash drives.)
LAN: Connection to configuration tool Elovision 3. Read and write parameters by MODBUS-TCP protocol.
Bus Type Remark
A B RS485 03 Parameter HW-config = RS232 / RS485
RxD TxD GND RS232 03 Parameter HW-config = RS232 / RS485
- + TTY 03 Parameter HW-config = TTY (current loop)
H L CAN 07 Not available at the moment
Pin 3 Data RxD / TxD - P
Pin 5 GND
Pin 6 +5V
Pin 8 Data RxD / TxD - N
Page 8
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 8 / 36
5 Display and Keyboard
The device is equipped with a backlight color LC-display. After switching on the controller and completion of the initialization, the actual process val-
ues and setpoints of all connected zones are displayed. The device is operated by menus. The different parameters are displayed mainly in plain text
and can be displayed in various languages.
There are several windows for different functions and settings.
5.1 Window-Overview
Home
Process
Log
Zone synopsis
Graph
Program controller
Main
Parameter
Tools
System
= Hold down the key (> 2 s)
Page 9
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 9 / 36
5.2 Display screens (Windows)
5.2.1 Window: Actual Process Values
Display of setpoints and actual process values of all connected zones.
The header displays
on the
left
the current unit,
here °C. The top right shows the time.
The hexagon displays the zone number. If the zone is turned off, the actual process value displays “OFF“, here seen in zone 5, and the hex­agon showing the number of the zone is grey.
8-zone-controller: For every zone the actual process value is written in large and the setpoint in small numbers.
4-zone-controller: For every zone the actual process value (in the right column) and the setpoint (in the left col­umn) is displayed.
Monitoring
1 of zone 4 is active.
Monitoring
2 of zone 8 is active.
At this point the signal has an enable function. Therefore the colour green was chosen.
Ramp
s of zone 3 and 6 are
active.
Soft start
function
of zone 7 is
active.
Auto tune
of zone 2 is active.
Contact of
Monitoring
relay 1 is closed.
Contact of Monitoring relay 2 is open.
T
apping the area of the zone, here zone 2,
leads to
the next
menu. A grey frame and blue zone symbols show up while pressing the key. Briefly pressing the key leads to the zone overview. Holding down the key (>2s) leads to the main.
Page 10
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 10 / 36
5.2.2 Window: Main
This window contains a summary of the other function windows.
One gets to this window by pressing the area of a
selected zone in the window ”Actual Process Value” for more than 2 seconds.
Likewise, you come into this window by pressing the following icon. In different windows this symbol ap­pears in the lower left corner.
Jump
to window “
Actual Process Value“
Display for all zones: Actual process value, setpoint, output ratio, alarms, ramp, autotune, softstart
Jump
to wi
ndow “
Zone synopsis
Display and entry for selected zone: Actual process value, setpoint, output ratio, current, monitoring state, ramp, autotune, softstart
Jump
to window “
Process“
(List view)
Display for all zones: Actual process value, setpoint, output ratio, current, monitoring state
Jump
to window “
Graph“
Display for selected zone: Graphical display of the actual value process­temperature over time
Jump
to window “
Log“
Display for all zones: Alarm- und status messages
Jump
to window “
Parameter“
Display and entry for all zones: All zone-parameter
Jump
to window “
Tools“
Configuration of the monitoring, the alarms and power-on mode. Calling of the Wizard (set-up assistance)
Jump
to window “
System“
Configuration inputs, outputs and interfaces
Hold down
< 2 sec
. = Return to previous window
Hold down > 2 sec. = Jump to window “Actual Process Value“
Page 11
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 11 / 36
5.2.3 Window: Zone synopsis
This window contains the most important information of the selected zone. The window appears after the area of the zone in the window “Actual Process Value” has been briefly pressed.
In the header the currently
selected
zone is
shown.
Underneath from left to right the following is dis­played: Actual process value, output ratio and heater cur­rent.
Negative output ratio implies cooling mode.
Shown is the current setpoint.
When editing the setpoint the blue area has to be pressed.
Setpoint 2 is active.
It is not allowed to edit setpoint 2 in this window.
Display of
m
onitoring
1.
Grey = signal not active. Colored = signal active Pressing the area leads to the window “Monitoring display”. The same applies to monitoring 2.
Output ratio
shown as bar.
White bar: positive output ratio (heating). Blue bar: negative output ratio (cooling).
Autotune
: grey = not active, yellow = active
Pressing the area leads to the window “Autotune”
Ramp: grey
= not
active
,
yellow = ac
tive
Pressing the area leads to the window “Ramp rising/falling”
Softstart
: grey = not active, yellow = active
Pressing the area leads to the window “Softstart”
Heating: grey = Heater switched off, yellow = Heater switched on
.
Cooling: grey
= Cooler switched off
,
blue =
Cooler switched on
”+“ switchover to the next zone.
Display of the current zone number
” - “ switchover to the previous zone.
J
ump
to window
Main
Jump
to window
Parameter“
Jump
to window
Graph“
Page 12
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 12 / 36
5.2.4 Window: Monitoring display
In the header the currently selected zone is
shown.
The key “configuration Moni x / Alarm“ leads to the configuration of monitoring and alarms. See chapter 5.4.8.1
The key “Log“ leads to the alarm logbook for fur­ther information regarding the occurred alarms
The light blue background and the colored frame shows that the
event ”-Alarm 1“ has triggered the monitoring. In case the event needs an acknowledgement it must be done by pressing the button.
The dark blue background shows that the event “Sensor error” is
programmed for triggering the monitoring. The event is not active.
The dark
grey background shows that the event “System error” is not
programmed for triggering the monitoring. In case of a system error the monitoring will not be active.
”+“ switchover to the next zone.
Display of the current zone number
” - “ switchover to the previous zone.
Jump
to window “
Main“
Return to previous window
Page 13
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 13 / 36
5.3 Adjusting windows
5.3.1 Window: Entering number value
This window helps entering number values, here for the setpoint 1.
