Elotech R 2000 - 431, R 2000 - 433, R 2000 - 432, R 2000 - 436, R 2000 - 437 Operating Manual

Page 1
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 1/24
R 2000 - 431 / 432 / 436 / 433 / 437
4 – Zones „heat-only“ and „heating-off-cooling“ Temperature Controller
- CANopen - Interface (Option)
- 2 x Analog input 0-10VDC (Option)
Format: 96 x 96 mm (1/4-DIN) Installation depth: 122 mm
DESCRIPTION AND OPERATING MANUAL
I.
ELOTECH Industrieelektronik GmbH Verbindungsstrasse 27 D – 40723 HILDEN FON +49 2103 / 255 97 0 FAX +49 2103 / 255 97 29 www.elotech.de Email: info@elotech.de
Page 2
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 2/24
Contents
I.
Contents ............................................................................................................... 1
I.
Contents ............................................................................................................... 2
II.
Type code ............................................................................................................ 3
III.
Connection Diagram: R2000 - 431 ...................................................................... 4
IV.
Connection Diagram: R2000 - 432 ...................................................................... 5
V.
Connection Diagram: R2000 - 436 ...................................................................... 6
VI.
Connection Diagram: R2000 - 433 ...................................................................... 7
VII. Connection Diagram: R2000 - 437 ...................................................................... 8
VIII. Display and Keyboard .......................................................................................... 9
IX.
Tendency Display............................................................................................... 10
X.
Operating Levels ................................................................................................ 11
XI.
Configuration Level, general settings ................................................................. 12
XII. Configuration Level, individual selectable for zones 1...4; d1, d2 .................... 16
XIII. Parameter Level, individual selectable for zones 1...4 ....................................... 19
XIV. Operating Level, individual selectable for zones 1...4 ........................................ 22
XV. Operating Level, Option: only inputs zones d1 and d2 ...................................... 23
XVI. Technical Data ................................................................................................... 23
XVII. Error displays ..................................................................................................... 24
XVIII. Installation Instructions ...................................................................................... 24
Please read this operating manual before starting up carefully. Observe the installation and connecting instructions.
Note: Only trained personnel following the regional safety regulations may operate the hereby discribed instruments. It is essential, that one has well experience in installing electric devices.
The instrument is not suitable for installation in hazardous areas. Do not open the device while the power lines are connected. Take care to the separat interface- and data transmission descriptions. Before operation, the unit must be configurated for its intended purpose under an expert guidance.
E.g. controller type, sensor type and range, alarm adjustment etc.. See: Configuration and Parameter levels.
Attention: The „heating“- or „cooling“-outputs can be active while programming or configuring the controller. This can cause a damage either to the plant itself or its contents.
Page 3
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 3/24
II. Type code
R 2000 - aaa - x - y - 000 - d - z
1: power supply: 230 V AC 2: power supply: 115 V AC 3: power supply: 24 V AC
5: power supply: 24 V DC 0: without serial interface
2: ser. interface RS232-C Protocol: ELOTECH - standard 4: ser. interface RS485 Protocol: ELOTECH – standard InterBus-S via gateway M-IBS -5 5: ser. interface 0/20mA Protocol: ASCII, ELOTECH - standard 7: CAN CANopen Device Profile DS-404 9: Profibus DP EN
0: standard 1: with analog input d1 (0...10 Vdc) (not available with CAN / Profibus-Interface) 2: with analog input d1 and d2 (each 0...10 Vdc) (not available with CAN / Profibus-Interface) 5: with heater current monitoring. Only with bistable voltage outputs. Codes: 432, 436, 437.
0: sensor programmable: RTD (Pt100-DIN), 2- or 3-wire; Type L, Type J; Type K
431 4- zones heat-only or heating-off-cooling controller; control outputs: all, relais (not with heater current monitoring) 432 4- zones heat-only or heating-off-cooling controller; control outputs: heating: bist. voltage signal. Com.: +
cooling: bist. voltage signal. Com.: + 436 4- zones heat-only or heating-off-cooling controller; control outputs: heating: bist. voltage signal. Com.: -
(Preference) cooling: bist. voltage signal. Com.: - 433 4- zones heat-only or heating-off-cooling controller; control outputs: heating: bist. voltage signal. Com.: +
cooling: relais 437 4- zones heat-only or heating-off-cooling controller; control outputs: heating: bist. voltage signal. Com.: -
(Preference) cooling: relais
Page 4
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 4/24
III. Connection Diagram: R2000 - 431
k4* k3 k2 k1 70 L / DC- 1 71 N / DC+ 2 72 3 73 A1 4 17 74 A1 5 18 75 A2 6 19 Option: d 2: 0...10Vdc+ 76 A2 7 20 0...10Vdc - 77 Out4 8 Out8 21 Option: d 1: 0...10Vdc+ 78 Out4 9 Out8 22 0...10Vdc - 79 Out3 10 Out7 23 Zone: Sensor: 80 Out3 11 Out7 24 TC Pt100 81 Out2 12 Out6 25 - 60 82 Out2 13 Out6 26 4 61 83 Out1 14 Out5 27 62 Out1 15 Out5 28 3 - 63
GND GND
90
64
RxDout RxD in
91
- 65
TxD in RxDout
92
2 66
H A TxDout TxDout
93
67
L B RxD in TxD in
94
1 - 68 95 69
CAN RS485 RS232 0/20mA
96
65: RTD 2. wire RTD 2. wire 66: 3-wire 1. wire 2-wire 1. wire
67: connection 3. wire connection 3. wire = jumper to 2. wire jumper jumper 67: RTD 3. wire RTD 3. wire = jumper to 2. wire
68: 3-wire 2. wire 2-wire- 2. wire 69: connection 1. wire connection 1. wire
„heat-only“ or „cool-only“ - controller: „heating-off-cooling“ - controller: Control output OUT 1: Zone 1; „heating“ or „cooling“ „heating“ to OUT 4: Zone 4; „heating“ or „cooling“ „heating
Control output OUT 5: Zone 1; „cooling“ to OUT 8: Zone 4; „cooling“
Alarm Output A1: Alarm 1 ( Temperature monitoring alarm A1 for all zones) Alarm Output A2: Alarm 2 ( Temperature monitoring alarm A2 for all zones)
Setpoint Controlling: K1: open = Setpoint 1 (SP1) valid
K1: closed = Setpoint 2 (SP2) valid, for all zones Adjustment lock (LOC): K2: open = Adjustment lock only via „software code“ (see parameter: LOC)
K2: closed = Adjustment locked according to the choosen „software code“. Setpoint changing: K3: open = individual setpoint adjustment for each zone
K3: closed = if setpoint has been changed in one zone, this new setpoint is valid (will be overtaken) for all other zones automatically.
