Elkay LZSTLG8WSLK Installation Manual

EZSTLG8WS*1B LZSTLG8WS*1B
INSTALLATION, CARE & USE MANUAL
Manual de Instalación, Cuidado y Utilización
Manuel d’installation/entretien/utilisation
EZ
& LZ™ Series Versatile Bottle Filling Stations & Coolers
EZ™ & LZ™ Serie versatil Botella Bombas y Enfriadores
EZ™ & LZ™ Stations versatile de Remplissage de Bouteille Série et Refroidisseurs
*Versatile Cooler Model LZSTLG8WSLK
conguration as shipped
*Versatile Cooler Model LZSTLG8WSLK
alternate installations
*Versatile cooler design allows units to be installed either left-hand high and right-hand low or left-low and right high.
Basin change may be required. See desired rough-in to help determine if the basin change is necessary.
Page 1 1000001714 (Rev. G - 06/16)
EZSTLG8WS*1B LZSTLG8WS*1B
Note: Danger! Electric shock hazard. Disconnect power before servicing unit.
Nota: peligro! Peligro de descarga eléctrica. Desconecte antes de reparar la unidad.
Remarque : Danger ! Risque d'électrocution. Débrancher avant de réparer l'appareil.
Pictured is unit only without bottle ller.
En la foto, la unidad sólo sin relleno botella.
Sur la photo, est une unité seulement sans remplissage de la bouteille.
Uses HFC-134A refrigerant Usa refrigerante HFC-134A
Utilise du uide frigorigéne HFC-134A
21
1
25B
1
20
14, 25A
24
15
16
12
Stream Height
Adjustment
See Note 9
19
22
6
3
12
19
See Fig. 9
19
18
2B
26
5
3
Stream Height Adjustment
See Note 9
2A
19
6
See Fig. 9
5
12
13
16
27
7
8
1000001714 (Rev. G - 06/16)
19
Fig. 1
Page 2
1723
4
19
EZSTLG8WS*1B LZSTLG8WS*1B
18 7/8"
479mm
3"
1 7/16"
77mm
90mm
3 9/16"
19"
483mm
HANGER BRACKET
8 1/16"
205mm
RIM
HEIGHT
936mm
36 13/16"
HEIGHT
38 3/8"
ORIFICE
975mm
ACTIVATION
SENSOR
7/16" X 3/4"
11mm X 19mm
OBROUND HOLES
(6)
15"
381mm
2"
51mm
2 7/8"
73mm
E
C
FILTER
HEIGHT
32 7/8"
ORIFICE
835mm
38 1/2"
979mm
732mm
28 13/16"
37mm
12 1/2"
318mm
27"
ADA
686mm
RIM
31 5/16"
796mm
21 7/8"
556mm
F
REQUIREMENT
HEIGHT
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
19"
483mm
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
7"
178mm
17 7/8"
454mm
7"
178mm
18 3/8"
467mm
6 3/8"
162mm
6 3/8"
162mm
7/8"
2"
6 3/8"
162mm
51mm
A
LOCATION
PREFERRED
B
22mm
D
(ALT. LOCATION)
6 3/8"
162mm
E
9/32" Ø
7mm Ø
HOLES
STANDARD ROUGH-IN FOR LEFT-HAND HIGH, BOTTLE FILLER LOW MODELS
12
2"
51mm
A
OPTIONAL
FILTER
(ALT. LOCATION)
F
D
PREFERRED
872mm
34 5/16"
2"
51mm
3 7/8"
17 7/16"
LOCATION
19 7/16"
494mm
583mm
22 15/16"
24 1/2"
622mm
7"
178mm
98mm
5 3/4"
146mm
354mm
13 15/16"
FINISHED FLOOR
7"
178mm
443mm
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
51 9/16"
1310mm
Fig. 2
MAXIMUM OUT FROM WALL
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
C = 1-1/2” TRAP NOT FURNISHED
Page 3 1000001714 (Rev. G - 06/16)
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
EZSTLG8WS*1B LZSTLG8WS*1B
3"
76mm
1 7/16"
90mm
3 9/16"
19"
483mm
HANGER BRACKET
38 3/8"
975mm
2"
51mm
8 1/16"
205mm
RIM
HEIGHT
936mm
36 13/16"
HEIGHT
ORIFICE
C
FILTER
HEIGHT
32 7/8"
ORIFICE
835mm
872mm
34 5/16"
A
LOCATION
9/32" Ø
7mm Ø
HOLES
12
PREFERRED
E
F
37mm
12 1/2"
318mm
27"
ADA
686mm
RIM
31 5/16"
796mm
24 1/2"
622mm
REQUIREMENT
HEIGHT
583mm
22 15/16"
19 7/16"
494mm
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
2"
6 3/8"
162mm
51mm
6 3/8"
18 3/8"
467mm
7"
178mm
m
54m
17 7/8"
4
7"
178mm
REQUIRES BASIN ASSY CHANGE. SEE PAGES 11-13 FOR INSTRUCTIONS
ALTERNATE ROUGH-IN FOR RIGHT-HAND HIGH, BOTTLE FILLER LOW MODELS