The header displays th
e current zone
and the
name of the Parameter, here “Setpoint 1 “.
By pressing the number keys the value of the pa­rameters can be entered. In order to take over the parameter value, it must be saved by pressing the “SAVE”– key.
The value
, entered by pressing the number keys, is now displayed
within the blue frame. Underneath, on the left the unit is shown and the previous value is displayed on the right (250). The allowed range is displayed at the bottom (0...800).
If this Button
is visible, two adjustable parameters are available.
Such as: Setpoint: 1 / 2 or Ramp: rising / falling Switch over by pressing this button. The name of the actual parame­ter is displayed in the header. After adjusting one parameter the win­dow will not be closed and the second parameter can be adjusted.
This key is visible when the parameter has a valid value “OFF”.
“OFF” can be selected like a number key.
Number key
Key to enter “M
inus”
or “C
omma
”.
The minus sign can be pressed before entering a number. After the first number was entered the key automatically changes to comma.
Delete last character
Return to previous window
Saving of what has been entered and return to previous window
.
By pressing “SAVE” for > 2s., a selection window appears, in which parameter values can be saved for other zones simultaneously. See 5.3.4 Window: Saving to multiple zones.
Page 14
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 14 / 36
5.3.2 Window: Selection with tiles
The header displays the
zone numb
er and the
parameter name on the left, here “Zone On/Off“.
By pressing the tile key, the element can be se­lected. Black text on a white background is used to dis­play the selected element.
In order to save the parameter value, the “SAVE”­key needs to be pressed.
Selected element.
Not
selected element.
“+” switchover to the next zone.
Display of the current zone number “–” switchover to the previous zone.
Saving of selection and return to previous window
.
When pressing
“SAVE” for >2s a selection window opens up, in which the parameter value can be saved onto other zones simultaneously. See 5.3.4 Window: Saving to multiple zones
Return to previous window
5.3.3 Window: Selection List view
The header displays the
zone and the
parameter
name, here “Zone On/Off“.
The actual value is displayed in the middle with light blue background. By pressing the +/- Buttons on the right (or pressing the upper or lower areas of the list) the list can slide up or down.
In order to save the parameter value, the “SAVE”-key needs to be pressed.
“+” switchover to the next zone.
Display of the current zone number “ – ” switchover to the previous zone.
Saving of selection and return to previous window
When pressing “SAVE” for >
2s a selection window opens up, in which
the parameter value can be saved onto other zones simultaneously. See 5.3.4 Window: Saving to multiple zones
Return to previous window
Page 15
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 15 / 36
5.3.4 Window: Saving to multiple zones
The
zone
(here 1)
that
now
has to be saved is se-
lected and cannot be deactivated.
By tapping the relevant zone field another zone can be added or deleted. Black number on white symbol means “Zone chosen to be saved“ The lowest key “1…8” selects all zones at the same time. “ESC” closes the window without saving.
“SAVE”, saves the adjusted parameter value for all zones selected and closes the window.
5.3.5 Window: Setting text
This window is used to enter text for description of program names.
The header
displays the actual program number
and the actual program name.
By pressing the number keys „0 ... 9” the new text can be entered. To set the following letters “ABC1” you have to press the key more times.
After one second the character is taken over and the next character can be entered.
In order to take over the new text, it must be saved by pressing the ”SAVE“– key.
The new text is displayed in the blue
/white
frame.
Delete last character
.
Delete all characters
.
Key for setting the text.
Repeated pressing changes to the next char-
acter. Here "A B C 2 Ä"
Switching case sensitive.
Capital and small letters.
Return to previous window
Saving of the new text and return to previous window.
Page 16
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 16 / 36
5.4 More display screens (more Windows)
5.4.1 Window: Process
This window displays an overview of all zones.
Six columns display
the following
for all zones:
1. Zone number
2. Actual Process Value (Proc[°C])
3. Actual Setpoint (Set[°C])
4. Output ratio (Y[%])
5. Heater current (I[A])
6. Monitoring 1+2 (bell symbols)
Display of Monitoring 1 (2).
Grey = signal not active. Coloured = signal active
Hold down
< 2 sec
. =
Return to previous
window
Hold down > 2 sec. = Jump to window “Actual Process Value“
Jump
to window “
Main
5.4.2 Window: Graph
This window shows the temperature progression for one selected zone. In the case of a technical incident the actual process value can still be examined afterwards.
On the right the actual p
rocess
v
alue is shown,
here 250°C.
By pressing the loupe keys “+” and “ – ” the reso­lution of the temperature axis can be altered.
The time axis can be determined by the parame­ter “Graph sampling time” in the window “Sys­tem/Settings“.
Turning off the device causes deletion of the val­ues.
”+ ” switchover to the
next zone.
Display of the current zone number “ - ” switchover to the previous zone.
Hold down
< 2 se
c
. =
Return to previous window
Hold down > 2 sec. = Jump to window “Actual Process Value“
Jump
to window “
Main
Page 17
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 17 / 36
5.4.3 Window: Log (Logbook)
This window displays alarm- and status messages for all zones.
The header displays
the
current date and time,
the window number and page.
Pressing the log-texts displays the full text if it is are abbreviated in the normal display.
The logbook can take up to 40 entries. The latest entry can be found on page 1/5. If 40 entries exist already, the oldest entry will be deleted. The logbook is stored in a power failure safe man­ner.
Switching between the logbook
-
pages
”+“ previous page; ” - “ next page
Alternatively press the upper or lower areas of the list for switching.
Hold down < 2 sec. = Return to previous window
Hold down > 2 sec. = Jump to window “Actual Process Value“
Deletion
of the logbook
-
entries
5.4.4 Window: Program (Program controller graph)
This image shows the graphical representation of the selected control program.
The header display
s the current program, the cur-
rent step and the status. Right above the graph is the indication of the cur­rent program setpoint.
On the right side, the zones are displayed, whose setpoints are specified by the program.
At the bottom (x-axis) the time is shown in hours.
