Elkay LZSTL8WSX2G, LZSTL8WSX3G, LZSTLDWSX1G, LZSTL8WSX1G, EZSTLDWSX1G User Manual

...
EZSTLDWS*1G EZSTL8WS*1G, 2G, 3G LZSTLDWS*1G LZSTL8WS*1G, 2G, 3G
Manual de instalación y uso
Manuel d’installation et utilisation
EZ
& LZ™ Series Versatile Bottle Filling Stations & Coolers
EZ™ & LZ™ Serie versatil Botella Bombas y Enfriadores
EZ™ & LZ™ Stations versatile de Remplissage de Bouteille Série et Refroidisseurs
*Versatile Cooler Model LZSTL8WSLK
conguration as shipped
*Versatile Cooler Model LZSTL8WSLK
alternate installations
*Versatile cooler design allows units to be installed either left-hand high and right-hand low or left-low and right high.
Basin change may be required. See desired rough-in to help determine if the basin change is necessary.
Refrigerated unit must be installed on right-hand side.
Page 1 1000002243 (Rev. G - 08/19)
EZSTLDWS*1G EZSTL8WS*1G, 2G, 3G LZSTLDWS*1G LZSTL8WS*1G, 2G, 3G
Note: Danger! Electric shock hazard. Disconnect power before servicing unit.
Nota: peligro! Peligro de descarga eléctrica. Desconecte antes de reparar la unidad.
Remarque : Danger ! Risque d'électrocution. Débrancher avant de réparer l'appareil.
Pictured is unit only without bottle ller.
En la foto, la unidad sólo sin relleno botella.
Sur la photo, est une unité seulement sans remplissage de la bouteille.
Uses HFC-134A refrigerant Usa refrigerante HFC-134A
Utilise du uide frigorigéne HFC-134A
See Fig. 18
8B
14
1
8A
1
14, 28
21
15
29
12
19
27
6
12
3
See Fig. 9
2A
5
5
3
13
19
2B
6
See Fig. 9
12
23
10 16 7
1919
25
19
Fig. 1
Page 21000002243 (Rev. G - 08/19)
22, 32
20
17
4
18
19
EZSTLDWS*1G EZSTL8WS*1G, 2G, 3G LZSTLDWS*1G LZSTL8WS*1G, 2G, 3G
18 7/8"
479mm
3"
1 7/16"
77mm
90mm
3 9/16"
19"
483mm
HANGER BRACKET
8 1/16"
205mm
RIM
HEIGHT
936mm
36 13/16"
HEIGHT
38 3/8"
ORIFICE
975mm
C
FILTER
HEIGHT
32 7/8"
ORIFICE
835mm
37mm
12 1/2"
318mm
27"
ADA
686mm
RIM
HEIGHT
31 5/16"
796mm
REQUIREMENT
38 1/2"
ACTIVATION
SENSOR
7/16" X 3/4"
11mm X 19mm
OBROUND HOLES
(6)
15"
381mm
7"
178mm
17 7/8"
454mm
7"
178mm
18 3/8"
467mm
6 3/8"
162mm
6 3/8"
162mm
6 3/8"
162mm
2"
51mm
2 7/8"
73mm
E
A
PREFERRED
B
7/8"
2"
22mm
51mm
6 3/8"
162mm
979mm
732mm
28 13/16"
21 7/8"
556mm
19"
483mm
F
2"
LOCATION
51mm
3 7/8"
7"
178mm
98mm
5 3/4"
146mm
354mm
13 15/16"
FINISHED FLOOR
7"
178mm
SUMINISTRO ELÉCTRICO (3) CAJA ENCHUFE DE ALAMBRE SALIDA DÚPLEX
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX DUPLEX OUTLET**
ALIMENTATION ÉLECTRIQUE (3) BOÎTIER ENCASTRÉ
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
REFRIGERATED UNIT MUST BE INSTALLED ON RIGHT-HAND SIDE.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
D
(ALT. LOCATION)
17 7/16"
443mm
D
LOCATION
PREFERRED
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
E
9/32" Ø
7mm Ø
HOLES
STANDARD ROUGH-IN FOR LEFT-HAND HIGH, BOTTLE FILLER LOW MODELS
12
2"
51mm
A
OPTIONAL
FILTER
(ALT. LOCATION)
51 9/16"
F
24 1/2"
622mm
872mm
34 5/16"
1310mm
Fig. 2
Page 3 1000002243 (Rev. G - 08/19)
19 7/16"
494mm
583mm
22 15/16"
MAXIMUM OUT FROM WALL
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
NOTE: IT IS HIGHLY RECOMMENDED THAT THE CIRCUIT BE DEDICATED AND THE LOAD PROTECTION BE SIZED FOR 20 AMPS.
