Elotech R 1140, R 1180 Description And Operation Manual

Temperature Controller - heating-off (2-point)
- heating-off-cooling (3-point)
- continuous controller
R 1140 R 1180
Description and Operation Manual
ELOTECH Industrieelektronik GmbH Verbindungsstrasse 27 D – 40723 HILDEN FON +49 2103 / 255 97 0 FAX +49 2103 / 255 97 29 www.elotech.de Email: info@elotech.de
Manual: R11X0-X0-0X-X_EN Release: 1.03 © Elotech GmbH Page 1/20
Contents
Type code Page 2 Connection diagram R1140 3 Connection diagram R1180 4 Technical data 5
Display and keyboard 6 Operating levels, general 7
Configuration level 8 Parameter level 14 Operating level 17
Error displays 18 Installation instructions 18
Parameterlist 19
Please read this operating manual carefully before starting up. Observe the installation and connecting instructions.
Type Code
R 1140 - x - 00 - z -54: Option, front side IP54 R 1180 - x - 00 - z
1: Power supply: 230 VAC 2: Power supply: 115 VAC
00: Sensor input (standard):
10: 2-Point- (heat-only or cool-only) / 3-Point- (heating-off-cooling) controller OUT2: Relay
OUT3: Relay
60: 2-Point- / 3-Point- continuous controller
OUT2: relay OUT3: relay 61: 2-Point- / 3-Point- continuous controller
OUT2: relay OUT3: relay
3: Power supply: 24 VAC 5: Power supply: 24 VDC, +/-25%
Pt100 (RTD); Fe-CuNi (Type L), Type J, Type K, Type S; 0-20mA, 4-20mA
01: Sensor input (option):
Pt100 (RTD); Fe-CuNi (Type L), Type J, Type K, Type S; 0-10VDC
OUT1: Relay and OUT4: bist. voltage 0/18VDC-signal
2-Point / 3-Point with analogue process output signal
OUT1: relay and OUT4: continuous output (control output or process) 0/4...20mA
2-Point / 3-Point with analogue process output signal
OUT1: relay and OUT4: continuous output (control output or process) 0...10V
Manual: R11X0-X0-0X-X_EN Release: 1.03 © Elotech GmbH Page 2/20
Connection diagram R1140
L / DC- 1
Power Supply N / DC+ 2
3 4
OUT 3 Alarm 3 5
6
OUT 2
Controller output 7 or Alarm 2 8 OUT 1 Controller output 9 20 + OUT 4 bistable 0/18VDC or 0/4...20mA
21 - OUT 4 or 0...10V
22 k1: external, potentialfree contact to switch over from setpoint SP1 to SP2
23 or to lock the adjustments. 24
25 0-20mA 26 TC 4-20mA Pt100/RTD 0-10VDC(Option)
27 2-wire connection: +
jumper between terminal 24 and 25.
It is not permitted to connect the grounds of the sensor-, bist. voltage- and continuous-outputs with each other.
OUT1 = Control output 2-point-controller: "Heating" or „Cooling“ 3-point-controller: „Heating“
OUT2 = Control output 3-point-controller: „Cooling“ or alarm output 2-point-controller: Alarm 2
Continuous-controller: Alarm 2
OUT3 = Alarm Output Alarm 3 OUT4 = Logic output (0/18VDC) or continuous Output (0/4...20mA) instead of output OUT1 or output OUT2
Please take attention at Configuration level: parameter „Out4“
1. R1140-10: OUT4 = Controller Output: logic 0/18VDC.
2. R1140-60: OUT4 = Controller Output: continuous 0/4...20mA or analogue process val. 0/4...20mA.
3. R1140-60: OUT4 = Controller Output: continuous 0…10V or analogue process value 0…10V.
Function of contact k1: programmable. See parameter Co.c1. Possible adjustments: „Loc“ or „SP2“.
1. Adjustment lock (LOC): k1: open = Adjustment lock only via "Software Code" k1: closed = Adjustment locked (according to the chosen software code)
2. Setpoint Controlling: k1: open = Setpoint 1 (SP1) valid k1: closed = Setpoint 2 (SP2) valid
Manual: R11X0-X0-0X-X_EN Release: 1.03 © Elotech GmbH Page 3/20
Connection diagram R1180
Power Supply N L
Controller Controller DC+ DC­ output output or Alarm2 Alarm3 OUT 1 OUT 2 OUT 3
9 8 7 6 5 4 3 2 1
27 26 25 24 23 22 21 20
k1
- + OUT 4 OUT4: - bistabil 0/18VDC
- or 0/4…20mA Pt100 / RTD, 2-wire connection: jumper from 24 to 25 - or 0…10V
k1: External, potentialfree contact to switch over from SP1 to SP2 TC: 26(+) and 25(-) or to lock the adjustments. See Parameter „Co.c1“
+ ­ 0-20mA: terminals 27(+) and 25(-) 4-20mA: terminals 27(+) and 25(-) 0-10VDC:terminals 27(+) and 25(-); (Option)
It is not permitted to connect the grounds of the sensor-, bist. voltage- and continuous-outputs with each other.
