Eliwell Televis EWCM 809/NH3/S User Manual

Page 1
AVAILABLE VERSIONS (from the 21/05/96, software n. 23)
EWCM 809/NH3/S (ammonia) with pres­sure (4…20 mA programmable) or with NTC temperature input probe and with se­rial connection for connection to the TELE­VIS system.
GENERAL FEATURES
FRONT KEYPAD
“PRG” button: to have access the pro­gramming. “HRS” button: to display/reset the run­ning hours of each compressor. “MAINT” button: to display/modify the “available” or “in service” status of each compressor. “SET” button: to display/modify the “nor­mal” or the”economy” Setpoints.
“UP” button: to increase the figures. “DOWN” button: to decrease the figures. “MUTE” button: to silence/reset an
alarm. “LOCK led”: to dispaly the keyboard lock function. “ALARM” led: to display an alarm condi­tion. “COMPRESSOR & STAGES” leds: red and green leds to display the output com­pressor status. 4 DIGIT DISPLAY: it shows the input probe value, the default unit of measure­ment can be programmed with “dEU” pa­rameter. As soon as an alarm occurs the display will switch back and forth between the probe read-out and the alarm code la­bel.
INPUT AND OUTPUT
Alarm relay output: remote alarm, the terminals 1 and 2 are closed when there is an active alarm. Safety relay output: the terminals 3 and 4 are open when an EWCM failure ap­pears. Pressurestat alarm input: high and low pressurestat input alarms (terminals 5 and 6, “SEP” parameter).
Power supply: input terminals 9 and 10. Economy set switch: to activate the
HOW IT IS MADE
• Housing: black ABS plastic, 72x144 mm, depth 120 mm
• Connections: quick-disconnect screw terminal block
• Type of refrigerant: ammonia
• Suction sensor input: NTC or 4…20 mA pressure transducer (scaleable)
• One pressurestat alarm input
• Global alarm output: relay 6(3)A 250V AC
• Controller breakdown output: re­lay 6(3)A 250V AC
• Configurable outputs: 9 relays outputs 6(3)A 250V AC
• Alarm inputs: 9 optoisolated in­puts (the same voltage of the sup­ply)
• Serial connection: RS-485 port for connection to the Televis system
• Consumption: 6 VA
• Power supply: 12, 24, 110, 220 Vac ±10%, 50/60 Hz
WHAT IT IS
The EWCM 809/NH3/S is a con­troller designed specifically for the control of a machine room in a re­frigeration system. EWCM 809/NH3/S provides control management of the compressors (single units, multistage systems or compressors having different pow­er).
EWCM 809/NH3/S
rel. 5/98 ing
compressors manager, model for ammonia
PLUS PRODUCT
• Alarm circuit combined with each compressor
• Clock to set the various operation setpoints in various time periods
• UL approval pending
Page 2
2EWCM 809/NH3/S 5/98 ing
economy setpoint (terminals 13 and 14 have free voltage contacts, “rSIP” parame­ter).
Suction probe: input terminals 15 and 16. Televis System: RS 485, input terminals
19, 20 and 21. Compressor alarms inputs: when ac­tive, the compressor output is swiched off (terminals from 22 to 39, “ALIP” parame­ter). Compressor relay outputs: to supply the contactors of the compressors (termi­nals from 44 to 61).
PARAMETER PROGRAMMING ENTERING THE PROGRAMMING MODE
The EWCM is provided with two levels of parameters programming: operating “oPr” and Configuration “CnF”. To have access the “oPr” menu, push and release the “prg” button and then the “UP” arrow. To have access the “CnF” menu, push the “prg” button twice and then the “UP” ar­row. If a password has been activated, the “PAS” label will be showed before entering the programming. To exit the programming mode, push the “prg” button another time, all the changes will be automatically memorized.
HOW TO DISPLAY AND MODIFY THE PARAMETERS
After entering programming, to display a parameter label push the “UP” or “DOWN” arrows:
- to show a parameter value push the “set” button;
- to modify the parameter value push the “UP” or “DOWN” arrows;
- to exit the parameter value push the ”set” button.