CAN-Interface, (Option): K4: open = CAN: „operational“. Operation only with CANopen protocoll. K4: closed = CAN: „operational“ always active. K4 must be closed, if the instrument is equipped with a CAN-interface but not used.
Input d1, (Option): 0 ... 10 VDC, Display: Zone: d1 Input d2, (Option): 0 ... 10 VDC, Display: Zone: d2
Page 5
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 5/24
IV. Connection Diagram: R2000 - 432
k4* k3 k2 k1 70 L / DC- 1 71 N / DC+ 2 72 3 73 A1 4 17 Option 74 A1 5 18 Analog Input 75 A2 6 19 76:
d 2: 0...10VDC+
76: L1 76
A2 7 20 77:
0...10VDC -
77: L1 77
8 21 78:
d 1: 0...10VDC+
78: L2 78
9 22 79:
0...10VDC -
79: L2 79 10 23 Zone: Sensor: 80: L3 80 Out 4 - 11 Out 8 - 24 TC Pt100 81: L3 81 Out 3 - 12 Out 7 - 25 - 60 Option 82 Out 2 - 13 Out 6 - 26 4 61 Heater current 83 Out 1 - 14 Out 5 - 27 62 transformer Com.+ 15 Com.+ 28 3 - 63
GND GND
90
64
RxDou RxD in
91
- 65
TxD in RxDout
92
2 66
H A TxDout TxDout
93
67
L B RxD in TxD in
94
1 - 68 95 69
CAN RS485 RS232 0/20mA
96
It is not permitted to connect the grounds of the sensor-inputs and bist. voltage-outputs with each other.
65: RTD 2. wire RTD 2. wire 66: 3-wire 1. wire 2-wire 1. wire
67: connection 3. wire connection 3. wire = jumper to 2. wire jumper jumper 67: RTD 3. wire RTD 3. wire = jumper to 2. wire
68: 3-wire 2. wire 2-wire- 2. wire 69: connection 1. wire connection 1. wire
„heat-only“ or „cool-only“ - controller: „heating-off-cooling“ - controller: Control output OUT 1: Zone 1; „heating“ or „cooling“ „heating“ to OUT 4: Zone 4; „heating“ or „cooling“ „heating
Control output OUT 5: Zone 1; „cooling“ to OUT 8: Zone 4; „cooling“
Alarm Output A1: Alarm 1 ( Temperature- or heater current monitoring alarm A1 for all zones) Alarm Output A2: Alarm 2 ( Temperature- or heater current monitoring alarm A2 for all zones)
Setpoint Controlling: K1: open = Setpoint 1 (SP1) valid
K1: closed = Setpoint 2 (SP2) valid, for all zones Adjustment lock (LOC): K2: open = Adjustment lock only via „software code“ (see parameter: LOC)
K2: closed = Adjustment locked according to the choosen „software code“. Setpoint changing: K3: open = individual setpoint adjustment for each zone
K3: closed = if setpoint has been changed in one zone, this new setpoint is valid (will be overtaken) for all other zones automatically.
CAN-Interface, (Option): K4: open = CAN: „operational“. Operation only with CANopen protocoll. K4: closed = CAN: „operational“ always active. K4 must be closed, if the instrument is equipped with a CAN-interface but not used.
Input d1, (Option): 0 ... 10 VDC, Display: Zone: d1 Input d2, (Option): 0 ... 10 VDC, Display: Zone: d2
Heater current monitoring: 1 current – transformer / phase
Single phase operation: terminals 76,77: L1 Three-phase operation: terminals 76 – 81: L1, L2, L3
Page 6
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 6/24
V. Connection Diagram: R2000 - 436
k4* k3 k2 k1 70 L / DC- 1 71 N / DC+ 2 72 3 73 A1 4 17 Option 74 A1 5 18 Analog Input 75 A2 6 19 76:
d 2: 0...10VDC+
76: L1 76
A2 7 20 77:
0...10VDC -
77: L1 77 8 21 78:
d 1: 0...10VDC+
78: L2 78
9 22 79:
0...10VDC -
79: L2 79 10 23 Zone: Sensor: 80: L3 80 Out 4 + 11 Out 8+ 24 TC Pt100 81: L3 81 Out 3 + 12 Out 7+ 25 - 60 Option 82 Out 2 + 13 Out 6+ 26 4 61 Heater current 83 Out 1 + 14 Out 5+ 27 62 transformer Com. - 15 Com.- 28 3 - 63
GND GND
90
64
RxDout RxD in
91
- 65
TxD in RxDout
92
2 66
H A TxDout TxDout
93
67
L B RxD in TxD in
94
1 - 68 95 69
CAN RS485 RS232 0/20mA
96
It is not permitted to connect the grounds of the sensor-inputs and bist. voltage-outputs with each other.
65: RTD 2. wire RTD 2. wire 66: 3-wire 1. wire 2-wire 1. wire
67: connection 3. wire connection 3. wire = jumper to 2. wire jumper jumper 67: RTD 3. wire RTD 3. wire = jumper to 2. wire
68: 3-wire 2. wire 2-wire- 2. wire 69: connection 1. wire connection 1. wire
„heat-only“ or „cool-only“ - controller: „heating-off-cooling“ - controller: Control output OUT 1: Zone 1; „heating“ or „cooling“ „heating“ to OUT 4: Zone 4; „heating“ or „cooling“ „heating
Control output OUT 5: Zone 1; „cooling“ to OUT 8: Zone 4; „cooling“
Alarm Output A1: Alarm 1 ( Temperature- or heater current monitoring alarm A1 for all zones) Alarm Output A2: Alarm 2 ( Temperature- or heater current monitoring alarm A2 for all zones)
Setpoint Controlling: K1: open = Setpoint 1 (SP1) valid
K1: closed = Setpoint 2 (SP2) valid, for all zones Adjustment lock (LOC): K2: open = Adjustment lock only via „software code“ (see parameter: LOC)
K2: closed = Adjustment locked according to the choosen „software code“. Setpoint changing: K3: open = individual setpoint adjustment for each zone
K3: closed = if setpoint has been changed in one zone, this new setpoint is valid (will be overtaken) for all other zones automatically.
CAN-Interface, (Option): K4: open = CAN: „operational“. Operation only with CANopen protocoll. K4: closed = CAN: „operational“ always active. K4 must be closed, if the instrument is equipped with a CAN-interface but not used.