The elapsed time is displayed as a blue ribbon. Here on the left below the 105. The current time is indicated by the thin blue line at the right end of the tape.
These keys are used to control the program.
Stop Pause and Start. If the program is stopped you will get to the menu for the program controller via the Edit button.
If the total time of the program has expired (Stop displayed), the set­point of the last program step is retained.
Hold down < 2 sec. = Return to previous window
Hold down > 2 sec. = Jump to window “Actual Process Value“
Page 18
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 18 / 36
5.4.5 Window: Program controller Selection/Setting
This window gives an overview of the 8 control programs. One arrives on the Edit button in the "Program controller graph" into this menu.
Select the program
The green frame shows the selected program.
Select a other program by pressing + and – keys.
Press the respective program button branches to the setup menu of the program.
Adjust the program steps
From this window, the individual steps can be set.
The name key is used to set the program name.
With the key "For Zone", the zones that will follow the program are defined.
Headline
Window:
Actual Process Values
„Home“
Headline of the screen: “Actual Process Values”
Program controller active, Step2 is running. Top picture: Program running. Bottom picture: Program paused or stopped.
Course of program control:
Preliminary the time and temperature values for the desired steps have to be entered in the window "program steps setting".
The time for the first step is the dwell time on the associated setpoint.
The time for the subsequent steps describes the duration, the program needs to reach from the setpoint value of the previous step to the setpoint value of the current step.
For example. Step 1: 0:20 h / 80 ° C -> Initially set the setpoint of 80 ° C for 20min.
Step 2: 0:30 h / 360 ° C -> After that the setpoint is continuously increased starting at 80 ° C, so that after 30 minutes 360 ° C has been reached. Step 3: 0:20 / 360 ° C -> Holding setpoint 360 ° C for 20 min. Step 4: 00:40 / 55 ° C -
> Reducing the setpoint continuously within 40 minutes from
Page 19
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 19 / 36
360 ° C to 55 °
C.
Step 5: OFF / 0 ° C -> This step is not executed. The last step is the step before the step with time is set to OFF. If no time of the program is turned "OFF", this is the Step 8.
After the total time of a started program the last setpoint is maintained.
After a power failure, during the program was running, the controller switches to the pro­gram step again, in which the interruption happened.
5.4.6 Window: Parameter
This window is used as a display and input of all zone-parameters for all zones.
The header displays on the left the
zone number
and the window name, here “Main/Parameter“.
The selected parameter is displayed in the middle with light blue background. By pressing the +/- Buttons on the right (or pressing the upper or lower areas of the list) the list can slide up or down.
Pressing the selected parameter will switch to a corresponding selection window.
“+” switchover to the next zone.
Display of the current zone number “ - ” switchover to the previous zone.
Hold down
< 2 se
c
. =
Return to previous window
Hold down > 2 sec. = Jump to window “Actual Process Value“
Jump to window “
Main
5.4.7 Zone – Parameter list
Zone On/Off On
Measuring
- or controlling zone active
<§>
Off
Measuring
- or controlling zone switched off
Setpoint
1 / 2
Setpoint
1 / S
etpoint
2
Setpoint 1 Setpoint min …
Setpoint max
S
etpoint
1 <§> =
0
Setpoint 2 OFF(Setpoint min) …
Setpoint max
S
etpoint
2 <§> =
OFF
As soon as the logic input In_1 is on level 1, setpoint 2 will become active on all zones in which the ad­justed value is unlike “Off“.
Page 20
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 20 / 36
Autotune off
Switches off autotune
<§>
on
Ac
tivates autotune
The tuning algorithm determines the characteristic values within the controlled process
and calculates the valid feedback parameters (P, D, I) and the cycle time. (= 0.3 x D) of a PD/I- controller for a wide section of the range.
The autotune mode works during start-up shortly before the setpoint is reached. If acti­vated after the setpoint has already been reached, the temperature will first drop by ap­prox. 5% of the measuring range.
The tuning algorithm can be activated at any time by selecting the parameter Autotune = ”on”. After having calculated the feedback parameters, the controller will lead the process value to the actual setpoint.
Selecting Autotune = ”off” will stop the autotune function.
Autotune active: Indication in display “Zone synopsis“ and “Actual process values” as an orange symbol:
Autotune duration > 2 hours: autotune stops with an error message.
Conditions for starting the autotune algorithm:
- The setpoint must amount to at least 5% of the measurement range
- The sensor must not have a failure.
- The softstart function must not be active
Configuration Heating­Cooling
Heating
Two-point controller: "Heating
"
<§>
Cooling
Two-point controlle
r: "
Cooling
"
Non-lin. Cooling
Two-point controller
: "
Cooling
" ,
with non
-
linear
characteristic curve for evaporation cooling
Heating-Cooling
Three
-
point controller: ”Heating
Off–Cooling”
Hints for adjusting the control parameters:
As standard the controller operates in PD/I control mode, i.e. controlling without deviation and with practically no overshoot during start-up. The control action can be altered in its structure by adjusting the following parameters:
t
X
t
X
Set
OPT on
self tune during start-up
OPT on self tune, after the setpoint has already been reached
self tune start
Set
Page 21
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 21 / 36
a. no control action
(on-off) Setting P = off
Continuing with the parameter “switching difference“
b. P-action
Setting D and I = off
c. PD
-
action
Setting I = off
d. PI
-
action
Setting D = off
e. PD/I
Modified PID
-
mode (set: P,D,I)
Depending on the configuration, certain parameters are not visible.
Menu: Heating Control Parameter
Only visible in operating modes heating and heating-cooling
P (xp) OFF, 0.1 ...400.0K
Proportional range
<§=
10
,0> Unit: Kelvin
D (tv) OFF, 1 … 200s
Derivative time
<§=30s>
I (tn) OFF, 1 … 1000s
Reset time
<§=150>
Cycle-time 0.5 … 240.0s
<§=10,0s>
The switching frequency of the actuator can be deter­mined through the cycle time. In this time interval the controller switches on and off once. Voltage outputs for solid state relays (SSR): Cycle time: 0,5...10 s Preferred settings for rapid control processes: 0,8s Relay outputs: Cycle time: > 10 s The cycle time should be adjusted to a time as long as possible in order to minimize wear of the relay contacts.
