Elnur CMX15, CM15 Installation Instructions And User Manual

DIGITAL MODULATING
ELECTRIC
FOR
CENTRAL
Please read these instructions before installing or using this appliance for the first time.
These instructions must be followed for the safe installation of the boiler.
Any problem, fault or damage caused by the non
This manual should be retained with the appliance by the user for future reference.
BOILERS & ELECTRIC
BOILERS
HEATING AND DOMESTIC
HOT WATER
CMX15
-observance of these instructions will
not be covered under the manufacturers warranty.
COMBI
CM15
INDEX
1 IMPORTANT 1
2 SAFETY 1
3 INTRODUCTION 2
3.1 DESIGN & OPERATION 2
3.2 PRINCIPLE COMPONENTS 2
3.3 KEY TO COMPONENTS 2
3.4 SAFETY DEVICES 3
4 INSTALLATION 3
4.1 GENERAL REQUIREMENTS 4
4.2 UNPACKING & CONTENTS 4
4.3 LOCATION 5
4.4 DIMENSIONS & CONNECTIONS
5
4.5 CLEARANCES 6
4.6 MOUNTING BRACKET 6
4.7 WATER CONNECTIONS 7
4.8 DHW DISCHARGE PIPE-WORK 8
4.9 PUMP DUTY 9
4.10 ELECTRICAL CONNECTIONS 9
5 COMMISIONING 11
5.1 LIMITING BOILER MAXIMUM OUTPUT 11
5.2 HEATING SYSTEM INITIAL FILLING 12
5.3 PUMP CHECKING & VENTING 12
5.4 HEATING SYSTEM FLUSHING 13
5.5 FILLING DOMESTIC HOT WATER 13
6 OPERATING THE BOILER
13
6.1 INITIAL SWITCHING ON 13
6.2 CONTROL PANEL DESCRIPTION 13
6.3 DHW OPERATION 14
6.4 CENTRAL HEATING OPERATION 15
6.5 ANTI-FREEZE MODE 15
6.6 HEATING MODULATION FEATURE 15
6.7 LOCKING THE CONTROL PANEL 15
6.8 PUMP ANTI-SEIZE FUNCTION 15
7 TROUBLE SHOOTING 16
7.1 POSSIBLE FAULTS & SOLUTIONS 16
7.2 OVERHEAT LOCK-OUT & RE-SETTING 17
7.3 HEATING FLOW SWITCH – E3 ERROR 17
7.4 CHECKING RATED HEAT OUTPUT 17
8 MAIN COMPONENTS LIST
18
9 MAINTENANCE & CARE 18
10 ENVIRONMENTAL INFORMATION 18
11 TECHNICAL DATA 19
12 WIRING DIAGRAMS 20
13 EC DECLARATION OF CONFORMITY 22
1 IMPORTANT
The following installation instructions are intended to guide the competent person throughout the entire installation process.
The boiler’s guarantee does not cover any damaged caused by non-observance of any of these instructions.
These installation instructions and user’s guide must be conserved and given to any new user.
The symbols used in the text are explained below:
WARNING This indication shows the possibility
of causing death from electric shock.
WARNING This indication shows the possibility
of causing death or serious injury.
CAUTION This indication shows the possibility
of causing injury or damage to properties only.
Symbol for useful information.
2 SAFETY
o This appliance is not destined for use by anyone
(including children) with reduced physical, sensorial or mental capacities or those who do not know how to use the appliance, unless they are supervised or instructed by a person responsible for their safety.
o Check that the voltage on the indicator plate of the
boiler coincides with the voltage of the mains circuit to which it is going to be connected.
o The use of these boilers in the presence of gases,
explosives or inflammable objects is prohibited.
o The air inputs and outputs of the boiler ensure its
correct operation and protect it from over-heating. They must never be covered.
o This boiler must be disconnected from the mains
electricity before carrying out any internal repairs.
o The boiler must be installed in such a manner that
the switches or other controls cannot be touched by anyone who is using the bath or shower.
o The installation must be performed in accordance
with current electricity regulations.
o This appliance is destined to be permanently
connected to a fixed installation. The power circuit of the boiler must incorporate an omni-polar cut­off switch with a separation between the contacts of at least 3 mm.
o The electricity supply circuit must incorporate a
Residual-Current Device.
o This boiler must be earthed.
i
2
o All the models incorporate different safety
elements. If one or more of them are activated, consult the section 7 TROUBLE SHOOTING.
o In time, the presence in the air of smoke, dust and
pollution may stain the walls and areas close to the appliance.
o Any improper use is forbidden. o Do not install the boiler in rooms prone to frost.
3 INTRODUCTION
3.1 DESIGN & OPERATION
The Gabarron CM15 boilers are electrically heated appliances providing wet central heating through a standard radiator system (or underfloor system with special kit).
The Gabarron CMX15 boilers are electrically heated combi boilers providing wet central heating through a standard radiator system (or underfloor system with special kit) and domestic hot water (DHW) delivered from an integral unvented store at mains water pressure.
Outputs are from 2 to 15kW. Maximum output can be adjusted to match the heat requirement of the system or the limitations of the incoming available power supply. Operation is possible on three phase 3x400V+N or single phase 230V - 50Hz.
The boilers are designed for internal installation on a suitable wall with consideration for the total weight of the appliance when full.
A digital control panel provides user control to adjust the temperatures of heating and hot water. A power modulation feature automatically adjusts the heating output to the demand to ensure economic operation.
A suitable external time clock/room thermostat should be fitted.
An adjustable thermostatic blending valve must be fitted on the hot water supply to ensure a safe and economic supply of hot water.
All components for sealed system central heating are built­in. A suitable filling loop should be fitted externally to comply with water supply regulations.
Heating and hot water functions will operate independently but not simultaneously with priority always to hot water production unless this function is not selected.