PASSWORDS
The passwords “Psc” and “Pso” are pro­vided to enter the Configuration and Operating parameters programming. To activate the password enter the pro­gramming mode, select the password la­bel and set the password number.
CONFIGURATION PARAMETERS
System capacity
CPnU: ComPressor nUmber. Number of compressors installed. CtyP: Compressor tyPe. 0 = compressors having different power (Neutral Zone Control); 1 = compressors having the same power (Proportional Control). Note: compressors having the same pow­er, but without partial reduction valves.
- Neutral Zone (dead band) is used with compressors having a big power.
- Proportional control is used with small power compressors.
CPSt: ComPressor Step. Number of steps of each compressor (only
Parameter Description Range Default Unit
CONFIGURATION PARAMETERS
CPnU ComPressor nUmber 1…11 7 number
Ctyp Compressor tyPe 0 / 1 1 number
CPSt ComPressor Step 1…6 1 number
PC1…PC11 Power Compressor 1…11 1…255 1 number
FtyP Freon tyPe / / /
PA04* Pressure At 0…4 mA 0…8 0,5 Bar
PA20* Pressure At 0…20 mA 0…31 8 Bar
CAL** CALibration –0.5…0.5 0 Bar
CAL*** CALibration –5…5 0 °C
SEP SEt (alarm) Polarity 0 / 1 1 number
rSIP reduced Set Input Polarity 0 / 1 1 number
ALIP ALarm Input Polarity 0 / 1 1 number
StPP Step outPuts Polarity 0 / 1 1 number
Psc Password configuration 0…255 0 number
tAb tAble of parameters / / /
OPERATING PARAMETERS
Pri Primes 0…59 0 minutes
HoUr HoUrs 0…23 0 hours
daY dAY 1…7 0 number
dEU dEfault Unit 0 / 1 / 2 0 number
Pbd Proportional band 0.1…5 0,4 Bar / °C / °F
onon on/on (compressor) 0…255 5 minutes
oFon oFF/on (compressor) 0…255 5 minutes
don delay on 0…5000 15 seconds
doF delay oFF 0…255 5 seconds
donF delay on/oFF 0…255 15 seconds
FdLy First deLay on 0 / 1 1 number
FdLF First deLay oFF 0 / 1 1 number
odo output delay at on 0…255 0 seconds
LSE Lower SEt 0.1 / HSE 0.2 Bar / °C / °F
HSE Higher SEt LSE / 25 5 Bar / °C / °F
StrS Start time reduced Set 0…24 0 hours
SPrS Stop (time) reduced Set 0…24 0 hours
rSd1…rSd7 reduced Set day 1…7 0 / 1 0 number
UAro Unit Alarm override 0 / 1 1 number
Aro Alarm override 0…255 15 minutes
PAO Power Alarm Override 0…255 30 minutes
LAL Lower ALarm 0.01…25 5 Bar
HAL Higher ALarm 0.01…25 5 Bar
tAo time Alarm override 0 255 minutes
SEr SErvice 1…9999 3000 hours
PEn Pressurestat Errors number 0…15 5 number
PEI Pressurestat Errors Interval (time) 0…15 15 minutes
CPP Compressor Probe Protection 0 / 1 0 number
SPr Step Probe protection 0 / CPnU 1 number
PoPr Power (with faulty) probe 0 / n 0 number
rELP rELative Pressure 0 / 1 1 number
Loc keyboard Lock function 0 / 1 1 number
Pso Password operating 0…255 0 number
FAA FAmily Address 13…14 13 number
dEA dEvice Address 0…14 0 number
DEFAULT SETTINGS - STANDARD MODELS
Page 3
3 EWCM 809/NH3/S 5/98 ing
for CtyP = 1). If CtyP = 0, this parameter will default to 1. PC1…PC9: Power Compressor 1…9. These parameters set the power of each compressor from1 to 255 (only for CtyP =
0). For instance: 3 compressors of 10, 20 and 40 Hp; “PC1” = 10, “PC2” = 20 and “PC3 ” = 40, or “PC1” = 1, “PC2” = 2 and “PC3” = 4. FtyP: Freon tyPe. Not available.