Max. Output ratio
0 .. 100%
<§=100%>
The limitation of the output ratio is only necessary, if the heating energy supply is grossly overdimensioned compared to the power required. Normally it should be switched off (Setting: 100 %). The limitation becomes effective when the controller´s calculated output ratio is greater than the maximum permissible (limited) ratio. Warning! The output ratio limiting does not work dur­ing autotune.
Hysteresis
Only adjustable if ”(xp)“ = off (on-off action, without feedback)
OFF,0.1 ..80.0
For measuring range without decimal point
<§=
0.1>
OFF, 0.01 .. 8.00
For measuring range with decimal point
<§=
0.01
>
process value
setpoint
Hysteresis:
10.0
-5.0 +5.0
Page 22
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 22 / 36
Menu: Cooling Control Parameter
Only visible in operating modes Cooling and Heating-Cooling
P (xp) OFF, 0.1 ... 400.0K
Proportional band
<§=
10
,0> Unit: Kelvin
D (tv) OFF, 1 … 200s
Rate
time
<§=30s>
I (tn) OFF, 1 …1000s
Reset time
<§=150>
Cycle time 0.5 … 240.0s
<§=10,0s>
The switching frequency of the actuator can be deter­mined by adjusting the cycle time. In this time interval the controller switches on and off once.
Voltage outputs for solid state relays (SSR): Cycle time: 0,5...10 s Optimal value for fast control loops: 0,8s Relay-Outputs: Cycle time: > 10 s In order to minimize the wear of the relay contacts the cycle time should be set as long as possible.
Max. Output ratio
0 ... 100%
<§=100%>
Limitation of the output ratio is only necessary, if the power supply of the control route is grossly overdi­mensioned. Normally it should be switched off (Setting: 100 %). Output ratio limiting interferes, if the calculated output ratio of the controller is higher than the max. output ratio that was set. Caution! Output ratio limiting does not work while auto-tune.
Hysteresis
Only adjustable if “P (xp)“ = off (on-off action, without feedback)
OFF, 0.1 … 80.0
For measuring range without decimal point
<§=
0.1>
OFF, 0.01 ... 8.00
For meas
uring range with decimal point
<§=
0.01
>
Deadband
Switching point distance ”heating“ and ”
cooling“
This parameter is available for “heating and cooling” operations only. (Configuration Heating-Cooling = Heating-Cooling)
OFF, 0.1 ... 80.0
For measuring range without decimal poin
t <§=
0.1>
OFF, 0.01 ... 8.00
For meas
uring range with decimal point
<§=
0.01
>
process value
setpoint
Hysteresis:
10.0
-5.0 +5.0
Page 23
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 23 / 36
Ramps: Ramp rising / Ramp falling
A programmed ramp is always
activated when the setpoint is changed or when the mains supply is switched on. The ramp starts at the actual pro­cess value and ends at the pre­selected setpoint. The ramp can be activated for both set­point 1 and setpoint 2. By pro­gramming the second setpoint a setpoint profile can be ob­tained, accordingly (see exam­ple with external contact In_1 (K1) below).
Ramp rising OFF<§>, 0.1 ... 99,9
°K/min for measurement range without decimal point
OFF<§>, 0.01 … 9.99
°K
/min for measurement range with decimal point
Ramp falling OFF<§>, 0.1 ... 99,9
°K/min for measurement range without decimal point
OFF<§>, 0.01 … 9.99
°K/min for
measurement range with decimal point
Menu: Softstart
Softstart-Function
For using the
softstart function, make sure that the instrument is
programmed to
voltage
(logic) outputs. This function is not allowed for relay outputs. Otherwise the relays will be damaged. During the softstart the controller's heating output response is limited to a pre­selected ratio, in order to achieve a slow drying of high performance heat cartridges. This results in a slower, more regular heating period. Simultaneously the output clock frequency is quadrupled. Once the process value reaches the softstart setpoint, it remains stable at this value for the preselected duration time. At the end of this period the process value rises to the valid setpoint. If the softstart is active, the controller's autotune function cannot operate. If a setpoint ramp has been programmed, the softstart has priority, and the ramp will be­come active after the softstart has been completed.
The softstart only works:
- if the parameter P (xp) is programmed > 0,1%
- if the actual process value is lower than the softstart setpoint – 5% of the selected measuring range
It is possible to select this function for each zone individually.
Softstart On/Off
Off
Softstart function not active.
<§>
The remaining softstart parameters are not displayed.
On
Softstart function is active.
Softstart Output ratio
10 ... 100%
<§ = 30>
Softstart setpoint
Range: Setpoint min…setpoint max.
<§ = 100°C>
Duration time Off, 0.1 … 10.0 min
<§ = 2.0 min>
Page 24
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 24 / 36
Output mode Controller mode
Control
ler mode
Mode AUTOM.
In
the
event of sensor break
the
last valid output ratio
is maintained.
Like the setpoint, the output ratio can be changed manually.
Under the following circumstances, the output ratio will be 0%:
- if the output ratio was at the time of sensor break 100%
- if the controller is working along a setpoint-ramp
- if the control deviation from the measuring range was at time of sensor break > 0,25%
- if parameter is set P (xp) = 0
- if softstart was active at the time of sensor break.
A few seconds after sensor break has been rectified, the controller returns to automatic operation and calculates the required output ratio.
Mode MANUAL
The controller now operates as an actuator only.
The control function is inactive
Process display: Actual process value. Setpoint display: Display of current output ratio in %. The output ratio can be changed manually.