3.2 PRINCIPLE COMPONENTS
Insulated steel boiler unit with immersed
stainless steel elements INCOLOY800
50 L stainless steel domestic hot water store
with CFC free insulation and immersed stainless steel elements INCOLOY800.
Fully integrated electronic control boards
featuring temperature control and modulation
function, pump over-run, anti-seize and frost protection. Self diagnostic fault information.
Sealed system heating components: circulating
pump, 6L expansion vessel, auto air-vent, 3 bar relief valve, pressure gauge, water flow switch and temperature limit safety thermostat.
Unvented hot water components: 7 bar relief
valve, 2l expansion vessel, non-return valve and temperature limit safety thermostat.
Silent TRIAC power switches.
Digital control board.
3.3 KEY TO COMPONENTS
1 DHW 7 bar relief valve. 2 Connection block. 3 ON / OFF switch. 4 DHW safety thermal limit switch. 5 Main contactor. 6 DHW electronic PCB 7 Anti-electrolysis DHW hoses. 8 DHW resistance. 9 Temperature sensor location. 10 Insulated tank 50L. 11 Automatic purge. 12 Heating expansion vessel 6L. 13 DHW expansion vessel 2L. 14 Circulation pump. 15 Insulated heating header tank. 16 Heating resistance. 17 Heating 3 bar relief valve. 18 Heating safety thermal limit switch. 19 Heating flow detector. 20 pressure gauge. 21 Main electronic PCB. 22 Controls card.











3
1 Controls card. 2 ON / OFF switch. 3 Heating safety thermal limit switch. 4 Main electronic PCB. 5 Heating resistance. 6 Circulation pump. 7 Insulated heating header tank. 8 Automatic purge. 9 Heating expansion vessel 6L. 10 Drip pan. 11 Heating flow detector. 12 Heating 3 bar relief valve. 13 Main contactor. 14 Connection block. 15 Pressure gauge.
3.4 SAFETY DEVICES
Safe operation under various conditions is ensured by the following controls:
o Water pressure switch that monitors water
pressure and flow in the heating system and will prevent operation in case of a blockage, if the system pressure is too low, the pump is not operating or the system flow rate is below the permitted level; Installation of a system by-pass may be necessary (see 7.3 HEATING SYSTEM FLOW SWITCH – E3 ERROR & SYSTEM BY-PASS REQUIREMENTS).
o Hot water high limit safety thermostat will prevent
operation if the temperature exceeds 80ºC. It requires re-setting manually.
o Heating system high limit safety thermostat will
prevent operation if the temperature exceeds 100ºC. It requires re-setting manually.
o Hot water pressure relief valve will discharge to
relieve excess pressure at 7 bar. (Requires piping to a safe external discharge point.)
o Heating system pressure relief valve will discharge
to relieve excess pressure at 3 bar. (Requires piping to a safe external discharge point.)
4 INSTALLATION
IMPORTANT PRE- INSTALLATION POINTS
In order to ensure the successful installation
and operation of your Gabarron boiler please consider the following points before commencing.
SITING THE BOILER
WARNING Wall and fixings must be suitable to
support the total weight; CMX boiler when full is
120 kg, CM boiler when full is 50 kg. Allow sufficient clearance and access for operating, maintenance and repair work. Boiler must be protected from any water, moisture, or dampness. Installation must comply with regulations for electrics if installed in bathrooms. Boiler electrical protection rating is IP20/IP2X. This boiler is not designed to be installed in the open air. The boiler must be installed in the upright position.
ELECTRICAL POWER SUPPLY & WIRING
WARNING Before carrying out any work inside
t
he boiler and obtaining access to terminals, all
supply circuits must be disconnected.
WARNING Earth the appliance. If the appliance is
n
ot earthed, it may hold voltage if a defect occurs.
Competency for electrical installation is required. The power supply must meet the capacity for the heat output required plus all other appliance that may be supplied. The cable, MCB and RCD must be of sufficient capacity to carry the required load.
Boiler is supplied set at maximum output and must be
adjusted to suit the incoming supply before being switched on. (See 5.1 LIMITING BOILER MAXIMUM OUTPUT).
HEATING SYSTEM & CONTROLS
Any existing system must be suitable for sealed system operation at up to 3bar pressure and may require flushing/cleansing. A combi filling loop, isolation valves and drain point are required. A time clock/room thermostat should be installed.(Necessary to activate automatic power modulation)






  


i
i
4
System by-pass will be required for fully TRV systems. The correct heat requirement for the dwelling should be calculated.
HOT WATER SYSTEM
Competency to install unvented hot water system is required. Any existing system and controls (e.g. shower) must be suitable to operate at mains water pressure. The incoming water main pressure and flow must be sufficient for requirements. If incoming mains pressure is excessive (above 5 bar) a pressure reducing valve is required. The boiler safety valves require piping to a safe discharge point. In hard water areas it is advisable to take normal precautions against lime scale formation.
4.1 GENERAL REQUIREMENTS
The installation should be carried out by a person certified as competent for the installation of unvented hot water systems in accordance with current building regulations.
Installation should also be in accordance with the relevant British Standards and Codes of Practice including the following:
BS 5449 Forced circulation hot water systems BS 5546 Installation of hot water supplies for domestic
purposes BS 6700 Design, installation, testing and maintenance of
services supplying water BS7074 Application, selection and installation of expansion
vessels and ancillary equipment for sealed water
systems. BS 7593 Code of Practice for treatment of water in heating
systems BS 7671 Requirements for electrical installations, IEE Wiring
Regulations
4.2 UNPACKING & CONTENTS
- Wall bracket with template.
- Boiler.
- Documentation.
- Bag with parts and fittings.
- Wall bracket with template.