Suction line sensor configuration
*not available for NTC models. PA04*: Pressure At 0…4 mA. Read-out corresponding to the low input signal of 4 mA. PA20*: Pressure At 0…20 mA. Read-out corresponding to the high input signal of 20 mA. CAL: CALibration. Read-out probe calibration.
Other inputs configuration
SEP: SEt (alarm) Polarity. Pressurestat input polarity (terminals 5 and
6). It selects the active condition for a pres­surestat alarm. 0 = active alarm without voltage; 1 = active alarm with voltage. rSIP: reduced Set Input Polarity. Economy set input polarity (terminals 13 and 14). It selects the active condition for an active economy set. 0 = active economy set with open contact; 1 = active economy set with closed con­tact. ALIP: ALarm Input Polarity. Alarm input polarity (terminals 22 to 39). It selects the active condition for an input compressor alarm. 0 = active alarm without voltage; 1 = active alarm with voltage. StPP: Step outPuts Polarity. It selects the active output of the partial re­duction valves (only for compressor having the same power). 0 = it means active step without voltage; 1 = it means active step with voltage.
Password
Psc: Password configuration. Password to have access to the program­ming Configuration parameters. tAb: tAble of parameters. It cannot be modified.
OPERATING PARAMETER
Economy set clock setting
Pri: Primes. Minute setting.
HoUr: HoUrs. Hours setting. dAY: daY. Day setting. NOTE: 1 = Sunday; 7 = Saturday.
Control cycle setting
dEU: dEfault Unit. Default unit of measurement. 0 = bar; 1 = °C; 2 = °F. Pbd: Proportional band. Proportional band width, the unit of mea­surement is expressed by “dEU” parame­ter. With compressors having the same power, the Proportional band width is di­vided by the number of the available re­sources to give the pressure step width for each resource. With compressors having different power, “Pbd” sets the dead band witdh: if the probe value is higher than the setpoint + Pb/2, the compressors will be swiched on by following the delay time pa­rameters setting. If the probe value is low­er than the setpoint – Pb/2, the compressors will be switched off by follow­ing the delay time parameters setting. If the probe value is within the proportional band no compressor will be swiched on or off. onon: on/on (compressor). Compressor on/on delay. Time delay in minutes, between two consecutive starts of the same compressor. oFon: oFF/on (compressor). Compressor off/on delay. Time delay be­tween stop and start of the same com­pressor. don: delay on. Step delay on. Time delay in seconds, be­tween starts of two steps. doF: delay oFF. Step delay off. Time delay in seconds, be­tween stops of two steps. donF: delay on/oFF. Step delay on/off. Minimum resource acti­vation time, in seconds. The activated compressor will work mini­mum for the time set in this parameter. FdLy: First delLay on. The delay time “don” can be used also be­fore the first request of power. 0 = no; 1 = yes. FdLF: First deLay oFF. The delay time “dof” can be used also be­fore the first request of power. 0 = no; 1 = yes. odo: output delay at on. After swiching on the power supply the output will be off during the time set in this
parameter.
Setpoint
LSE: Lower SEt. Lower setpoint limit for both setpoints, the default unit of measurement is expressed by “dEU” parameter. HSE: Higher SEt. Higher setpoint limit for both setpoints, the default unit of measurement is expressed by “dEU” parameter. StrS: Start time reduced Set. Start time for economy set. SPrS: StoP (time) reduced Set. Stop time for economy set. rSd1…rSd7: reduced Set day 1…7. Day of the week to activate the economy set. 0 = no; 1 = yes. NOTE: rSd1 = Sunday; rSd7 = Saturday.
Alarms
UAro: Unit Alarm override. Unit of measurment for alarm silencing (“Aro”). 0 = minutes; 1 = hours. Aro: Alarm override. Alarm silencing override time. PAO : Power Alarm Override. Power on pressure alarms override time, in minutes. After turning on the power supply, the pressure alarms are silenced during this time. LAL: Lower Alarm. Low pressure alarm limit. If the probe sig­nal is lower than Set – LAL, the “Er03” low alarm label is displayed. HAL: Higher Alarm. High pressure alarm limit. If the probe sig­nal is higher than Set + HAL, the “Er04” high alarm label is displayed. tAo: time Alarm override. Time delay before displaying the “Er03/Er04” alarm condition, in seconds. SEr: SErvice. Numer of compressor running hours. When a compressor running hours reache the number set in this parameter, the “Er14” maintenance warning message will be displayed. PEn: Pressurestat Errors number. Number of high and low pressurestat er­rors on terminals 5 and 6.
