label of the first folder in the programming menu will appear.
NOTE: At this point the folders will
only display all the level 2 parameters.
Therefore level 1 parameters will only be
visible if you quit the Programming Menu
and repeat procedure 1).
To enter the folder, press “set”. The label
of the first visible parameter will appear.
To scroll through the other parameters,
use the “UP” and “DOWN” buttons. To
change the parameter, press and release
“set”, then set the desired value using the
“UP” and “DOWN” buttons and confirm
with the “set” button. Move on to the next
parameter.
NOTE: We strongly recommend that you
switch the instrument off and on again
each time parameter configuration is
changed in order to prevent malfunctioning of the configuration and/or ongoing
timings.
PASSWORD
Passwords “PA1” and “PA2” allow level 1
and level 2 parameters to be accessed.
There are no passwords in the standard
configuration. To enable them (value ≠0)
and assign them the desired value, access
the Programming menu in the “diS” folder.
If passwords are enabled, they will be
requested:
- PA1 when entering the Programming
menu (see the “Programming Menu“ section);
- PA2 in the “Cnf” folder containing the
level 1 parameters.
FnC FUNCTION FOLDER
The FnC folder (last folder visible from
the Programming Menu, level 1) contains the following functions.
They are activated using the “set” button
If the unit is switched off, the function
labels go back to their default status.
ACTIVATING MANUAL DEFROST CYCLE
To activate the defrost cycle manually,
press the “UP” button (if configured =1)
for 5 seconds. If the right defrosting conditions are not present (the temperature
of the evaporator probe is higher than the
end of defrost temperature, for example)
or parameter OdO≠0, the display will flash
three (3) times to indicate that the operation will not be performed.
USING THE COPY CARD
The Copy Card is an accessory connected
to the TTL serial port and used for quick
programming of the unit parameters
(upload and download parameter map to
one or more units of the same type).
Operations are described below:
Fr-Format (level 2 parameter)
This command can be used to format the
copy card necessary when used for the
first time or when used with models that
are not compatible. Warning: when the
copy card has been programmed all the
data entered is cancelled when the “Fr”
parameter is used. This operation cannot
be undone.
UL-Upload
This operation uploads the programming
parameters from the instrument.
dL-Download
This operation downloads the programming parameters to the instrument.
NOTE:
• UPLOAD: instrument —> Copy Card
• DOWNLOAD: Copy Card —> instr.
The operations are performed by accessing
the folder identified by the “FPr” label and
selecting the “UL”, “dL” or “Fr” commands.
The operation is confirmed by pressing the
“set” button.
If the operation is successful, a “y” is displayed whereas if it is unsuccessful an “n”
will be displayed.
Download “from reset”
Connect the Copycard with the instrument
OFF
When the instrument is switched on the
programming parameters will be downloaded; when the lamp test has been completed, the following appear on the display
for about 5 seconds:
• label dLY if copy operation is successful
• label DLn if operation fails
NOTE: after downloading the instrument
will work with the parameter map settings
that have just been downloaded.
KEYBOARD LOCKED
Keyboard operating can be locked by programming the “Loc” parameter (see folder
with “diS” table). If the keyboard is locked
you can access the Programming Menu by
pressing the “set” button.
The Set point can also be displayed.
ADVANCED FUNCTIONS
DOOR SWITCH INPUT
This is a clean contact digital input with
programmable polarity. The door switch
input functions are controlled by the values of the following parameters:
If activation state forcing is enabled (dOA
is not 0), the compressor and/or fan outputs can be activated when the time set in
parameters dCO and dFO expires.
Parameter H11 is used to configure the
digital input with values between -9 and
+9. Positive and negative values are used
to select the polarity assigned to the input
and:
NOTE:
the sign “-” indicates that the input is
activated when the contact is closed
The ‘+’ sign indicates that the input is
activated when the contact is open
DEVICE STAND-BY CONTROLLER
This controls the operating mode of the
device when it is on stand by according to
the following parameters:
The Stand-by controller can be digital input
or button enabled if suitably configured.
The status of the instrument when on
stand-by is determined by the value of
parameter H08. Three possible operating
modes are defined:
EXAMPLE 1: the display is off and the controllers active, the instrument signals any
alarms by reactivating the display - OFF DISPLAY
EXAMPLE 2: the display is off and all the
controllers, including the alarms, are also
disabled - STAND-BY
EXAMPLE 3: the display shows the “OFF”
label and all the controllers, including the
alarms, are also disabled- STAND-BY
DEFROST CONTROL
The instrument can be used to select different types of defrosting with the parameter dty, defrost type.
(defrost execution mode).
The dty parameter can have these values:
0 = electrical defrosting; the compressor is
turned off.
1 = cycle reversing defrosting (hot gas);
the compressor continues operating.
2 = Free mode defrosting (compressor dis
abled).
Configuration of 3
rd
probe as 2nd evap-
orator probe
The 3
a
probe can be used to control the
defrosting of a second evaporator by configuring a relay output as a 2nd evaporator
defrost relay (see par. H21…H26).
To implement this function:
a) configure the 3
rd
probe in 2nd evaporator defrost control mode (par. H43=2EP).
b) configure a relay output as 2nd evaporator defrost relay (configuration parameters H21…H26).
c) define the defrost mode by setting
parameter H45.
Start of defrosting
If two evaporators are used, defrosting
starts in three different ways that are
ID 985 2/10
Function
Reduced set point
Aux
Pressure switch alarm reset
**default
Function Label
NOT ATTIVA
SP**
AoF
rAP
Label
function
ACTIVE
OSP
Aon
rAP
Par Description
dOd Digital input switches off loads
dAd D.I. activation delay
OAO Alarm signal delay after disabling the digi-
tal input (door closed)
tdO Time out door open. Time out signalled
when D.I is activated.
(door open)
dOA Forced behaviour from
digital input
PEA Enables forced behaviour from door
switch and/or external alarm
dCO Delay in enabling compressor with
consensus
dFO Delay in enabling fans with
consensus
H11 Digital output configurability/polarity 1
H21...H25 Digital output configurability 1...5
Par Description
PAO alarm exclusion at start-up
OdO Output delay from power-on
H08 Operating mode in stand-by.