MFWS100 MOUNTING FRAME INSTRUCTIONS
IMPORTANT: DOUBLE STUD OR 3 INCHES (76 mm) BETWEEN MOUNTING FRAMES IF PLACED NEXT TO ANOTHER BOTTLE FILLER, FOUNTAIN OR WALL
WOOD OR STEEL FRAME SHOWN (NOT PROVIDED)
FRAME
5/16" SCREW S OR BOLTS (10 REQ'D-NOT PROVIDED )
HOOK RODS (2) P/N 101567443730
SCREWS OR BOLTS (NOT PROVIDED)
INSTALL (2) SCREWS (P/N 111008343890) IN FRAM E BEFORE INSTALLING IN OPENING
40"
1016mm
4 1/2
114mm
CHILLER SHELF P/N 27638C
18 3/4"
476mm
FLOOR LINE
1" 25mm
5 1/8"
130mm
ELECTRICAL INLET LOCATION ON CHILLER
8"
203mm
TO FLOOR LINE
BACK OF WALL TO
BE 12" (305mm)
MIN DEPTH
1. Cut a square rectangular wall opening 18 3/4" (476mm) W x 40" (959mm) H and 4 1/2" (114mm) above the floor line.
2. Reinforce the wall opening on all sides so that it will adequately support the bottle filling station. This reinforcement must support up to 150 lbs static load and provide a means for securing the frame
assembly in place. NOTE: Building construction must allow for adequate air flow on both sides and top of remote chiller unit. Minimum of 4" (102mm) is required.
3. Install plumbing and electrical rough-ins. A junction box for a (3) wire, 10 amp branch circuit is provided on the inside of the chiller. (Standard 120 Volt s, 60 Hz and single phase)
4. Remove frame and related hardware from packaging. Install the frame squarely in wall opening with frame upright edges flush with the finished wall face. Place shelf inside frame and line up the (2) holes on each. Insert loose ends of rods into holes on sides of shelf panel. Using appropriately sized screws or bolts (not provided), fasten the shelf and frame to bottom of wall opening. Secure the frame sides and top to the wall using (10) 5/16" bolts or screws (not provided). NOTE: Be sure that frame is squared in location. Do not use less than the required screw quantity and size.