Elkay ERFPVR8C, LNFE8C*B Installation, Care & Use Manual

Page 1
ERFP8C*B ERFPVR8C LNFE8C*B
Installation/Care/Use Manual
Soft Sides® Refrigerated Fountains with FLEXI-GUARD
ERFP8C
Installer
To assure you install this model easily and correctly, PLEASE READ THESE SIMPLE INSTRUCTIONS BEFORE STARTING THE INSTALLA­TION. CHECK YOUR INSTALLATION FOR COMPLIANCE WITH PLUMBING, ELECTRICAL AND OTHER APPLICABLE CODES. After installation, leave these instructions inside the fountain for future reference.
®
IMPORTANT
ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SERVICE PERSON
IMPORTANT! INSTALLER PLEASE NOTE.
THE GROUNDING OF ELECTRICAL EQUIPMENT SUCH AS TELEPHONE, COMPUTERS, ETC. TO WATER LINES IS A COMMON PROCEDURE. THIS GROUNDING MAY BE IN THE BUILDING OR MAY OCCUR AWAY FROM THE BUILDING. THIS GROUNDING CAN CAUSE ELECTRICAL FEEDBACK INTO A FOUNTAIN, CREATING AN ELEC­TROLYSIS WHICH CAUSES A METALLIC TASTE OR AN INCREASE IN THE METAL CONTENT OF THE WATER. THIS CONDITION IS AVOIDABLE BY USING THE PROPER MATERIALS AS INDICATED. ANY DRAIN FITTINGS PROVIDED BY THE INSTALLER SHOULD BE MADE OF PLASTIC TO ELECTRICALLY ISOLATE THE FOUNTAIN FROM THE BUILDING PLUMBING SYSTEM.
1/4" O.D. TUBE WATER INLET TO COOLER
FIG. 1
3/8" O.D. UNPLATED COPPER TUBE CONNECT COLD WATER SUPPLY
NOTE: WATER FLOW
DIRECTION
4
3
17
BUILDING WATER INLET
SERVICE STOP (NOT FURNISHED)
2
10
FIG. 2
5
6
NOTE: WHEN INSTALLING REPLACEMENT BUBBLER AND PEDESTAL, TIGHTEN
7
NUT (ITEM 9 OR 32) ONLY TO HOLD PARTS SNUG IN POSITION. DO NOT
8
OVER TIGHTEN.
34
33
FIG. 3
11
19
PAGE 1
FIG. 4
9
32
FIG. 5
97157C (Rev. L - 1/02)
Page 2
ERFP8C*B ERFPVR8C LNFE8C*B
MODEL LNFE8C
LEGEND A = 3/8" O.D. TUBE CONNECT (CHILLER WATER OUTLET) B = 3/8" O.D. TUBE CONNECT (CHILLER WATER INLET) SHUT OFF VALVE BY OTHERS C = 1-1/4" TRAP FURNISHED D = ELECTRICAL INLET
97157C (Rev. L - 1/02)
FIG. 6
PAGE 2
Page 3
ERFP8C*B ERFPVR8C LNFE8C*B
INSTALLATION INSTRUCTIONS
1. Install remote chiller. Remove front panel of chiller. Remove and discard cardboard inner pack from between compressor and side panel. Slide chiller onto the shelf and position it to the left within the guides on the shelf. NOTE: Building construction must allow for adequate air flow on both sides, top, and back of chiller. See chiller instructions for additional instructions.
2. Make water supply connections. Install a shut-off valve and union connection to building water supply (valve and union not provided). Turn on the water supply and flush the line thoroughly.
3. ERFP MODELS: Make connection between remote chiller and building supply line. Inlet port is marked on the chiller (1/4" O.D. copper tube). Bend the copper tube (provided) at an appropriate length from chiller to opening in frame. Install a 1/4" x 3/8" union (provided) on the marked chiller inlet port. Connect building supply line to union. (See Figures 7 or 12) LNFE MODEL: Mount filter head assembly to side of chiller (See Figure 9). Make connection between filter and building supply line (3/8" O.D. tube not provided). Inlet port is marked on the chiller (1/4" O.D. copper tube). Install a 1/4" x 1/4" union (provided). Bend the copper tube (provided) at an appropriate length from the filter and connect to the union on the chiller. (See Figures 8 or 11).
4. Hang the upper panel on the mounting frame hanger. Align holes in the panel with the holes in the mounting frame. Be sure that panel is engaged with hanger at top of frame before releasing it.
5. Install the fountain. Remove access cover plate on underside of fountains and save the screws. Mount the fountain to the upper panel and the wall frame with (4) 5/16" x 3/4" (19mm) long bolts and nuts (provided). Tighten securely.
6. Remove elbow from end of p-trap and attach it to drain tube. Re-attach elbow to p-trap and cut waste tube to required length using plumbing hardware and trap as a guide.