- Boiler.
- Documentation.
- Bag with parts and fittings.
C C
1/2
C
5
Dispose of the cardboard packaging at a cardboard recycling site. Observe national regulations.
4.3 LOCATION
WARNING INSTALL UPRIGHT ON A WALL SUITABLE TO SUPPORT THE TOTAL WEIGHT OF
THE BOILER WHEN FULL OF WATER – 120 kg.
The location should be clean and dry with no presence of gases, explosives or flammable objects.
It is not suitable for installation outside and should be protected from moisture and frost.
The boiler must be sited so that the boiler and controls are not accessible to any persons whilst using a bath or shower and there should be no possibility of water dripping or splashing onto the boiler or controls.
Electrical safety regulations for clearances must be followed if installed in a bathroom or shower area.
The boiler has an electric protection rating of IP20/IP2X.
Where possible the boiler should be sited to minimize the pipe distance to hot water outlets.
The power supply cable should be carefully routed and secured and provision made for a suitable isolation switch and MCB/RCD.
4.4 DIMENSIONS & CONNECTIONS
i
200
80
245
285
355
435
535
8
3
450
3
160
200
30
80
350
300
760
265
DIMENSIONS & CONNECTION
A BBCFF
D
D
E
E
A cold water input 1/2"
B safety valve drain
C
DHW
. outlet 1/2"
D heating return 3/4"
E heating flow 3/4"
F electrical connection
830
30
6
4.5 CLEARANCES
A: 50 mm B: 10 mm C: 200 mm
The clearances around the boiler as shown above must be observed for correct operation.
A minimum of 200mm clearance must be maintained underneath the boiler to allow replacement of the heating elements if required. A minimum of 500 mm clearance must be maintained in front of the boiler to enable easy access for servicing. Ensure sufficient space to make all water connections including the outlet pipes for the heating and hot water safety valves which should be routed to a suitable discharge point.
4.6 MOUNTING BRACKET
Mark the holes positions using the wall bracket as a template per the diagram.
Fit bracket securely onto wall before lifting appliance into position. Drill the holes and fit the bracket ensuring it is level using suitable high strength screws, with appropriate plugs or fixings, minimum M10 size.
C C
C
7
Filling loop
Always use assistance if required. Wear suitable cut
resistant gloves when handling the appliance.
Ensure safe lifting techniques are used. Do not lift the appliance by attached pipe-work or components.
When lifting the boiler ensure that the fixing elements and the wall have a sufficient load-bearing capacity. Check the quality of the wall.
4.7 WATER CONNECTIONS
CAUTION The hydraulic connections must be carried out respecting the flow and return marked on the
boiler.
CAUTION When tightening or loosening threaded connections, always use suitable tools as open-end
spanners. Do not use pipe wrenches, extensions or unsuitable tools that may cause damage or water leaks.
Install purges in the radiators and high points of the installation.
Filling Loop
A combi filling loop is required for filling of the heating system and replacing water lost during servicing or bleeding and should be installed close to the boiler. The loop should be as shown in the diagram and comply with current Water Supply Regulations. The temporary connection should be removed after filling and the valves sealed with suitable caps.
Heating Flow & Return
These connections are ¾ “ for connection to 22mm pipe using the tails provided. Service valves should be installed at this position to allow the boiler to be isolated for maintenance without the need to drain the entire system. The valves should be of sufficiently large bore so not to restrict the heating circulation.
The boiler is not suitable for single pipe heating systems, only a twin-pipe heating system should be used.
Drain Point
A drain point should be fitted at the lowest point of the system. It is not acceptable to drain the boiler through the safety valve as debris and deposits will prevent correct operation of the valve.
Heating System By-pass
The heating water flow switch requires a minimum flow rate through the boiler of 7 L per minute for correct operation. Systems fitted throughout with Thermostatic Radiator Valves will require provision of a System By-pass to maintain sufficient flow should all the valves be closed. (see 7.3 HEATING SYSTEM FLOW SWITCH – E3 ERROR & SYSTEM BY-PASS REQUIREMENTS).
System Expansion
An integral 6 L expansion vessel provides for expansion of the heated system water under normal conditions however a system with larger volumes of water may require extra expansion capacity to be provided.
i
Mains water
supply
Heating
system
valve valve
8
Cold Water Inlet
A ½” connection is provided for connection to 15mm pipe. An integral isolating valve provides control of the incoming water supply. An internal non-return valve prevents possible back-flow should the water main fail.
CAUTION: If the incoming water pressure exceeds 5 bar it is necessary to install a Pressure Reducing Valve set at 2.5 bar on the water main into the dwelling. This will protect the boiler and prevent constant opening of the 7 bar relief valve.
Hot Water Outlet
A ½“ connection is provided for connection to 15mm pipe. To ensure economic operation the pipe run between the boiler and taps should be in not more than15 mm dia. pipe and the distance as short as possible. The pipe-work should be insulated to reduce heat loss.
Safety Valve Connections
The 7 bar pressure relief valve on the domestic hot water store may discharge boiling water and should be piped to a safe but visible drain point e.g. a gulley where any discharge will not cause damage or injury.
CAUTION : A tundish should be incorporated close to the appliance where any discharge will be visible but not hazardous. The pipe-work should have a continuous fall to the drain and should be of minimum 22mm dia. if more than one discharge is connected to it.
The 3 bar pressure relief on the sealed heating system may discharge boiling water and should be piped with a continuous fall to a safe yet visible point where any discharge cannot cause damage or injury.
4.8 DHW DISCHARGE PIPE-WORK
The CMX electric combi boiler range incorporates a 50 L unvented hot water storage vessel and an internal, temperature and pressure relief valve.
CAUTION: The discharge pipe-work from the T&P relief valve must be installed by a competent person and in accordance with Part G3 of The Building Regulations.