Menu: Alarm values
Adjustment of the alarm values. It is necessary to
set the alarm configuration first. See: 5.4.8.2
-Alarm value 1 _
Insufficient temperature Alarm 1
OFF(MRS) ... MRE
For a
bsolute
temperature
alarms
<§>
= OFF
-100 ... OFF(0)
For r
elative
temperature
alarms
-Alarm value 1 ˉ
Excessive temperature Alarm 1
OFF(MRS) ... MRE
For absolute
temperature
alarms
<§>
= OFF
OFF(0) ... 100
For relative
temperature
alarms
-Alarm value 2 _
Insufficient temperature Alarm 2
OFF(MRS) ... MRE
For absolute
temperature
alarms
<§>
= OFF
-100 ... OFF(0)
For relative
temperature
alarms
-Alarm value 2 ˉ
Excessive temperature Alarm 2
OFF(MRS) ... MRE
For absolute
temperature
alarms
<§>
= OFF
OFF(0) ... 100
For relative
temperature
alarms
Undercurrent val. OFF(0) ... 99,9
<§>
= OFF
Overcurrent val. OFF(0) ... 99,9
<§>
= OFF
Page 25
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 25 / 36
Menu: Sensor settings
All parameters for sensor configuration
Sensor
See 0
Process offset -999..0..1000°C
<§= 0°C>
This parameter serves to correct the input signal:
- the correction of a gradient between the measuring point and the sensor tip
- line resistance balancing at 2-wire-RTD
- Correction of the control deviation when using P or PD action. If for example the offset value is set to +5°C, then the real temperature measured by the sensor is 5°C less than the displayed actual process value. Make sure that the adjusted actual temperature value should not fall below or exceed the measur­ing range limits.
Setpoint min. MR-Start ...
Setpoint max.
Lowest adjustable setpoint value.
<§ = 0
>
MR-Start: Start of measurement range
Setpoint max. Setpoint min …
MR-End
Highest adjustable setpoint value.
<§= 400
>
MR-End: End of measurement range
The minimal span of l
inear value min. and max. is 100, the maximal span is 2000.
Linear value min.
For linear measure­ment range only
-900 … (Linear value max. -100)
Measuring range starting value of the linear scale.
<§= 0>
Linear value max.
For linear measure­ment range only
(Linear value min. +100) …
10.000
Measuring range final value of the linear scale.
<§= 1000>
Lin-Exponent 0 … 2
Exponent of the linear measuring range.
<§= 0>
5.4.8 Window: Tools
Pressing the configuration key leads to windows in
which the associated parameters can be selected or set.
Pressing the wizard key activates a guided setting help for the most important device parameters.
Hold down
< 2 sec
. =
Return to previous
window
Hold down > 2 sec. = Jump to window ”Actual Process Value“
Jump to window ”
Main
Page 26
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 26 / 36
Configuration Monitoring 1+2
Settings
for
messages of monitoring 1
.
The same applies to monitoring
(2).
The controller has two independent monitoring relays.
With the help of the monitoring several events of the controller can be routed (wired OR) to the relays.
If the monitoring is active it is displayed by the bell symbols ( ). The colour of the symbols is programmable for the -alarms and fixed for all other events. In case of several events with different colours at the same time the priority of the colours is: red, yellow, green.
-Alarm 1 ---
Not selected
for Monitoring2
>
One zone => Message
Once
-
alarm 1 is active in one
zone
, monitoring 1
(2)
is set
.
for Monitoring1>
All zones => Message
Monitoring 1
(2)
is not set until
-alarm 1 is active in all zones.
-Alarm 2 ---
Not selected
for Monitoring1
>
One zone => Message
Once
-
alarm 2 is active in one zone, monitoring 1
(2)
is set.
for Monitoring2>
All zones => Message
Monitoring 1
(2)
is not set until
-
alarm 2 is active in all zones.
Sensor error
Colour: red
---
Not selected
for Monitoring2
>
Active
In
the case of sensor break m
onitoring 1
(2)
is set
.
for Monitoring1>
Restart lock­out
Colour: yel­low
---
N
ot selected
<§>
generate Signal
Monitoring 1
(2) is set, if
a restarting
-
incident triggered.
Current alarm Colour: red
---
Not selected
for
Monitoring1
>
Active
Monitoring 1
(2)
is set
, if
current alarm
occurred
.
for Monitoring2>
System error
Colour: red
---
Not selected
<§>
Active
Monitoring 1
(2)
is set, if
system error
occurred
.
Moni 1(2) Relay
Direct
Relay
switches on, if monitoring 1
(2)
is active
.
<§>
Indirect
Relay
switches off
,
if monitoring 1
(2)
is active.
Page 27
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 27 / 36
Configuration 
-Alarm 1+2
Settings for
temperature
alarm values and configuration of
temperature
alarm 1/2
The controller features two independent
temperature
alarms.
These temperature alarms can be connected to the monitoring relays via the monitoring function (5.4.8.1). Independent of this the -alarms can be connected to the zone relays or logic outputs. If a setpoint ramp has been programmed, the -alarms that are based on the setpoint fol- low the setpoint ramp. In case of sensor error the -alarms react in the same way as range override.
Desired function
Setpoint based
-
alarm
Absolute
-
alarm
Single sided
-
alarm "top":
(over temperature alarm)
The temperature has to be higher to activate the alarm.
Single sided
-
alarm "bottom":
(under temperature alarm)
The temperature has to be lower to activate the alarm.
Both
-
sided
-
alarm:
(limit-alarm)
The temperature has to be outside the selected range.
-Alarm values Min/Max
Undertemperature Alarm 1 / 2
Relative to
setpoint
: -
100...0(OFF
<§>
)
Absolute: MB-Start<§> ... MB-End
Overtemperature Alarm 1 / 2
Relativ
e to
setpoint
: 0(OFF
<§>
)...100
Absolute: MB-Start<§> ... MB-End
Type
Absolute
Absolute
-
a
larm
-
limits
. Not dependent
on setpoint
.
<§>
Based on setpoint
-
Alarm
-
limits relative to
setpoint.
Delay OFF
-Alarm delay switched off
.
<§>
1 ... 8000 s
-
Alarm
is delayed by selected time.