Input d1, (Option): 0 ... 10 VDC, Display: Zone: d1 Input d2, (Option): 0 ... 10 VDC, Display: Zone: d2
Heater current monitoring: 1 current – transformer / phase
Single phase operation: terminals 76,77: L1 Three-phase operation: terminals 76 – 81: L1, L2, L3
Page 7
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 7/24
VI. Connection Diagram: R2000 - 433
k4* k3 k2 k1 70 L / DC- 1 71 N / DC+ 2 72 3 73 A1 4 17 Option 74 A1 5 18 Analog Input 75 A2 6 19 76:
d 2: 0...10VDC+
76: L1 76
A2 7 20 77:
0...10VDC -
77: L1 77 8 Out 8 21 78:
d 1: 0...10VDC+
78: L2 78
9 Out 8 22 79:
0...10VDC -
79: L2 79 10 Out 7 23 Zone: Sensor: 80: L3 80 Out 4 - 11 Out 7 24 TC Pt100 81: L3 81 Out 3 - 12 Out 6 25 - 60 Option 82 Out 2 - 13 Out 6 26 4 61 Heater current 83 Out 1 - 14 Out 5 27 62 transformer Com.+ 15 Out 5 28 3 - 63
GND GND
90
64
RxDout RxD in
91
- 65
TxD in RxDout
92
2 66
H A TxDout TxDout
93
67
L B RxD in TxD in
94
1 - 68 95 69
CAN RS485 RS232 0/20mA
96
It is not permitted to connect the grounds of the sensor-inputs and bist. voltage-outputs with each other.
65: RTD 2. wire RTD 2. wire 66: 3-wire 1. wire 2-wire 1. wire
67: connection 3. wire connection 3. wire = jumper to 2. wire jumper jumper 67: RTD 3. wire RTD 3. wire = jumper to 2. wire
68: 3-wire 2. wire 2-wire- 2. wire 69: connection 1. wire connection 1. wire
„heat-only“ or „cool-only“ - controller: „heating-off-cooling“ - controller: Control output OUT 1: Zone 1; „heating“ or „cooling“ „heating“ to OUT 4: Zone 4; „heating“ or „cooling“ „heating
Control output OUT 5: Zone 1; „cooling“ to OUT 8: Zone 4; „cooling“
Alarm Output A1: Alarm 1 ( Temperature- or heater current monitoring alarm A1 for all zones) Alarm Output A2: Alarm 2 ( Temperature- or heater current monitoring alarm A2 for all zones)
Setpoint Controlling: K1: open = Setpoint 1 (SP1) valid
K1: closed = Setpoint 2 (SP2) valid, for all zones Adjustment lock (LOC): K2: open = Adjustment lock only via „software code“ (see parameter: LOC)
K2: closed = Adjustment locked according to the choosen „software code“. Setpoint changing: K3: open = individual setpoint adjustment for each zone
K3: closed = if setpoint has been changed in one zone, this new setpoint is valid (will be overtaken) for all other zones automatically.
CAN-Interface, (Option): K4: open = CAN: „operational“. Operation only with CANopen protocoll. K4: closed = CAN: „operational“ always active. K4 must be closed, if the instrument is equipped with a CAN-interface but not used.
Input d1, (Option): 0 ... 10 VDC, Display: Zone: d1 Input d2, (Option): 0 ... 10 VDC, Display: Zone: d2
Heater current monitoring: 1 current – transformer / phase
Single phase operation: terminals 76,77: L1 Three-phase operation: terminals 76 – 81: L1, L2, L3
Page 8
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 8/24
VII. Connection Diagram: R2000 - 437
k4* k3 k2 k1 70 L / DC- 1 71 N / DC+ 2 72 3 73 A1 4 17 Option 74 A1 5 18 Analog Input 75 A2 6 19 76:
d 2: 0...10VDC+
76: L1 76
A2 7 20 77:
0...10VDC -
77: L1 77 8 Out 8 21 78:
d 1: 0...10VDC+
78: L2 78
9 Out 8 22 79:
0...10VDC -
79: L2 79 10 Out 7 23 Zone: Sensor: 80: L3 80 Out 4 + 11 Out 7 24 TC Pt100 81: L3 81 Out 3 + 12 Out 6 25 - 60 Option 82 Out 2 + 13 Out 6 26 4 61 Heater current 83 Out 1 + 14 Out 5 27 62 transformer Com. - 15 Out 5 28 3 - 63
GND GND
90
64
RxDout RxD in
91
- 65
TxD in RxDout
92
2 66
H A TxDout TxDout
93
67
L B RxD in TxD in
94
1 - 68 95 69
CAN RS485 RS232 0/20mA
96
It is not permitted to connect the grounds of the sensor-inputs and bist. voltage-outputs with each other.
65: RTD 2. wire RTD 2. wire 66: 3-wire 1. wire 2-wire 1. wire
67: connection 3. wire connection 3. wire = jumper to 2. wire jumper jumper 67: RTD 3. wire RTD 3. wire = jumper to 2. wire
68: 3-wire 2. wire 2-wire- 2. wire 69: connection 1. wire connection 1. wire
„heat-only“ or „cool-only“ - controller: „heating-off-cooling“ - controller: Control output OUT 1: Zone 1; „heating“ or „cooling“ „heating“ to OUT 4: Zone 4; „heating“ or „cooling“ „heating
Control output OUT 5: Zone 1; „cooling“ to OUT 8: Zone 4; „cooling“
Alarm Output A1: Alarm 1 ( Temperature- or heater current monitoring alarm A1 for all zones) Alarm Output A2: Alarm 2 ( Temperature- or heater current monitoring alarm A2 for all zones)
Setpoint Controlling: K1: open = Setpoint 1 (SP1) valid
K1: closed = Setpoint 2 (SP2) valid, for all zones Adjustment lock (LOC): K2: open = Adjustment lock only via „software code“ (see parameter: LOC)
K2: closed = Adjustment locked according to the choosen „software code“. Setpoint changing: K3: open = individual setpoint adjustment for each zone
K3: closed = if setpoint has been changed in one zone, this new setpoint is valid (will be overtaken) for all other zones automatically.
CAN-Interface, (Option): K4: open = CAN: „operational“. Operation only with CANopen protocoll. K4: closed = CAN: „operational“ always active. K4 must be closed, if the instrument is equipped with a CAN-interface but not used.
Input d1, (Option): 0 ... 10 VDC, Display: Zone: d1 Input d2, (Option): 0 ... 10 VDC, Display: Zone: d2
Heater current monitoring: 1 current – transformer / phase
Single phase operation: terminals 76,77: L1 Three-phase operation: terminals 76 – 81: L1, L2, L3
Page 9
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 9/24
VIII. Display and Keyboard
LED 1: Control output „heating“ of the choosen zone active LED 2: Control output „cooling“ of the choosen zone active LED A1: Alarm output A1, indication LED _/ : Setpoint ramp of the choosen zone active LED A2: Alarm output A2, indication LED SP2: Setpoint 2 valid (for all zones)
ZONE
Zone preselection
P
Parameter key (parameter preselection)
Adjustment of chosen parameter (e.g. setpoint) to higher or lower values.