The position of the tundish shall be visible to the occupants and shall be positioned away from any
electrical device.
The pipe size and distance from the T&P valve to the tundish and from the tundish to termination point
must comply with the requirements of Part G3 of the Building Regulations
The discharge pipe must fall continuously from the valve outlets and be un-obstructed
The discharge pipe material must be capable of conveying water / steam at 100ºC
The final discharge point must be in a safe and visible position
Table 1 – Sizing of copper discharge pipe “D2” for common temperature relief valve outlet sizes
*Refer to paragraphs 3.5, 3.9, and 3.9(a) of Approved Document G
Valve
Outlet Size
Minimum size if
discharge pipe
D1*
Minimum size of
discharge pipe
D2* from tundish
Maximum resistance allowed,
expressed as length of straight
pipe (i.e. no elbows or bends)
Resistance created by
each elbow or bend
G1/2
15mm
22mm
28mm 35mm
Up to 9m
Up to 18m Up to 27m
0.8m
1.0m
1.4m
G3/4 22mm
28mm
35mm 42mm
Up to 9m
Up to 18m Up to 27m
1.0m
1.4m
1.7m
G1 28mm
35mm
42mm 54mm
Up to 9m
Up to 18m Up to 27m
1.4m
1.7m
2.3m
9
Typical Discharge Pipe terminations (source: Building Regulation G3) :
All installations must be fitted in accordance with all local regulations in force at that time. Failure to comply with these regulations will invalidate the manufacturers’ warranty.
4.9 PUMP DUTY
The boiler is fitted with a UPS 25-40 3-speed circulating pump. The graph shows the flow rate available for the system after allowance for the loss through the boiler.
4.10 ELECTRICAL CONNECTIONS
Connection to Mains Supply
The CM15 and CMX15 boilers must be installed in premises having a system impedance of not more than 0.25 + j0.25Ω.
The CM15 and CMX15 boilers comply with the technical requirements of BS EN 61000-3-3.
The CM15 and CMX15 boilers must be installed in premises having a service capacity ≥100 A per phase.
Complete all the pipe-work before connecting the boiler to the electricity supply.
Any re-installation must be performed by qualified electricians.
Ensure that the mains voltage available coincides with that shown on the rating label.
WARNING IMPORTANT: CHECK THAT THE TOTAL POWER SUPPLY TO THE BUILDING HAS SUFFICIENT LOAD CAPACITY TO SUPPLY THE BOILER AT THE HEAT OUTPUT REQUIRED IN ADDITION TO ALL OTHER APPLIANCES THAT MAY BE SUPPLIED.
P
UPS 25-40
(kPa)
40
4
3
2
1
0
0 20 40 60
(l/min)
0
0
0.5
1
0.5 1.0 1.5 2.0 2.5 3.0
3.5
4.0 4.5 Q(m /h)
3
H(m)
20
0
10
WARNING T
H
E SUPPLY CABLE TO THE BOILER SHOULD BE OF SUFFICIENT SIZE TO CARRY THE LOAD CAPACITY REQUIRED. IT SHOULD BE WIRED THROUGH A LINKED ISOLATOR SWITCH WITH MINIMUM CONTACT GAPS OF 3mm IN EVERY POLE AND PROTECTED BY A SUITABLY RATED CIRCUIT BREAKER MCB/RCD Install the necessary electrical protections as indicated in the current regulations. In the event of these regulations not being complied with, the manufacturer will not be liable for any bodily injury or material damage that may occur.
WARNING IT IS ESSENTIAL THAT THE BOILER IS PROPERLY EARTHED and the wiring tested to
current IEE regulations.
Electrical Supply Sizing
The following table shows the specification for a boiler installed on single phase supply.
Connection to Boiler
WARNING Touching live connections can cause serious personal injury.
Before establishing a mains connection switch off the power supply. Secure the power supply against being switched on again. Mains connection terminals remain live even if the on/off switch is turned off.
The boiler is delivered ready for operation on 3x400V three phase supply. For operation on 230V single phase the bridging connection supplied must be connected across the terminals of the connection block as shown.
The terminal connection block is at the rear right-han
d side of the boiler and is accessed after removing the boiler front panel . The supply cable should be safely routed to this point through the cable entry point on the right hand bottom of the boiler.
CAUTION: A mains voltage at the incorrect plug terminal can destroy the electronics.
Make sure the connectin cables are securely fastened to the plug terminals.
Wiring External Controls
It is recommended that the boiler is controlled by an external control such as a time clock or room thermostat or a combined programmable room thermostat such as the Elnur model CTP-10.
CAUTION: The switching connection of this control should be VOLT FREE and connected to the terminals
indicated ‘TA’ on the PCB. The factory fitted link across these terminals must be removed.
The boiler’s automatic power modulation feature is activated by the initial interruption of this switching link.







i
Rated output of boiler
4kW 5kW 6kW 7kW 8kW 9kW 10kW 11kW 12kW 13kW 15kW
Supply current
17.4A 21.7A 26.1A 30.4A 34.8A 39.1A 43.5A 47.8A 52.2A 56.5A 65.2A
MCB rating
20A 25A 32A 32A 40A 50A 50A 63A 63A 63A 80A
Minimum cable size
2.5mm 4mm 4mm 6mm 6mm 10mm 10mm 10mm 16mm 16mm 16mm
5 COMISSIONING
5.1 LIMITING BOILER MAXIMUM OUTPUT
The boiler is
supplied for operati
maximum to match the heat load required.
WARNING
: ON INSTALLATIONS WHERE THE INCOMING POWER SUPPLY IS NOT CAPABLE OF
MAXIMUM LOAD THE BOILER CONTROL MUST BE RE
SWITCHING ON.