7/16" X 3/4"
11mm X 19mm
OBROUND HOLES
(6)
ACTIVATION
162mm
7/8"
2"
22mm
6 3/8"
162mm
6 3/8"
162mm
15"
381mm
2 7/8"
73mm
18 7/8"
479mm
2"
51mm
SENSOR
51mm
E
B
F
OPTIONAL FILTER
732mm
28 13/16"
"
m
38 1/2"
979mm
7"
5 3/4"
178mm
146mm
7"
178mm
D
FINISHED FLOOR
(ALT. LOCATION)
D
LOCATION
PREFERRED
3 7/8"
98mm
A
(ALT. LOCATION)
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
354mm
13 15/16"
17 7/16"
443mm
19"
483mm
21 7/8"
556mm
1000001714 (Rev. G - 06/16)
Fig. 3
Page 4
MAXIMUM OUT FROM WALL
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
C = 1-1/2” TRAP NOT FURNISHED
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
EZSTLG8WS*1B LZSTLG8WS*1B
18 7/8"
479mm
3"
1 7/16"
77mm
90mm
3 9/16"
19"
483mm
HANGER BRACKET
ORFICE
38 3/8"
975mm
2"
51mm
ACTIVATION
SENSOR
7/16" X 3/4"
11mm X 19mm
OBROUND HOLES
(6)
2 7/8"
73mm
15"
381mm
A
LOCATION
PREFERRED
8 1/16"
205mm
RIM
HEIGHT
936mm
36 13/16"
HEIGHT
44"
1118mm
E
C
FILTER
HEIGHT
32 7/8"
ORIFICE
835mm
872mm
34 5/16"
F
37mm
12 1/2"
318mm
27"
ADA
686mm
RIM
31 5/16"
796mm
24 1/2"
622mm
REQUIREMENT
HEIGHT
583mm
22 15/16"
19 7/16"
494mm
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
7"
178mm
17 7/8"
454mm
7"
178mm
18 3/8"
467mm
6 3/8"
162mm
6 3/8"
162mm
7/8"
2"
22mm
6 3/8"
162mm
51mm
2"
51mm
6 3/8"
162mm
E
B
9/32" Ø
7mm Ø
HOLES
12
ALTERNATE ROUGH-IN FOR RIGHT-HAND HIGH, BOTTLE FILLER HIGH MODELS
2"
51mm
57 1/16"
1450mm
F
OPTIONAL FILTER
732mm
28 13/16"
7"
5 3/4"
178mm
146mm
7"
178mm
FINISHED FLOOR
D
(ALT. LOCATION)
D
LOCATION
PREFERRED
3 7/8"
98mm
A
(ALT. LOCATION)
354mm
13 15/16"
17 7/16"
443mm
19"
483mm
21 7/8"
556mm
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
Fig. 4
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
C = 1-1/2” TRAP NOT FURNISHED
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
MAXIMUM OUT FROM WALL
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
Page 5 1000001714 (Rev. G - 06/16)
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
EZSTLG8WS*1B LZSTLG8WS*1B
18 7/8"
479mm
3"
1 7/16"
77mm
90mm
3 9/16"
19"
483mm
HANGER BRACKET
38 3/8"
ORIFICE
975mm
8 1/16"
205mm
RIM
HEIGHT
935mm
36 13/16"
HEIGHT
C
FILTER
HEIGHT
32 7/8"
ORIFICE
835mm
37mm
12 1/2"
318mm
27"
ADA
686mm
REQUIREMENT
RIM
HEIGHT
31 5/16"
796mm
2"
51mm
E
A
LOCATION
6 3/8"
162mm
6 3/8"
18 3/8"
467mm
7"
178mm
17 7/8"
454mm
7"
178mm
7/16" X 3/4"
11mm X 19mm
OBROUND HOLES
(6)
6 3/8"
6 3/8"
ACTIVATION
SENSOR
9/32" Ø
162mm
162mm
15"
381mm
162mm
7mm Ø
HOLES
12
2"
51mm
E
2 7/8"
73mm
2"
51mm
PREFERRED
B
7/8"
22mm
D
D
F
A
OPTIONAL
FILTER
(ALT. LOCATION)
872mm
34 5/16"
REQUIRES BASIN ASSY CHANGE. SEE PAGES 11-13 FOR INSTRUCTIONS
ALTERNATE ROUGH-IN FOR LEFT-HAND HIGH, BOTTLE FILLER HIGH MODELS
44"
1118mm
732mm
28 13/16"
21 7/8"
556mm
19"
483mm
F
2"
51mm
7"
178mm
3 7/8"
98mm
354mm
13 15/16"
FINISHED FLOOR
7"
5 3/4"
146mm
178mm
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
(ALT. LOCATION)
17 7/16"
443mm
LOCATION
PREFERRED
19 7/16"
494mm
583mm
22 15/16"
24 1/2"
622mm
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
1000001714 (Rev. G - 06/16)
57 1/16"
1450mm
Fig. 5
Page 6
MAXIMUM OUT FROM WALL
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
C = 1-1/2” TRAP NOT FURNISHED
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
CAJA RECESIVA DE ALAMBRES (3) DE SUMINISTRO ELÉCTRICO
BOÎTE ENCASTRÉE D’ALIMENTATION ÉLECTRIQUE (3) FILS
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX**
Loading...
+ 12 hidden pages