Self-retaining off
No self
-
holding of the temperature alarm
.
<§>
on
An
activation
of the
-
alarm will be
stored
. The
-
alarm
can be acknowledged in the window ”Monitoring“.
Start suppression
OFF Without start up
Start
-
up -alarm suppression switched off
<§>
Start up Suppression active
Start
-
up -alarm suppression
active
:
Temperature must be within the limits once. Only then the -alarm is activated when reaching the alarm value.
Display col­our
Red
The
monitoring
displays the
-
alarm in red
colour
. <§>
Green
Intended for
enabling
signals:
D
isplay
colour
is
green.
Orange
setpoint
alarm value over temperature
0
alarm value over temperature
0
alarm value under temperature
setpoint
0
alarm value under temperature
0
setpoint
alarm value over temperature
0
alarm value under temperature
alarm value over temperature
0
alarm value under temperature
Page 28
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 28 / 36
Configuration Current alarm (option)
The heater current monitoring function is valid for all connected zones.
Only zones with logic output for the heating signal will take part in current monitoring. Ensure that the limit value is set correctly to avoid false alarms in case of supply voltage changes. The alarm can be delayed by selecting a delay time to avoid false alarms caused by single disturbances. The heater current measuring is designed for a current transformer 1:1000. (Accessory type: M2000 1:1000 max. 60A) When using other transformers the ratio can be modified.
Current alarm limits / Undercurrent alarm value
OFF, 0.1 ... 99.9 A
Zone parameter: Absolute value
<§=OFF>
Currents below this value will cause an alarm.
Current alarm limits / Overcurrent alarm value
OFF, 0.1 ... 99.9 A
Zone parameter: Absolute value
<§=OFF>
Currents above this value will cause an alarm.
Leakage limit
Monitoring an impermissible continuous current
Limit value: OFF, 0,0...99,9 A
<§>=0,3A
SSRs (especially if they are combined with RC-combinations) nor­mally have small leakage currents. These currents add up and the sum can lead to a permanent leakage current. A leakage current limit value is programmable. All values below this limit will not be considered in the alarm monitoring.
The field “act. Leakage current” displays the leakage current that has
just been measured. If a permanent current (SSR short circuit) is detected the alarm will be activated.
The zone with a permanent current can be detected by observing the actual process values (proves value too high).
act. Leakage curr.
Display of the actual leakage current
Current transformer
Turns ratio
1:100 … 1:9999
<§ = 1:1000
for M2000
>
Cycle time
1...60s
Time interval between the current measurements of
two successive zones. <§ = 2s>
Delay
Settings in 5 steps, unit: seconds
The values depend on the cycle time and the number of active con­troller zones.
Off = no delay time active <§=off>
Page 29
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 29 / 36
5.4.9 Wizard
The wizard serves as a support for initial commis-
sioning of the controller or in the occasion of a reconfiguration.
Please notice the wise order in which the parame­ters of the wizard have to be adjusted. The wizard can be cancelled at any time. By pressing the arrow keys you will move on to the next step. Pressing the OK-key will lead to the parameters.
New controllers automatically start with the wizard. After pressing “finish” in the last window of the wizard the wizard will not be shown anymore at startup.
5.4.10 Window: System
Pressing the configuration key leads to windows in
which the associated parameters can be selected or set.
Pressing the key “About“, shows hardware infor­mation of the controller .
Hold down
< 2 sec
. =
Return to previous window
Hold down > 2 sec. = Jump to window “Actual process value“
Jump to “
Main
Page 30
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 30 / 36
Settings
Language
Deutsch (German)
German
<§>
English (English)
Englis
h
Time
Hours
Number value
0 … 23
Minutes
Number value
0 … 59
Day / Month
Day
Number
value
1 … 31
Month
Number value
1 … 12
Year
2000 … 2150
Adjustment of
calendar
year
Zone Offset OFF
<§>
1 … 91
The adj
usted offset value is added to t
he displayed zone
numbers in the windows. Therefore a continuous num­bering of the zones can be achieved if more than one device is used. Examples: Offset= OFF: Zone numbering: 1-8 Offset= 4: Zone numbering: 5-12
Authorisation (LOC)
All Parameter adjustable
All parameters
adjustable
<§>
Only setpoint 1 adjustable
All other parameters are locked
Setp. and ramps adjustable
Setpoints, alarm values and ramps are adjustable.
All other parameters are locked.
All parameters locked
No parameter is adjustable
The parameters that have been locked can be displayed
but not changed.
This parameter cannot be changed if the logic input In_2 is active.
Sample rate
Scanning time for recorder function
Time interval between the current
measurements
of two successive
zones
.
In brackets the complete time interval as shown on display:
2,5 s (Total time: 8,2 Min) 5 s (Total time: 16,5 Min) 10 s (Total time: 33 Min) <§> 30 s (Total time: 99 Min) 1 Min. (Total time: 3,3 h) 5 Min. (Total time: 16,5 h) 10 Min.(Total time: 33 h)
A maximum of 198 temperature points can be saved.
Restart lock-out OFF
No function
<§>
On
After power
-
on all zones are switched off and a message
is displayed. Switch on must be acknowledged. After acknowledgement all zones, that were on before the power fail, will be switched on again. In addition the alarm “Restart lock-
out“ will be set and can
be handled in the monitoring.
Page 31
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 31 / 36
Field bus / USB / LAN
Menu: Fieldbus
It depends on the installed field bus module
what parameters will be visible.
Protocol
off
No protocol selected
Elotech
<SERIAL>
ELOTECH
-
Standard
-
protocol
Modbus
<SERIAL>
Modbus
-
RTU-protocol
Arburg 1
<SERIAL>
Hot runner: One device address for all zones.
Arburg 2
<SERIAL>
Hot runner: Every zone has its own
address.