As the output for Domestic Hot Water will also be limited to the same level it is recommended to adjust to the
highest output possible so as to maintain the best hot water performance.
The boiler will not exceed this pre
demand and ensuring economic operation.
Adjustment is made by selecting the desired position of switches numbered 1 to 4 in a block situated on the main
PCB. The PCB is located after isolating from the mains,
The switches are positioned upside down as shown below.
With a small screwdriver move the switches to correspond to the positions shown in the tables for the required
output, referring to a single or three phase supply.
Correct configuration for the
selected output can be checked on the boiler display panel f
shown in 7.
4 CHECKING RATED HEAT OUTPUT
CAUTION: It is
essential
i
Location of electronic card.
11
on on maximum heat output of 15
kW. The output can be rated below this
-
CONFIGURED TO LIMIT THE OUTPUT BEFORE
-set maximum but will still modulate
in heating mode up to this level, adapting to
removing the case and tilting the control panel.
.
to confirm the power output with the use of a clamp meter.
ollowing the procedure
ATTENTION!
The switches are
upside down.
* The standard configuration of the boiler only allows a maximum of 12kW when connected SINGLE
230V – 50Hz.
5.2 HEATING SYSTEM INITIAL FILLING
Ensure both flow and return isolation valves are open. Identify the boiler automatic air release valve at the top right
hand side of boiler and loosen the cap. Close any manual air vents fitted on the
Be careful n
ot to splash any of the electrical components.
Connect the filling loop and fill slowly until the pressure gauge indicates between 1 and 1.5 bar.
Proceed to vent all the manual release valves until all air is purged from the system. It
through the filling loop during this operation.
5.3 PUMP CHECKING & VENTING
It is important the pump is properly vented and spinning freely.
Connection THREE-PHASE 3x400V~+N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
1
234
O
N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
1
234
O
N
123
4
O
N
POSITION OF
THE SWITCHES
MAXIMUM OUTPUT
LIMITED TO :
15kW
13kW
12kW
11kW
10kW
9kW
8kW
7kW
6kW
5kW
4kW
3kW
2kW
LIMITATION OF OUTPUT ON MODELS CM15 & CMX15
12
system.
The boiler must be disconnected from the mains.
Be careful not to splash any of
Carefully unscrew the cap in the pump centre whilst
protecting the electrics from any water that is released.
Using a suitable screwdriver rotate the exposed spindle and
replace the cap.
NOTE: If excess air remains in the system
insufficient pressure or flow rate the boiler will fail to
operate and display fault E3.
Connection SINGLE PHASE 230V~
123
4
O
N
1
234
O
N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
1
2
3
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
123
4
O
N
21.7A 21.7A 21.7A
13.0A 21.7A 21.7A
21.7A 21.7A 8.7A
13.0A 13.0A 21.7A
21.7A 8.7A 13.0A
13.0A 13.0A 13.0A
13.0A 8.7A 13.0A
8.7A 13.0A 8.7A
8.7A 8.7A 8.7A
- 13.0A 8.7A
8.7A 8.7A -
- - 13.0A
8.7A - -
POSITION OF
THE SWITCHES S
-PHASE
will be necessary to top-up
the electrical components.
or there is
1
O
1
O
1
O
1
O
1
O
1
O
1
O
1
O
1
O
1
O
1
O
1
O
1
O
MAXIMUM OUTPUT
LIMITED TO :
15kW*
65.2A*
13kW*
56.5A*
12kW
52.2A
11kW
47.8A
10kW
43.5A
9kW
39.1A
8kW
34.8A
7kW
30.4A
6kW
26.1A
5kW
21.7A
4kW
17.4A
3kW
13.0A
2kW
8.7A
5.4 HEATING SYSTEM FLUSHING
CAUTION:
Flush the heating installation thoroughly prior to installation.
The heating system should be flushed in accordance with BS7593 & BS5449 which will remove any debris or
contaminants detrimental to the operation and life of the boiler. Any cleanser or additives used should comply with
current standards and the
manufactur
NOTE: IT IS IMPORTANT NOT TO USE THE BOILER PRESSURE RELIEF VALVE TO DRAIN OR FLUSH THE
SYSTEM AS TRAPPED DEBRIS WILL CAUSE INCORRECT OPERATION. A PURPOSE PROVIDED DRAIN POINT
SHOULD BE USED.
5.5 FILLING DOMESTIC HOT W
Open the mains water inlet valve underneath the boiler. Turn on all the hot water system taps and thoroughly flush
allowing water to flow until no air is present. This will automatically vent the integral hot water store of any air.
6 OPERATING THE
BOILER
6.1 INITIAL SWITCHING ON
CAUTION:
THE MAXIMUM HEAT OUTPUT MUST BE ADJUSTED BEFORE SWITCHING ON.
BOILER SHOULD NEVER BE SWITCHED ON WITH THE HEATING SYSTEM OR DHW
TANK EMPTY. DAMAGE COULD OCCUR.
6.2 CONTROL PANEL DESCRIPTION
MODELS CMX15
Increases
DHW.
temperature
Power ON/OFF
DHW
.
key
Decreases
DHW.
temperature
Red dot shows
DHW
. heating
elements on duty
13
er’s instructions carefully followed.
ATER
When the boiler is first connected it
general self-
check and if a fault is detected it will be indicated
on the display.
Turn on the boiler with the on/off switch located at the back
of the boiler as shown.
Mains connection terminals remain live even if the on/off
switch is turned off.
i
Increases
heating water
temperature
DHW
.
temperature and
other messages
Heating water
temp. and other
messages
Red dot shows
heating heating
elements on duty
Decreases
heating water
temperature
THE
will perform a
Keyboard lock
indicator
Keyboard power ON/ OFF
block ON/OFF
Power ON/OFF heating
key
MODELS CM15
Push the
button to start the boiler up. The same button will turn the boiler off when pushed again.