OUT1 = Control output 2-point-controller: "Heating" or „Cooling“ 3-point-controller: „Heating“
OUT2 = Control output 3-point-controller: „Cooling“ or alarm output 2-point-controller: Alarm 2
Continuous-controller: Alarm 2
OUT3 = Alarm Output Alarm 3 OUT4 = Logic output (0/18VDC) or continuous output (0/4...20mA / 0…10V) instead of output OUT1 or OUT2
Please take attention at Configuration level: parameter „Out4“
1. R1140-10: OUT4 = Controller Output: logic 0/18VDC.
2. R1140-60: OUT4 = Controller Output: continuous 0/4...20mA or analogue process val. 0/4...20mA.
3. R1140-60: OUT4 = Controller Output: continuous 0…10V or analogue process value 0…10V.
Function of contact k1: programmable. See parameter Co.c1. Possible adjustments: „Loc“ or „SP2“.
1. Adjustment lock (LOC): k1: open = Adjustment lock only via "Software Code" k1: closed = Adjustment locked (according to the chosen software code)
2. Setpoint Controlling: k1: open = Setpoint 1 (SP1) valid k1: closed = Setpoint 2 (SP2) valid
Manual: R11X0-X0-0X-X_EN Release: 1.03 © Elotech GmbH Page 4/20
Technical Data
Input Thermocouple: Built-in internal compensation point and protection against sensor breakage
and incorrect polarity. Re-calibration not required for a line resistance of up to 50 Ohms. Calibration accuracy: < 0,25% Error of compensation point:
Input RTD: Built-in protection against sensor breakage and short circuit. Max. permissible line resistance by 3-wire connection: 80 Ohms Sensor current: < 0,5 mA Calibration accuracy: < 0,2 %
Input 0/4-20mA: Load max. 10 Ohm Input 0-10VDC: Load >10KOhm/V (Option)
Linear error: < 0,2 % Influence of the ambient temperature: < 0,01 % / K
Setpoint selection (k1): Ext. potential-free contact, switching voltage appr. 24 V dc, max. 1 mA. Selection between SP1 (main setpoint) and SP2.
Outputs: Version 10: - Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load)
- Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof Version 60: - Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load)
- Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
- Continuous output: 0/4...20 mA, Load max. 500 Ohm Linearity: < 1,5 %, Delay time: app. 2 secs. Version 61: - Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load)
- Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
- Continuous output: 0...10V, input resistance of receiver > 50kOhm Linearity: < 1,5 %, Delay time: app. 2 secs.
Alarm output OUT 2: - Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load). Only for 2-point-controller and continuous-controller configuration.
Alarm output OUT 3: - Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load). Process output OUT 4: Only version R11x0-60/61. Output range according to the choosen measurement range.
0/4…20mA (-60) or 0…10V (-61)
7-Segment-Display: Process: 10 mm red, Set: 10 mm red Data protection: EAROM CE-Mark Tested according to 2004/108/EC; EN 61326-1
Electr. safety: EN 61010-1
Power supply: Standard: 230 V AC. ± 10 %, 48...62 Hz. Others possible. See Type Code. Connections: Screw terminals (UR appr.).
Protection mode IP 20 (DIN 40050), Insulation class C. Permissible operating conditions: Operating temperature: 0...50 °C / 32...122 °F
Storage temperature: -30...70 °C / -22...158 °F Climate class: KWF DIN 40040; Equivalent to annual average max. 75 % rel. humidity.
Casing: R1140-Format: 48 x 96 mm (DIN 43700). Installation depth 122 mm Panel cutout: 45 +0,6 mm x 92 +0,8 mm R1180-Format: 96 x 48 mm (DIN 43700). Installation depth 122 mm Panel cutout: 92 +0,8 mm x 45 +0,6 mm Material: Noryl, self-extinguishing, non-drip, UL 94-V1 Protection mode: IP 20 (DIN 40050), IP 50 front side Front side IP 54: Option
Weight: app. 380g Subject to technical improvments!
< 0,5K
No condensation.
Manual: R11X0-X0-0X-X_EN Release: 1.03 © Elotech GmbH Page 5/20
Display and Keyboard
Display PROCESS: Process Value Display SET: Setpoint Value
LED 1: Output OUT1 active: Control Output 1 LED 2: Output OUT2 active: Control Output 2 or
Alarm Output A2
LED 3: Output OUT3 active: Alarm Output A3
LED SP2: Setpoint 2 active
P
Adjustment of chosen parameter (e.g. setpoint) to higher or lower values. E.g. setpoin adjustment. Short operation: single-step adjustment Longer operation: quick-scanning When the parameter adjustments have been altered but not entered, the display will flash bright/dark.
E
The display will shortly show a light chain as a control of this function. To return to the process- and setpoint-display: press „E“ appr. 2 sec..
P
Any alterations made to the parameters, that are not confirmed (E-key) within 30 seconds, will not be accepted and the parameter will return to ist originally stored value.
Parameter key
Confirmation and storage of the pre-selected values
Sets the parameter back to the originally stored value.
Manual: R11X0-X0-0X-X_EN Release: 1.03 © Elotech GmbH Page 6/20