Short operation: single-step adjustment Longer operation: quick-scanning When the parameter adjustments have been altered but not entered, the display will flash bright/dark.
E
Confirmation and storage of the pre-selected values.
The display will show a light chain as a control of this function.
P
Sets the parameter back to the originally stored value.
Any alterations made to the parameters, that are not confirmed (E-key) within 30 seconds, will not be accepted and the parameter will return to its originally stored value. The actual process value and the setpoint value will be indicated.
F1
Function key, E. g. all zones are displayed cyclic (zone scanning on/off).
Zones, which are not in action (OFF), are not displayed. The function of this key can be programmed into the configuration level of zone 0. See parameter „Co.F1“
Page 10
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 10/24
IX. Tendency Display
After switching the instrument „on“ a temperature tendency display will be shown, to give an overview about the temperatures deviations relating to the setpoints in the individual controller zones.
Tendency display. Zone 1 2 3 4
Display „PROCESS“: Temperature deviation zones 1...4: high temperature, X 0,5 % > W
(SP) temperature o.k.
low temperature, X 0,5 % < W (SP) Zone Zone Zone Zone 1 2 3 4 The displayed dec.-point shows the „heating“ or „cooling“: on off off on actual situation of the controllers output.
Flashing: Alarm indication in the matching zone
high temperature, X 0,5 % > W (SP) temperature o.k.
low temperature, X 0,5 % < W (SP) Zone Zone Zone Zone 1 2 3 4 The displayed dec.-point shows the „heating“ or „cooling“: on off off off actual situation of the controllers output.
Zone 2: Zone „OFF“, not in use (display: off) Zone 3: Bottom range end has been reached ( sensor error ) Zone 4: Top range end has been reached ( sensor break, no sensor connected )
Flashing: Alarm indication in the matching zone
O = Selftuning algorithm: active (Opt.) H = Manual mode (Hand) Dec.-point flashing acc. to the actual output
ratio
Zone scanning:
Now ( according to the configuration of key „F1“ ) the process and setpoint values of the individual zones are shown in a scanning mode. If „F1“ is not configurated in this mode (see configuration level) , the individual zones have to be selected manual by pressing key „ZONE“.
Page 11
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 11/24
X. Operating Levels
The operation of the controller is divided into 3 levels.
After switching on the unit, it will be automatically in the operating level.
and and
press press appr. 5 sec. Parameter- Configuration-
Controller: Operating level level level “on“ process value Y ( output ratio ) Zone : on / OFF (process) setpoint value (set) Y ConF
1Y.Hi SEn
Alarm A1 Alarm A2 OFSt COPY
Back into the operation level:
- Press 1 sec. or automatically after appr. 30 sec.
Operating level
(for each zone separatly):
Process- and Setpoint value will be displayed simultaneously. Within the operating level the setpoint can be adjusted by pressing the " up " / " down " - keys. Every adjustment has to be quit by pressing the „ E “ - key. All parameters within the operating level ( including the alarm values ) can , in succession, be displayed by pressing the „ P “ - key and adjusted by pressing the " up " / " down " - keys. Quit by pressing the „ E “ - key.
Parameter level
(for each zone separatly):
Within the parameter level the values are adjusted to suit each individual process. This level is reached by simultaneously pressing the "P" - and " E " -keys. The display of each single parameter within the parameter level and their adjustment, are made in the same way as within the operating level. After either pressing the „E“ - key for approx. 1 second, or waiting for a period of approx. 30 seconds, the unit will automatically return to the operating level (display of process value and setpoint).
Configuration level:
This primary informations have to be entered before taking the instrument into operation.
The configuration level is reached by simultaneously pressing the "P" - and " E " - keys for a period of approx. 5 seconds. First choose the configuration level in zone 0. Here general settings have to be made. This has to be programmed at first:
- Only TC- or RTD-connection for all zones? Or: Mixed connection ?
- Alarm configuration (valid for all zones) - Function of key „F1“
- Software key - Serial interface informations
- Heater current monitoring
Than choose the configuration level of each individual controller zone. This has to be programmed at second:
- Controller type (for each zone)
- Input type (sensor type), sensor range (for each zone)
- Min. and max. setpoint range (for each zone) The display of each single parameter within the configuration level and their adjustment, made in the same fashion as within the operating level. There is also a copy function available. So it is possible, to copy the programmed parameters of one zone to other zones. After either pressing the „E“ - key for approx. 1 second, or waiting for a period of approx. 30 seconds, the unit will automatically return to the operating level (display of process value and setpoint).
P
E
E
P
P
P
P
P
E
P
P
Page 12
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 12/24
XI. Configuration Level, general settings
Select zone 0 and press „P“ - and „E“ - key appr. 5 sec.
Display Parameter Display "Process" „Set“
P - tc Sensor mix - 4 all 4 zones : Thermocouple - connection 2 2 Zones 1 - 2 : RTD - connection; zones 3-4: Thermocouple- connection 4 - all 4 zones : RTD - connection
Co.A1 Alarm 1-Configuration The selected configuration is effective for all control zones. (switches relay A1) The individual temperature alarms A1 of all zones are connected to the main, common contact A1. If a control zone indicates a fault (sensor short circuit / break ), the alarm output A1 is generally switched.
OFF alarm OFF, no alarm signalisation (ex works) 1 signal contact, setpoint depentend: off-on 2 limit contact, process value depentend: off-on 3 limit comparator: off-on-off 4 signal contact: on-off 5 limit contact: on-off 6 limit comparator: on-off-on 7 limit comp. with start-up suppression: off-on-off
8 heater current monitoring; limit contact: off-on 9 heater current monitoring; limit contact: on-off
The signal contact is adjusted and displayed The limit contact is adjusted and displayed relative to the setpoint (deviation alarm). as an absolute value.
LED, Switching behaviour: Configuration: LED, Switching behaviour: Configuration:
off on 1 off on 2, 8
on off 4 on off 5, 9
setpoint process process
The limit comparator is adjusted and displayed The alarm relay of the limit comparator with relative to the setpoint. The selected start-up suppression is activated when the controller value is effective below and above the setpoint. is first switched on. It is only then deactivated, when the process value has been within, and left, the o.k. -zone.