If the heating or DHW
function are not selected
the relevant screen will not
display a value but just a
red dot.
6.3 DOMESTIC HOT WATER OPERATION
To select the DHW
function push the press the
display to just a red dot.
When the DHW
mode is selected the display will show the actual temperature in the
boiler will always give priority to
reached.
If heat is demanded by the
DHW
temperature display.
This light will go out when the desired temperature is
The setting of the DHW
temperature can be modified by pushing
using the same buttons to adjust the setting that flashes on the display. The modified setting will be stored
automatically after a few
seconds, or instantly if we push the
The DHW
setting can be varied between 20 and 55°C.
The DHW
has priority over the central heating operation and so the outputs are never added together.
i
Heating water
temp. and other
messages
Red dot shows
heating heating
elements on duty
14
button.
Pushing again will switch the function off and return
DHW production over centr
al heating until the selected
and the elements are energized a small red indicator is displayed to the right of the
reached.
either the
button or the
button.
Increases
heating water
temperature
Power ON/OFF heating
key
Decreases
heating water
temperature
DHW accumulation tank. The
DHW temperature is
button and
Keyboard lock
indicator
On / Off button
Block / Unblock
Water storage at maximum temperature will provide the best protection against the possible formation of
legionella bacteria.
6.4 CENTRAL HEATING OPERATION
First ensure that any external controls such as room thermostat or time clock are demanding heat.
To select the heating function, push the
just a red dot.
When the heating mode is selected the display will show the temperature of the heating water
We can modify the setting o
f the temperature of the water by pushing either the
the button and
using the same buttons to adjust the value
The modified setting will be stored af
The heating setting can be varied between 8ºC and 85°C.
value. If we select this value, the heating will function in anti
If the setting is higher than the actual temperature of the he
will connect and a small red indicator of the consumption of heating resistances will light up.
6.5 ANTI-FREEZE MODE
(Frost Protection)
It is possible to select an anti-
freeze mode for frost protection during periods of inactivity. The power supply to the
boiler must be maintained.
By attempting to set a central heating temperature below the 8
appear on the display. By selecting this value the heating will only work in anti
temperature falls to 7ºC
the heating will activate automatically.
6.6 HEATING MODULATION FEATURE
The advanced control board on the boi
save energy.
This function works by the boiler learning and anticipating the time taken to reach the temperature level demanded
by the external thermostatic control. The power
consumption on warmer days or when another heat source is present.
An external ‘volt free’ control must be fitted across the terminals marked TA on the PCB and the bridge removed
for this function to be activated.
6.7 LOCKING THE CONTROL PANEL
It is possible to lock the buttons of the control panel to prevent any adjustment.
By keeping the
button pressed down for a few seconds, the padlock will light up
The control buttons of the boiler
remain the same and the boiler will function normally.
To unlock the buttons, press the same button down for a few seconds until the padlock light goes off. If the boiler
disconnected from the mains or there is a failure in the houses electricity supply, the buttons will also be unlocked.
6.8 PUMP ANTI-
SEIZE FUNCTION
The advanced boiler control will automatically energize the pump for 10 seconds each month to protect
seizing during long periods of inactivity. The power supply must be maintained for this function to operate.
i
15
button.
Pushing again will switch the function off and return display to
that flashes on the display.
ter a few seconds or instantly if we push the
The symbol H appears after the 85 value or before the 8
-freeze mode.
ating water and the
DHW
ºC
value or above the 85
-
freeze mode i.e. if the boiler
ler will automatically modulate the heating output to the demand required to
output is automatically adjusted therefore reducing power
will be locked and no button will respond when pressed. Internally all the settings
.
button or
button.
is not connected, the heating
ºC value the symbol H will
.
is
it from
16
7 TROUBLESHOOTING
7.1 POSSIBLE FAULTS & SOLUTIONS
Problem
Possible cause
Solution
Boiler will not start
power to
boiler.
Check in
coming power supply.
No power
. Check boiler control switch is on.
(See Section 6.1.)
H
eating
overheat. Switch tripped.
Locate switch and reset. (
See
Section 7.2)
DHW
Overheat
switch tripped.
Locate switch and reset. (See
Section 7.2)
DHW
tank empty.
Open a hot water tap until the
water flows.
Fault
E1 displayed
Heating flow temperature sensor
Heating water out temperature
probe defective.
Contact Technical Service
Fault E2 displayed
Heating return temperature sensor
Heating water
return temperature
probe defective.
Contact Technical Service
Fault E3 displayed
Heating system water flow switch
Low heating system pressure.
Check for leaks.
Refill heating system to 1.5 bar.
Fault E3 continued
Pump not turning.
Check rotating freely (sect
5
.3)
Replace pump if necessary.
Fault E3 continued
Air in system.
Purge thoroughly.
Check automatic air valve open. Vent pump (sect 5.3)
Fault E3 continued
System resistance too high or
blockage.
Check pump speed 3.
Check pump duty (sect 4.9) Open all radiator valves. Install system by-pass.
Fault E5 displayed
Error in configuration for maximum
heat output.
Check correct configuration (
See
Section 5.1)
Fault
E6 displayed
DHW temperature sensor
Defective DHW tank
te
mperature
sensor.
Check connections. Replace sensor
if necessary.
Heating system water discharging from 3 bar safety valve
Excessive heating system pressure.
Check filling loop not passing and
remove. Check expansion vessel is charged with air. Check system expansion volume.
Domestic water discharging from 7 bar valve
Excessive pressure in domestic
water system.
Check incoming mains pressure is
below 5 bar. Fit pressure reducing valve. Check 2L expansion vessel charged with air.
The buttons do not respond
Control panel blocked
See Section 10.2 BLOCKING THE
CONTROLS
Low heating temperature
S
etting
s too
low. Check temperatura & output
selected.
