13.8Vdc Switch Mode Power Supply
GEN2-08-y
for 8Ah Battery and up to 1.0A* Continuous Load Current
GEN2-18-y#
for 18Ah Battery and up to 1.5A* Continuous Load Current
F
EATURES
High efficiency cost effective power supply suitable for use in systems designed to comply with
PD6662:2010 and EN50131-6:2008 Grade 2 and Environmental Class II requiring 8Ah or 18Ah standby
battery capacity. Two independent output signals are provided for loss of mains fault (EPS**), and
general fault (including APS** fault). Self-diagnostics can detect blown output and battery fuses and
low battery voltage (APS fault). The PSU incorporates a battery management system comprising low
battery voltage detection and deep discharge protection to ensure that the battery is not permanently
damaged through excessive discharge. A brownout filter ensures that short mains voltage dips do not
create a false loss of mains alarm. Two LEDs assist with quick and easy installation by showing
presence of mains, correct battery charging and a fault condition. Comprehensive protection is built-in
as standard including mains transient filtering, electronic output overload protection and fuses on the
load and battery outputs.
• PD6662:2010 and EN50131-6:2008
Type A, Security Grade 2
Environmental Class II Compliant
• Low quiescent battery monitoring current during standby operation
• Fault signals for loss of mains, power supply fault, and battery low voltage warning
• Battery Deep Discharge Protection
• Protection against reverse battery connection
• LED for comprehensive diagnostics
• Thermal protection of power circuitry
• Mains transient suppression and brown-out filter
• Fully enclosed lid tamper circuit
#
“y” Denotes enclosure size – see overleaf
* See table overleaf to determine continuous standby battery current available for given standby times
** EN50131 Definitions: EPS = External Power Source APS = Alternative Power Source
Elmdene International Ltd
Tel: +44(0)23 9269 6638
3 Keel Close, Interchange Park, Fax: +44(0)23 9266 0483
Portsmouth, Hampshire, PO3 5QD, UK
Web: www.elmdene.co.uk
2
Technical Support: +44(0)23 9269 6638 (option 3) PAK200545_03B May 2016 ©2016 ELMDENE INTERNATIONAL LTD
S
PECIFICATION
Mains Input
Rated Voltage / (Operational Voltage) 100-240Vac / (90 – 265Vac)
Frequency 50/60Hz
Input current GEN2-08 & GEN2-18 < 1.0A at full load
Fuse T2A 20mm HRC
Output
Mains power
Battery standby
12.8 –14.2Vdc (13.8Vdc nominal)
9.8 – 13.0Vdc
Continuous Output Current
Mains
Battery for 12 hours
1.0 A
0.6A with 8Ah Battery
1.5A
1.5A with 18Ah Battery
*See below for quiescent current of PSU under battery when calculating total system standby current resources.
Mechanical
Environmental
Temperature -10 to +40°C (operating) 75% RH non-condensing
-20 to +80°C (storage)
Standby Battery Management
Warning: risk of explosion if incorrect battery type fitted
Maximum Battery Size GEN2-08: 8Ah 12V Valve Regulated Lead Acid
(Not supplied with unit) GEN2-18: 18Ah 12V Valve Regulated Lead Acid
Intelligent Battery Recharge Time: < 72 hours to 80% - A heavily discharged battery having a
terminal voltage > 9.0V will attempt to be charged.
Testing: Battery Not Present: <9.0V battery voltage
Low battery voltage: <11.5V (no mains present)
Protection: Reverse battery connection protection
Deep discharge protection - Battery disconnect at 10.6V battery
terminal voltage
Quiescent Current: 64 mA when running on battery - less than 1 mA after deep
discharge protection.
Battery Cold Start (BCS) Momentarily link BCS pins together to connect battery to load if
PSU commissioned without any mains
3
Technical Support: +44(0)23 9269 6638 (option 3) PAK200545_03B May 2016 ©2016 ELMDENE INTERNATIONAL LTD
S
IGNALLING OUTPUTS
Rating: 0.10A @ 60Vdc 16Ω solid state relay contacts, volt free.
EPS Fault: Open if Loss of mains for >8s
GEN Fault: Open if Battery terminal voltage < 11.5v (when operating in standby with no
mains present), battery not present or Output and/or battery fuse blown
Tamper: 0.5A @ 30Vdc volt free contact. Open when lid is open.
C
ONNECTIONS
O/P +, - Connection to equipment to be powered (Observe polarity)
EPS Fault: Relay output for mains fail. Open if loss of mains.
GEN Fault: Relay output for General Fault. Open in fault condition
BATT +, - Connection to standby battery. Use cables provided (Observe polarity)
I
NSTALLATION AND COMMISSIONING
This unit is only suitable for installation as permanently connected equipment. This PSU is NOT SUITABLE for
external installation. EQUIPMENT MUST BE EARTHED. Before installation, ensure that external disconnect
device is OFF. The PSU should be installed according to all relevant safety regulations applicable to the
application.
Fig 1 Mounting of Power Supply
L E N
Min 10cm clearance
Fasten cables
using cable tie
Load output cable:
Current rating to
match maximum load
Mains Input cable rated:
3A, 300Vac minimum