C = 1-1/2” TRAP NOT FURNISHED
EZSTLDWS*1G EZSTL8WS*1G, 2G, 3G LZSTLDWS*1G LZSTL8WS*1G, 2G, 3G
3"
76mm
1 7/16"
90mm
3 9/16"
19"
483mm
HANGER BRACKET
38 3/8"
975mm
2"
51mm
8 1/16"
205mm
RIM
HEIGHT
936mm
36 13/16"
HEIGHT
ORIFICE
C
FILTER
HEIGHT
32 7/8"
ORIFICE
835mm
872mm
34 5/16"
A
LOCATION
9/32" Ø
7mm Ø
HOLES
12
PREFERRED
E
F
37mm
12 1/2"
318mm
27"
ADA
686mm
RIM
31 5/16"
796mm
24 1/2"
622mm
REQUIREMENT
HEIGHT
583mm
22 15/16"
19 7/16"
494mm
SUMINISTRO ELÉCTRICO (3) CAJA ENCHUFE DE ALAMBRE SALIDA DÚPLEX
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX DUPLEX OUTLET**
ALIMENTATION ÉLECTRIQUE (3) BOÎTIER ENCASTRÉ
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
REFRIGERATED UNIT MUST BE INSTALLED ON RIGHT-HAND SIDE.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
2"
6 3/8"
162mm
51mm
6 3/8"
18 3/8"
467mm
7"
178mm
7/8"
17
454mm
7"
178mm
REQUIRES BASIN ASSY CHANGE. SEE PAGES 11-13 FOR INSTRUCTIONS
7/16" X 3/4"
11mm X 19mm
OBROUND HOLES
(6)
ALTERNATE ROUGH-IN FOR RIGHT-HAND HIGH, BOTTLE FILLER LOW MODELS
ACTIVATION
162mm
7/8"
2"
22mm
6 3/8"
162mm
6 3/8"
162mm
15"
381mm
2 7/8"
73mm
18 7/8"
479mm
2"
51mm
SENSOR
51mm
E
B
F
OPTIONAL FILTER
732mm
28 13/16"
38 1/2"
979mm
51 9/16"
1310mm
7"
5 3/4"
178mm
146mm
7"
178mm
D
FINISHED FLOOR
(ALT. LOCATION)
D
LOCATION
PREFERRED
3 7/8"
98mm
A
(ALT. LOCATION)
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
354mm
13 15/16"
17 7/16"
443mm
19"
483mm
21 7/8"
556mm
Fig. 3
Page 41000002243 (Rev. G - 08/19)
MAXIMUM OUT FROM WALL
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
NOTE: IT IS HIGHLY RECOMMENDED THAT THE CIRCUIT BE DEDICATED AND THE LOAD PROTECTION BE SIZED FOR 20 AMPS.