PEI: Pressurestat Errors Interval (time). CPP: Compressor Probe Protection.
It selcts the system protection when the probe is faulty “Er01”. 0 = the system operates with the same compressors which were working when the probe failed; 1 = the system operates with the number of stages set in “SPr” in case of compres­sors having the same power; or with the power level set in “PoPr” in case of com­pressor having different power. SPr: Step Probe protection. Number of stages to run the system if the probe is faulty (CtyP = 1 and CPP = 1).
Parameter Description Range Default Unit
tAb tAble of parameters / / /
EL 1 ELIWELL 1 / / /
EL 2 ELIWELL 2 / / /
* Not available for NTC models. ** For programmable input 4…20 mA. *** For input probe NTC.
Page 4
4EWCM 809/NH3/S 5/98 ing
PoPr: Power (with faulty) Probe. Power level to run the system if the probe is faulty (CtyP = 0 and CPP = 1).
User interface
rELP: rELative Pressure. Relative or absolute pressure read-out. 0 = absolute; 1 = relative. Loc: keyboard Lock function. It disables the following functions: setpoint adjustment, compressor running hours re­set, avilable and in service compressor status control. The “Loc” parameter can however be modified. 0 = keyboard unlocked; 1 = keyboard locked. Pso: Password operating. Password to access the programming Operating parameters.
Tele-assistance
FAA: FAmily Address. It selects the family number when con­nected to a Televis network. dEA: dEvice Address. It selects the device number when con­nected to a Televis network. tAb: tAble of parameters. This parameter can not be modified. EL1: ELIWELL 1. This parameter can not be modified. EL2: ELIWELL 2. This parameter can not be modified.
USER INFORMATIONS
How to display/modify the setpoint
The EWCM is provided with two setpoints: normal and economy (used during the night time or holidays). Push and release the “set” key to display the normal set, the other unit of measure­ment and the economy set can be dis­played by pushing repeatedly the “set” key whithin 5 seconds. The corresponding led status lights on the right side of the display shows the unit of measurement selected, the active setpoint displayed is identified by the “N” or “R” green led, the other setpoint by the “N” or “R” blinking light. By pushing “UP” or “DOWN” arrow keys the selected setpoint can be modified.
Compressors leds status
Before switching on an output the corre­sponding green led blinks, this blinking pe­riod depends on the delay parameters. When the relay output has been swiched on the corresponding red led will light. Note: after turning on the power supply the pressure may result out of range, therefore to start up the system the EWCM controls the compressors simply as the probe val­ue were higher than the alarm limits. After the time delay set to the parameter “PAO”, if the probe value is still out of range, the EWCM will start working follow­ing the “CPP”, “SPPr” and “PoPr” parame­ters setting.
How to display/reset the compressors running hours
Push and release the “hrs” key to display the first compressor running hours, the “hrs” led will light; push the “UP” arrow within 5 seconds to display the successive compressors, the corresponding red led will blink; the compressor running hours can be reset by keeping pressed the “mute” key for 5 five seconds; to exit this procedure push and release the “hrs” key once again.
How to display/modify the “MAINTE­NANCE” and “IN SERVICE” status
Push and release the “maint” key to dis­play the first compressor status, the corre­sponding red led blinks and the “maint” green led is on. The “onLn” (on line) message means that the output is “in service”. To modify it keep the “mute” key pressed for 5 seconds, the “oFLn” message means that the output is in “maintenance” and the corresponding red led will blink. During the working cycle the “maintence” status of a compressor is shown by the blinking of the corresponding red and green leds, in this case the output com­pressor is always swiched off.