7. ERFP MODELS: Make connections between remote chiller outlet tube and fountain strainer. Outlet port is marked on the chiller (3/8" O.D. copper tube). Install a 3/8" x 3/8" union (provided) on the marked chiller outlet port. Insert the 3/8" unplated copper water line (provided) into the union and the inlet side of the strainer by pushing it in until it reachs a positive stop, approximately 3/4" (19mm). Connect 1/4" copper tubing coming from fountain to the strainer. Turn on water supply and check for leaks. DO NOT
SOLDER TUBES INSERTED INTO THE STRAINER AS DAMAGE TO THE O-RINGS MAY RESULT. (See Figures 7 or 12). LNFE MODEL: Make connections between remote chiller and fountain. Outlet port is marked on the chiller (3/8" O.D. copper
tube). Install a 3/8" x 3/8" union (provided) on the marked chiller outlet port. Insert the 3/8" unplated copper water line (provided) into the union. Install a 1/4" x 3/8" union (provided) on the 3/8" copper tube and connect to the 1/4" copper tubing coming from the fountain. Turn on water supply and check for leaks. DO NOT SOLDER TUBES INSERTED INTO THE UNIONS AS DAMAGE TO THE O-RINGS MAY RESULT. (See Figures 8 or 11).
8. These products are designed to operate on 20-105 PSIG supply line pressure. If inlet pressure is above 105 PSIG, a pressure regulator must be installed in the supply line. Any damage caused by reason of connecting these products to supply line pressures lower than 20 PSIG or higher than 105 PSIG is not covered by warranty.
9. Make electrical connections to the chiller. See chiller instructions.
10. Check stream height from bubbler. Stream height is factory set at 35 PSI. If supply pressure varies greatly from this, remove items 3 & 4 and adjust the screw on regulator (Item 10). Clockwise adjustment will raise stream height and counter-clockwise will lower stream height. For best adjustment stream should hit basin approximately 6 1/2" from the bubbler.
11. Mount lower panel. Loosen the (2) #10-24 x 5/8" (16mm) screws at frame bottom lip. Slide upper tongue of lower panel under lower edge of already installed upper panel. Tighten previously loosened screws securely.
12. Replace bottom access panel to fountain basin using screws provided. Tighten securely.
TROUBLE SHOOTING AND MAINTENANCE
1. Orifice Assy: Mineral deposits on orifice can cause water flow to spurt or not regulate. Mineral deposits may be removed from orifice with a small round file not over 1/8" diameter or a small diameter wire. CAUTION: Do not file or cut orifice materials.
2. Stream Regulator: If orifice is free of material deposits, regulate flow according to instruction 10 stated above.
3. Actuation of Quick Connect Water Fittings: Cooler is provided with lead-free connectors which utilize an o-ring water seal. To remove tubing from the fitting, relieve water pressure, push in on the gray collar while pulling on the tubing (See Fig. 2) To insert tubing, push tube straight into the fitting until it reaches a positive stop, approximately 3/4".
TO
BUBBLER
CHILLER OUTLET
ERFP8C
TUBE ROUTING
13
22
21
CHILLER INLET
TO
BUBBLER
CHILLER OUTLET
21
LNFE8C
TUBE ROUTING
26
WATER INLET
27
24
29
23
30
25
28
FIG. 7
FIG. 8
PAGE 3
97157C (Rev. L - 1/02)
Page 4
1 2 3 4 5 6 7 8
9 10 11 12 13 14
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
NS NS
PART NO.ITEM NO.
LK464 15005C 45662C 45663C 50986C A54874 50934C 50168C 70012C 61313C 70022C
110711942550
55996C
55000612
27959C
55000665
26837C 40045C 70055C 27057C 26833C 70745C 70870C 22490C 51294C 51299C 70683C 70792C 70818C 70822C 70823C 70682C 15009C
100322740560
45392C 56092C 62095C
111577243890 111577343890
ERFP8C*B ERFPVR8C LNFE8C*B
PARTS LIST
DESCRIPTION
Drain Retaining Nut Push Button Push Button Sleeve Regulator Holder Orifice Assy Housing Assy Pedestal Bubbler Locknut Regulator Setscrew - #6-32 X .31" Screw - #8-32 X .38" TH Strainer Fountain Arm Fountain Arm - (Glassfiller) Bottom Cover Plate Back Panel Hex Nut Speed Nut Regulator Mounting Bracket Lower Panel Union - 3/8 X 1/4 Union - 3/8 X 3/8 Filter Mounting Bracket Filter Head Assy Filter Assy Union - 1/4 Screw - #8-18 x .75" PH Elbow - 3/8" (10mm) Fitting - Superseal 1/4" (6mm) Fitting - Superseal 3/8" (10mm) Tee - 1/4 Nipple - Bubbler - VR Model Gasket - VR Model Bubbler - VR Model Poly Tubing (Cut To Length) Tube - Water In Screw - Mach 5/16-18 x 3/4 Nut - Hex 5/16-18
FIG. 9
FIG. 10
14
35
SEE
FIG. 3
36
SEE FIG. 4 OR 5
12, 15, 18
ERFP8FC TUBE ROUTING
16
20
13
1
TO
BUBBLER
CHILLER OUTLET
31
21
LNFE8FC TUBE ROUTING
32
TO GLASSFILLER
26
WATER INLET
TO
BUBBLER
31
22
CHILLER OUTLET
FIG. 12FIG. 11
www.DrinkingFountainDoctor.com 800-518-5388
32
TO GLASSFILLER
13
21
CHILLER INLET
97157C (Rev. L - 1/02)
PAGE 4
Loading...