Failure of heating elements
Check and replace.
Heat requirements miscalculated.
Re-
calculate &
configure.
If the suggested action fails to resolve a problem please contact ELNUR technical service for further advice.
7.2 OVERHEAT LOCK-
OUT & RE
Central heating overheat.
If the boiler detects a overheat condition
safety thermal limit switch will operate and switch the boiler off disabling all functions including DHW production.
The cause of the overheat should be investigated.
The safety limit switch
is on the left underside of the boiler and will require re
procedure shown:
Unscrew & remove the black cap and push the
small pin behind it until you hear a click.
The limiter will not re-
set until the
temperature in t
he heating header drops below
100°C or 80°C if the boiler is adapted for
radiant floor heating.
Domestic Hot Water overheat.
As with the heating circuit a second thermal limit switch, situated on the right underside of the boiler, will operate if
a ov
erheat condition (80ºC) is detected in the DHW circuit and switch the boiler off disabling all functions including
central heating.
The cause should be investigated and the above procedure followed to re
7.3 HEATING SYSTEM FLOW
SWITCH
If the error E3 appears on the display, the flow switch has detected insufficient water flow in the heating circuit and
heat production is disabled to protect the boiler from overheating.
The possible caus
es for this condition are:
-
Insufficient water pressure in the heating system requiring re
-
Pump not circulating or seized. Check as shown (Sect
-
Blockage in heating circuit from debris or a foreign object in the boiler or
-
Insufficient flow rate caused by restrictions such as insufficient size
with restricted bore.
-
Closed radiator valves (Thermostatic). In this situation it is essential the required minimum flow rate o
minute is maintained through the boiler during all conditions. It may be sufficient to maintain one radiator with
permanently open valves however the guidance under current Building Regulations relating to the conservation of
energy recommends th
e fitting of an automatic by
ensure that the appropriate minimum flow rate is maintained through the boiler, at all other times it is closed thus
preventing unnecessary and wasteful circulatio
7.4 CHECKING RATED HEAT OUTPUT
It is possible to check the actual heat power output configuration that is set on the boiler and also the
modulated operating output at that moment.
Press the
button for three seconds.
The heating display will show
On pushing
button the display will show
according to the tables (see 5.
1)
On pushing
button again the display will show
that moment.
i
17
-SETTING
of 100ºC (80ºC if adapted floor heating
) in the central heating circuit a
-
setting manually by following the
-
set the DHW limit switch.
– E3 ERROR & SYSTEM BY-
PASS REQUIREMENTS
-filling to 1.5bar
5.3) pipe-
work
pipe-work
, too many bends or isolation valves
-
pass valve. This type of valve modulates open when necessary to
n through the bypass and the boiler.
followed by the temperature value of the return probe of the heating circuit.
followed by the value of the limited maximum output
.
followed by the actual modulated output power at
.
f 7 L per
18
8 MAIN COMPONENTS
9 MAINTENANCE & CARE
Gabarron electric boilers do not require any special maintenance for a prolonged and trouble-free life however the following points should be observed:
-Check and maintain the heating system pressure between 1 & 1.5 bar when cold. Frequent re-filling of the system could cause scaling and corrosion and should be avoided. Regular pressure loss could indicate a leak and should be investigated promptly.
CAUTION – Under no circumstances should the boiler be switched on when the system is dry..
CAUTION - Never start the boiler when the DHW tank is empty; to fill it for the first time open a hot
water tap and wait until water comes out of it.
-Keep the ventilation openings on the boiler clear to ensure correct operation and protect from overheating. Do not place or store objects on the boiler.
-Protect against freezing by ensuring power is maintained to the boiler at all times unless the water supply is interrupted or the heating system is empty. In dwellings frequently un-occupied or at risk of freezing an appropriate anti-freeze can be added to the heating system at a concentration of not more than 30% by volume. Otherwise it is recommended to isolate the power and completely drain the heating and hot water systems.
- The outer case can be cleaned with a damp cloth having first isolated the boiler from the mains. Do not use solvents or abrasive cleaners.
10 ENVIRONMENTAL INFORMATION
Gabarron boilers are manufactured within a certified environmental management system. From the design stage, all the production phases are performed taking into account the most rigorous environmental requirements. For example, the selection of materials involves guaranteeing their biodegradability, re-use and recycling.
When this boiler’s long, useful life is over; it must be handed in to an electrical equipment collection point for proper recycling. By ensuring that this product is correctly disposed of, you will help to avoid any possible negative effects on the environment and public health that could occur if this product is not properly handled. To obtain more detailed information on the recycling of this product, contact your local authority, your waste disposal service or the shop where you purchased the product. These regulations only apply in EU member countries.