LED, Switching behaviour: Configuration: LED, Switching behaviour: Configuration:
on off on off 3 off on off 7
on off on 6 setpoint process setpoint process
Please note: In case of sensor error the alarms will react in the same way as range override. The alarm contacts therefore do not offer protection against all types of plant breakdown. With this in mind, we recommend the use of a second, independent monitor unit. Care should be used to ensure, that the setpoints of the alarm contacts are programmed within the selected measuring range. If a setpoint ramp has been programmed, the alarms that are relative to the setpoint (signal contact, limit comparator) follow the setpoint up the ramp.
signal value
limit range
limit value
limit range
Page 13
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 13/24
Display Parameter Display "Process" „Set“
rE.A1 Relay A1 switching behaviour dir on: LED A1 „on“. Relay A1 "activated"
off: LED A1 „off“. Relay A1 "not active" inv on: LED A1 „on“. Relay A1 "not active"
off: LED A1 „off“. Relay A1 "activated"
Co.A2 Alarm 2-Configuration The selected configuration is effective for all control zones. (switches relay A2) The individual temperature alarms A1 of all zones are connected to the main, common contact A1. If a control zone indicates a fault (sensor short circuit / break ), the alarm output A1 is generally switched.
OFF alarm OFF, no alarm signalisation (ex works) 1 signal contact, setpoint depentend: off-on 2 limit contact, process value depentend: off-on 3 limit comparator: off-on-off 4 signal contact: on-off 5 limit contact: on-off 6 limit comparator: on-off-on 7 limit comp. with start-up suppression: off-on-off
8 heater current monitoring; limit contact: off-on 9 heater current monitoring; limit contact: on-off
rE.A2 Relay A2 switching behaviour dir on: LED A2 „on“. Relay A1 "activated"
off: LED A2 „off“. Relay A1 "not active" inv on: LED A2 „on“. Relay A1 "not active",
off: LED A2 „off“. Relay A1 "activated",
Heater current monitoring
The following parameters will only be displayed if the heater current monitoring system is activated as descriped below: Heater current monitoring via relay A1: Program parameter Co.A1 to number 8 or 9
Heater current monitoring via relay A2: Program parameter Co.A2 to number 8 or 9 The heater current to be monitored, has to be programed as an absolute value into the operating level for both relays A1 and A2.
See: Operating level, Parameter „A1“ or „A2“. Please note if the supply voltage is low the heater current is higher than the monitoring value otherwise the alarm signal will be
activated. If the heater current value falls below the monitoring value, an alarm signal (the relay switches) will be activated. With the help of the parameter „dL.Ax“ it is possible to program a delay time. If you do so, it is virtually impossible to get an unauthorized alarm signal. When switching the power-on, the alarm signalisation will be suppressed until the heating current values for all zones has been scanned and verified. The monitoring function and all possible adjustments are valid for all connected heating zones.
Display Parameter- Parameter value „Process" description Display „Set“
dL.A1 delay time, relay A1 5 steps adjustable (in sec.) Adjustment and display in seconds. If alarm relay A1 is selected OFF= no delay time The values are dependent on the
for the heater current current detection interval time and the monitoring. number of active controller zones.
dL.A2 delay time, relay A2 5 steps adjustable (in sec.) Adjustment and display in seconds. If alarm relay A2 is selected OFF= no delay time The values are dependent on the
for the heater current current detection interval time and the monitoring. number of active controller zones.
Page 14
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 14/24
Display Parameter- Parameter value „Process" description Display „Set“
Cu.CY Current detection intervall 1 ... 60 sec. Time between the current measuring
of two zones following each other.
C x.x Min. leakage current value OFF; Adjustment of the allowed min.
and leakage current display 0,0...99,9 A leakage current value. with continous current display. The heater current will be monitored to detect circuits with an eventual leakage current (e.g. SSR damage).
SSR`s (especially if they are combined with RC-combinations) normally have small leakage currents. Heaters also have small leakage currents.
The actual leakage current will be displayed in display „PROCESS“. Via display „SET“ the min. allowed leakage current value can be adjusted. Currents below this value will be ignored.
If a permanent current is detected in one zone the alarm relay will be activated and the display „PROCESS“ will show the error signalisation „Er.Cu“. The zone with a measured permanent current can be located by pressing the zone key and watching all temperature indications. Display indication in this case: „Comparable with„temperature too high.“ But there is no special indication via tendency- or alarm status display.
Display: C 0.2 Er. Cu PROCESS PROCESS
1.0
SET SET
Leakage current: 0,2A Permanent current detected in one zone. Min. leakage current Error signalisation: flashing value: 1,0A
Display Parameter- Parameter value „Process" description Display „Set“
Co.F1 Select funktion OFF No function of key „F1“ OPt Selftuning algorithm can be activated by pressing key „F1“ in the matching zone. „F1“ and „E“: stop selftuning. Y Shows the actual percentage output ratio, while pressing „F1“. Display „PARAMETER“: Y LEd.t Lamp (LED) test, while pressing „F1“.
LOC Adjustment lock OFF No adjustment lock (ex works) P C Parameter and configuration levels locked n.SP1 All parameters apart from SP1 locked (not SP1) ALL All parameters locked All parameters that have been locked with „LOC“ can be selected and read, but not altered. This adjustment cannot be changed if the external contact K2 is closed.
Zo.OF Zones offset preselection OFF No offset preselection. Zones indication: 1 - 4 (Continuous numbering of 1 - 91 Zones will be numbered with preselected offset value. the controller zones) Example: Zo.OF = 1 -> Zone indication: 2 - 5 Zo.OF = 8 -> Zone indication: 9 - 12
Page 15
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 15/24
Display Parameter- Parameter value „Process" description Display „Set“
The following parameters are only valid, if the unit is equipped with a serial interface. RS232, RS485, 0/20mA.
Prot Protocol preselection ELO ELOTECH- standard protocol IbS Gateway-protocol valid for Profibus-DP, InterBus-S
Only with RS 485-interface (Code-No.: 4).
Adr Unit adress 1 .... 255 (ex works: 1)
The computer adresses the unit/controller at this adress. Each unit has ist own adress. With RS-485 it is possible to adress 32 units.
For Data format 7E1 7 data, even, 1 stopbit 7o1 7 data, odd, 1 stopbit 7E2 7 data, even, 2 stopbit 7o2 7 data, odd, 2 stopbit 7n2 7 data, none, 2 stopbit 8E1 8 data, even, 1 stopbit 8o1 8 data, odd, 1 stopbit 8n1 8 data, none, 1 stopbit InterBus-S Gateway 8n2 8 data, none, 2 stopbit
bAud Baud rate OFF; 0,3 ... 9,6 kBaud The baud rate denotes the transmission rate at which one bit is transmitted. InterBus-S Gateway = 9,6 kBaud
Details, see: - sep. interface description: ELOTECH – standard-protocol
- sep. interface description: Gateway: M-IBS-5
- Download: www.elotech.de
The following parameters are only valid, if the unit is equipped with a CAN interface.