Arburg 3
<SERIAL>
Protocol for temperature control systems
Profibus DP
<PROFIBUS>
Profibus DP
Status
Display only
---
<SERIAL>
No data communication
Data Exchange
<SERIAL>
Data communication is active
<PROFIBUS>
Data-Exchange-Mode
Wait Param
<PROFIBUS>
Controller waits for configuration / parametrisation
No connection
<PROFIBUS>
No m
aster connected / Master not active
Baudrate
<SERIAL>
1.2 kBaud
1.200 Bit/s
2.4 kBaud
2.400 Bit/s
4.8 kBaud
4.800 Bit/s
9.6 kBaud
9.600 Bit/s
<§>
19.2 kBaud
19.200 Bit/s
38.4 kBaud
38.400 Bit/s
Baudrate
<PROFIBUS>
Display only
45,5 kBaud
– 12Mbaud (
forced by the master
)
Not detected = no master connected
Address 1 … 255
1<§>... 255 (ELOTECH-Standard) 1<§>... 247 (Modbus-RTU-Protocol) 1<§>... 32 (Arburg-Protocols) 2<§>... 125 (Profibus)
At this address a master communicates with the controller. Each controller needs a unique address.
Format
<SERIAL>
7 E 1
7 Data bits, 1 Stop bit, Parity Even
<§>
7 O 1
7 Data bits, 1 Stop bit, Parity Odd
7 E 2
7 Data bits, 2 Stop bits, Parity Even
7 O 2
7 Data bits, 2 Stop bits, Parity Odd
7 N 2
7 Data bits, 2 Stop bits, Parity None
8 E 1
8 Data bits, 1 Stop bit, Parity Even
8 O 1
8 Data bits, 1 Stop bit,
Parity Odd
8 N 1
8 Data bits, 1 Stop bit, Parity None
8 N 2
8 Data bits, 2 Stop bits, Parity None
HW-config
<SERIAL>
The serial fieldbus module has three integrated interfaces.
Select here the desired interface:
RS232/RS485
Signals see
connection diagram.
TTY
Signals see connection diagram.
Remote
<PROFIBUS>
On
Profibus can read and write
.
Local operation is locked.
Off
Profibus
can read only
.
Local operation is permitted
.
<§>
Page 32
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 32 / 36
Menu: USB
Save controller data
on a
n USB-Stick.
(USB-flash drive)
The data is stored as a text file in an adjustable CSV-format. The USB-flash-drive must be formatted with FAT. (FAT16/ FAT32) The file name contains the last 5 digits “xxxxx” of the MAC-ID.
Save to USB All parameters
Save all
parameters for all zones.
Generates the file -> LogParaxxxxx.txt and LogPara.bin
Al. Logbook
Save the entries of the Alarm Logbook.
Generates the file -> LogBookxxxxx.txt
Graph
Save the measuring points of the graph for all zones.
Generates the file -> LogGraphxxxxx.txt
USB status
- - -
Display of the USB
-
status: no stick detected.
Key detected
USB-stick detected:
Files can be saved or loaded from the USB flash drive.
Load
Load all Parameters
Loading a previously saved parameter set.
The file
“LogPara.bin” must exist on the USB flash drive.
Separator
none <§>
Delimiter symbol between single data sets
:
Spaces
comma
,
semicolon
;
colon
:
tabulator
<TAB>
Sample­Interval
OFF;
<§>
5…720s
Cycle time for writing an output line
with time stamp
on the
USB stick. The values setpoint, actual value, output ratio and current actual value of all zones are written out.
If the parameter "Log interval" is set to a numerical value, so a file named
“LogR4000_xxxxx_YYYY_MM_DD.txt” is generated on the USB stick. “xxxxx” the last 5 dig­its of the MAC-ID. YYYY, MM and DD mean the year, month, day. After a change of date a new file is created. With the included names MAC-ID “xxxxx”, the files can be assigned to different R4000 con­trollers. Each "Log interval" time a new row is added. The line includes a time-stamp, setpoint, the actual value, the output ratio and the actual current value of Zone 1 to Zone 4/8.
Menü: LAN
Ethernet
interface
for connection to the configuration tool Elovision 3 or for a MODBUS-TCP communication. Default subnet mask: 255.255.255.0
IP-address 1 IP-address 2 IP-address 3 IP-address 4
IP-Ad
dress
192 . 168 . 100 . 100 Part
1 <§>
IP-Ad
dress
192 .
168 . 100 .
100
Part 2
IP-Ad
dress
192 . 168 .
100 . 100
Part 3
IP-Ad
dress
192 . 168 . 100 .
100 Part 4
MAC ID
549A11:5xxxxx
Display of the
MAC
-
ID: 54:9A:11:5x:xx:xx
Page 33
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 33 / 36
About / 
Firmware update
Firmware
Displays the current firmware version.
Language version
Displays the current language version
Firmware update
Start the firmware update by selecting the button "Start Update" and
confirm with SAVE. A confirmation prompt opens. If this window is con­firmed with YES, the unit turns into the loader mode.
When the loader mode is accidentally turned on, you can switch back by a mains reset into the existing user program.
If an update should be performed, a USB flash drive must be plugged in with the new firmware. After a short time the firmware folder appears in the line "Folder". E.g. „EL4000.01_V20xx_xx.ELO“.
Now you can start the loading process by touching the touch screen. The controller must not be disconnected from the power supply until the download is complete! After finished loading the new user program is started by a power inter­ruption.
Type R4000­0x-x-000-0x-5
Type key of the controller
Sensor
Sensor
Linear 0…10 V
V
oltage 0 to
10 V
Linear 0…20 mA
C
urrent
0…20mA
Linear 4…20 mA
C
urrent
Live Zero
4…20mA
PT100 2-wire
Pt 100 2
-
wire connection
-100…800°C
PT100 3-wire
Pt 100 3
-
wire connection
-100…800°C
Ni120 2-wire
Nickel 120 2
-
wire connection
0…250°C
Ni120 3-wire
Nickel 120 3
-
wire connection
0…250°C
(TC) Fe-CuNi (J)
Thermo
couple
Type J
0…800°C
(TC) NiCr-Ni (K)
Thermocouple
Type K
0…1200°C
(TC) Fe-CuNi (L)
Thermocouple
Type L
0…800°C
NiCrSi-NiSi (N)
Thermocouple
Type
N
0…1200°C
(TC) PtRh-Pt (S)
Thermocouple
Type S
0…1600°C
Please NOTE
:
If the sensor selection is changed, the following parameters will be reset:
Setpoint
1, Set
point
2:
Lower setpoint limitation:
Highest setpoint limitation:
Setpoint ramp rising/falling:
Alarm values:
Actual process value offset:
Setpoint softstart:
softstart:
Setpoint limitation min.