Heating expansion vessel 6L
ref. 60091510
DHW. expansion vessel 2L ref. 60091515 DHW. expansion vessel hose CMX ref.60100020 50 L DHW. insulated tank ref. 60100072 Insulated heating header tank ref. 60101700 Circulation pump 25-40 (130) ref. 60190070 Circulation pump 25-60 (130) ref. 60190071 Main electronic card with support ref. 60101310 DHW. electronic card with support ref. 60101320 Controls card CM15 & CM18 ref. 60100510 Controls card CMX15 & CMX18 ref. 60100540 Temperature probe, white connector ref. 60100580 Temperature probe, black connector ref. 60100590 15 kW heating resistance & joint 140 ref. 60100750
18 kW heating resis
tance & joint 140
ref. 60100760
15 kW DHW. resistance & joint ref. 60100700 DHW. resistance joint ref. 60100068 ¾” heating flow detector ref. 60100800 0-4 bar pressure gauge ref. 60100820 100°C thermal limiter ref. 60091140 80°C thermal limiter ref. 60091150 Automatic purge ref. 60091280 3 bar central heating relief valve ref. 60100840 7 bar DHW. relief valve ref. 60100850 DHW. retention valve ref. 60100830 ½” filling / shut off valve ref. 60091160 Adhesive controls cover 220x60 ref. 60100502 Adhesive controls cover 140x50 ref. 60100508
19
11 TECHNICAL DATA
CMX15 CM15
Frequency
Hz 50 50
Connection 3x400V+N~
Output limited to
15kW
; Maximum intensity
A
21.7 21.7
Output limited to
13kW
; Maximum intensity
A
21.7 21.7
Output limited to
12kW
; Maximum intensity
A
21.7 21.7
Output limited to
11kW
; Maximum intensity
A
21.7 21.7
Output limited to
10kW
; Maximum intensity
A
21.7 21.7
Output limited to
9kW
; Maximum intensity
A
13.0 13.0
Output limited to
8kW
; Maximum intensity
A
13.0 13.0
Output limited to
7kW
; Maximum intensity
A
13.0 13.0
Output limited to
6kW
; Maximum intensity
A
8.7 8.7
Output limited to
5kW;
Maximum intensity
A
13.0 13.0
Output limited to
4kW
; Maximum intensity
A
8.7 8.7
Output limited to
3kW
; Maximum intensity
A
13.0 13.0
Connection 230V~ single phase
1
1
Nominal maximum intensity
15kW
A
65.2 65.2
Maximum converted intensity at
13kW
A
56.5 56.5
Maximum converted intensity at
12kW
A
52.2 52.2
Maximum converted intensity at
11kW
A
47.8 47.8
Maximum converted intensity at
10kW
A
43.5 43.5
Maximum converted intensity at
9kW A 39.1 39.1
Maximum converted intensity at
8kW A 34.8 34.8
Maximum converted intensity at
7kW A 30.4 30.4
Maximum converted intensity at
6kW A 26.1 26.1
Maximum converted intensity at
5kW A 21.7 21.7
Maximum converted intensity at
4kW A 17.4 17.4
Maximum converted intensity at
3kW A 13.0 13.0
DHW
available time with
15kW
min 5’49” -
DHW
available time with
13kW
min 6’42” -
DHW
available time with
12kW
min 7’16” -
DHW
available time with
11kW
min 7’56” -
DHW
available time with
10kW
min 8’43” -
DHW
available time with
9kW min 9’41” -
DHW
available time with
8kW min 10’54”
-
DHW
available time with
7kW min 12’27”
-
DHW
available time with
6kW min 14’32”
-
DHW
available time with
5kW min 17’26”
-
DHW
available time with
4kW min 21’48”
-
DHW
available time with
3kW min 29’04”
-
DHW
available time with
2kW min 43’36”
-
Weight
kg 70 32
Insulated steel heater header
50 L
stainless steel insulated
DHW
store No CFC
-
Stainless steel plated
resistance elements INCOLOY800
DHW
-
Stainless steel plated resistance elements INCOLOY800
Heating
6 litre expansion vessel
DHW
2 litre expansion vessel
-
Electronic regulation of heater modulation
Electronic regulation
DHW
-
Digital display
0-4 bar pressure gauge
Accelerator pump
Automatic purge
TRIACS silent power switches
Heating flow detector
100°C heating temperature limiter
80°C
DHW
temperature limiter
-
3 bar central
heating relief valve
7 bar DHW
relief valve
-
DHW
retention valve
-
Ambient thermostat intake
Anti-electrolysis
DHW
hoses.
-
included 1 using connecting bridge included
20
12 WIRING DIAGRAMS
21
EC DECLARATION OF
Manufacturer’s name:
Manufacturer’s address:
Declares, that the product:
Product:
Trade Mark:
Models:
has
been manufactured to the technical specifications of the product and conforms in all
respects to the relevant standards and regulations in force and especially to :
Safety:
EN 60335
EN 60335
EN 50106:2008
EMC:
EN 55014
EN 55014
EN 61000
EN 61000
Additional information:
The product
herewith complies with the requirements of the Low Voltage Directive 2006/95/EC and
the EMC Directive 2004/108/EEC and carries the CE mark.
Any use not according to the instructions and/or any change to the appliance will invalidate this
declaration of conformity.
Algete, 1 de Febrero de 2013
Place, date
22
CONFORMITY
According to ISO/CEI guide 22 and EN 45014
ELNUR S.A.
ELNUR S.A. Villa Esther, 11; Pol. Ind. El Nogal 28110 Algete, Madrid
D
igital Modulating Electric Boiler
GABARRÓN
CM15; CM18; CMX15; CMX18; CMX15P; CMX18P
-1:2010
-2-35:2002+A1:2007+A2:2011
-1:2006+A1:2009+A2:2011
-2:1997+A1:2001+A2:2008
-3-2:2006+A1:2009+A2:2009
-3-3:2008
Director
A. Fernández
-Gerente
Supplier
ELNUR UK Ltd. Telephone +44(0)1942 670119 www.elnur.co.uk info@elnur.co.uk
Manufactured by:
ELNUR s.a. Travesía de Villa Esther, 11 28110, ALGETE – Madrid Telephone +34 916281440
As a part of the policy of continuous product improvement
The symbol on the product or in its packaging indicates that this product may not be treated as
household waste. Instead it shall be handed over to the
electrical and electronic equipment. By ensuring this product is disposed of correctly, you will help
prevent potential negative consequences for the environment and human health, which could otherwise
be c
aused by inappropriate waste handling of this product. For more detailed information about recycling
of this product, please contact your local city office, your household waste disposal service or the shop
where you purchased the product. These instructio
23
,
Elnur s.a reserves the right to alter specifications without notice.
applicable collection point for the recycling of
ns are only valid in the EU member states.
@2013
Cod. 60100005 rev.6
Loading...