Adr Unit adress 1 .... 127 (ex works: 1)
bAud Baud rate 10, 20, 50, 100, 125, 250, 500 kBaud, 1MBaud (ex works: 20)
CANopen-specfication: CANopen Master: no CANopen Slave: yes Extended Boot-up: no Minimum Boot-up: yes COB ID Distribution: yes; default via SDO Node ID Distribution: no; via device keyboard No. of POD´s: 0RX, 1TX PDO Modes: async. Variable PDO mapping: no Emergency message: yes Life guarding: yes No. of SDO`s: 1RX, 1TX Device Profile: CiA DS-404
Details, see: - CANopen Device Profile CiA DS-404; ELOTECH Object Dictionary
- Download: www.elotech.de
20xx EL.xx Control number No function. End of configuration level
Page 16
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 16/24
XII. Configuration Level, individual selectable for zones 1...4; d1, d2
Select zone n and press „P“ - and „E“ - key appr. 5 sec.
Display Parameter Display "Process" „Set“
Zone Zone on / off OFF measuring- or controller zone „off“ on measuring- or controller zone „on“
ConF Controller configuration 2P h 2-point-controller „heating-off“ (ex works) 2P c 2point-controller „cooling-off“ 2Pnc 2point-controller „cooling-off“ with non-linear cooling *) 3P 3point-controller „heating-off-cooling“ 3Pnc 3point-controller „heating-off-cooling“ with non-linear cooling *) *) non-linear cooling: Cooling action can be pre-selected with either linear or non-linear cooling response curve ( e.g. for vapour cooling). diSP Zone works as an indicator, no controller action
SEn Sensor selection P1 °C Pt 100, -50,0...100,0 °C P1 °F Pt 100, -58,0...212,0 °F P2 °C Pt 100, -90,0...205,0 °C P2 °F Pt 100, -130... 401 °F P4 °C Pt 100, 0... 400 °C (ex works) P4 °F Pt 100, 32... 752 °F P8° C Pt 100, 0... 800 °C P8 °F Pt 100, 32...1472 °F
or, if selected as a thermocouple-input zone (depending on parameter „P - tc“ in Zone 0): L4 °C T/C Fe-CuNi (L), 0... 400 °C
L4 °F T/C Fe-CuNi (L), 32... 752 °F L8 °C T/C Fe-CuNi (L), 0... 800 °C L8 °F T/C Fe-CuNi (L), 32... 1472 °F J8 °C T/C Fe-CuNi (J), 0... 800 °C J8 °F T/C Fe-CuNi (J), 32... 1472 °F n1 °C T/C NiCr-Ni (K), 0... 1200 °C n1 °F T/C NiCr-Ni (K), 32... 2192 °F S1 °C T/C Pt10Rh-Pt (S), 0... 1600 °C S1 °F T/C Pt10Rh-Pt (S), 32... 2912 °F
If the Sensor selection is changed, the following parameters will be set as follows and need to be re-adjusted: Setpoint 1, setpoint 2: SP.Lo Process value offset: OFF Lower setpoint limitation: Bottom range end; Higher setpoint limitation: Top range end; Setpoint-ramp values: OFF; Alarm values: OFF;
OPTION: The following parameters are only valid for zones d1 and d2 (Input: 0...10 Vdc). It is to configurate the display range of the 0...10 Vdc inputs. The difference between the bottom end of the display range and the top end must amount to a minimum of 100 units and a maximum of 2000 units. By adjustment of one of the above parameters, the other in this case will automatically follow.
rA.dP decimal points 0; 1; 2 (ex works: 1) rA.Hi display range top end rA.Lo ... 9999 (ex works: 100,0) rA.Lo display range bottom end -1999 ... rA.Hi (ex works: 0,0)
unit selectable physical. unit shown in the display „set“ ( e.g. : °C, °F, ba r, volt ... )
SP.Hi higher setpoint limitation programming range: SP.Lo ... top range (ex works: 400) SP.Lo lower setpoint limitation programming range: bottom range ... SP.Hi (ex works: 0)
COPY Copy function to 1 ... to x Copy all datas of the actual zone to the selected zone x.
Select the target zone (1,2 .... or „to A“ (to all) with the „up/down“ - keys
and press „E“ (enter). After this, the datas would be copied. Note: It is only possible to copy the configuration, if the sensor configuration ( Parameter: P - tc ) in the target-zone is the same as in the actual zone. This means, that it is not possible, to copy configurations of e.g. RTD-input zones to thermocouple-input zones.
Page 17
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 17/24
Display Parameter Display "Process" „Set“
Softstart-function
TAKE CARE: If you take the softstart-function, make sure that the heating control outputs are
equipped with bistable voltage (logic) outputs. This function is not allowed for instruments with relay-outputs (in this case set So.St = OFF). Otherwise the relais will be destroid becuse they switch too fast.
Softstart (general function):
During the softstart the controllers’ heating output response is limited to a pre-selected ratio, in order to achieve a slow baking out of high performance heat cartridges. Simultaneously the output clock frequency is quadrupled. Once the process value reaches the softstart setpoint, it remains stable at this value for a pre-selcted hold-duration time. At the end of this period the process value rises to the valid setpoint. This results in a slower, more regular heating period. For this purpose the bistable voltage output must be taken, that actuates SSR relays. If the softstart is active, the controllers’ autotune function can’t operated (Er.OP). If a setpoint-ramp has been programmed, the softstart has priority, and the ramp will only become active after the softstart has been completed.
The softstart only works,
- if the parameter „1 P“ (prop. band, xp) is programmed > 0,1%.
- if the actual process value is lower than So.SP – 5% of the selected measuring range. It is possible, to select this function for each zone individally.
Setpoint SP
So.SP Softstart setpoint
So. Y So.ti
t
So.St Softstart-function OFF: Softstart not active (ex works) Next parameter So.Y, So.SP, So.ti are not shown. On: Softstart in action. The softstart function always runs, if the controller is switched on and / or if the actual temperature is below the softstart setpoint So.SP minus 5% of the range (e.g. range: 400^C -> 5%= 20°C).
So. Y Softstart output ratio 10 ... 100%
So.SP Softstart setpoint range: SP.Lo .... SP.Hi
So.ti Softstart duration time OFF; 0,1 ... 10,0 min.
Page 18
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 18/24
Display Parameter Display "Process" „Set“
Hand manual output ratio OFF, Auto, Man (ex works: OFF)
Setting: OFF
Function not active
Setting: Auto
In event of sensor break the controller automatically maintains the
last valid output ratio as the actuating signal.
An „H“ is then displayed as the first digit in the setpoint display, followed by the valid output ratio. This ratio can be manually altered in steps of 1% (up/down-keys; enter). Under the following circumstances, the output ratio will be 0%:
- if the output ratio at time of the sensor break was 100%.
- if the controller is working along a setpoint-ramp.
- if the control deviation was more than 0,25% of the total range at the time of sensor break.