Measuring range bottom Measuring range top off off off 100°C off
Page 34
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 34 / 36
Configuration Output relay
For every zone one relay output is available. Select the desired output signal.
When using as a control output, set the cycle time to a value as long as possible in order to minimize wear of the relay contacts.
Relays 1 ... 8 OFF
No function
Heating
Output heating
-
signal at relay x
<§>
Cooling
Output cooling
-
signal at relay x
-Alarm 1
Output
temperature
alarm 1 at relay x
-Alarm 2
Output
temperature
alarm 2 at relay x
Configuration Output digital
For every zone one digital output (logic out) is available. Select the desired output signal.
Digital 1 ... 8 OFF
No function
Heating
Output heating
-
signal at logic output x
<§>
Cooling
Output
cooling
-
signal at logic output
x
-Alarm 1
Output
temperature
alarm 1 at logic
-
output
x
-Alarm 2
Output
temperature
alarm 2 at logic output
x
6 Error Messages
Error
message
Cause
Possible remedy
At actual process value
maximum value flashes
Top
range end has
been exceeded, sen­sor defect
Check sensor and cable
At actual process value
minimum value flashes
Bottom range end
has been exceeded, sensor defect
Check sensor cable
Check process value offset TC connected with inverted polarity
REMOTE:
Parameter locked
Adjusting of parame-
ters is not allowed. Device is controlled by fieldbus
Pr
ofibus: The parameter “Remote“
in the
menu Field bus is set to “on”.
The configuration-tool Elovision is active.
Field bus module
unavailable
The controller
is not fitted with the
correct
hardware for the selected protocol.
DfErr
Text display error
Please send the controller back to the
manufacturer.
ERR0
System error
Please send the controller back to the
manufacturer.
ERR8
System error
Quit error
message.
Check the parameters. If the error is still there, send the controller back to the manufacturer.
Page 35
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 35 / 36
7 Technical Data
Input
Pt100 (DIN)
2- or 3-
wire connection possible
Built-in protection against sensor breakage and short circuit Sensor current: … < 1 mA Calibration accuracy: … < 0,2 % Linear error: … < 0,2 % Influence of the ambient temperature: … < 0,01 % / K
Input Thermocouple
Built
-
in internal compensation point and protection against sensor
breakage and incorrect polarity. Re-calibration not required for a line resistance of up to 50 Ohm. Calibration accuracy: … < 0,25 % Linear error: … < 0,2 % Cold junction error: 0,5K Influence of the ambient temperature: … < 0,01 % /
Input voltage
0…10V
Internal resistance
> 100 k
-
Ohm
Calibration: < 0,25 % Linearity error: < 0,2 % Ambient temperature influence: < 0,01 % / K
Input current
0…20mA
Internal resistance
< 100 Ohm
Calibration < 0,25 % Linearity error: < 0,2 % Ambient temperature influence: < 0,01 % / K ! No input current when the controller is without supply voltage.
Logic input
Internal resistance
>
22k-Ohm
Level 0 < 2V Level 1 > 9V; max 30V
Heater current moni-
toring
Measuring input range: 0… 100mA corresponding 0,0…99,9A when
using a current transformer 1: 1000. If the range is exceeded, the controller may be damaged.
Logic outputs
Bist. voltage
, 0/24
V DC, max.
50
0 mA,
short
-
circuit proof
Relay outputs/
Alarm outputs
Relay
;
max. 250V
AC, max. 2A,
resistive load
Fieldbus Interface
:
Depends on the version of
the device
:
- Serial: RS232, RS485, TTY (20mA)
- Profibus DP, according to EN 50170 All with optical isolation.
Service
-
Interface
Ethernet:
Modbus TCP
USB-Interface
Host for
USB-Stick; max. 100mA
Supply voltage
24 V DC, +/
-
25 %, appr
. 6W
+ Power of
logic outputs
LCD-Display
8,8 cm (3,5“) RGB
-display
with LED-backlight
.
320 x 240 pixel with resistive Touch-Panel
Dat
a protection
EAROM,
Semiconductor storage
When using a Fieldbus interface please note: Permissible writing operations per parameter must not exceed 1 000 000.
Page 36
Manual: R4000-XX-X-000-X-X_EN Release: 1.08 ©Elotech GmbH Seite 36 / 36
Casing
Format, case
:
Panel cut-out: Material: Protection mode:
96x96mm,
acc
. DIN 43700,
Installation depth 122 mm 92 +0,5 mm x 92 +0,5 mm Sheet steel and Makrolon UL 94-V1 IP 20 (DIN 40050), Front side: IP 50
Connectors
Service
-
Interface:
Ethernet
RJ45
USB-Interface: Type A Profibus: SUB-D 9 Others: Screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C
Real time clock
Backup b
attery: Lithium CR2032
W
eight
Approx
. 800g,
depends on the
version of t
he device
Permissible operating
conditions
Operating
:
Temperature: Storage temperature:
Climate class:
0...50°C / 32...122°F
-30...70°C / -22...158°F KWF DIN 40040; equivalent to annual average max. 75% rel. humidity, no condensation
CE -
mark
EN 61326
-
1:2013 / EN 61000
-3-
2:2006+A1:2009+A2:2009
EN 61000-3-3:1995+A1:2001+A2:2005 Electrical safety: EN 61010-1
Subject to technical improvements.
Loading...