C = 1-1/2” TRAP NOT FURNISHED
EZSTLDWS*1G EZSTL8WS*1G, 2G, 3G LZSTLDWS*1G LZSTL8WS*1G, 2G, 3G
/8" 8 7
1
479mm
6"
mm
9/1
90
3
"
mm
19
483
HANGER BRACKET
ORFICE
38 3/8"
975mm
" 2
51mm
9mm X 1
7/16" X 3/4"
11mm
OBROUND HOLES
ACTIVATION
SENSOR
(6)
15"
m
2 7/8"
73m
A
LOCATION
PREFERRED
381mm
8 1/16"
205mm
RIM
HEIGHT
936mm
36 13/16"
HEIGHT
44"
1118mm
E
C
FILTER
RIM
31 5/16"
796mm
HEIGHT
32 7/8"
ORIFICE
835mm
72mm 8
34 5/16"
24 1/2"
622mm
F
" 7
178mm
17 7/8"
454mm
m
7"
78m
1
6 3/8"
6 3/8"162m
162mm
m
2"
5 3/4"
51mm
146mm
3"
1 7/16"
77mm
37mm
12 1/2"
318mm
27"
ADA
686mm
REQUIREMENT
HEIGHT
583mm
22 15/16"
19 7/16"
494mm
7"
178mm
7"
178mm
FINISHED FLOOR
SUMINISTRO ELÉCTRICO (3) CAJA ENCHUFE DE ALAMBRE SALIDA DÚPLEX
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX DUPLEX OUTLET**
ALIMENTATION ÉLECTRIQUE (3) BOÎTIER ENCASTRÉ
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
REFRIGERATED UNIT MUST BE INSTALLED ON RIGHT-HAND SIDE.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
D
(ALT. LOCATION)
m
18 3/8"
467m
6 3/8"
162mm
7/8"
2"
22mm
51mm
6 3/8"
162mm
E
Ø 2"
9/3
7mm Ø
HOLES12
B
OPTIONAL FILTER
ALTERNATE ROUGH-IN FOR RIGHT-HAND HIGH, BOTTLE FILLER HIGH MODELS
2"
51mm
57 1/16"
1450mm
Fig. 4
Page 5 1000002243 (Rev. G - 08/19)
732mm
28 13/16"
D
LOCATION
PREFERRED
3 7/8"
98mm
A
(ALT. LOCATION)
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
F
21 7/8"
556mm
354mm
13 15/16"
17 7/16"
443mm
19"
483mm
MAXIMUM OUT FROM WALL
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
NOTE: IT IS HIGHLY RECOMMENDED THAT THE CIRCUIT BE DEDICATED AND THE LOAD PROTECTION BE SIZED FOR 20 AMPS.
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
C = 1-1/2” TRAP NOT FURNISHED
EZSTLDWS*1G EZSTL8WS*1G, 2G, 3G LZSTLDWS*1G LZSTL8WS*1G, 2G, 3G
18 7/8"
479mm
3"
1 7/16"
77mm
90mm
3 9/16"
19"
483mm
HANGER BRACKET
38 3/8"
ORIFICE
975mm
8 1/16"
205mm
RIM
HEIGHT
935mm
36 13/16"
HEIGHT
C
FILTER
HEIGHT
32 7/8"
ORIFICE
835mm
37mm
12 1/2"
318mm
27"
ADA
686mm
REQUIREMENT
RIM
HEIGHT
31 5/16"
796mm
2"
51mm
E
A
LOCATION
6 3/8"
162mm
6 3/8"
18 3/8"
467mm
7"
178mm
7/8"
17
454mm
7"
178mm
7/16" X 3/4"
11mm X 19mm
OBROUND HOLES
(6)
6 3/8"
6 3/8"
ACTIVATION
SENSOR
9/32" Ø
7mm Ø
162mm
162mm
15"
381mm
REQUIRES BASIN ASSY CHANGE. SEE PAGES 11-13 FOR INSTRUCTIONS
162mm
HOLES
12
7/8"
2"
51mm
E
2 7/8"
73mm
2"
51mm
ALTERNATE ROUGH-IN FOR LEFT-HAND HIGH, BOTTLE FILLER HIGH MODELS
PREFERRED
B
22mm
F
A
FILTER
(ALT. LOCATION)
34 5/16"
44"
1118mm
732mm
28 13/16"
21 7/8"
556mm
19"
483mm
F
2"
51mm
D
7"
178mm
3 7/8"
98mm
354mm
13 15/16"
FINISHED FLOOR
7"
5 3/4"
146mm
178mm
SUMINISTRO ELÉCTRICO (3) CAJA ENCHUFE DE ALAMBRE SALIDA DÚPLEX
LEGEND/LEYENDA/LÉGENDE
D = ELECTRICAL SUPPLY (3) WIRE RECESSED BOX DUPLEX OUTLET**
ALIMENTATION ÉLECTRIQUE (3) BOÎTIER ENCASTRÉ
ASEGURE UNA VENTILACIÓN ADECUADA MANTENIENDO UN ESPACIO E 6” (152 mm) (MÍN.) DE HOLGURA ENTRE LA REJILLA
DE VENTILACIÓN DEL MUEBLE Y LA PARED.