Digital alarm inputs High and low pressurestat alarm
Terminal 5 and 6, “SEP” parameter. Until the condition alarm on these termi­nals is active, the EWCM keeps all the compressor outputs switched off. This kind of alarm does not need a manual re­set. If during the “PEI” interval time the number of pressurestat errors reaches the “PEn” value, the “Er0L” or the “Er0H” warning message will be displayed. “Er0L” means low pressurestat alarm and “Er0H” means high pressurestat alarm. Press the “mute” button for 5 seconds to reset this alarm. This function can be excluded by setting PEn = 0.
Alarm inputs linked to outputs
Terminals from 22 to 39, “ALIP” parameter. Each compressor alarm protection must be connected to the corresponding alarm input (e.g. low compressor oil level, klixon etc.). If one of these alarms is active, the corresponding compressor output will be switched off, the corresponding red led will blink, the “alarm” red led will light and the display will show the “Er02” warning mes­sage. This alarm does not need a manual reset.
Alarm silencing
When an alarm condition is active, the alarm relay will be energized and the termi­nal 1 and 2 are closed. To silence an alarm push and release the “mute” key, the alarm relay will be de-ener­gized and the “alarm” led will blink if the
alarm condition is still active. The silencing time depends on the “UAro” and “Aro” pa­rameters setting. If during the silencing time another alarm becomes active, the silencing time will be reset, and the new alarm condition will be displayed. Alarms that need a manual reset: keep pressed the “mute” key, the display will show the “CAnC” message and then the “rES” message.
ALARM WARNING MESSAGES
Er0L…Er0H: Error Low…High. Low and high pressurestat alarms. It switches off all the compressor outputs. Er01: Error 01. Faulty probe alarm, see “CPP”, “SPr” and “PoPr” parameters setting. Er02: Error 02. Inputs linked to outputs compressor alarms. It switches off the corresponding compressor output. Er03: Error 03. Low pressure alarm. It appears when the probe value is lower than the Set – LAL. Er04: Error 04. High pressure alarm. It appears when the probe value is higher than the Set + HAL. Er11: Error 11. Wrong clock programming. Check “Pri”, “HoUr” and “dAY” parameters setting. Er12: Error 12. Wrong parameter programming. More than the 9 available outputs have been programmed. It needs a manual reset. Er13: Error 13. Wrong data memory. It needs a manual re­set. Er14: Error 14. Maintenance alarm.
TECHNICAL DATA
Housing: black ABS plastic, 72x144 mm, depth 120 mm. Mounting: flush panel mount (67x136 mm) with brackets. Connections: quick-disconnect screw terminal block. Data storage: non-volatile EEPROM memory.
Type of refrigerant: ammonia. Suction sensor input: NTC or 4…20 mA
(scaleable).
Pressure switch input: one (1). Global alarm output: relay 6(3)A 250V
AC. Controller breakdown output: relay 6(3)A 250V AC. Configurable outputs: 9 relays outputs 6(3)A 250V AC. Alarm inputs: 9 inputs (250 Vac optoiso­lated; other voltages on request). Serial connection: RS-485 port for con­nection to the TELEVIS system.
Consumption: 6 VA. Power supply: 12, 24, 110, 220 Vac
±10%, 50/60 Hz.
Page 5
5 EWCM 809/NH3/S 5/98 ing
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
t2 t3 C2 t2 t3C1
K1 K2 K3 K4 K5 K6 K7 K8 K9
44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61
K1 K2 K3 K4 K5 K6 K7 K8 K9
EWCM 809 NH3 terminals 44 - 61
P
N
EWCM 809 NH3 terminals 22 - 39
alarm inputs
1 2 3 4 5 6
EWCM 809 NH3 terminals 1 - 21
10
13 14 15 16 19 20 21
POWER SUPPLY
low
pressure
alarm input
reduced
set
alarm
relay
gnd
+
NTC
evap. probe
TELEVIS system connection (optional)
safety relay
C
3
t2 t3
9
out 1 out 2 out 3 out 4 out 5 out 6 out 7 out 8 out 9
relay outputs
THREE COMPRESSORS HAVING THE SAME POWER AND TWO PARTIAL REDUCTION VALVES
Loading...