- if th prop. band (P; xp) = 0.
- if the soft start was active at the time of the sensor break. A few seconds after the sensor break has been rectified, the controller returns to automatic operation and calculates the required output ratio. An additional signal can be issued in the event of sensor break, if the alarm contacts are programmed accordingly.
Setting: Man
The controller now operates only as an actuator. Within the operation level, an output ratio can be entered instead of the setpoint. An „H“ is then displayed as the first digit in the setpoint display, followed by the output ratio. There is no controlling action.
Page 19
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 19/24
XIII. Parameter Level, individual selectable for zones 1...4
Select zone “n” and press „P“ - and „E“ - key appr. 1 sec.
Display Parameter Display "Process" „Set“
Y valid output ratio -100...0...100 % The output ratio shows the momentary calculated ratio. It cannot be altered. The display is in percent of the installed performance capability for heating or cooling. Output ratio for cooling is shown as a negative value.
1Y.Hi output ratio limit 0...100 % (ex works: 100) „heating“ Limitation of the output ratio is only necessary when: the heating or cooling energy supply is grossly over­ dimensioned compared to the power required, or to turn off a control output (setting = 0%). under normal circumstances no limitation is needed (setting = 0%). the limitation becomes effective, when the controllers’ calculated output ratio is greater than the maximum permissible (limited) ratio. Warning! The output ratio limitation does not work during autotune.
2Y.Hi output ratio limit 0...100 % (ex works: 100) „cooling“
1 P „heating“ OFF; 0,1...100,0 % (ex works: 3,0) prop. band (P) If „ 1 P “ = OFF (control action: on-off, without feedback) next parameter: „ 1 Sd “.
1 d „heating“ OFF; 1...200 secs (ex works: 30) rate (D)
1 J „heating“ OFF; 1...1000 secs (ex works: 150) reset (I) Normally the controller works using PD/I control action. This means, controlling without deviation and with practically no overshoot during start-up. The control action can be altered in its structure by making the following adjustments to the parameters: a. no control action, on-off (setting P = OFF) b. P-action (setting D and I = 0) c. PD-action (setting I = 0) d. PI-action (setting D = 0) e. PD/I modified PID-action
1 C „heating“ 0,5...240,0 secs (ex works: 10,0) cycle time The switching frequency of the actuator can be determined by adjusting the cycle time. This is the total time needed for the controller to switch on and off once. a) Relay outputs: cycle time > 10 secs b) Bistable voltage outputs: cycle time 0,5...10 secs
1 Sd „heating“ Control sensitivity Only if: 1 P = Xp = OFF (On-off action, without feedback)
OFF; 0,1...80,0 °C (ex works: 0,1) OFF; 0,01 ... 8,00 °C (ranges with dec.point )
Sd = 10,0
on
-5,0 +5,0 off
SETPOINT PROCESS VALUE
Page 20
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 20/24
Display Parameter Display "Process" „Set“
The following parameters are only displayed and valid if configuration is „ 3 P “ or „ 3 Pnc “ .
Only for „heating-off-cooling“ action.
Sh switch-point difference OFF; 0,1... 80,0 °C (ex works: OFF)
OFF; 0,01... 8,00 °C This parameter raises the setpoint (switch-point) for cooling output by the displayed value. It can be help to reduce the switching frequency between the heating and cooling outputs, if this is to high. Simultaneously activation of heat and cool outputs is not possible.
2 P „cooling“ OFF; 0,1...100,0 % (ex works: 3,0) prop. band (P) If „ 2 P “ = OFF (control action: on-off, without feedback) next parameter: „ 2 Sd “.
2 d „cooling“ OFF; 1...200 secs (ex works: 30) rate (D)
2 J „cooling“ OFF; 1...1000 secs (ex works: 150) reset (I)
2 C „cooling“ 0,5...240,0 secs (ex works: 10,0) cycle time The switching frequency of the actuator can be determined by adjusting the cycle time. This is the total time needed for the controller to switch on and off once. a) Relay outputs: cycle time > 10 secs b) Bistable voltage outputs: cycle time 0,5...10 secs
2 Sd „cooling“ Control sensitivity Only if: 2 P = OFF (On-off action, without feedback)
OFF; 0,01 ... 8,00 °C (ranges with dec.point ) OFF; 0,1...80,0 °C (ex works: 0,1)
Sd = 10,0
on
off -5,0 +5,0
SETPOINT PROCESS VALUE
Page 21
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 21/24
Display Parameter Display "Process" „Set“
OPt self tuning OFF self tuning out of action (autotune) on self tuning on request ( one time)
The tuning algorithm determines the characteristic values within the controlled process, and calculates the valid feedback parameters ( P,D,I ) and the cycle time ( C = 0.3 x D ) of a PD/I-controller for a wide section of the range.
The self tuning activates during start-up shortly before the setpoint is reached. The setpoint must amount to the least 5% of the total range. If activated after the setpoint has already been reached, the temperature will first drop by approx. 5% of the total range, in order to detect the exact amplification of the process.
Using the heat-cool controller, the temperature drop will be accelerated by switching on the cooling for a short duration. The tuning algorithm can be activated at any time by selecting the OPT=on and pressing the „E“-key. Zone display: During self tuning „OPt“ is shown in the display, alternating with the setpoint value.
Tendency display: „O“ is shown. After having calculated the correct feedback parameters, the controller will lead the process value
to the setpoint.
X X
Set Set
OPT on t OPT on t Self tune Self tune, after the setpoint during start-up has already been reached
Self-tuning can be stopped by selecting the option OPT = OFF and pressing the „E“ - key.
OFSt process value offset -999 ... OFF ...1000 Units (ex works: OFF)
-99,9 ... OFF ... 100,0 This parameter serves to correct the input signal, e.g. for:
- the correction of a gradient between the measuring point and the sensor tip,
- the line resistance balancing of 2-line RTD (Pt100) sensors and
- correction of the control devition when using P- or PD-action. If for example the offset value is set to +5°C , then the real temperature measured
by the sensor (when process is balanced) is 5°C less than the setpoint and the displayed process value.
Page 22
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 22/24
XIV. Operating Level, individual selectable for zones 1...4
Display Parameter Display "Process" „Set“
Process value
(process)
and Setpoint 1 SP.Lo...SP.Hi (ex works: 0)
(set)
are displayed simultaneously (basic setting) in the selected zone.
SP2 Setpoint 2 OFF; SP.Lo SP.Hi (ex works: OFF)
The 2. setpoint is active when the external contact K1 is closed. The corresponding LED „SP2“ lights up on the faceplate,and the second setpoint is shown in the setpoint-display. In order to change the value the parameter SP2 has to be selected.