E = INSURE PROPER VENTILATION BY MAINTAINING 6” (152 mm) (MIN.) CLEARANCE FROM CABINET LOUVERS TO WALL.
ASSUREZ-VOUS UNE BONNE VENTILATION EN GARDANT 6” (152 mm) (MIN.) ENTRE LES ÉVENTS DE L’ENCEINTE ET LE MUR.
AGUJEROS DE LAS TUERCAS DE 7/16 PARA SUJETAR LA UNIDAD A LA PARED
TROUS D’ÉCROUS 7/16 POUR FIXER L’APPAREIL AU MUR
**NEW INSTALLATIONS MUST USE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
**Las nuevas instalaciones deben utilizar el interruptor de circuito de tierra de la avería (GFCI)
**Les nouvelles installations doivent employer l’interrupteur de circuit moulu de défaut (GFCI)
REFRIGERATED UNIT MUST BE INSTALLED ON RIGHT-HAND SIDE.
F = 7/16 BOLT HOLES FOR FASTENING UNIT TO WALL
(ALT. LOCATION)
17 7/16"
443mm
D
LOCATION
PREFERRED
19 7/16"
494mm
583mm
22 15/16"
24 1/2"
622mm
REDUCE HEIGHT BY 3 INCHES FOR INSTALLATION OF CHILDREN’S ADA COOLER
872mm
57 1/16"
1450mm
Fig. 5
Page 61000002243 (Rev. G - 08/19)
MAXIMUM OUT FROM WALL
LEGEND/LEYENDA/LÉGENDE
A = RECOMMENDED WATER SUPPLY LOCATION 3/8 O.D. UNPLATED COPPER TUBE CONNECT STUB WITH SHUT OFF (BY OTHERS) 3 IN. (76mm)
EMPLACEMENT RECOMMANDÉ POUR LE DRAIN DE D.E. 1-1/2” DE SORTIE D’EAU. STUB 2 HORS DU MUR
PURGADOR DE 1-1/2” NO PROPORCIONADO
SIPHON 1-1/2” NON FOURNI
(POR OTROS) 3 en. (76 Mm) el MAXIMO FUERA DE PARED
LES AUTRES) 3 dans. (76 mm) le MAXIMUM HORS DU MUR
UBICACIÓN RECOMENDADA PARA EL DRENAJE DE SALIDA DE AGUA, DE 1-1/2” DE DIÁMETRO. El TALONARIO 2 FUERA DE PARED
B = RECOMMENDED LOCATION FOR WASTE OUTLET 1-1/2” O.D. DRAIN STUB 2 IN. OUT FROM WALL
La UBICACION 3/8 O RECOMENDADA de ABASTECIMIENTO DE AGUA. D. El TUBO del COBRE de UNPLATED CONECTA TALONARIO CON APAGO
L’O.D de 3/8 d’EMPLACEMENT DE PROVISION D’EAU RECOMMANDE. LE TUBE DE CUIVRE DE UNPLATED CONNECTE STUB AVEC ETEINT (PAR
NOTE: IT IS HIGHLY RECOMMENDED THAT THE CIRCUIT BE DEDICATED AND THE LOAD PROTECTION BE SIZED FOR 20 AMPS.
C = 1-1/2” TRAP NOT FURNISHED
Loading...