SP rising ramp OFF; 0,1...100,0 °C/min. or °F/min. (ex works: O FF) SP falling ramp OFF; 0,1...100,0 °C/min. or °F/min. (ex works: OFF )
A programmed ramp is always activated when the setpoint is altered or when the mains supply is switched on. The ramp constructs itself out of the momentary process value and the pre-selected setpoint. If the ramp is active, the corresponding LED lights up on the faceplate. The ramp can be activated for both setpoint1 and setpoint2. By programming the second setpoint accordingly a setpoint profile can be oblained (please see example below).
process SP2
SP1
time K1, open K1, closed K1, open
A1 Alarm value 1, switching point Temparature monitoring: alarm value adjustment (switches relay A1) Signal contact, limit comparator, limit contact OFF; -199... 199 °C/°F (ex works: OFF) OFF; -19,9... 19,9 °C/°F OFF; 0... 999 °C/°F or Heater current monitoring: alarm value adjustment Limit contact OFF: 0,0 ...99,9 A (ex works: OFF)
A2 Alarm value 2, switching point Temparature monitoring: (switches relay A2) Signal contact, limit comparator, limit contact OFF; -199... 199 °C/°F (ex works: OFF) OFF; -19,9... 19,9 °C/°F OFF; 0... 999 °C/°F or Heater current monitoring: alarm value adjustment Limit contact OFF: 0,0 ...99,9 A (ex works: OFF)
The range of adjustment is dependant on the sensor, the connected current transformers and the alarm configuration. Both have to be set in the configuration level.
Cur Actual heater current indication
Page 23
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 23/24
XV. Operating Level, Option: only inputs zones d1 and d2
Display Display "Process" „Zone“
input d1 d1 Display 1: 0...10 Vdc, corresp. the progr. range (ex works: 0...100)
input d1 d2 Display 2: 0...10 Vdc, corresp. the progr. range (ex works: 0...100)
XVI. Technical Data
Input RTD, Pt 100 (DIN): 2 - or 3 - wire connection possible.
Built-in protection against sensor breakage and short circuit. Max. permissible line resistance by 3-wire connection: 80 Ohms Sensor current: < 1 mA Calibration accuracy: < 0,2 % Linear error: < 0,2 % Influence of the ambient temperature: < 0,01 % / K
Input Thermocouple: Built-in internal compensation point and protection against sensor breakage and incorrect polarity. Re-calibration not required for a line resistance of up to 50 Ohms. Calibration accuracy: < 0,25%
Analog inputs (Option): 0 ... 10 V DC (Display range programmable) Setpoint selection: Ext. potential-free contact, switching voltage appr. 24 V DC, max. 1 mA.
Selection between SP1 and SP2 valid for all zones. Control outputs OUT 1 ... OUT 8: Bist. voltage signal, 0/18 V DC, max. 10 mA, short-circuit proof
or Relay, max. 250 VAC, max. 3 A (cos-phi = 1)
Alarm outputs A1 and A2: Relay, max. 250 VAC, max. 3 A (cos-phi = 1) 7-Segment-Display: Process: 10 mm red, Set: 10 mm red Data protection: EAROM CE-Mark Tested according to 2004/108/EC; EN 61326-1; industrial areas
Electr. safety: EN 61010-1
Power supply: Standard: 230 V AC, ± 10 %, 48...62 Hz, appr. 10VA Connections: Screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C Permissible operating conditions: Operating temperature: 0...50 °C / 32...122 °F
Storage temperature: -30...70 °C / -22...158 °F Climate class: KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation
Casing: Format: 96 x 96 mm (DIN 43700), installation depth 122 mm Panel cutout: 92 +0,5 mm x 92 +0,5 mm Material: Noryl, self-extinguishing, non-drip, UL 94-V1 Protection mode: IP 20 (DIN 40050), IP 50 front side
Weight: app. 800 g
Heater current monitoring:
Current transformer 1:1000: Passive through current transformer with snap-in attachment for DIN rail (Type M2000) mounting (EN 50022, 35mm). Connections to the controller: 2 x 6,3mm flat connectors. Heater current detection and indication range: 0...max. 60,0A. Single-phase operation.
0...max. 99,9 A. Three-phase operation. The sum of the current of all three phases of one controller zone will be monitored. Variations of the power supply voltage have to be considered when the the alarm values are programmed.
Current detection interval time programmable (1...60 sec.). This is the time between the measuring of two successive controller zones.
Alarm delay time programmable. It depends upon the current detection interval time and the number of the connected temperature zones (min. 8 sec.).
Subject to technical improvments!
Page 24
Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 24/24
XVII. Error displays
Display Cause Possible remedy SP.Lo Lower setpoint limit has been reached Reduce limit, if need be SP.Hi Upper setpoint limit has been reached Increase limit, if need be LOC Parameter has been locked Unlock, if need be Er.H Top range end has been exceeded, Check sensor and cable
sensor defect Er.L Bottom range end has been exceeded, Check sensor and cable
sensor defect Er.OP Self tuning error Extinguish error signal by pressing the „E“-key.
Check the self tuning conditions and restart. Er.SY System error Extinguish error signal by pressing the „E“-key.
Check all parameters. If the error signal continues please send the controller for examination.
Co.A1 Alarmconfiguration of alarm A1: OFF No alarm signal available Co.A2 Alarmconfiguration of alarm A2: OFF No alarm signal available
-no- Parameter not available in this zone.
-PA­Er.Cu Short circuit current in one or more loads. Check load.
Look at ssr`s with short circuit.
The zone or the zones were a permanent current is measured, can be detected by controlling the actual temperatur indications of all zones. The tempearture should be too high.
XVIII. Installation Instructions
Make certain that the devices described here are used only for the intended purpose. They are intended for installation in control panels. The controller must be installed so that it is protected against impermissible humidity and severe contamination. In addition, make sure that the permitted ambient temperature is not exceeded.
The electrical connections must be made according to the relevant locally applicable regulations.
If using a thermocouple sensor, the compensation cables must be laid directly to the controller terminals. Transducers must be connected only in compliance with the programmed range. Transducer cables and signal lines (e.g. logic or linear voltage outputs) must be laid physically separated from control lines and mains voltage supply cables (power cables) and must be shielded. Spatial separation between controller and inductive loads is recommneded. Interference from contactor coils must be suppressed by connecting adapted RC-combinations parallel to the coils. Control circuits (e.g. for contactors) should not be connected to the mains power supply terminals of the controller.
Disclaimer of liability
We have checked the contents of the document for conformity with the hardware and software described. Nevertheless, we are unable to preclude the possibility of deviations so that we are unable to assume warranty for full compliance. The information given in the publication is, however, reviewed regularly. Necessary amendments are incorporated in the following editions. We would be pleased to receive any improvement proposals which you may have.
The information contained herein is subject to change without notice.